DSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-1 Revision 36 Page 1 of 1 HISTORIC SERVICE WATER SYSTEM FLOW REQUIREMENTS (gpm)

Component Name Critical Service Water Header CCW Heat Exchangers <6000 Control Room Air Conditioning 12(1)

Instrument Air Compressors (C-2A, C-2C) 16 Alternate to Replenish SFP(3) 40 Noncritical Service Water Header(2)

Instrument Air Compressor C-2B Aftercooler 8 Circ Water and Intake Basin Chlorinator 50 Aux Building Addition Air Conditioning Unit 28.8 Ventilation Equipment Room Air Cooling Unit 28.8 Radwaste Area Compressor 20 Auxiliary Building Condensing Unit 130 FWP Air Compressor 65.2 CD Bldg Boiler Sample (measured) Cooler 1.6 Plant Htg Condensate Return Heat Exchanger (E-924) 100(4)

Radiation Monitors 10 NOTES:

(1)- Only one unit (or set of coolers) is operated at one time.

(2)- Flows listed here are from original Bechtel figures and have not been verified.

(3)- Provisions exist to allow the Service Water System to replenish the Spent Fuel Pool (SFP)

(4)- Flow is temperature controlled.

DSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-2 Revision 36 Page 1 of 2 SERVICE WATER SYSTEM CONSTRUCTION OF COMPONENTS

1. Service Water Pumps Type Vertical Turbine With Water Lubrication Number 3 Material Bowls Cast Iron or Cast Steel or Cast Stainless Steel Discharge Head Carbon Steel Bowl Shaft 416 SS Line Shaft 1045 CS or 416 SS Discharge Column Carbon Steel Impeller Bronze or Stainless Steel Motor 350 hp, 3 Ph, 60 Hz, 2,300 V Codes Standards of Hydraulic Institute, NEMA, ASA and ASTM

DSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-2 Revision 36 Page 2 of 2 SERVICE WATER SYSTEM CONSTRUCTION OF COMPONENTS

2. Basket Strainers Type Simplex Multi-Basket Number 3 Screen Mesh 3/16 in Perforation Material Body Cast Steel Baskets 304 SS
3. Piping, Fittings and Valves Material Carbon Steel, Bronze, Stainless Steel, or Cast Iron & Ductile Iron (non-safety related only)

Piping and Fittings(a) 2-1/2 in and Larger - Butt- Welded Except at Flanged Equipment(a) 2 in and Smaller - Socket Welded Except at Flanged Equipment or Threaded Valves(a) 2-1/2 in and Larger - Butt-Welded 150 lb(a) 2 in and Smaller - Socket Welded 600 lb or Threaded 200 lb or Flanged 150 lb Class Code ASA B31.1-1955 ASA B16.5-1961 (a) These are considered to be classified as flanged equipment.

DSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-3 Revision 36 Page 1 of 3 REACTOR PRIMARY SHIELD COOLING SYSTEM CONSTRUCTION OF COMPONENTS

1. Shield Cooling Coils Length (Each Coil) Approx 24 ft Spacing of Coils 9 in Center-to-Center Number of Coil Sections in Each Set 3 Coil Diameter 3/4 in Material Seamless Carbon Steel Code ASA B31.1
2. Shield Cooling Pumps Type Horizontal Centrifugal With Mechanical Seals Number 2 Material Case Cast Iron Impeller CD4MCU (Stainless Steel)

Shaft Stainless Steel (Solid)

Motor 7.5 hp, 3 Ph, 60 Hz, 460 V, 1750 r/min Codes Standards of Hydraulic Institute, NEMA, ASA and ASTM

DSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-3 Revision 36 Page 2 of 3 REACTOR PRIMARY SHIELD COOLING SYSTEM CONSTRUCTION OF COMPONENTS

3. Shield Cooling Heat Exchanger Type Horizontal Counterflow, Shell With Straight Tubes Rolled Into Fixed Tube Sheets Number 1 Material Shell Carbon Steel Tubes Admiralty Channels Carbon Steel Tube Sheets Aluminum Bronze Codes ASME B&PV Code,Section III, Class C and ASME B&PV Code,Section VIII, Par UW-2 (a);

TEMA Class C

4. Shield Cooling Surge Tank Type Vertical Number 1 Material Carbon Steel Code ASME B&PV Code Section III, Class C and ASME B&PV Code,Section VIII, Par UW-2 (a)

DSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-3 Revision 36 Page 3 of 3 REACTOR PRIMARY SHIELD COOLING SYSTEM CONSTRUCTION OF COMPONENTS

5. Piping, Fittings and Valves Material Seamless Carbon Steel Not Embedded in Embedded In Concrete Concrete Construction Pipe, 2-1/2 in and Larger Butt-Welded Except None at Flanged Equipment Pipe, 2 in and Smaller Screwed Except at Socket Flanged Equipment Welded Valves, 2-1/2 in and Larger Cast Iron, None Flanged 125#

Valves, 2 in and Smaller Bronze, Screwed None 200# and Carbon Steel, flanged 150#

Code ASA B31.1

DSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-4 Revision 36 Page 1 of 1 COMPONENT COOLING SYSTEM HEAT LOADS (x 106 Btu/hr)

Component and (Number)

Spent Fuel Pool HX (1) 9.2 Waste Gas Compressors (3) 0.01 Total 9.21

DSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-5 Revision 36 Page 1 of 2 COMPONENT COOLING WATER SYSTEM CONSTRUCTION OF COMPONENTS

1. Component Cooling Pumps Type Horizontal Centrifugal With Mechanical Seals Number 3 Material Case Carbon Steel Impeller Bronze Shaft Alloy Steel Motor 300 hp, 3 Ph, 60 Hz, 2,300 V Codes Standards of Hydraulic Institute, NEMA, ASA and ASTM
2. Component Cooling Heat Exchangers Type Horizontal, Counterflow, Shell Straight Tubes, Tubes Rolled Into Tube Sheets Number 2 Original Heat Transfer Area (Each) 7,840 ft2 Material Shell Side Carbon Steel, Firebox Quality Tube Side Admiralty Tube Sheet Carbon Steel With Aluminum Bronze Overlay Codes ASME B&PV Code,Section III, Class C, 1965 and ASME B&PV Code,Section VIII, Par UW-2 (a); TEMA Class C

DSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-5 Revision 36 Page 2 of 2 COMPONENT COOLING WATER SYSTEM CONSTRUCTION OF COMPONENTS

