DSAR CHAPTER 10 - STEAM AND POWER CONVERSION SYSTEM TABLE 10-1 Revision 36 Page 1 of 1 TURBINE CASING PROPERTIES Tensile Strength, psi, Min 70,000 Yield Strength, psi, Min 36,000 Elongation in 2 Inches, %, Min 22 Reduction of Area, %, Min 35

DSAR CHAPTER 10 - STEAM AND POWER CONVERSION SYSTEM TABLE 10-2 Revision 36 Page 1 of 1 STUD MECHANICAL PROPERTIES Size, Inches 2-1/2 Over 2-1/2 Over 4 and Less to 4 to 7 Tensile Strength, psi, Min 125,000 115,000 110,000 Yield Strength, psi, Min (0.2% Offset) 105,000 95,000 85,000 Elongation in 2 Inches, %, Min 16 16 16 Reduction of Area, %, Min 50 50 45

DSAR CHAPTER 10 - STEAM AND POWER CONVERSION SYSTEM TABLE 10-4 Revision 36 Page 1 of 2 COOLING TOWER DESIGN

SUMMARY

(SPX MARLEY TOWER E-30A)

Number of Towers 1

Number of Cells 16/Tower Type Induced/Cross Flow Performance at Design Point Hot Water Flow, gpm 185,000 Approach Temperature, °F 112.77 Range, °F 32 Cold Water Temperature, °F 80.77 Fan Brake Horsepower, bhp 166 Pumping Head Above Sill, ft 90 Fans and Fan Motors Number of Fans 16 Number of Blades 9

Blade Diameter, ft 28 Blade Material Fiberglass Reinforced Vinyl Ester Tip Speed, ft/s 196 Fan Speed, r/min 134 Rated hp/Voltage 200/460V

DSAR CHAPTER 10 - STEAM AND POWER CONVERSION SYSTEM TABLE 10-4 Revision 36 Page 2 of 2 COOLING TOWER DESIGN

SUMMARY

(SPX MARLEY TOWER E-30B)

Number of Towers 1

Number of Cells 18/Tower Type Induced/Cross Flow Performance at Design Point Hot Water Flow, gpm 185,000 Approach Temperature, °F 110.9 Range, °F 32 Cold Water Temperature, °F 78.9 Fan Brake Horsepower, bhp 166 Pumping Head Above Sill, ft 90 Fans and Fan Motors Number of Fans 18 Number of Blades 9

Blade Diameter, ft 28 Blade Material Fiberglass Reinforced Vinyl Ester Tip Speed, ft/s 196 Fan Speed, r/min 134 Rated hp/Voltage 200/460V

DSAR CHAPTER 10 - STEAM AND POWER CONVERSION SYSTEM TABLE 10-5 Revision 36 Page 1 of 1 COOLING TOWER PUMPS Number of Pumps 2

Type Vertical, Wet Pit Design Flow, gpm 164,000 Design Head, ft 87 Design NPSH, ft 29 Pump Speed, r/min 253 Motor Type Induction Horsepower, hp 7,000 Voltage 4,160