ML22307A020

From kanterella
Jump to navigation Jump to search

EN 56194 - Emerson - Notification Under 10 CFR Part 21 for Rosemount 3153N Series Pressure Transmitter with Rosemount 3159 Remote Seals with the LG1 Option
ML22307A020
Person / Time
Site: Dresden, LaSalle  
Issue date: 11/01/2022
From: Hanson G
Emerson Automation Solutions, Rosemount Nuclear Instruments
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
56194
Download: ML22307A020 (4)


Text

Nov.1.2022 7:56AM 4'

~

EMERSON.

To; Operation Desk Company: NRC Fax number: (301) 816 5151 Date:

From: Nathan Schukei Phone number: 952-949-5213 Subject/Comments: Notification under 10 CFR Part 21 for Rosemount 3153N Series Pressure Transmitter with Rosemount 3159 Remote Seals with the LG1 option cc:

Phone number:

No.0195

p. I Facsimile EmerMn Automation Solutions Rosem0unt Nuclear and Subsaa 0200 Market Blvd Chanhassen, MN 55317 USA No. of pages (i11clr,1ding covE!r,;he<i!I): 4 E-mail: Nathan.Schukei@Emerson.com Fax number:

Nov.1.2022 7:56AM 4t Ii EMERSON.

01 November 2022 U.S. Nuclear Regulatory Commission Washington, DC 20555-0001 Attn: Document Control Desk No.0195 P. 2 RoGemounl Nuclear lnslrument.s, In<:

8200 M1:1.rl<et Boulevard Chanhassen, MN 55317 USA Tel 1 (95Z) 049-5200 www.RosemountNuclear.com Re:Notlflcatlon under 10 CFR Part 21 for Rosemount 3153N Series Pressure Transmitters with Rosemount 3159 Remote Seals with the LG1 Option Pursuant to 10 CFR Part 21, section 21.21 (a)(2), Rosemount Nuclear Instruments, Inc. (RNII) is writing to provide notification of a deviation in bolts provided with the LG 1 option on Rosemount 3159 remote seals. Bolts provided with the LG 1 option were delivered without the zinc plating required per Rosemount Nuclear Instruments Report D2019023 Rev B Technical Authori:tation for the LG1 Option Code.

1.0 Name and address of the individual providing the information:

Mr. Gerard Hanson Vice President & General Manager Rosemount Nuclear Instruments, Inc.

8200 Market Blvd Chanhassen. MN 55317 2.0 Identification of Items supplied:

Rosemount 3153N Series Pressure Transmitters with Rosemount 3159 Remote seals with the LG1 option, which were supplied to Constellation Energy's Dresden Generating Station and LaSalle County Nuclear Generating Station during a period from December 2019 to June 2022. See Appendix A for a list of affected serial numbers.

Rosemount 3153N Series Pressure Transmitters with Rosemount 3159 Remote Seals with the LG1 option are a subset of the Rosemount 3150 Series offering. All other Rosemount 3150 Series Pressure Transmitters supplied with Rosemount 3159 Remote Seals are not affected by this notification.

3.0 Identification of firm supplying the item:

Rosemount Nuclear Instruments, Inc.

8200 Market Blvd Chanhassen, MN 55317 4.0 Nature of the failure and potential safety hazard:

The LG 1 remote seal option supplies a modified Rosemount 3159 Remote Seal upper housing and hardware that is compatible with the legacy Rosemount 1159 Remote Seal lower housing. The remote seal bolts on units supplied with this option are specified to be SAE J429 Grade 8 with zinc-plating per ASTM F1941 5CN for corrosion resistance. RN II Identified a single manufacturing lot of LG1 bolts lacKed the required zinc-plating.

Page 1 of 2

Nov.1.2022 7:56AM No.0195 P. 3 The SAE J429 Grade 8 bolts may experience corrosion without zinc-plating when exposed to prolonged environments with high humidity or with direct contact with aqueous solutions. Sufficient corrosion may result In a reduction of pressure boundary integrity.

As a result of the above Information, RNII determined on October 251h, 2022 that a notification to affected licensees was warranted.

5.0 The corrective action which has been taken; the name of the individual or organization responsible for that action; and the length of time taken to complete that action:

RNII has quarantined all inventory of non-zinc-plated bolts. Further RNII has Identified all Rosemount 3153N Series Pressure Transmitters with Rosemount 3159 Remote Seals with the LG1 option that were shipped with the affected bolts.

Non-conforming bolts were returned to the vendor to be zinc-plated and have subsequently been returned to RNII.

Orders in RNll's backlog have been inspected and confirmed to be equipped with the correct SAE J429 Grade 8 bolts with zinc-plating per ASTM F1941 5CN.

Mr. Gerard Hanson. VP&GM of Rosemount Nuclear Instruments, Inc. is responsible for any further factory action related to this issue.

