- 05000369/LER-1982-008-03, /03L-0:on 820115,exam of Programs on Operator Computer Revealed Equipment Run Time on Fuel Pool Ventilation Sys Exceeded Tech Specs W/O Sample Being Taken from Charcoal Absorber.Caused by Lack of Procedure + (ML20071H406)
- ML20071H411 + (ML20071H411)
- 05000369/LER-1982-007, Forwards LER 82-007/03L-0.Detailed Event Analysis Encl + (ML20071H412)
- ML20071H415 + (ML20071H415)
- ML20071H416 + (ML20071H416)
- 05000369/LER-1982-010-03, /03L-0:on 820120,while in Mode 1,all Digital Rod Position Indications for Control Rod K-8 Lost.Caused by Cabling to Detectors Susceptible to Conductor Damage Due to Own Weight.Bulkhead Connector Cable Replaced + (ML20071H422)
- ML20071H425 + (ML20071H425)
- ML20071H427 + (ML20071H427)
- 05000335/LER-1983-026-09, /09T-0:on 830513,67 of 264 Bergen Paterson EA-3 Clamps Discovered Oriented Improperly.Caused by Vendor Catalog Interpreted Improperly.Clamps Will Be Replaced During Present Outage + (ML20071H429)
- 05000328/LER-1982-011, Forwards LER 82-011/03L-0 + (ML20071H430)
- DCL-94-135, Comment Supporting Petition for Rulemaking PRM-50-59 Re Proposed Amend to 10CFR50.54(p) Concerning Frequency W/Which Licensee Conducts Independent Reviews of Security Programs + (ML20071H431)
- 05000369/LER-1982-007-03, /03L-0:on 820111,many Instrument Lines Froze W/ Instruments Declared Inoperable Leading to Inadvertent Actuation of ESF Causing Safety Injection,Steamline Isolation & Reactor Trips.Caused by Cold Weather + (ML20071H435)
- ML20071H436 + (ML20071H436)
- 05000296/LER-1982-003, Forwards LER 82-003/03L-0 + (ML20071H440)
- 05000296/LER-1982-002-03, /03L-0:on 820121,during Surveillance Test SI 4.11.C.1 & 5 Smoke Detector in Auxiliary Instrument Room 3 Would Not Alarm.Caused by Loose Annunciator Point Card Due to Incorrect Installation of Retainer Bar + (ML20071H443)
- ML20071H445 + (ML20071H445)
- 05000296/LER-1982-003-03, /03L-0:on 820123,during Refueling Outage,While Performing SI 4.2.A-39,temp Switches TS-69-30A,B,C & E on Reactor Cleanup Sys Floor Drain High Temp,Operated at Less than 160 F.Caused by Improper Calibr or Instrument Drift + (ML20071H449)
- ML20071H453 + (ML20071H453)
- ML20071H456 + (ML20071H456)
- ML20071H457 + (ML20071H457)
- ML20071H459 + (ML20071H459)
- 05000244/LER-1982-003, RO 82-007/01T:on 820125,unit Experienced Event Described in LER 82-003 Leading to RCS Cooldown Rate Greater than 100 F/H.Further Info Will Be Submitted w/14-day Written Rept + (ML20071H460)
- ML20071H462 + (ML20071H462)
- ML20071H463 + (ML20071H463)
- ML20071H465 + (ML20071H465)
- ML20071H466 + (ML20071H466)
- 05000328/LER-1982-011-03, /03L-0:on 820122,performance of SI-16 Revealed Boron Injection Tank Records Not Kept.Caused by Inadequate Procedures.Revisions to SI-16 Recordkeeping Procedures Include Boron Injection Tank Heat Tracing + (ML20071H470)
- ML20071H474 + (ML20071H474)
- 05000260/LER-1982-007, Forwards LER 82-007/03L-0 + (ML20071H479)
- ML20071H480 + (ML20071H480)
- ML20071H481 + (ML20071H481)
- 05000499/LER-1994-005-02, :on 940607,standby Diesel Generator 22 Had Received Unexpected Test Mode Start Signal.Caused by Voltage Spike Generated by Emergency Fuel Oil Solenoid Deenergizing. Replaced Parts Found to Be Weak + (ML20071H485)
- ML20071H486 + (ML20071H486)
- ML20071H489 + (ML20071H489)
- ML20071H490 + (ML20071H490)
- HL-4647, Monthly Operating Repts for June 1994 for Ei Hatch Nuclear Plant + (ML20071H491)
- ML20071H492 + (ML20071H492)
- 05000328/LER-1983-060-03, /03L-0:on 830419,automatic Control Valve 2-LCV-3-156 in Auxiliary Feedwater Sys Failed to Open on Demand.Caused by Incorrect Size of Metering Orifice.Correct Parts Installed + (ML20071H493)
- ML20071H494 + (ML20071H494)
- 05000259/LER-1982-011, Forwards LER 82-011/03L-0 + (ML20071H495)
- ML20071H496 + (ML20071H496)
- PY-CEI-NRR-1829, Monthly Operating Rept for June 1994 for Perry Nuclear Power Plant + (ML20071H497)
- ML20071H499 + (ML20071H499)
- ML20071H500 + (ML20071H500)
- 05000395/LER-1983-035-03, /03L-0:on 830420,horizontal Fire Barrier Above Svc Water Booster Pump a Found Damaged.Caused by Maint Activities in Immediate Area of Fire Barrier.Damaged Barrier Replaced + (ML20071H501)
- JAFP-82-0131, Responds to NRC Re Violations Noted in IE Insp Repts 50-333/81-22,50-333/81-28 & 50-333/81-29.Corrective Actions:Urea Formaldehyde Process Will Not Be Used in Future W/O Prior Demonstration of Acceptable Results + (ML20071H502)
- ML20071H504 + (ML20071H504)
- ML20071H505 + (ML20071H505)
- 05000348/LER-1983-017-03, /03L-0:on 830417,specific Gravity of Train a Svc Water Battery Bank Cells 34 & 43 Less than 1.190.Cause Undetermined.Cells Replaced & Battery Bank Returned to Svc + (ML20071H506)
- JAFP-82-0203, Forwards Effluent & Waste Disposal Semiannual Rept,Jul-Dec 1981 + (ML20071H507)
- ML20071H509 + (ML20071H509)