ML24178A252

From kanterella
Jump to navigation Jump to search
County Station – Acknowledgement of Response to NRC Inspection Report 05000373/2024001 and 05000374/2024001 and Disputed Non-Cited Violation
ML24178A252
Person / Time
Site: LaSalle  
Issue date: 06/27/2024
From: Robert Ruiz
NRC/RGN-III/DORS/RPB1
To: Rhoades D
Constellation Energy Generation, Constellation Nuclear
References
EA-24-070 IR 2024001
Download: ML24178A252 (1)


See also: IR 05000373/2024001

Text

EA-24-070

David P. Rhoades

Senior Vice President

Constellation Energy Generation, LLC

President and Chief Nuclear Officer (CNO)

Constellation Nuclear

4300 Winfield Road

Warrenville, IL 60555

SUBJECT:

LASALLE COUNTY STATION - ACKNOWLEDGEMENT OF RESPONSE TO

NRC INSPECTION REPORT 05000373/2024001 and 05000374/2024001 AND

DISPUTED NON-CITED VIOLATION

Dear David P. Rhoades:

This letter acknowledges your June 12, 2024, correspondence (Agencywide Document and

Access Management System (ADAMS) Accession No. ML24164A061) sent in response to

U.S. NRC Inspection Report 05000373/2024001 and 05000374/2024001 (ML24131A151) dated

May 13, 2024. In your letter, you dispute one non-cited violation (NCV 05000374/2024001-02)

associated with the failure to meet the in-service testing requirements set forth in the American

Society of Mechanical Engineers (ASME) Operations and Maintenance Code and Addenda

Code Case OMN-1 after performing maintenance that could affect motor-operated valve (MOV)

performance. Specifically, the failure to perform testing on primary containment isolation

MOV 2B21-F016, prior to returning the valve to service after electrically backseating the valve,

which was maintenance that could affect the valves performance. The NRC is currently

reviewing your basis for contesting the violation in accordance with Section 2.8 of the

Enforcement Manual. Accordingly, we will provide the results of our evaluation by written

response once the evaluation is completed.

June 27, 2024

D. Rhoades

2

In accordance with 10 CFR 2.390, Agency Rules of Practice, a copy of this letter will be made

available electronically for public inspection in the NRC Public Document Room or in the NRCs

ADAMS, accessible from the NRCs website at http://www.nrc.gov/reading-rm/adams.html.

Should you have any questions concerning this inspection, please contact me at

Robert.Ruiz@nrc.gov or 630-829-9732.

Sincerely,

Robert Ruiz, Chief,

Reactor Projects Branch 1

Division of Operating Reactor Safety

Docket Nos. 05000373 and 05000374

License Nos. NPF-11 and NPF-18

cc: Distribution via LISTSERV

Signed by Ruiz, Robert

on 06/27/24

ML24178A252

SUNSI

Review

Non-Sensitive

Sensitive

Publicly Available

Non-Publicly Available

OFFICE

RIII-DORS

RIII-EICS

RIII-DORS

NAME

NShah:sw

DBetancourt-Roldan

RRuiz

DATE

06/26/2024

06/26/2024

06/27/2024