Nebraska Public Power District "Always there when you need ius" 54.17 NLS2009062 September 24, 2009 U.S. Nuclear Regulatory Commission Attention: Document Control Desk Washington, D.C. 20555-0001

Subject:

Response to Request. for Additional Information for the Review of Cooper Nuclear Station License Renewal Application Cooper Nuclear Station, Docket No. 50-298, DPR-46

References:

1. Letter from Tam Tran, U.S. Nuclear Regulatory Commission, to Stewart B. Minahan, Nebraska Public Power District, dated July 29, 2009, "Request for Additional Information for the Review of the Cooper Nuclear Station License Renewal Application (TAC No. MD9763 and MD9737)"

(ADAMS Accession Number ML092090276).

2. Letter from Bennett M. Brady, U.S. Nuclear Regulatory Commission, to Stewart B. Minahan, Nebraska Public Power District, August 28, 2009, "Request for Additional Information for the Review of the Cooper Nuclear Station License Renewal Application (TAC No. MD9763 and MD9737)"

(ADAMS Accession Number ML092310654).

3. Letter from Stewart B. Minahan, Nebraska Public Power District, to U.S.

Nuclear Regulatory Commission, dated September 24, 2008, "License Renewal Application."

Dear Sir or Madam:

The purpose of this letter is for the Nebraska Public Power District to respond to the Nuclear Regulatory Commission Requests for Additional Information (RAI) (References 1 and 2) regarding the Cooper Nuclear Station License Renewal Application (LRA). These responses are provided in Attachments 1 and 2, respectively. Certain changes to the LRA (Reference 3) have been made to reflect these RAI responses and other clarifications. These changes are provided in .

Should you have any questions regarding this submittal, please contact David Bremer, License Renewal Project Manager, at (402) 825-5673.

COOPER NUCLEAR STATION P.0. Box 98 / Brownvylle, NE 68321-0098 Telephone: (402) 825-3811 / Fax: (402) 825-5211 www nppd.czm

NLS2009062 Page 2 of 2 I declare under penalty of perjury that the foregoing is true and correct.

Executed on (bate)

Sincerely, Stewart B. Minahan Vice President - Nuclear and Chief Nuclear Officer

/wv Attachments cc: Regional Administrator w/ attachments USNRC - Region IV Cooper Project Manager w/ attachments USNRC - NRR Project Directorate IV-l Senior Resident Inspector w/ attachments USNRC - CNS Nebraska Health and Human Services w/ attachments Department of Regulation and Licensure NPG Distribution w/ attachments CNS Records w/ attachments

4 ATTACHMENT 3 LIST OF REGULATORY COMMITMENTS© 4

ATTACHMENT 3 LIST OF REGULATORY COMMITMENTS@

Correspondence Number: NLS2009062 The following table identifies those actions committed to by Nebraska Public Power District (NPPD) in this document. Any other actions discussed in the submittal represent intended or planned actions by NPPD. They are described for information only and are not regulatory commitments. Please notify the Licensing Manager at Cooper Nuclear Station of any questions regarding this document or any associated regulatory commitments.

COMMITMENT COMMITTED DATE COMMITMENT NUMBER OR OUTAGE None 4 4 4 4

  • $

4 4 t I 4 4 4 4 4 4 I ¶ I PROCEDURE 0.42 REVISION 24 PAGE 20 OF 27

NLS2009062 Page 1 of 2 Attachment 1 Response to Request for Additional Information for License Renewal Application Cooper Nuclear Station, Docket No. 50-298, DPR-46 The Nuclear Regulatory Commission (NRC) Request for Additional Information (RAI) regarding the License Renewal Application is shown in italics. The Nebraska Public Power District's (NPPD) response to this RAI is shown in block font.

NRC Request: RAIB.1.20-1

Background:

There have been reoccurringfailures of main steam line pipe supports at CNS since the 1980's.

In 2006 a Condition Report (CR-CNS-2006-09590, Action Item 8) was initiatedto address the recurringpipe support deficiencies with completion of all redesign and associatedhardware changes (if necessary) by June 30, 2011.

Issue:

Continuedfailures of steam line supports during each period of operation between plant outages can affect the structuralintegrity of the main steam line pipingsystem.

