ML20217N800
ML20217N800 | |
Person / Time | |
---|---|
Site: | Farley ![]() |
Issue date: | 12/31/1997 |
From: | Dennis Morey SOUTHERN NUCLEAR OPERATING CO. |
To: | NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM) |
References | |
NUDOCS 9805050434 | |
Download: ML20217N800 (101) | |
Text
[- . -)
it l_ Dave Morey S:uthern Nuclzr l' We President " -: Operating Compa:y .
, Farley Project R0, Box 1295 .
3 Birmingham, Alabama 35201
} '
Tel 205.992.5131 o SOUTHERN h
. Ap il .27 v 1998 CQMM Energyto SernYourWorld" l Docket Nos.: 50-348 10 CFR 50.4 50-364 l U.S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington,DC 20555 Joseph M. Farley Nuclear Plant- j Annual Radioactive Effluent Release Report l Ladies and Gentlemen: ,
In accordance with the Unit I and Unit 2 Technical Specifications, Sections 6.9.1.8 and 6.9.1.9, the FNP Annual Radioactive Effluent Release Report for 1997 is hereby submitted. "
Should you have any questions, please advise.
Respectfully submitted, p Mfe Dave Morey
. EWC/ cit:97effrad. doc
Enclosure:
Subject Report ec: ' Mr. L.'A. Reyes, Region II Administrator Mr. J. I. Zimmerman, NRR Project Manager Mr. T. M. Ross, Plant Sr. Resident Inspector . \g Mr. .K. E. Whatley, Alabama Department of Public Health Mr. J. C. Hardeman, Jr., Georgia Department of Natural Resources
- h M8 i
SOUTHERN NUCLEAR OPERATING COMPANY FARLEY NUCLEAR PLANT UNIT NO. ONE LICENSE NO. NPF-2 t I: AND 1 l FARLEY NUCLEAR PLANT UNIT NO. TWO I LICENSE'NO. NPF-8 ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT CALENDAR. YEAR 1997 l
t l
t i j I -l I i i
l l
i I
l' I
l l
l
!. FARLEY NUCLEAR. PLANT ~
l ,
ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT:
i SECTION TITLE PAGE
1.0 INTRODUCTION
'l l . .
2.0 LIQUID EFFLUENTS 3 2.1 ODCM Limits 3 2.2 Measurements and Approximation ~ 3 of Total Radioactivity L 2.3 Abnormal Releases 4 2.4 Batch Releases 4 l
2.5 . Release Summaries 9 2.5.1 Liquid Effluents - Summation of 9 All Releases 12.5.2 ' Liquid Effluents - Continuous 11 6 and Batch Releases
'2.6 -Radiological Impact 29 3.0 GASEOUS EFFLUENTS 39
' 3 .1 ODCM Limits 39 3.2 Measurements and Approximation 39 of Total Radioactivity 3.3 Abnormal Releases 41 3.4' Batch Releases 41 l
t
FARLEY NUCLEAR PLANT .
AMNUAL RADIOACTIVE EFFLUENT RELEASE REPORT SECTION TITLE PAGE 3.5' . Release Summaries 50 3.5.1 Gaseous! Effluents - Summation of 15 0 '
All Releases- ,
3.5.2 ' Gaseous Effluents'- Mixed Mode 57 Releases 3.5.3. Gaseous' Effluents - Ground' Mode 64 Releases 3.6 Radiological Impact .71 j 4.0 SOLID WASTE 81 l
