14154847068 13018165151 pg 1 of4 Aad!!!!,!~n':ir!!! -
ll"flLJ tmw.nutlierm.com 501 South 11th Street September 25, 2020 Mount Vernon, IL 62864 U.S. Nuclear Regulatory Commission Docwnent Control Desk Washington, DC 20555-0001
Subject:
USNRC 10CFRPart 21 Notification
Reference:
Continuously Energiz.ed_F.aton D26 Relays Phone:618-244-6000 Fax:618-244-6641 Pursuant to 10CFR 21.21 (d) (3) (ii), Nutherm International, Inc. is providing written notification of the identification of a potential defect fotmd in Eaton D26 relays.
The following information is required per 1 OCFR 21.21 ( d) ( 4):
- i.
Nrune and address ofllie ili.diviailliloriruiivitluals-infonning-the-NRC;----- - - ---------- ---- --- --- -
Thomas A. Sterbis, President Nuthenn International, Inc.
501 South 11th Street Mount Vernon, Illinois 62864 ii.
Identification of the facility, the activity or the basic component supplied for such facility or such
- activity within the United States which fails to comply or contains a defect.
It has been identified that Nutherm International, Inc has supplied Eaton relays to the following facilities:
Exelon Generation Company, LLC-Dresden Nuclear Station Exelon Generation Company, LLC - Quad Cities Nuclear Station Energy Operations, Inc. - Palisades Nuclear Power Plant Duke Energy - HB Robinson Steam Electric Plant NextEra Energy Point Beach, LLC - Point Beach Nuclear Plant iii.
Identification-of the firm constructing the facility or supplying the basic component which fails to comply or contains a defect.
Nutherm International, Inc., 501 South 11th Street. Mount Vernon, Illinois 62864.
iv.
Nature of the defect or failure to comply and the safety hazard which is created or could be created by such defect or failure to comply.
- (9 09/25/2020 4:55 PM 14154847068 13018165151 pg 2 of 4 Page2 September 25, 2020 On July 23, 2019, Eaton Corporation released a letter, "Update on Reports of Size 1 & 2 AC Contactors that Failed to Open When Deenergized". This letter described a condition observed on AC contactors after being energized for a long period of time without being "cycled". Eaton also stated that this would occur in only a few isolated cases in continuously energized applications.
The cause of the problem is the coating on each of the steel laminations in the cores of these devices.
This steel is coatoo with an organic insulating varnish classified as C3. This coating, when heated for a long time period, can migrate from the lamination surfaces to the edges at the area between the separate core pieces (referred to as annatures and magnets); This substance is sticky and can potentially hold the core pieces together with enough strength to overcome the forces of the device's return springs.
Potentially impacted Eaton components may include:
Freedom contactors NEMA Size 00 through 5 A200 contactors NEMA Size 00 through 4 D15 Relays D26Relays AR Relays (AC Only)
BF Relays (AC Only and including NBF relays)
Vacuum contactors NEMA Size 4
- v.
The date on which the infonnation of such defect or failure to comply was obtained.
September 25, 2020.
vi.
In the case of a basic component which contains a defect or failure to comply, the number and location of all such components in use at, supplied for one or more facilities or activities subject to the regulations of 1 0CFR2 l.
Nutherm has provided relays to the following plants. Nutherm cannot determine if these relays are normally energized.
Entergy - Palisades Nuclear Power Plant Part Number: D26MR22A All installed in Motor Control Centers.
Exelon Generation Company. LLC - Dresden Station Part Number: AR660AR Exelon Generation Company. LLC - Quad Cities Nuclear Station Part Number: AR660AR Part Number: AR440AR
(9 09/25/2020 4:55 PM 14154847068 13018165151 pg 3 of4 Page3 September25,2020 VII.
Duke Energy - HB Robinson Steam Electric Plan Part Number. AR440AR NextEra Energy Point Beach, LLC - Point Beach Nuclear Plant Part Number: BF22F Part Number.BF40F Part Number: BF08F PartNumber: BF31F 1becorrective action which has been, is being or will be taken; the name of the individual or organization responsible for the action; and the length of time that has been or will be taken to complete the action.
The manufacturer has completed corrective actions on A200 contactors. This was completed in the
__ firstquarterof2Q2Q.______
The impacted customers were notified of this condition date September 28, 2020.
viii.
Any advice related to the defect or failure to comply about the facility, activity or basic component that has been, is being or will be given to purchasers or licensees.
The manufacturer conservatively estimated that a monthly operation ( cycling) would be sufficient to prevent the substance from binding the surfaces together. Cycling or replacement of the units in continuously energized conditions is suggested.
ix.
In the case of an early site permit, the entities to whom an early site pennit was transferred.
Not applicable.
If you have any questions please contact Adrienne Smith at 618-244-6000, extension 3034, email adrienne.smith@nuthenn.com or Kyle Mitchell at 618-244-6000, extension 3097 email kyle.mitchell@nutherm.com.
(9 09/25/2020 4:55 PM 14154847068 Page4 Since.rely,*
NUTHERM INTERNATIONAL, Inc.
Thomas A. Sterbis President TAS/abs 13018165151 pg4of4 September25,2020