Request.

Explain how the corrective action process will address the potential aging effects (i.e. structural fatigue) on the piping system due to the unanalyzed loading condition associatedwith the past pipe supportfailures.

NPPD Response:

Reoccurring failures of Cooper Nuclear Station (CNS) main steam (MS) line pipe supports and the potential effect on the piping system have been identified by NPPD and addressed through the Corrective Action Program (CAP).

The follow up CAP Apparent Cause Evaluation indicated MS pipe support deficiencies are the result of high-cycle fatigue loadings due to normal flow and thermal dynamic operating conditions of the system (not aging-related). A detailed vendor-assisted engineering study of the 24" diameter MS system in the heater bay is necessary to determine modifications to the piping system which may help to eliminate the recurring pipe support deficiencies. The vendor has developed recommendations to resolve the MS line support deficiencies. Plans are in place at CNS, and are being tracked under CAP, to modify the 24" diameter MS system piping in the heater bay to eliminate the recurring pipe support deficiencies resulting from high-cycle fatigue loadings, and to reduce system vibration levels due to normal operating conditions of the system.

NLS2009062 Page 2 of 2 As part of ongoing corrective actions, the MS pipe supports are visually examined for discrepancies at the end of each operating cycle.

NLS2009062 Page 1 of 9 Attachment 2 Response to Request for Additional Information for License Renewal Application Cooper Nuclear Station, Docket No. 50-298, DPR-46 The Nuclear Regulatory Commission (NRC) Request for Additional Information (RAI) regarding the License Renewal Application is shown in italics. The Nebraska Public Power District's (NPPD) response to each RAI is shown in block font.

NRC Request: RAI 3.5-1

Background:

In the license renewal application(LRA) Section 3.5.2.2.1.1, Section 3.5.2.2.1.2, Section 3.5.2.2.1.4, Section 3.5.2.2.1.10, Section 3.5.2.2.2.1, Section 3.5.2.2.2.2, and Section 3.5.2.2.2.4, the applicantstated that there are no aging effects requiringmanagementfor Cooper Nuclear Station (CNS) concrete due to thefollowing:

1. Concrete is designed in accordancewith AC1 318-63
2. The CNS below-grade environment is not aggressive Issue:

The staff is unable to verify the applicantclaims due to lack ofsupporting data and/or information in the LRA in the following areas:

1. Air-entrainedvalue and water-cement ratio
2. Datafor below-grade water chemistry Request:

In order to complete the staff's review, additionalinformation is needed asfollows:

A. Provide supportingdata/informationfor the above items.

B. Explain what action will be taken for inaccessible areas, if degradation(as a source of aging effects) is discovered in accessibleareas? Will this involve additional commitments?

Explain why there are no aging effects requiringmanagementfor CNS concrete (both accessible and inaccessible)while the Generic Aging Lessons Learned (GALL) Report recommends the Structures MonitoringProgramand/or a Plant-Specific Program to manage concrete aging effects for LRA Section 3.5.2.2.1.2, Section 3.5.2.2.2.1, and Section 3.5.2.2.2.4.

NLS2009062 Page 2 of 9 NPPD Response:

Part A The CNS concrete specification provided for air content between four and six percent. Concrete strength was established based on Method 2 of ACI 318-63. Method 2 provided for tests of trial mixes to ensure required concrete strength at water-cement ratios that provided sufficient workability. The maximum permissible water-cement ratio for the concrete used at CNS was that established by the water-cement ratio versus concrete strength curve produced by Method 2 that yielded an average strength which satisfied the requirements of ACI 318-63 Section 504 "Strength Test of Concrete." The maximum permissible water-cement ratio was 0.71 for concrete with 3000 psi strength and 0.52 for concrete with 4000 psi strength.

Sampling of three test wells in November 2006 yielded the following results for CNS below-grade water chemistry.

Test Hole B-31 Test Hole B-12 Test Hole B-I pH 7.0 8.0 7.6 Chloride 24.4 ppm 17.0 ppm 22.0 ppm Sulfate 82.5 ppm 33.0 ppm 74.1 ppm Part B The CNS Structures Monitoring Program provides for inspections of accessible areas. If findings on accessible structures or components indicate that potential degradation may be occurring in inaccessible areas, an evaluation will be performed and appropriate corrective actions will be taken under the Corrective Action Program. This involves no additional commitments since the corrective action and confirmation processes are elements of the existing Structures Monitoring Program.