3. Surge Tank Type Vertical Number 1 Material Carbon Steel Code ASME B&PV Code,Section III, Class C, 1965
4. Piping, Fittings and Valves Piping Material Carbon Steel, Seamless and Seam Welded (Seam Weld 100% Radiographed)

Inside Outside Containment Containment Construction Pipe, 2-1/2 in and Larger Butt-Welded Except Butt-Welded at Flanged Equipment, Except at 10% of Circumferen- Flanged tial Welds Examined Equipment by Radiography Pipe, 2 in and Smaller Socket Welded Screwed Except-Except Flanged at Flanged Equipment Equipment Valves (Except Butterfly), Carbon Steel, Cast Iron, 2-1/2 in and Larger Butt Weld Flanged Ends, 150# Ends, 125#

Butterfly Valves, Carbon Steel, Carbon Steel, 2-1/2 in and Larger Flanged Ends, 150# Flanged Ends, 150#

Valves, 2 in and Smaller Carbon Steel, Socket Bronze, Welded Ends, Screwed 600# Ends, 200#

Code ASA B31.1-1955 ASA B31.1-1955 ASA B16.5-1961 ASA B16.5-1961

DSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-6 Revision 36 Page 1 of 1 COMPONENT COOLING SYSTEM REQUIRED FLOW RATES (GPM)

Component and (Number) Normal Spent Fuel Pool HX (1) *** 650 Waste Gas Compressors (3) 6 Vacuum Degasifier Pump Seal 8 Water Cooler (1)

Total 664

DSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-7 Revision 36 Page 1 of 4 SPENT FUEL POOL COOLING SYSTEM DESIGN RATINGS AND CONSTRUCTION OF COMPONENTS

1. Fuel Pool Cooling Pumps Type Horizontal Centrifugal With Mechanical Seals Number 2 Capacity (Each) 1,700 gpm TDH 64 ft Temperature Transient Designed To Withstand an Increase from 60qF to 212qF in 5 Seconds Material Stainless Steel Motor 40 hp, 460 V, 60 Hz 3 Ph, Code Motor, NEMA; Pump, Standards of Hydraulic Institute
2. Spent Fuel Pool Cooling Heat Exchange Unit Type Horizontal Counterflow, With Straight Tubes Rolled Into Tube Sheets Number 2 Shells in Series Original Duty (Total) 23 x 106 Btu/h Original Heat Transfer Area 4,080 ft2 Component Cooling Water Temperature: In/Out 90/115qF Spent Fuel Cooling Water Temperature: In/Out 125/110qF Temperature Transient Designed To Withstand an Increase From 60qF to 212qF in 5 Seconds

DSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-7 Revision 36 Page 2 of 4 SPENT FUEL POOL COOLING SYSTEM DESIGN RATINGS AND CONSTRUCTION OF COMPONENTS Material Shells Carbon Steel Tubes Stainless Steel Tube Sheets Stainless Steel With SS 308L Weld Overlay Codes ASME B&PV Code,Section III, Class C and ASME B&PV Code,Section VIII, Par UW2 (a);

TEMA Class C

3. Fuel Pool Recirculation Booster Pump Type Horizontal Centrifugal With Mechanical Seals Number 1 Capacity 160 gpm TDH 160 ft Temperature Transient Designed To Withstand Increase From 60qF to 212qF in 5 Seconds Material Type 316 Stainless Steel Motor 15 hp, 3 Ph, 60 Hz 460 V Code Motor, NEMA; Pump, Standards of Hydraulic Institute

DSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-7 Revision 36 Page 3 of 4 SPENT FUEL POOL COOLING SYSTEM DESIGN RATINGS AND CONSTRUCTION OF COMPONENTS

4. Fuel Pool Filter Type Cartridge With Replaceable Filter Element Number 1 Design Flow 150 gpm Design Pressure 200 psig Design Temperature 250qF Temperature Transient Designed for Increase From 60qF to 212qF in 5 Seconds Filter Rating 25 Microns Nominal Material Stainless Steel Codes ASME B&PV Code,Section III, Class C and ASME B&PV Code,Section VIII, Par UW2 (a)
5. Fuel Pool Demineralizer Type Mixed Bed Number 1 Design Flow 150 gpm Design Pressure 200 psig Design Temperature 220qF Temperature Transient Design for an Increase From 60qF to 212qF in 5 Seconds Resin Equivalent Capacity Mixture of Nuclear Grade Cation and Anion

DSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-7 Revision 36 Page 4 of 4 SPENT FUEL POOL COOLING SYSTEM DESIGN RATINGS AND CONSTRUCTION OF COMPONENTS Material Type 304 Stainless Steel for Vessel and Integral Parts Codes ASME B&PV Code,Section III, Class C and ASME B&PV Code,Section VIII, Par UW2 (a)

6. Piping, Fittings and Valves Material Stainless Steel Design Pressure 125 psig Design Temperature 150qF Joints, 2 in and Larger ButtWelded Except at Flanged Equipment 1-1/2 in and Smaller Socket Welded Except at Flanged Equipment Valves, 2 in and Larger Stainless Steel, Butt Weld Ends, 150#

11/2 in and Smaller Stainless Steel, Socket Weld Ends, 150#

Butterflies, All Sizes Stainless Steel Flanged, 150#

Code ASA B31.1 Welds 100% Radiographically Checked

7. Spent Fuel Pool Volume of Empty SFP Cavity 21,885 ft3 Volume of Empty North Tilt Pit Cavity 4,095 ft3

DSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-8 Revision 36 Page 1 of 5 INSTRUMENT AIR SYSTEM DESIGN RATINGS AND CONSTRUCTION OF COMPONENTS

1. Instrument Air System
a. Air Compressors Type Rotary Screw, Oil Free, Air Cooled Number 3 Design Capacity (Each) 288 scfm Design Pressure 125 psig Main Motor (Compressor) 75 hp, 3 Ph, 60 Hz, 460 V Fan Motor 5 hp, 3 Ph, 60 Hz, 460 V Code Motor, NEMA
b. Aftercoolers
1. Type Shell and Tube Number 3 (1 per Compressor)
2. Type Cooling Coil Number 3 (1 per Compressor - onboard)
c. Air Receivers Type Vertical Number 3 Design Pressure 125 psig Capacity 57 ft3 Code ASME B&PV Code,Section VIII

DSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-8 Revision 36 Page 2 of 5 INSTRUMENT AIR SYSTEM DESIGN RATINGS AND CONSTRUCTION OF COMPONENTS

d. Air Dryer Type Silica Gel Absorbent, Electric Heater Reactivated Number 1 Capacity 205 scfm Outlet Moisture Content With Saturated Air Inlet -40°F Dew Point at 100 psig Code ASME B&PV Code,Section VIII
e. Piping and Valves Upstream of Dryer Carbon Steel Piping and CI, or Bronze Valves Downstream of Dryer Copper Piping and Bronze or Stainless Steel Valves Except at Containment Penetration and at Isolation Valves (Carbon Steel)

