- 05000267/LER-1981-034-03, /03L-0:on 810504,equipment Necessary to Terminate Release from Liquid Waste Sys & Reactor Sump Found Not Operating Properly.Caused by Plugged Sense Lines on Flow Element Associated W/Control Valve + (ML20009A534)
- ML20009A535 + (ML20009A535)
- 05000334/LER-1981-041-04, /04T-1:on 810513,tritium Level in Quarterly Composite of Weekly Grab Samples Collected from Oh River Was Found Higher than Tech Spec Requirements.Caused by Normal Plant Discharge.New Tech Spec Limits Submitted + (ML20009A536)
- 05000333/LER-1981-045, Forwards LER 81-045/03L-0 + (ML20009A537)
- ML20009A538 + (ML20009A538)
- 05000298/LER-1981-010-03, /03L-0:on 810505,static Inverter 1A Spike Suppressor Capacitor Failed Causing Inverter to Become Inoperable.Caused by Aging & Effects of High Ripple Charger + (ML20009A539)
- 05000219/LER-1981-021, Forwards LER 81-021/03L-0.Detailed Event Analysis Encl + (ML20009A540)
- ML20009A541 + (ML20009A541)
- 05000267/LER-1981-038, Forwards LER 81-038/03L-0.Detailed Event Analysis Encl + (ML20009A542)
- ML20009A543 + (ML20009A543)
- 05000333/LER-1981-045-03, /03L-0:on 810601,during Normal Operation,While Conducting Surveillance,Reactor Water Level Instrument Switch for Recirculation Pump Trip Failed.Caused by Age. Switch Replaced & Calibr.Instrument Returned to Svc + (ML20009A544)
- 05000334/LER-1981-056, Forwards LER 81-056/03L-0 + (ML20009A545)
- ML20009A546 + (ML20009A546)
- 05000293/LER-1981-021, Forwards LER 81-021/01T-0 + (ML20009A547)
- ML20009A548 + (ML20009A548)
- 05000219/LER-1981-021-03, /03L-0:on 810603,high Pressure Sensor Switches RE03B, C & D Were Found Tripping within 8 Lb of Setpoint. Caused by Sensor Repeatability.Switches Reset.Switches Will Be Replaced During Next Refueling Outage + (ML20009A549)
- 05000267/LER-1981-038-03, /03L-0:on 810507,two Class I Hydraulic Shock Suppressors Removed from Svc.Caused by Decision to Modify Suppressors to Original Configuration W/Zero Bleed Rate Block Valves + (ML20009A550)
- 05000317/LER-1981-045, Forwards LER 81-045/03L-0 + (ML20009A551)
- ML20009A552 + (ML20009A552)
- 05000334/LER-1981-056-03, /03L-0:on 810601,train a Chemical Addition Tank Level Transmitter Failed Low.Cause Unknown.Channel Returned to Svc.Instrumentation Dept to Monitor Operation + (ML20009A553)
- 05000293/LER-1981-021-01, /01T-0:on 810615,review of Analysis Responding to 10CFR50.44 Determined Inadequate.Mgt Controls Failed to Identify Effect of Rendering post-accident Nitrogen Supply Sys Inoperable.Caused by Inadequate Mgt Controls + (ML20009A554)
- ML20009A555 + (ML20009A555)
- 05000317/LER-1981-045-03, /03L-0:on 810601,channel a Power Range Instrument Was Found Faulty.Caused by Loose Upper sub-channel Cable Connector,Amphenol 31-4374,due to Normal Use.Connector Remade & Tightened + (ML20009A556)
- 05000318/LER-1981-026, Forwards Updated LER 81-026/03X-1 + (ML20009A557)
- ML20009A558 + (ML20009A558)
- 05000333/LER-1981-044, Forwards LER 81-044/03L-0 + (ML20009A559)
- ML20009A560 + (ML20009A560)
- 05000318/LER-1981-026-03, Discharge Damper to ECCS Pump Room Exhaust Fan 22 Failed Shut.Caused by Linkage Rod Shifting from Proper Position.Linkage Repaired & Adjusted. Preventive Maint Procedure to Be Instituted + (ML20009A561)
- 05000333/LER-1981-044-03, /03L-0:on 810601,w/oxygen Analyzer B Out of Svc, Drywell Oxygen Analyzer a Found Indicating Downscale.Caused by Instrument Drift.Calibr Restored Instrument to Svc + (ML20009A562)
- ML20009A564 + (ML20009A564)
- ML20009A566 + (ML20009A566)
- ML20009A567 + (ML20009A567)
- ML20009A569 + (ML20009A569)
- IR 05000482/1981006 + (ML20009A571)
- IR 05000461/1981010 + (ML20009A572)
- ML20009A573 + (ML20009A573)
- ML20009A574 + (ML20009A574)
- ML20009A576 + (ML20009A576)
- ML20009A577 + (ML20009A577)
- IR 05000313/1981017 + (ML20009A578)
- ML20009A579 + (ML20009A579)
- ML20009A580 + (ML20009A580)
- IR 05000358/1981017 + (ML20009A582)
- ML20009A583 + (ML20009A583)
- 05000298/LER-1981-009, Forwards LER 81-009/03L-0.Detailed Event Analysis Submitted + (ML20009A584)
- ML20009A585 + (ML20009A585)
- 05000298/LER-1981-009-03, /03L-0:on 810503,two Pacific Scientific Model PSA-10 Mechanical Shock Suppressors Found Inoperable.Cause Under Evaluation.Snubber Replaced + (ML20009A586)
- ML20009A587 + (ML20009A587)
- IR 05000407/1981001 + (ML20009A589)
- ML20009A590 + (ML20009A590)
- ML20009A592 + (ML20009A592)