LRA Section 3.5.2.2.1.2 corresponds to NUREG-1800 Section 3.5.2.2.1.2 which discusses cracks and distortion due to increased stress levels from settlement, and reduction of foundation strength, cracking and differential settlement due to erosion of porous concrete subfoundations.

As indicated in LRA Table 3.5.1 (Structures and Component Supports, NUREG- 1801 Vol. 1),

Item 3, the CNS containment is a Mark I steel containment with a foundation integral to the floor of the reactor building. The containment foundation is not exposed to a soil environment.

Consequently, the NUREG- 1801 items that reference this Standard Review Plan (SRP) section are not applicable to Mark I steel containments. The Structures Monitoring Program includes inspections of the reactor building structures to confirm the absence of aging effects caused by settlement. A porous concrete subfoundation is not a design feature of the CNS reactor building.

NLS2009062 Page 3 of 9 LRA Section 3.5.2.2.2.1 corresponds to SRP Section 3.5.2.2.2.1. Each discussion in LRA Section 3.5.2.2.2.1 for a specific aging effect is intended to explain why there is no aging effect requiring management based on the criteria provided in the SRP discussions and the associated criteria of NUREG-1801 Volume 2. Nevertheless, as indicated in LRA Chapter 3.5, the Structures Monitoring Program is applied to the affected structures to confirm the absence of significant aging effects. Accessible concrete inspected under the Structures Monitoring Program provides indication of the condition of inaccessible concrete since it is constructed to the same standards and is exposed to similar or more severe environments. For example, accessible exterior concrete is exposed to greater extremes of temperature than inaccessible concrete. For sliding surfaces addressed in Paragraph 8 of LRA Section 3.5.2.2.2.1, the Structures Monitoring Program and Inservice Inspection - IWF Program confirm the absence of aging effects requiring management.

LRA Section 3.5.2.2.2.4 corresponds to SRP Section 3.5.2.2.2.4. Each discussion in LRA Section 3.5.2.2.2.4 for specific aging effects is intended to explain why there are no aging effects requiring management based on the criteria provided in the SRP discussions and the associated criteria of NUREG-1801 Volume 2. Nevertheless, as indicated in LRA Chapter 3.5, the Structures Monitoring Program is applied to the affected structures to confirm the absence of significant aging effects. Per LRA Section B.1.36, Structures Monitoring Program activities will be enhanced to include examination of the exposed portions of the below grade concrete, when excavated for any reason. The program enhancements also include periodic monitoring of below-grade water chemistry to confirm that groundwater remains nonaggressive.

NRC Request: RAI3.5.2.2.2.2-1

Background:

StandardReview Plan (SRP) Section 3.5.2.2.2.2, "Aging Management of InaccessibleAreas,"

consists offive sub-sections to review asfollows:

1. Loss of Material (spalling,scalling)and crackingdue to freeze-thaw in below grade inaccessible concrete areasfor group 1-3, 5, and 7-9 structures.
2. Cracking due to expansion and reaction with aggregates could occur in below-grade inaccessible concrete areasfor group 1-5, and 7-9 structures.
3. Cracks and distortion due to increasedstress levels from settlement and reduction of foundation strength, cracking, and differential settlement due to erosion ofporous concrete subfoundation could occur in below-grade inaccessible concrete areas of groups 1-3, 5 and 7-9 structures.
4. Increase in porosity andpermeability, cracking, loss of material due to aggressive chemical attack.
5. Increase in porosity andpermeability, and loss of strength due to leaching of calcium hydroxide.