Code ASA B31.1

2. High Pressure Air System
a. Air Compressors Type Single Acting, Air Cooled Number 3 Design Capacity (Each) 22.3 scfm Design Pressure 325 psig Motor 10 hp, 440 V, 3 Phase Code Motor, NEMA

DSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-8 Revision 36 Page 3 of 5 INSTRUMENT AIR SYSTEM DESIGN RATINGS AND CONSTRUCTION OF COMPONENTS

b. Air Dryer Type Desiccant Number 3 (1 per Compressor)

Capacity (Each) 35 scfm Dewpoint -40 °F at 350 psig Code ASME B&PV Code,Section VIII

c. Air Receivers Type Horizontal Number 3 (1 per Compressor)

Design Pressure 350 psig Capacity 60 ft3 Code ASME B&PV Code,Section VIII

d. Aftercoolers Number 3 (1 per Compressor)

Type Air Cooled

e. Piping Material Carbon Steel Code ASA B31.1 (Seismic Class I Supported From Receivers to Operators on Engineered Safe-guards Systems)

DSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-8 Revision 36 Page 4 of 5 INSTRUMENT AIR SYSTEM DESIGN RATINGS AND CONSTRUCTION OF COMPONENTS

3. Feedwater Purity Air System
a. Air Compressors Type Two stage air screw, oil free Number 2 Design Capacity (Each) 297 scfm Design Pressure 117 psi Motor 75 hp, 460 V, 3 Phase Air Dryer (Integral to Compressor)

Type Refrigerant Power Consumption (at full load) 1.6 kW Pressure 102 psig Dew Point 37.4°F @ 68°F/100% RH

c. Aftercooler Number 2 Type Air Cooled
d. Receiver Type Vertical Number 1 Design Pressure 150 psig Design Temp 100°F Capacity 1060 gal Code ASME B&PV Code,Section VIII

DSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-8 Revision 36 Page 5 of 5 INSTRUMENT AIR SYSTEM DESIGN RATINGS AND CONSTRUCTION OF COMPONENTS

4. Nitrogen Backup Stations
a. Nitrogen Bottles Pressure (nominal) 2400 psig

DSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-9 Revision 36 Page 1 of 2 EFFECT OF LOSS OF AIR TO AIR-OPERATED VALVES Position Safety (a) After Loss No Valve Description Position of Air Service Water System CV-0821 CCW Heat Exchanger Temp Control C C CV-0822 CCW Heat Exchanger Temp Control C C CV-0823 Component Cool HX Dischg O O CV-0824 Return From Containment Coolers O/C O CV-0825 Eng Safe Room Cooler Supply O O CV-0826 Component Cool HX Dischg O O CV-0844 Critical Service Wtr Header Iso O O CV-0845 Critical Service Wtr Header Iso O O CV-0846 Critical Service Water Header Cross Connect O O CV-0847 Supply to Containment Coolers O O CV-0857 Critical Service Water Header Cross Connect O O CV-0861 8" Return From Cont Coolers O O CV-0862 Containment Cooler Supply O O CV-0864 8" Return From Cont Coolers O O CV-0865 Containment Cooler Supply O O CV-0867 8" Return From Cont Coolers O O CV-0869 Containment Cooler Supply C C CV-0870 Containment Cooler Supply O O CV-0873 8" Return From Cont Coolers O O CV-0876 Diesel Generator Cool Supply O O CV-0877 Diesel Generator Cool Supply O O CV-0878 Eng Safe Room Cooler Supply O O CV-0879 Backup Cool Safeguards Pumps C C CV-0880 Backup Cool Safeguards Pumps C C CV-0884 Diesel Generator Cool Supply O O CV-0885 Diesel Generator Cool Supply O O CV-1318 Service Water Pump Header Iso O O CV-1319 Service Water Pump Header Iso O O CV-1359 Noncritical Service Water Header Isolation C C CV-1655 Control Room HVAC Service Water O O CV-1656 Control Room HVAC Service Water O O (a) Safety position is maintained in this table, but safety is no longer applicable as none of the systems are safety-related.

O Open C Closed

DSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-9 Revision 36 Page 2 of 2 EFFECT OF LOSS OF AIR TO AIR-OPERATED VALVES Position Safety (a) After Loss No Valve Description Position of Air Component Cooling System CV-0915 Comp Cool Surge Tank Vent C C CV-0944 Supply to Radwaste Evaporator C C CV-0944A Supply to Spent Fuel HX C C CV-0945 Supply to Comp Cool HX O O CV-0946 Supply to Comp Cool HX O O CV-0977B Return From Radwaste Evaporator C C Radioactive Waste Treatment System CV-1001 Primary System Drain Tank Recirc C C CV-1002 Primary System Drain Tank Outlet C C CV-1004 Degasifier Pump Discharge C C CV-1007 Primary System Drain Tank Outlet C C CV-1036 Pump P-70 Inlet C C CV-1037 Clean Waste Tank Recirc C C CV-1038 Pump P-70 Inlet C C CV-1044 Pump P-69 A/B Suction C C CV-1045 Pump P-69 A/B Suction C C CV-1064 Clean Waste Tank Vent C C CV-1065 Clean Waste Tank Vent C C CV-1101 Waste Gas Surge Tank Vent C C CV-1102 Waste Gas Surge Tank Vent C C CV-1103 Containment Sump Drain C C CV-1104 Containment Sump Drain C C (a) Safety position is maintained in this table, but safety is no longer applicable as none of the systems are safety-related.