5.0 ONSITE DOSES TO MEMBERS OF 86 THE PUBLIC 6.0 MISCELLANEOUS 93 6.1 -Total Dose From Uranium Fuel Cycle 93 1
6.2 Licensee Initiated Changes to 93 !
the ODCM
'6.3 Program Deviations 93 ;
6.4 Major Changes to the-Radwaste 94 Treatment Systems
FARLEY NUCLEAR PLANT ANNUAL-RADIOACTIVE EFFLUENT RELEASE REPORT H
TABLE LIST OF TABLES PAGE f
1-4A ' Liquid Effluents - Batch Release 5 Summary, Unit 1 1-4B Liquid Effluents - Batch Release 7 Summary, Unit 2 1-1A Liquid Effluents - Summation of l 10 1 All Releases, Unit.1 1-1B Liquid Effluents - Summation of 12 j All Releases, Unit 2 1-1C Liquid Effluents - Summation of 14 All Releases, Site 1-2A Liquid Effluents - Continuous 17 and Batch Releases, Unit 1 i
L 1-2B Liquid Effluents - Continuous 21 ;
and Batch Releases, Unit 2 !
l l_ 1-2C Liquid Effluents - Continuous 25 and Batch Releases, Site-1-3A Doses to a MEMBER OF THE PUBLIC 30 Due to Liquid Releases, Unit 1 1-3B Doses to a MEMBER OF THE PUBLIC 32 Due to Liquid Releases, Unit 2 1-5 Typical Liquid MDC's Achieved 34 on Counting System 1-6A Liquid Effluents - Abnormal Release 35 Summary, Unit 1 1-6B Liquid Effluents - Abnormal Release 37 Summary, Unit 2 1 l
2-8A Gaseous Effluents - Abnormal Release 42 i Summary, Unit 1 l
2-8B Gaseous Effluents - Abnormal Release 44 i Summary, Unit 2 ;
I 2-6A Gaseous Effluents - Batch Release 46 1 l Summary, Unit 1 2-6B Gaseous Effluents - Batch Release 48 Summary, Unit 2
)
FARLEY NUCLEAR PLANT ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT TABLE' LIST OF' TABLES PAGE-2-1A -Gaseous Effluents Summation of 51-All Releases, Unit 1 2-1B Gaseous Effluents - Summation of 53 All~ Releases, Unit 2 1C Gaseous Effluents - Summation of 55 All Releases, Site
~2-2A Gaseous Effluents - Mixed Mode 58 Level Releases, Unit l' 2-2B Gaseous Effluents - Mixed Mode 60 Level Releases, Unit 2 2-2C Gaseous Effluents - Mixed Mode =62 Level Releases, Site-2-3A' Gaseous Effluents - Ground '65 Level Releases, Unit-1 2-3B' Gaseous Effluents - Ground 67 -
Level Releases, Unit 2 2-3C Gaseous Effluents --Ground 69 j Level Releases, Site 2-4A Air Doses Due to Gaseous 72 Releases,. Unit 1 2-4B Air Doses Due to Gaseous 74 Releases, Unit 2 2-5A Doses to a MEMBER OF THE PUBLIC 76 Due to Radioiodines, Tritium, and Particulates in Gaseous Releases, Unit l' 2-5B Doses to a MEMBER OF THE PUBLIC 78 Due to Radioiodines, Tritium, and Particulates in Gaseous Releases, Unit 2 2-7 Typical Gaseous MDC's Achieved 80 on Counting System 3 Solid Waste and Irradiated 82 Fuel Shipments
FARLEY NUCLEAR PLANT ANNUAL RADIOACTIVE EFFLUENT RELEASE REP'3RT TABLE LIST OF TABLES PAGE 4-1 Doses to a MEMBER OF THE PUBLIC 87 Due to Activities Inside the Site Boundary, Site ;
l I
i i
1.0 INTRODUCTION
I In accordance with Technical Specification (TS) 6.9.1.8 and 6.9.1.9 and Offsite Dose Calculation Manual (ODCM) 7.2, this l Annual Radioactive Effluent Release Report covers the operations of the Farley Nuclear Plant (FNP) during 1997. l y Information regarding the radioactive liquid and gaseous l
effluents and solid waste releases are summarized in formats i
similar to those provided in the Nuclear Regulatory Commission l (NRC) Regulatory Guide 1.21, " Measuring, Evaluating, and Reporting Radioactivity in Solid Wastes and Releases of Radioactive. Materials in Liquid and Gaseous Effluents from Light Water Cooled Nuclear Power Plants", Revision 1, June 1974. In addition the report i
includes required or appropriate information regarding meteorology, dose assessment and other pertinent matters.