NLS2009062 Page 4 of 9 Issue:

LRA Section 3.5.2.2.2.2 states that groups 1-3, 5 and 7-9 inaccessible concrete areasprovided in accordancewith specificationA CI 318-63, Building Code Requirements for Reinforced Concrete and that concrete also meets requirements of later ACI guide 201.2R-77. The LRA further states that inspection of accessible concrete have not revealed degradationrelated to corrosionof embedded steel and that the below-grade environment is not aggressive. The LRA concludes that corrosionof embedded steel is not an aging effect requiringmanagementfor concrete (Reference to RAI 3.5-1). However, the staff was unable to complete its review because the LRA did not contain the related informationfor Sub-section 3.5.2.2.2.2.1 through Sub-section 3.5.2.2.2.2.5 of the SRP.

Request:

Provide the related informationfor Sub-section 3.5.2.2.2.2.1 through Sub-section 3.5.2.2.2.2.5 for the staff to review.

NPPD Response:

The related information in SRP Section 3.5.2.2.2.2 is addressed in LRA Section 3.5.2.2.2.

Specifically, Item 1 is addressed by Section 3.5.2.2.2.1.4, Item 2 by Section 3.5.2.2.2.1.5, Item 3 by Section 3.5.2.2.2.1.6 and Section 3.5.2.2.2.1.7, and Item 4 by Section 3.5.2.2.2.1.2. The related information applicable to Item 5 (SRP Subsection 3.5.2.2.2.2.5) is provided in LRA Subsection 3.5.2.2.2.4.3. While LRA Subsection 3.5.2.2.2.4.3 is under the category of Group 6 structures, the discussion also applies to concrete in Groups 1-3, 5 and 7-9.

NRC Regquest: RAI3.5.2.2-1

Background:

NUREG-1801, "Generic Aging Lessons Learned (GALL) Report, "Revision 1, states that the IWE Inservice Inspection Programshould be supplemented and that additionalappropriate examinations to detect stress-corrosioncracking (SCC) in bellows assemblies and dissimilar metal welds are warranted. In addition,Information Notice 92-20 describes instances of containment bellows cracking.

Issue:

LRA Section 3.5.2.2.1.7 states that the existing ContainmentLeak Rate and Containment Inservice Inspection - IWE Programsare adequate to detect crackingsince the susceptible components are not subject to a corrosive environment. The staff could not determine the basis for this position.

Request:

The staff requests that the applicantprovide a discussion on the augmented exams discussedin LRA Table 3.5-1, Items 10 and 11, and indicate how the exams will detectfine cracks.

NLS2009062 Page 5 of 9 NPPD Response:

The CNS Containment Inservice Inspection Program contains provisions for performing augmented examinations of components likely to experience accelerated degradation and aging.

Components subject to augmented examination in accordance with ASME Section XI, Subsection IWE, Item 4.11 receive a VT-I examination of the accessible areas based on the limitations set forth in 10 CFR 50.55a(b)(2)(ix)(G). Direct VT-I visual examinations are conducted within a maximum examination distance of 2' (24") or less from the surface to be examined and with a minimum illumination level that is adequate to resolve the VT-I sized characters (0.044" maximum height) on a character card. Examinations performed to this standard are capable of detecting fine cracks.

Although the CNS Inservice Inspection Program has no components subject to augmented examination in accordance with ASME Section XI, Subsection IWE Item 4.12, any components subject to this provision in the future would receive ultrasonic thickness examinations for inaccessible areas that cannot be examined visually. Examinations performed to this standard are similarly capable of detecting fine cracks.

The augmented examinations of the Containment Inservice Inspection Program discussed above are not applied to stainless steel components and dissimilar metal welds identified in LRA Table 3.5.1, Items 10 and 11 since those components have not been judged likely to experience accelerated degradation and aging. Information Notice 92-20 primarily entailed problems with local leak rate testing and did not identify a cause of the containment bellows cracking that would indicate similar CNS components are susceptible to accelerated degradation or aging. As stated in LRA Section 3.5.2.2.1.7, these components are not subject to a corrosive environment, which is a necessary factor for establishing susceptibility to SCC.

Within the Primary Containment Leak Rate Program, CNS will continue to perform a periodic integrated leak rate test of the overall primary containment, which is capable of detecting leakage in the unlikely event of through-wall cracking. Additionally, this program requires local leakage rate tests of expansion bellows.

In summary, the combination of the Containment Leak Rate and Containment Inservice Inspection Programs provides reasonable assurance that cracking will be managed.