O Open C Closed

DSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-10 Revision 36 Page 1 of 3 FIRE DETECTION INSTRUMENTATION INSTRUMENT LOCATION DETECTORS TYPE OF DETECTORS

1. Cable Spreading Rm, Col M-28 1 Water Flow Sw (WFS-2B)
2. 1-D Switchgear Rm, Col G-28; Col G-22; Col G-22 4 Water Flow Sw (WFS-2B1, WFS-2B2, WFS-2B3, WFS-2D)
3. 1-1 Diesel Generator Rm , Col J-28 1 Water Flow Sw (WFS-2G1)
4. 1-2 Diesel Generator Rm , Col M-28 1 Water Flow Sw (WFS-2G2)
5. Turbine Bldg 590', Col H-9 1 Water Flow Sw (WFS-2I)
6. Control Room (Room 325) 8 Smoke
7. Control Room Adj Offices Rms 324 & 320 2 Smoke
8. Cable Spreading, Room 224 13 Smoke
9. Refueling & Spent Fuel Area, Rm 220 4 Smoke
10. 1-D Switchgear Rm, Rm 223 9 Smoke
11. North Penetration, Rm 332 2 Smoke

DSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-10 Revision 36 Page 2 of 3 FIRE DETECTION INSTRUMENTATION INSTRUMENT LOCATION DETECTORS TYPE OF DETECTORS

12. 1-C Switchgear Rm, Rm 116A 2 Smoke
13. Southwest Cable Penetration, Rm 250 2 Smoke
14. Engineered Safeguards Panel Area, Rm 121 3 Smoke
15. Stairwell Outside Engineered Safeguards Panel Area, Rm 016 2 Smoke
16. Component Cooling Pump, Rm 123 2 Smoke
17. Safeguard Area, Rm 4 3 Smoke
18. Safeguard Area, Rm 5 2 Smoke
19. Corridor 106 on 590' Elevation, Rm 106 6 Smoke
20. Charging Pump, Rm 104 2 Smoke
21. Containment, Interior North Penetration Area, Rm 332 3 Smoke
22. Containment, Interior SW Penetration Area, Rm 141, 250 3 Smoke
23. Containment Instrument Air Room 3 Smoke
24. Auxiliary Feed Pump Room 570' Level of Turbine Bldg, 3 Smoke Rm 007
25. Battery Rm 225A 1 Smoke

DSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-10 Revision 36 Page 3 of 3 FIRE DETECTION INSTRUMENTATION INSTRUMENT LOCATION DETECTORS TYPE OF DETECTORS

26. Battery Rm 225B 1 Smoke
27. HVAC Equipment Rooms & Chase: Smoke West Mechanical Equipment Room 300 1 Smoke East Mechanical Equipment Room 300A 1 Smoke Duct Chase, Rm 300B 1
28. Air Handling Unit V-95 & V-96 Inlet Ducts, Rm 300, 300A 2 Smoke
29. Electrical Equipment Room, Rm 725 6 Smoke
30. Technical Support Center, Rm 320A 2 Smoke
31. Intake Structure, Room 136 11 Ultraviolet
32. Charging Pump Rooms 104, 104A, and 104B 1 Water Flow Sw (WFS-2J)
33. Diesel - Driven Auxiliary Feedwater Pump Shed 2 Fire & Flame Det.

1 Water Flow Sw

DSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-11 Revision 36 Page 1 of 3 FIRE PROTECTION SYSTEM DESIGN RATINGS AND CONSTRUCTION OF COMPONENTS

1. Fire Pump, Motor Driven Type Vertical Turbine Number 1 Capacity 1,500 gpm Discharge Pressure 125 psig Material Discharge Head Cast Iron Impeller Bronze Motor 150 hp, 460 V, 3 Ph, 60 Hz Codes Underwriters Lab Label Motor, NEMA; Pump, Standards of Hydraulic Institute
2. Fire Pump, Diesel Engine Driven Type Vertical Turbine Number 2 Capacity 1,500 gpm Discharge Pressure 125 psig Material Discharge Head Cast Iron Impeller Bronze Gear Drive Reduction Ratio 1:1, 200 hp Rating Diesel Engine 150 hp Codes Underwriters Lab Label Diesel Engine, NEMA; Pump, Standards of Hydraulic Institute

DSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-11 Revision 36 Page 2 of 3 FIRE PROTECTION SYSTEM DESIGN RATINGS AND CONSTRUCTION OF COMPONENTS

3. Fire System Jockey Pump Type Vertical Turbine Number 1 Capacity 50 gpm Discharge Pressure 117 psig nominal Material Discharge Head Fabricated Steel Impellers Bronze Motor 7-1/2 hp, 460 V, 3 PH, 60 Hz Codes Motor, NEMA; Pump Standards of Hydraulic Institute
4. Piping, Fittings and Valves
a. To Auxiliary Feedwater Pump Suction Header and Critical Service Waterlines Material Seamless Carbon Steel Design Pressure 125 psig Design Temperature 100°F Construction Butt-Welded Except at Flanged Equipment Valves Carbon Steel, Butt-Weld Ends, 150#,

or Cast Iron, Flanged End, 175#,

Underwriters lab Label

DSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-11 Revision 36 Page 3 of 3 FIRE PROTECTION SYSTEM DESIGN RATINGS AND CONSTRUCTION OF COMPONENTS

b. To Spent Fuel Pool Blind Flange and Normal Fire Protection Service Underground Aboveground Material Original- Cast Iron Carbon Steel (150# Class)

Replacement- Ductile Iron (350# Class)

Design Pressure 150 psig 125 psig Design Temperature 100°F 100°F Construction Original- Mechanical Joint Butt-Welded Except at Flanged Equipment Replacement- Push-on Joint Valves Original- Cast Iron, Cast Iron, Flanged Mechanical Joint, End, 175#,

175#, Underwriters Underwriters Lab Lab Label Label Replacement- Ductile Iron, Mechanical Joint, 250#, UL Listed, FM Approved

DSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-12 Revision 36 Page 1 of 4 AUXILIARY FEEDWATER SYSTEM CONSTRUCTION OF COMPONENTS

1. Motor-Driven Auxiliary Feedwater Pump (P-8A)

Type Horizontal Centrifugal, With Packed Glands Number 1 Material Case 4.6% Chrome Alloy Steel Impeller Bronze Shaft 11%-13% Chrome Alloy Steel Motor 450 hp, 3 Ph, 60 Hz, 2,300 V Codes Motor, NEMA; Pump, Standards of Hydraulic Institute, 11th Edition, 1965

2. Turbine-Driven Auxiliary Feedwater Pump (P-8B)

Type Horizontal Centrifugal, With Packed Glands Number 1 Material Case 4.6% Chrome Alloy Steel Impeller Bronze Shaft 11%-13% Chrome Alloy Steel Turbine Single Stage, Axial Flow, Exhaust to Atmosphere, 450 hp Codes Turbine, NEMA; Pump, Standards of Hydraulic Institute, 11th Edition, 1965

DSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-12 Revision 36 Page 2 of 4 AUXILIARY FEEDWATER SYSTEM CONSTRUCTION OF COMPONENTS