Detailed informaticn on liquid effluents is provided in Section 2.
The quantities of the radioactive effluents (including any unplanned l releases) are summarized on a quarterly basis. A tabulation of the total body and organ doaes which were calculated in accordance with ODCM 2.4 are presented to show conformance with the limits of ODCM l 2.1.3. j i
Detailed information on gaseous effluents similar to that for liquid j effluents is provided in Section 3. Tabulations are provided of the i offsite air doses calculated in accordance with ODCM 3.4.2 to show conformance with the limits of ODCM 3.1.3, and the offsite organ doses to a member of the public calculated in accordance with ODCM 3.4.3 to show conformance with the limits of ODCM 3.1.4.
Detailed information as specified by ODCM 7.2.2.4 on any solid radwastes shipped offsite is provided in Section 4. The data is summarized on a semiannual basis.
Assessments of the doses to members of the public due to their
, activities inside the site boundary are provided in Section 5.
l These aseessments are performed as specified by ODCM 6.2.
A number of miscellaneous matters are addressed in Section 6.
These are matters which require reporting only under certain
! conditions. The alphabetized list given below includes the conditional matters addressed.
A. An assessment of the radiation doses to the likely most exposed member of the public from reactor releases and other nearby uranium fuel cycle sources to show conformance with 40CFR190, should a determination be required by ODCM 5.1.2.
l 1
l
'B. Any. licensee initiated changes to the ODCM pursuant to TS 6.14 including changes to the sampling locations in the Radiological Environmental Monitoring Program pursuant to ODCM 4.1.1.2.3 or 4.1.2.2.2, or changes in the location of the controlling dose receptor identified in ODCM 3.4.3 pursuant to ODCM 4.1.2.2.1.
l C. Discussions of deviations in the Radioactive Effluent Control ,
Program pursuant to ODCM 7.2.2.6.
t D. Any major changes to the liquid or gaseous radwaste treatment systems initiated by the licensee as required by ODCM 2.1.5 and 3.1.6, restactively, or to the solid radwaste treatment system-pursuant to the Process Control Program (PCP) App. B section B.4.1.
Meteorological' data are retained onsite; these data 1are available l to the NRC upon request. The meteorological data. include annual as.well as' quarterly summaries of hourly measurements of wind speed, L wind direction and atmospheric stability in the form of joint frequency distribution tables.
k.
2 l
2.0 LIQUID EFFLUENTS This section contains applicable ODCM limits for liquid effluents as well as the quantities of radioactive liquid effluents released during 1997. These quantities are summarized on a quarterly basis and include any unplanned releases. A tabulation of the total body and organ doses which were calculated in accordance with ODCM 2.4 are presented to show conformance with the limits of ODCM 2.1.3.
2.1 ODCM Limits In accordance with Technical Specifications 6.8.3.e (ii) and
- 6. 8. 3. e (iii) , the concentration of radioactive material released in liquid effluents to UNRESTRICTED AREAS (see ODCM Figure 10-1) shall be limited at all times to ten times the concentrations specified in 10CFR20, Appendix B, Table 2, Column 2 for radionuclides other than dissolved or entrained noble gases. For dissolved or entrained noble gases, the concentration shall be limited to 1E-04 uCi/ML total activity.
In accordance with Technical Specifications 6.8.3.e (iv) and
- 6. 8. 3. e (v) , the dose or dose commitment to a MEMBER OF THE PUBLIC from radioactive materials in liquid effluents released, from each unit, to UNRESTRICTED AREAS (see ODCM Figure 10-1) shall be limited:
- a. During any calendar quarter to less than or equal to 1.5 mrem to the total body and to less than or equal to 5 mrem to any organ, and
- b. During any calendar year to less than or equal to 3 mrem to the total body and to less than or equal to 10 mrem to any organ.