NRC Request: RAI 3.5.2.2-2

Background:

NUREG-1801, "GenericAging Lessons Learned (GALL) Report, "Revision 1, states that the IWE Inservice Inspection Programshould be supplemented in that VT-3 visual inspection may not detectfine cracks.

NLS2009062 Page 6 of 9 Issue:

LRA Section 3.5.2.2.1.8 states that the existing containment Leak Rate Programwith augmented exams and Containment Inservice Inspection - IWE will be used to detect cracking.

LRA Section 3.5.2.2.1.8 and LRA Table 3.5.1, Items 12 and 13 refer to augmented inspections but do notprovide a discussion on the specifics of the augmented inspections.

Request:

The staff requests that the applicantprovide a discussion on the augmented inspections, and indicate how they will be used to detectfine cracks.

NPPD Response:

LRA Table 3.5.1 Items 12 and 13 correspond to the analogous items in NUREG 1800, Table 3.5-1, "Summary of Aging Management Programs for Structures and Component Supports Evaluated in Chapters II and III of the GALL Report." Upon further review, Items 12 and 13 of this SRP table were found not applicable for CNS components. As stated in NUREG-1801, "Generic Aging Lessons Learned (GALL) Report" Items II.B4-3 (C- 14) and II.B 1.1-3 (C-20),

the aging effect "cracking/cyclic loading" applies to these structural components only if a current licensing basis fatigue analysis does not exist. CNS does have fatigue analyses for the subject components. Accordingly, LRA Section 3.5.2.2.1.8 and Tables 3.5.1 and 3.5.2-1 have been revised (see Attachment 3, Changes 1, 2, 3, and 4).

NRC Request: RAI3.5.2.2.2.6-1

Background:

NUREG-1801, "Generic Aging Lessons Learned (GALL) Report, "Revision 1, Generic Item T-30, recommends the Structures MonitoringProgram to manage loss of materialand general corrosion.

Issue:

LRA Section 3.5.2.2.2.6.2 states that the Structures MonitoringProgram manages loss of materialforsteel structuralcomponents. The LRA further states thatfor some components the Fire ProtectionProgramsupplements the Structures MonitoringProgramand,for other components, the PeriodicSurveillance and Preventive Maintenance,Fire Protection,or Fire Water System Programsbe used to manage the loss of material. The staff could not determine how the above mentionedprograms meet or exceed the Structures Monitoring Program.

Request:

The staff requests that the applicantprovide a comparison of the above mentionedprograms to the Structures MonitoringProgram and specify how the programs will meet or exceed the requirements of the StructuresMonitoringProgram,relative to the aging effect "loss of material/generaland pitting corrosion."

NLS2009062 Page 7 of 9 NPPD Response:

A comparison of the three programs demonstrates that the Fire Protection, Fire Water System, and Periodic Surveillance and Preventive Maintenance Programs are as effective as the Structures Monitoring Program for managing the aging effect "loss of material/general and pitting corrosion."

For steel structural components, the Structures Monitoring Program manages loss of material through visual inspection of component surface condition at a frequency of at least once every five years. The acceptance criteria include no indications of loss of material, such as excessive rust or corrosion. The identified supplemental programs also employ the same visual inspection method, comparable frequencies, and the same acceptance criteria for managing loss of material for steel structural components. The parameter monitored for loss of material in all four programs is the condition of component external surfaces.

NRC Request: RAI 3.5.2.2.2.6-2

Background:

NUREG-1801, "Generic Aging Lessons Learned (GALL) Report," Revision 1, Generic Item T-29, includes grouted anchors and grout as components/materialwhich should be managed by the Structures MonitoringProgram.

Issue:

LRA Section 3.5.2.2.2.6.1 states that the StructuresMonitoringProgramwill confirm the absence of aging effects for CNS concrete components, but does not discuss grouted anchors.

Request:

The staff requests that the applicant discuss whether grout and grouted supports are included within the Structures MonitoringProgram. In addition, ifgrout and grouted supports are not included within the StructuresMonitoring Program,provide a discussion on how aging effects will be managed.