3. Motor Driven Auxiliary Feedwater Pump (P-8C)

Type Horizontal Centrifugal, With Mechanical Seals Number 1 Material Case 18 Cr, 8 Ni Stainless Steel Impeller 12 Cr Stainless Steel Shaft 12 Cr, 0.6 Mo Stainless Steel Motor 400 hp, 3 Ph, 60 Hz, 2,300 V Codes Motor, NEMA; Pump, Standards of Hydraulic Institute, 11th Edition, 1965

4. Piping and Valves for P-8A, P-8B, and P-8C
a. Pump Suction Underground Aboveground Material 304 Stainless Steel Carbon Steel Construction Welded Except at Flanged Equipment Connections Valves 2-1/2 in and Larger - Carbon Steel, Butt-Welded, 150#

Valves 2-1/2 in and Smaller - Carbon Steel, Socket Welded, 600#

Code ASA B31.1-1955 ASA B31.1-1955 ASA B16.5-1961 ASA B16.5-1961

DSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-12 Revision 36 Page 3 of 4 AUXILIARY FEEDWATER SYSTEM CONSTRUCTION OF COMPONENTS

b. Pump Discharge Underground Aboveground Material 304 Stainless Steel Carbon Steel Upstream Downstream of FW of FW Control Control Valve Valve Construction Welded Except at Flanged Equipment Only Valves 2-1/2 in and Larger - Carbon Steel, Butt-Welded, 600#

Valves 2-1/2 in and Smaller - Carbon Steel, Socket Welded, 600#

Code ASA B31.1-1955 ASA B31.1-1955 ASA B16.5-1961 ASA B16.5-1961

c. Auxiliary Turbine Steam Supply Piping and Valves Same as for Aboveground Pump Discharge Piping
5. Diesel-Driven Auxiliary Feedwater Pump (P-8D)

Type Horizontal Centrifugal, with Mechanical Seals Number 1 Diesel Engine (K-17) 800 hp, Starter with Storage Batteries Codes NFPA 20, NFPA 37, UL 1247

DSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-12 Revision 36 Page 4 of 4 AUXILIARY FEEDWATER SYSTEM CONSTRUCTION OF COMPONENTS

6. Piping and Valves for P-8D
a. Pump Section Underground Aboveground Material 304 Stainless Steel Carbon Steel Construction Welded Except at Flanged Equipment Connections Valves 2-1/2 in and Larger Carbon Steel, Butt-Welded, 150#

Valves 2-1/2 in and Smaller Carbon Steel, Butt-Welded, 600#

Code ASA B31.1 1-2012 for procurement ASA B31.1 1-1973 for qualification

b. Pump Discharge Underground Aboveground Material 304 Stainless Steel Carbon Steel Construction Welded, Except Flanged at Material Transition Valves 2-1/2 in and Larger Carbon Steel, Butt-Welded, 900#

Valves 2-1/2 in and Smaller Carbon Steel, Butt-Welded,1500#

Code B31.1 (1973) B31.1 (1973)

DSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-13 Revision 36 Page 1 of 1 DESIGN BASIS AMBIENT CONDITIONS HVAC Original Design Winter, °F Summer, °F Location Outside Inside Outside Inside Turbine Building Operating Floor (EEQ Harsh Area) -10 50 95 104 Piping Area (EEQ Harsh Area) -10 50 95 110 Shops and Offices -10 65 95 104 Auxiliary Building (Non-EEQ Harsh Areas)

Radwaste Area and Radwaste Area Addition -10 50 95 110 Fuel Handling Area and Fuel Handling Area

-10 50 95 104 Addition Office Area -10 75 95 75 Auxiliary Building (EEQ Harsh Areas)

Room 123 (590 Component Cooling) (Note 1) -10 50 95 104 Room 238 (607-6 Containment Purge Exhaust) (Note 1) -10 50 95 104 Room 338 (625 Containment Purge Air Fan) (Note 1) -10 50 95 104 Containment Building (EEQ Harsh Area) -10 50 95 104 Control Room (Non-EEQ Harsh Area) (Note 2) -10 75 95 75 Condensate and Makeup Demineralizer Building -

Non-EEQ Harsh Areas Process and Equipment Area -10 50 90 104 Covered Receiving and Loading Area -10 50 90 104 Boiler Room -10 50 90 104 Pipe Gallery -10 50 90 104 Instrument Room -10 75 90 90 Note 1: Rooms 123, 238 and 338 have a design temperature of 120°F per M-391, Specification for Installation of Ventilation Equipment and Ductwork Penetration and Fans Rooms.

Note 2: The relative humidity in the control room is 50%

DSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-14 Revision 36 Page 1 of 3 CONTROL ROOM HVAC SYSTEM MAJOR COMPONENT DESIGN DATA Makeup/Recirculation Air Filter Units Quantity Two - 100% Capacity Each Capacity 3,200 ft3/min Filters (per Filtering Unit)

Prefilter Quantity 3 Media Glass Fiber or Knitted Pad HEPA Filter Quantity 3 Upstream Filters 3 Downstream Filters Media Glass Fiber Charcoal Filter Trays Quantity 18 [2 Banks of 9]

Media Activated Carbon, 4 in. Bed Depth (Two-2 inch deep Trays in Series)

Fan Type Vaneaxial Fan Static Pressure at Rating, in wg 10 in Motor 20 hp, 460 V, 3 Ph Filter Test Efficiency HEPA 99.97% of Particulate Carbon Adsorber 99.9% of Elemental Iodine Electric Heating Coil Type Nickel/Chromium Capacity 15 kW, 480 V, 3 Ph Air Filter Unit Assembly

'P of wg 8.00 in (Maximum)

NOTE: All electrical equipment is Class 1E unless otherwise noted.

DSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-14 Revision 36 Page 2 of 3 CONTROL ROOM HVAC SYSTEM MAJOR COMPONENT DESIGN DATA Air Handling Unit V-95 or V-96 Type Package (Filter, Cooling Coil, Fan)

Capacity 12,500 ft3/min Cooling Coil Type Direct Expansion Refrigerant Capacity (Total) 603,500 Btu/h Heating Coil (Nonclass 1E)

Type 80% Nickel and 20% Chromium Capacity 177 kW, 480 V, 3 Ph Fan Type Centrifugal Total Pressure, wg 3.85 in Motor 25 hp, 460 V, 3 Ph Filter Type, Media 6 in Thick Moderate Efficiency Prefilter P of wg (Clean) 0.25 in Refrigerant Condensing Unit Type Water-Cooled Reciprocating Refrigerant R-22 Compressor Type Reciprocating, 4 Cylinder Motor 60 hp, 460 V, 3 Ph Capacity 554,400 Btu/h @ 85 °F, 39 gpm Service Water Condenser Water Flow Set per RO-216 NOTE: All electrical equipment is Class 1E unless otherwise noted.

DSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-14 Revision 36 Page 3 of 3 CONTROL ROOM HVAC SYSTEM MAJOR COMPONENT DESIGN DATA Smoke Purge Exhaust Fan V-94 (Nonclass 1E)

Type Vaneaxial Capacity 7,800 ft3/min Motor 7-1/2 hp, 460 V, 3 Ph Exhaust Fan V-16 (Existing)

(Nonclass 1E)

Type Centrifugal Capacity 160 ft3 /min Motor 1/12 hp, 120 V, 1 Ph Humidifiers VH-12 and VH-13 (Nonclass 1E)

Type Steam Generator Capacity 50 lb/h (17 kW, 480 V, 3 Ph)

NOTE: All electrical equipment is Class 1E unless otherwise noted.

DSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-15 Revision 36 Page 1 of 7 VENTILATION DAMPERS: FUNCTIONS AND POSITIONS FOR VARIOUS MODES OF PLANT OPERATION Position Position After After Damper Description Normal Position Auto Actuation Loss of Air Control Room D-1 Normal Outside Air - Open - Train A NA Close Train A Close - Train B D-2 Normal Outside Air - Modulate - Train A NA Close Train A Close - Train B D-3 Normal Recirc Air - Open NA Open Train A D-4 Supply Air Back Open - Train A NA NA Draft Dampers - Close - Train B (Back Draft)

Train A D-5 Charcoal Filter Unit Close NA NA Supply Air - Train A (Back Draft)

D-6 Charcoal Filter Unit Close NA Open Return Air - Train A

DSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-15 Revision 36 Page 2 of 7 VENTILATION DAMPERS: FUNCTIONS AND POSITIONS FOR VARIOUS MODES OF PLANT OPERATION Position Position After After Damper Description Normal Position Auto Actuation Loss of Air D-7 Charcoal Filter Unit Close NA NA Outside Air - (Elect Op FAI)

Train A D-8 Normal Outside Air - Open - Train B NA Close Train B Close - Train A D-9 Normal Outside Air - Modulate - Train B NA Close Train B Close - Train A D-10 Normal Recirc Air - Open NA Close Train B D-11 Supply Air Back Open - Train B NA NA Draft Damper - Close - Train A (Back Draft)

Train B D-12 Charcoal Filter Unit Close NA NA Supply Air - (Back Draft)

Train B

DSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-15 Revision 36 Page 3 of 7 VENTILATION DAMPERS: FUNCTIONS AND POSITIONS FOR VARIOUS MODES OF PLANT OPERATION Position Position After After Damper Description Normal Position Auto Actuation Loss of Air D-13 Charcoal Filter Unit Close NA Close Return Air -

Train B D-14 Charcoal Filter Unit Close NA NA Outside Air - (Elect Op FAI)

Train B D-15 Purge Fan Isolation Close NA Close D-16 Purge Fan Isolation Close NA Close D-17 Exhaust Fan V-16 Open NA Close Isolation D-18 Exhaust Fan Open NA Close Isolation D-19 Number Not Used - - -

D-20 Charcoal Filter Flow Open NA Open Control - Train A

DSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-15 Revision 36 Page 4 of 7 VENTILATION DAMPERS: FUNCTIONS AND POSITIONS FOR VARIOUS MODES OF PLANT OPERATION Position Position After After Damper Description Normal Position Auto Actuation Loss of Air D-21 Charcoal Filter Flow Open NA Open Control - Train B Radioactive Waste Area and Engineered Safeguards Rooms PO-3010 Fresh Air Supply Open Close on Trip of Close Fan V-10 PO-1809 Radwaste Area Supply Open Close (RE-1809) Close PO-1839 Radwaste Area Open Close on Trip of Close Exhaust Fan V-14A PO-1840 Radwaste Area Open Close on Trip of Close Exhaust Fan V-14B PO-1817 East Safeguards Open NA Close Room Supply PO-1810 East Safeguards Open NA Close Room Exhaust

DSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-15 Revision 36 Page 5 of 7 VENTILATION DAMPERS: FUNCTIONS AND POSITIONS FOR VARIOUS MODES OF PLANT OPERATION Position Position After After Damper Description Normal Position Auto Actuation Loss of Air PO-1812 West Safeguards Open NA Close Room Supply PO-1811 West Safeguards Open NA Close Room Exhaust Auxiliary Building Addition Radwaste Area Ventilation System PO-8006 Fresh Air Supply Open Close on Trip of Close Fan V-67 PO-8016A Radwaste Add Open Close on Trip of Close Exhaust Fan V-68A PO-8016B Radwaste Add Open Close on Trip of Close Exhaust Fan V-68B

DSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-15 Revision 36 Page 6 of 7 VENTILATION DAMPERS: FUNCTIONS AND POSITIONS FOR VARIOUS MODES OF PLANT OPERATION Position Position After After Damper Description Normal Position Auto Actuation Loss of Air Fuel Handling Area Damper PO-3007 is normally open and fails closed on loss of instrument air.

Auxiliary Building Addition Fuel Handling Area Ventilation System PO-8001 Fresh Air Supply Open Close on Trip of Close Fan V-69 PO-8013A Fuel Handling Add Open Close on Trip of Close Exhaust Fan V-70A PO-8013B Fuel Handling Add Open Close on Trip of Close Exhaust Fan V-70B Penetration and Fan Rooms Heating and Ventilation System PO-8035 Outside Air Supply Open Close (RIA-5710) Close PO-8036 Exhaust Open Close (RIA-5710) Close

DSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-15 Revision 36 Page 7 of 7 VENTILATION DAMPERS: FUNCTIONS AND POSITIONS FOR VARIOUS MODES OF PLANT OPERATION Position Position After After Damper Description Normal Position Auto Actuation Loss of Air Containment CV-1813 Air Space Purge Open / Close NA Close Supply CV-1814 Air Space Purge Open / Close NA Close Supply CV-1806 Cont Purge Exhaust Open / Close NA Close CV-1805 Cont Purge Exhaust Open / Close NA Close CV-1808 Cont Purge Exhaust Open / Close NA Close CV-1807 Cont Purge Exhaust Open / Close NA Close

DSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-16 Revision 36 Page 1 of 1 SAMPLING STATIONS NSSS Sampling Station Containment Hydrogen Monitoring System Turbine Analyzer Panel Radwaste Sampling Station Waste Gas Sample Panel Radwaste Addition Sampling System

DSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-17 Revision 36 Page 1 of 1 SAMPLE POINT

