Search by property
Jump to navigation
Jump to search
This page provides a simple browsing interface for finding entities described by a property and a named value. Other available search interfaces include the page property search, and the ask query builder.
List of results
- ML19331B583 + (ML19331B583)
- ML19331B584 + (ML19331B584)
- ML19331B586 + (ML19331B586)
- 05000339/LER-1980-038-03, /03L-0:on 800717,results of Periodic Reactor Coolant Leak Rate Tests Showed Tech Spec Limit Exceeded. Caused by Flange Leak on a Reactor Coolant Protection Seal Injection Line Due to Relieving Tension on Flange Bolts + (ML19331B587)
- ML19331B588 + (ML19331B588)
- ML19331B589 + (ML19331B589)
- ML19331B590 + (ML19331B590)
- ML19331B591 + (ML19331B591)
- ML19331B593 + (ML19331B593)
- ML19331B594 + (ML19331B594)
- ML19331B595 + (ML19331B595)
- 05000321/LER-1980-085-03, /03L-0:on 800720,w/unit at 300 Mwt & O Mwe,Reactor Water Not Sampled & Analyzed for Chlorides & Ph.Caused by Personnel Oversight.Retraining Session for Responsible Employees Conducted + (ML19331B596)
- ML19331B597 + (ML19331B597)
- ML19331B599 + (ML19331B599)
- ML19331B602 + (ML19331B602)
- 05000259/LER-1980-055, Forwards LER 80-055/03L-0 + (ML19331B604)
- ML19331B605 + (ML19331B605)
- 05000321/LER-1980-083, Forwards LER 80-083/03L-0 + (ML19331B607)
- ML19331B608 + (ML19331B608)
- ML19331B610 + (ML19331B610)
- ML19331B611 + (ML19331B611)
- ML19331B614 + (ML19331B614)
- ML19331B615 + (ML19331B615)
- 05000324/LER-1980-039, Forwards LER 80-039/03L-0 + (ML19331B617)
- ML19331B618 + (ML19331B618)
- 05000339/LER-1980-034, Forwards LER 80-034/03L-0 + (ML19331B619)
- ML19331B620 + (ML19331B620)
- ML19331B621 + (ML19331B621)
- 05000320/LER-1980-028, Forwards LER 80-028/03L-0 + (ML19331B622)
- 05000259/LER-1980-055-03, /03L-0:on 800708,during HPCI Special Instruction 4.5.E.1.d & E,Pdv 73-43 Failed to Operate Properly.Caused by Valve Stuck Closed Due to Loose Valve Guide.Valve Disassembled & Cleaned & Valve Guide Tightened + (ML19331B624)
- ML19331B625 + (ML19331B625)
- 05000321/LER-1980-083-03, /03L-0:on 800713,w/reactor Mode Switch in Run Mode at Power Level of 2241 Mwt,Surveillance Procedure HNP-1-3103 Not Performed within Required Grace Period.Caused by Personnel Error.Surveillance Immediately Performed + (ML19331B626)
- 05000324/LER-1980-039-03, /03L-0:on 800721,during Visual Insp of Accessible Snubbers on safety-related sys,PT-19.6.0.2-2,Bergen- Paterson snubber,2G41-12SS33 Found Missing Paddle Bushing. Cause Undetermined.Bushing Replaced + (ML19331B627)
- ML19331B628 + (ML19331B628)
- 05000320/LER-1980-028-03, /03L-0:on 800707,while Being Tested by Surveillance Procedure,Emergency Diesel Generator DF-X-1B Tripped on High Crankcase Pressure.Caused by Loose Hose Clamp Resulting in Crankcase Vacuum Loss + (ML19331B629)
- AECM-80-172, Interim Deficiency Rept Re Contact & Indication Malfunction of Series 20,Type PR-20 Electro Switches.Evaluation Incomplete.Determination of Reportability & Final Rept Will Be Sent by 801028 + (ML19331B630)
- 05000339/LER-1980-034-03, /03L-0:on 800711,during Mode 2 Operation,Leak from RCS Occurred in Excess of Tech Spec Limit.Caused by Packing Failure on Valve RHR-MOV-2700.Valve Repaired,Tested & Returned to Svc + (ML19331B631)
- 05000278/LER-1980-016, Forwards LER 80-016/01T-0 + (ML19331B632)
- ML19331B633 + (ML19331B633)
- ML19331B634 + (ML19331B634)
- ML19331B637 + (ML19331B637)
- ML19331B638 + (ML19331B638)
- 05000278/LER-1980-016-01, /01T-0:on 800717,reanalysis by Bechtel of as-built Piping Determined That Stresses on Snubber 3-10-GB-S-44 Exceeded Operability Criteria.Caused by Inadequate Design Due to as-built Condition & Seismic Analysis Info Variance + (ML19331B639)
- ML19331B640 + (ML19331B640)
- ML19331B641 + (ML19331B641)
- ML19331B643 + (ML19331B643)
- AECM-80-170, Submits Addl Response to NRC Ltr Re Deficiency Noted in IE Insp Repts 50-416/80-07 & 50-417/80-06.Equipment to Complete Dredging Operation Has Not Been Available.Full Compliance Will Be Achieved by 800905 + (ML19331B644)
- ML19331B645 + (ML19331B645)
- ML19331B646 + (ML19331B646)
- ML19331B648 + (ML19331B648)
- 05000285/LER-1980-014, Forwards LER 80-014/03L-0 + (ML19331B649)