NPPD Response:

Grout pads for structural base plates are sub-components of the concrete group and not specifically identified as separate components. Therefore, structural grout (e.g. support base plates) is grouped with concrete. Per LRA Table 3.5.1 (Structures and Component Supports, NUREG-1801 Vol. 1), Item Number 40, grout pads for equipment are included with concrete components. Consequently, in LRA Table 2.4.4 (Bulk Commodities Subject to Aging Management Review) and Table 3.5.2-4 (Bulk Commodities Summary of Aging Management Evaluation), grout pads for equipment and support base plates are included with the concrete

NLS2009062 Page 8 of 9 bulk commodity "Equipment pads/foundations." Accordingly, grout and grouted supports are included in the scope of the Structures Monitoring Program.

NRC Request: RAI 3.5.2.2.2.6-3

Background:

LRA Section 3.5.2.2.2.6.3 states that the CNS aging management review did not identify any component support structure/agingeffect combination correspondingto NUREG-1801 Volume 2 Item III.B4.2-a.

Issue.

The staff could not determine whether vibration isolation elements exist at CNS and are included within the scope of license renewal, or whether the applicanthas determined that vibration isolation elements included within the scope of license renewal have no aging effect.

Request:

The staff requests that the applicantindicate whether or not vibration isolation elements are included within the scope of license renewal at CNS. If vibration isolation elements are included within scope the scope of license renewal,provide a basisfor why they are not covered by the Structures MonitoringProgram.

NPPD Response:

Vibration isolation elements are not uniquely identified in the application because they are an integral part of the overall structural support component. These components are addressed in the LRA in Table 2.4-4 (Bulk Commodities Subject to Aging Management Review) and Table 3.5.2-4 (Bulk Commodities) under line item "Component and piping supports." Aging management activities for managing the entire structural support assembly under the Structures Monitoring Program will manage the effects of aging on these vibration isolation elements.

NRC Request: RAI3.5.2.3-1

Background:

GALL Report, "Revision 1, GenericItem TP-6, says stainless steel support members and bolted connections in an outdoor environment should be monitored by the Structures Monitoring Programfor the aging effect loss of material.

Issue:

LRA Table 3.5.2-4 lists five stainless steel support and bolting component groups in an "air-outdoor" environment. The LRA lists the aging effect and aging managementprogram as none and refers to Note I and Note 503, which state that aging management is not requiredfor stainless steel components exposed to the external environment because the environment at CNS

NLS2009062 Page 9 of 9 is not chemically polluted. The staff did not determine that Note 503 is adequate to conclude that aging management is not requiredfor these components.

Request:

Provide a basisfor the conclusion that no aging effect is applicable to the above mentioned component groups and why the component groups were not included in the Structures MonitoringProgram.

NPPD Response:

CNS external ambient environment is non-aggressive and does not include vapors of sulfur dioxide or sodium chloride from saltwater spray which could result in loss of material. Industry experience has shown that stainless steel is very resistant to general corrosion for both interior and exterior exposures and under conditions of high or low humidity. Stainless steel also contains chromium at levels sufficient to provide adequate resistance to corrosion in both industrial and marine environments. CNS is located in a predominantly agricultural environment not located near seawater, and no significant industrial plants are in the area which could result in an aggressive air-outdoor environment. Therefore, the conditions required to cause loss of material for stainless steel elements exposed to an air-outdoor environment is not present at CNS and loss of material is not an aging effect requiring management. Nevertheless, the Structures Monitoring Program includes inspections of the five stainless steel support and bolting component groups in an "air-outdoor" environment, with the exception of ASME Class 1, 2, 3 and MC supports bolting, which is included in the Inservice Inspection - IWF Program.

NLS2009062 Page 1 of 3 Attachment 3 Changes to the License Renewal Application Cooper Nuclear Station, Docket No. 50-298, DPR-46 This attachment provides changes to the License Renewal Application based on the responses to the Requests for Additional Information provided in Attachments 1 and 2, as well as for other clarifications. The changes are presented in underline/strikeout format.