SUMMARY

1. Radwaste Sampling Station Primary System Drain Tank Recirc Grab Sample Equipment Drain Tank Recirc Grab Sample Vacuum Degasifier Pump Discharge Grab Sample Receiver Tank Pumps Discharge Grab Sample Receiver Tank Circ Pumps Discharge Grab Sample Radwaste Demin Tanks Outlet (3) Grab Sample Treated Waste Mon Tanks Recirc (2) Grab Sample Controlled Chem Lab Drain Tank Grab Sample Filtered Waste Monitor Tank Recirc Grab Sample Dirty Waste Drain Tank Recirc Grab Sample Component Cooling Pumps Discharge Grab Sample
2. Waste Gas Sample Panel Volume Control Tank Bomb Waste Gas Surge Tank Bomb Waste Gas Decay Tanks (6) Bomb Spurt Resin Storage Tank Bomb
3. Radwaste Addition Sampling System Radwaste Polishing Demineralizer Discharge Grab Sample, Conductivity Clean Waste Transfer Pump Discharge Grab Sample Clean Waste Distillate Pump Discharge Grab Sample Misc Waste Distillate Pumps Discharge (2) Grab Sample Misc Waste Demineralizer Tank Discharge (2) Grab Sample, Conductivity (1)

Misc Waste Transfer Pumps Discharge (2) Grab Sample Misc Waste Filter Inlet Grab Sample Misc Waste Filter Discharge (2) Grab Sample Primary System Makeup Water Pump Discharge Grab Sample Utility Water Transfer Pump Discharge Grab Sample Spurt Resin Storage Tank Gas Bomb Waste Gas Decay Tanks (3) Bomb Radwaste Evaporator Distillate (2) Grab Sample

DSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-18 Revision 36 Page 1 of 11 CHEMICAL AND VOLUME CONTROL SYSTEM DESIGN PARAMETERS 1.1 Regenerative Heat Exchanger - E-56 Quantity 1 Type Shell and Tube, Vertical Normal Heat Transfer 6.6 x 106 Btu/h Code ASME B&PV Code,Section III, Class C, 1965 Shell Side (Charging)

Fluid 15,000 ppm Boric Acid, Maximum (Design)

Design Pressure 2,735 psig Design Temperature 650qF Material Stainless Steel Tube Side (Letdown)

Fluid 15,000 ppm Boric Acid, Maximum (Design)

Design Pressure 2,485 psig Design Temperature 650qF Material Stainless Steel

DSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-18 Revision 36 Page 2 of 11 CHEMICAL AND VOLUME CONTROL SYSTEM DESIGN PARAMETERS 1.2 Letdown Orifice - RO-2003, RO-2004 and RO-2005 Quantity 3 Capacity (Each) 40 gpm Design Pressure 2,485 psia Design Temperature 650qF Material Stainless Steel 1.3 Letdown Heat Exchanger - E-58 Quantity 1 Type Shell and Tube, Horizontal Design Heat Transfer 19.1 x 106 Btu/h Code ASME B&PV Code,Section III, Class C Tube Side (Letdown)

Fluid 15,000 ppm Boric Acid, Maximum (Design)

Design Pressure 650 psig Design Temperature 550qF Material Stainless Steel Shell Side (Cooling Water)

Fluid Component Cooling Water Design Pressure 150 psig Design Temperature 250qF

DSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-18 Revision 36 Page 3 of 11 CHEMICAL AND VOLUME CONTROL SYSTEM DESIGN PARAMETERS Material Carbon Steel 1.4 Process Radiation Monitor - Element RE-0202 Quantity 1 Design Pressure 200 psig Design Temperature 250qF Code ASA B31.1 1.5 Ion Exchangers - T-51A, T-51B and T-52 Quantity 3 Type Flushable Design Pressure 200 psig Design Temperature 250qF Resin Volume 32 ft3 Retention Screen 80 US Mesh Code for Vessel ASME B&PV Code,Section III, Class C Material Stainless Steel Fluid 15,000 ppm Boric Acid, Maximum (Design)

DSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-18 Revision 36 Page 4 of 11 CHEMICAL AND VOLUME CONTROL SYSTEM DESIGN PARAMETERS 1.6 Purification Filters - F-54A and F-54B Quantity 2 Type of Elements Synthetic Fiber Retention 0.05 to 6.0 Micron Absolute; 1.0 Micron Nominal (or finer)

Design Pressure 200 psig Design Temperature 250qF Design Flow 120 gpm Code for Vessel ASME B&PV Code,Section III, Class C, 1965 Material Stainless Steel Fluid 15,000 ppm Boric Acid, Maximum (Design) 1.7 Volume Control Tank - T-54 Quantity 1 Type Vertical, Cylindrical Design Pressure, Internal 75 psig Design Pressure, External 15 psig Design Temperature 250qF Internal Volume, Minimum 4,170 gal Code ASME B&PV Code,Section III, Class C, 1965 Material Stainless Steel

DSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-18 Revision 36 Page 5 of 11 CHEMICAL AND VOLUME CONTROL SYSTEM DESIGN PARAMETERS 1.8 Spray Nozzle (Volume Control Tank)

Quantity 1 Type Medium Angle, Full Cone Design Pressure 200 psig Design Temperature 250qF Maximum Spray Flow 120 gpm Material Stainless Steel 1.9 Variable Speed Charging Pump - P-55A Quantity 1 Type Positive Displacement Design Pressure 2,735 psig Design Temperature 250qF Maximum Discharge Pressure (Short Term) 2,900 psig NPSH Required 7.65 ft (Ref. 25)

Maximum Pressure Pump Starts Against 2,485 psig Driver Rating 100 hp Type Variable Capacity Device Fluid Drive Materials in Contact With Pumped Stainless Steel or Equivalent Fluid Corrosion Resistance Fluid 12 Wt% Boric Acid, Maximum (Design)

DSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-18 Revision 36 Page 6 of 11 CHEMICAL AND VOLUME CONTROL SYSTEM DESIGN PARAMETERS 1.10 Constant Speed Charging Pumps - P-55B and P-55C Quantity 2 Type Positive Displacement Design Pressure 2,735 psig Design Temperature 250qF Flow Rate 40 gpm Maximum Discharge Pressure (Short Term) 3,010 psig NPSH Required 7.41 ft (Ref. 25)

NPSH Available P-55B/C 28.22/28.18 ft (Ref. 25)

(Normal Suction From VCT)

Maximum Pressure Pump Starts Against 2,500psig Driver Rating 75 hp Pump Cooling Water Requirements 5 gpm, 15qF Rise Fluid 12 Wt% Boric Acid, Maximum (Design)

DSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-18 Revision 36 Page 7 of 11 CHEMICAL AND VOLUME CONTROL SYSTEM DESIGN PARAMETERS 1.11 Boric Acid Batching Tank - T-77 Quantity 1 Internal Volume 580 gal Design Pressure Atmospheric Design Temperature 200qF Type Heater Electric Immersion Heater Capacity 31.5 kw Minimum Code ASME B&PV Code,Section VIII Fluid 12 Wt % Boric Acid, Maximum (Design)

Material Stainless Steel 1.12 Boric Acid Strainer - F-10 (YS-0224)

Quantity 1 Type Basket Design Pressure 125 psig Design Temperature 250qF Screen Size 100 x 100 US Mesh Design Flow 50 gpm Material Stainless Steel Fluid 12 Wt % Boric Acid, Maximum (Design)

DSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-18 Revision 36 Page 8 of 11 CHEMICAL AND VOLUME CONTROL SYSTEM DESIGN PARAMETERS 1.13 Concentrated Boric Acid Storage Tanks - T-53A and T-53B Quantity 2 Internal Volume 6,550 gal Design Pressure Atmospheric Design Temperature 200qF Type Heater Electrical, Dry Well Installation Heater Capacity Two Independent 4 kW Banks per Tank Fluid 12 Wt % Boric Acid, Maximum (Design)

Material Stainless Steel Code ASME B&PV Code,Section III, Class C, 1965

DSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-18 Revision 36 Page 9 of 11 CHEMICAL AND VOLUME CONTROL SYSTEM DESIGN PARAMETERS 1.14 Boric Acid Pumps - P-56A and P-56B Quantity 2 Type Centrifugal Design Pressure 150 psig Design Temperature 250qF Design Head 225 ft Design Flow 143 gpm NPSH Required 7.50 ft (Ref. 25)

NPSH Available P-56A/B 25.06/25.23 (Ref. 25)

Horsepower 30 Fluid 12 Wt % Boric Acid, Maximum (Design)

Material in Contact With Liquid Stainless Steel 1.15 Boric Acid Filter - F-9 Quantity 1 Type Elements Synthetic Fiber Retention of 5 Micron Particles 98%

Design Pressure 150 psig Design Temperature 250qF

DSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-18 Revision 36 Page 10 of 11 CHEMICAL AND VOLUME CONTROL SYSTEM DESIGN PARAMETERS Design Flow 140 gpm Material Stainless Steel Liquid 12 Wt % Boric Acid, Maximum (Design)

Code ASME B&PV Code,Section III, Class C, 1965 1.16 Chemical Addition Tank - T-56 Quantity 1 Capacity 10.5 gal Design Pressure Atmospheric Design Temperature 200qF Material Stainless Steel Fluid Hydrazine (N2H4), LiOH, KOH, NH4OH Code ASME B&PV Code,Section VIII 1.17 Chemical Addition Strainer - F-58 Quantity 1 Type Basket Design Pressure 100 psig Design Temperature 250qF Screen Size 60 US Mesh

DSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-18 Revision 36 Page 11 of 11 CHEMICAL AND VOLUME CONTROL SYSTEM DESIGN PARAMETERS Design Flow 30 gph Material Stainless Steel Fluid Hydrazine (N2H4), LiOH, KOH, NH4OH 1.18 Metering Pump - P-57 Quantity 1 Type Air Operated Double Diaphragm Design Pressure 120 psig Design Temperature 190qF Design Flow Rate 0 to 35 gpm Design Air Consumption 0 to 50 scfm Material Stainless Steel Fluid Hydrazine (N2H4), LiOH, KOH, NH4OH

DSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-19 Revision 36 Page 1 of 1 FUEL HANDLING DATA

1. New Fuel Storage Rack Core Storage Capacity 1/6 Equivalent Fuel Assemblies 36 Center-to-Center Spacing of Assemblies 11 in
2. Spent Fuel Storage Pool Core Storage Capacity 4.3 Equivalent Fuel Assemblies 892 Number of Space Accommodations for Spent Fuel Shipping Casks 1 Center-to-Center Spacing of Assemblies Region 1 10-1/4 in Region 2 9.17 in Maximum keff With Unborated Water Less Than 1.0
3. Miscellaneous Details Wall Thickness for Spent Fuel Storage Pool 4 ft to 6-1/2 ft Weight of Fuel Assembly 1,500 lb Capacity of Refueling Water Storage Tank 285,000 gal Quantity of Water Required for Fuel Handling 250,000 gal

DSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-20 Revision 36 Page 1 of 2 FUEL BUILDING CRANE Main Hoist 3 ft/min at Full Load (3 Steps), 25 hp at 900 r/min Main Hoist Brake Capacity 179 ft-lb Auxiliary Hoist 25 ft/min at Full Load (Stepless), 25 hp at 900 r/min Trolley 25 ft/min at Full Load (3 Steps), 3 hp at 1,800 r/min

  • Bridge 25 ft/min at Full Load (3 Steps), 5 hp at 1,800 r/min
  • Service Class Class A, Electric Overhead Crane Institute Specification 70 Lift Main Hoist 54 ft 0 in Lift Auxiliary Hoist 108 ft 5 in Span 44 ft 10 in Center-to-Center Rails Bridge Travel Approximately 100 ft Lifting Tackle Main Hoist - Rope 16 Parts 13/4-Inch SS, Drum 521/2-Inch Pitch Diameter, Sheaves 28-Inch Pitch Diameter Auxiliary Hoist - Rope 4 Parts 3/4-Inch SS, Drum 15-Inch Pitch Diameter, Sheaves 13-Inch Pitch Diameter Girders Welded Box Section Runway Rail 100 lbs ASCE Trolley Rail 175 lbs USS Bridge Drive Direct Drive Arrangement With Oiltight Center Gear Case Trolley Drive Direct Drive Arrangement With Oiltight Center Gear Case
  • Single failure proof mode of operation only

DSAR CHAPTER 9 - AUXILIARY SYSTEMS TABLE 9-20 Revision 36 Page 2 of 2 FUEL BUILDING CRANE Capacity in Net Tons Bridge 110 Tons, Main Hoist 110 Tons, Auxiliary Hoist 15 Tons Wheels Bridge Has Eight 21-Inch Steel Hardened Treads Trolley Has Four 21-Inch Diameter Steel Hardened Treads Bridge End Assembly Rotating Axle Bumpers Rubber Bearings Antifriction Throughout Gearing Helical Gearing Heat-Treated Steel Throughout Except Trolley Traverse. All Gearing in Oiltight Casing