6.0 Any advice related to the potential failure of the item:

The affected Rosemount 3153N Series Pressure Transmitters equipped with Rosemount 3159 Remote Seals with the LG1 option were supplied during a period from December 2019 to June 2022. RNII recommends end users evaluate the significance of this notice to their specific pressure transmitter applications and environments. RNII further recommends that end users replace the un-plated bolts in susceptible applications to mitigate the potential for corrosion induced failure over time.

Rosemount Nuclear Instruments, Inc. Is committed to the nuclear industry and we assure you that we are dedicated to the supply of high-quality products and services to our customers. If there are any questions, or for customer inquiries for obtaining replacement bolts please contact Rosemount Nuclear Instruments Inc at 952-949-5200 (RNll.info@emerson.com) or Nathan Schukei (Customer Care Manager) at 952-949-5213.

Gerard Hanson Vice President & General Manager Rosemount Nuclear Instruments, Inc.

EMERSON.

Page 2 of 2

Appendix A: 10 CFR PART 21 Notification - 31 October 2022 CONSTEUATlON Et-lERGY GEN LLC / EXELON GmERATION CO lLC Purchase Order Numbe-r Model Number Serial Number Ship Date Site 00690790 3153ND4R252A7 / 3159B02SP2B1F1KOOLG1 19CHNQ0020986 12-Dec-19 LaSalle County Nuclec1r Generating Station 00690790 3153ND4R252A7 / 3159S025P2B1F1KOOLG1 19CH NQ0020987 12-Dec-19 LaSalle County Nuclear Generating S1ation 00690790 3153ND4R252A7 / 31598025P281F1KOOLG1 19CH NQ0020988 12-Dec-19 LaS-a Ile County Nuclear Generating Station 00690790 3153ND2R251A7 / 3159H015P281F1Kl3LG1 19CH NQ0020990 12.-Dec--19 LaSalle County Nuclear Genera1lng S1ation 00690790 3153ND2R251A7 / 3159H015P2BlF1K13LGl 19CH NQ0020991 12-Dec-19 LaS-alle County Nuclear Generating S1atlon 00690790 3153ND2R251A7 / S159H015P281FlK13LGl 19CH NQ0020992 12-Dec-19 LaSalle County Nuclear Generating Station 00690790 3153ND2R251A7 / 3159H015P2S1F1Kl3LG1 19CH NQ0020993 12-Dec-19 LaSa lie Co u.nty Nudear Generating Station 00690790 3153ND2R251A7 / 3159H015P281FlK13LGl 19CHNQ00209'l4 12-Dec... 19 Las.a lie County Nuclear Generating Station 00690790 3153ND2R251A7 / 3159H015P2BlF1Kl3LG1 19CH NQ0020995 12-Dec-19 Las.a lie County Nudar Generating Station 00690790 3153ND2R251A7 / 3159H015P281F1Kl3LG1 19CHNQ0020996 12-Dec-19 LaSalle Countv Nuclear Generating Station 00690790 3153ND2R251A7 / 3159H015P281F1Kl3LG1 19CHNQ0020997 12-Dec-19 LaSalle County f4udearGeneratingStation 00690790 3153ND2R251A7 / 3159H015P2SlF1K13LG1 19CHNQ002Cl998 12-Dec-19 LaSalle County Nuclear Generating Station 00722631 3153ND2R252A7 / 3159B010P2B1FIKODLG1 20CHNQ0021948 13-Apr-20 Ores.cl.en G*enerating Station 1331706 3153ND2R2S2A7 / 3159B010P1EllF1KODLGl 21CHNQ0024620 10-Sep-21 Dresden Ger.ieratingStation 1331706 3153ND2R252A7 / 3159B010PlB1FlKODLGl 21CHNQ0024621 10-Sep-21 Oresd.en Genera.ting Station 1331706 3153ND2R2S2A7 / 3159B010PlEllF1KOOLGl 21CHNQ0024622 10-5ep-21 Dresden Ger.eratingStation 1331706 315SND2R2S2A7 / 3159B010PlB1FlKODLG1 21CHNQ0024623 10-Sep-21 Dresden Ge n:1:<rating Station 00076959 REL 00614 3153ND2R2S2A7 / 3159B010PlEllF1KOOLGl 22CHNQ0025704 6-Jun-22 Dresden Ger.erating:Station 00076959 REl 00614 3153ND2R252A7 / 31598010Pl81F1KODLG1 22CHNQ0025705 o-Jun-22 Dresden Ge r1erating Station 00076959 REl00614 3153ND2R252A7 / 3159B010Pl81F1KOOLG1 22CHNQ0025706 fi..-Jun-22 Dresden Generating Station 00076959 REL 00614 3153ND2R2S2A7 / 3159B010P1SlF1KODLGl 22CHNQ0025707 6-Jun-22 D re.sd en Ge r1eratlng Station RN!I Sales Order 5546136 5546136 5546136 5546136 5546136 5546136 5546136 5546136 5546136 5546136 5546136 5546136 5930404 6382S68 6382'!68 6382968 6382S68 55s2n6 6582n6 6582776 6582776

=