I1. LRA Section 3.5.2.2.8 is revised to read:

"*Cycli loading can lead to c-reaking of steel and stainless steel penetration bellows, an dissimilar- mtal welds N1 of BWR ntainments and BWR sup nd shell and dewneemer--

With propera desip,fracking due to yacliC leading is not expected to occur in the df~p~vll, torus and asseciatcd penetr-ation bellows, penetratiein sleeves, unbr-accd dewncomer-s, and dissimilar-metal welds. A review of plant opcrating ecxper-icncc did o identify any cracking of co thes mponents," and priar' containmcnt leakage has net been identified as a conccm. Noncthclcss, the existing Contaimnment Leak Ratc ProEgr-amf with aueentced exas and Containmnt inservie inspection !WE will continu35e to be used to detect cracking. Obscrvcd conditions that have the potential for impacting an intended function arc evaluated or corr-ectcd in accordance with the eeffective actio pr2oess. The Containmnent insenfor Inspection !WE and Containment Leak Rate programs arc deser-ibcd in Appendix B-.

In accordance with NUREG- 1801 Volume 2, Items 11.131. 1-3 and II.B4-3, this line is applicable only for structures without a CLB fatigue analysis. CNS has a CLB fatigue analysis for these components."

Reference:

Response to RAI 3.5.2.2-2.

2. The Discussion column entry for LRA Table 3.5.1 (Structures and Component Supports, NUREG-1801 Vol. 1), Item Number 3.5.1-12, Page 3.5-24 is revised to read:
  • notexpected to occuir. Nonetheless, the Contaifnment Leak Rate Proegram with augmented exams and Containment insen'ice Inspection will continyue to be used to exams to detect fine rac Not applicable. CNS has a CLB fatigue analysis for these components.

See Section 3.5.2.2.1.8."

NLS2009062 Attachment 3 Page 2 of 3

Reference:

Response to RAI 3.5.2.2-2.

3. The Discussion column entry for LRA Table 3.5.1 (Structures and Component Supports, NUREG-1801 Vol. 1), Item Number 3.5.1-13, Page 3.5-25, is revised to read:

"With proper desig, J T 1 to eraA4CinJ1*4.Auc*,,aa,Acc.

  • A 4AAA . s1 nSot cxnc*

--1-- .......

t. to o.,ur.*.

rnitmp~n+ Pn I-~pt Pr-orrp amwtaa4 A31a a C.ontaiiInJenit I.sefnvec Inspection will continue to be used to detect fac*king. The

.. ,~Jntannn Tan lopt,;p n1/4 T~ ppI+;^"f~i ig ný~5 ;alit iii jp i U4~i.' -+.flJ iAt -q ";p p n4l:" *A detect fine cracks. Not applicable. CNS has a CLB fatigue analysis for these components.

See Section 3.5.2.2.1.8."

Reference:

Response to RAI 3.5.2.2-2.

4. Table 3.5.2-1 (Reactor Building and Primary Containment Summary of Aging Management Evaluation), Page 3.5-58, is revised to read:

Primary PB,SSR Carbon Air- indoor Cracking Gil !WE 1.B4- 3 .51 12 B containment steel uncontrolled Gentainii (C-14) mechanical Leak Rate 3.5.1-9 A penetrations II.B4-4 (includes TLAA- (C--13) those with metal bellows) _fatige

Reference:

Response to RAI 3.5.2.2-2.

5. Section B. 1.18 (Flow Accelerated Corrosion), Exceptions to NUREG-1801, Page B-57 is revised to read:

"Exceptions to NUREG-1801 The FAC Program is consistent with the program described in NUREG-1801,Section XI.M17, Flow-Accelerated Corrosion, with the following exception.

ý . I NLS2009062 Attachment 3 Page 3 of 3 Elements Affected Exception

4. Detection of Aging Effects NUREG-1801 recommends using both ultrasonic (UT) and radiographic testing to detect wall thinning. CNS uses UT for detecting wall thinningefo-ly.

Exception Note

1. This is suffiient be,,aus aAs stated in NSAC-202L Revision 2, both UT and RT methods can be used to investigate whether or not wear is present. However, the UT method provides more complete data for measuring the remaining wall thickness. As a result UT is the preferred method for detecting wall thinning.

The CNS program does not preclude the use of other inspection techniques such as RT if conditions do not permit the use of UT."

Reference:

Clarification based on discussions with Nuclear Regulatory Commission.

inspectors during License Renewal Regional Inspection.