2.2 Measurements and Approximation of Total Radioactivity The radionuclides listed below are considered when evaluating liquid effluents:
MN-54 CS-134 FE-59 CS-137 CO-58 CE-141 CO-60 CE-144 ZN-65 MO-99 SR-89 FE-55 SR-90 H-3 I-131 3
Batch Releases: Representative pre-release grab samples are obtained and analyzed in accordance with ODCM Table 2-3. i 1
Isotopic analyses are performed using the computerized pulse height analysis system utilizing high resolution germanium !
detectors. Isotopic values thus obtained are used for release '
rate calculations as specified in the ODCM. Only those nuclides that are detected are used in the calculations. All Strontium and Iron-55 samples are sent offsite to the Georgia Power Environmental Laboratory for analysis. Gross beta and gross alpha determinations are made using 2 pi gas flow proportional counters. Tritium determinations are made using liquid scintillation techniques. Dissolved gases are determined employing _
grab sampling techniques and then counting on the pulse height analyzer.
Continuous Releases: Continuous' releases are analogous to batch releases except that they are analyzed on a weekly composite basis in accordance with ODCM Table 2-3.
The maximum error associated with volume and flow measurements, i based upon plant calibration practice is estimated to be + or -
10%. The average error associated with counting is estimated to be less than + or - 15%.
2.3 Abnormal Releases There were no abnormal liquid releases on either Unit 1 or Unit 2 during 1997.
Abnormal release information for Units 1 and 2 is summarized in the following tables:
Unit 1 1997 Liquid Abnormal Releases : Table 1-6A Unit 2 1997 Liquid Abnormal Releases : Table 1-6B 4 2.4 Batch Releases Batch release information for Units 1 and 2 is summarized in the following tables:
Unit 1 1997 Liquid Batch Releases : Table 1-4A Unit 2 1997 Liquid Batch Releases : Table 1-4B i
4
1 TABLE 1-4A Joseph M. Farley Nuclear Plant I ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1997 Liquid Effluents - Batch Release Summary Unit: 1 Starting : 1-Jan-1997 Ending : 30-Jun-1997 l
l l
LIQUID RELEASES i NUMBER OF BATCH RELEASES : 228 TOTAL TIME PERIOD FOR BATCH RELEASES : 21627.00 MINUTES MAXIMUM TIME PERIOD FOR A BATCH RELEASE : 117.00 MINUTES AVERAGE TIME PERIOD FOR BATCH RELEASES : 94.86 MINUTES MINIMUM TIME PERIOD FOR A BATCH RELEASE : 80.00 MINUTES AVERAGE STREAM FLOW DURING PERIODS OF RELEASE OF LIQUID EFFLUENT INTO A FLOWING STREAM : 1.22E+04 CFS
- 0 Average River Flow Rate, taken at Walter F. George Lock and Dam, located 30.7 miles above Farley Nuclear Plant.
l l
l i
5 l
TABLE 1-4A Joseph M. Farley Nuclear' Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1997 LiquidLEffluenta.- Batch Release Summary Unit: 1 Starting : 1-Jul-1997 Ending : 31-Dec-1997 i'
LIQUID RELEASES ,
NUMBER OF BATCH RELEASES : -105 l
, ' TOTAL TIME PERIOD FOR BATCH RELEASES : 9672.00 . MINUTES l-MAXIMUM TIME. PERIOD FOR A BATCH. RELEASE : 110.00 MINUTES.
AVERAGE TIME PERIOD 1FOR BATCH RELEASES : 92.11 MINUTES MINIMUM TIME PERIOD FOR A BATCH. RELEASE : 86.00 MINUTES AVERAGE STREAM FLOW DURING PERIODS OF
-RELEASE OF LIQUID EFFLUENT INTO A FLOWING STREAM : 9.09E+03 CFS
- l l-L o Average River Flow Rate, taken at Walter F. George Lock and Dam, located 30.7 miles above Farley Nuclear Plant.
l 6
i i
l
TABLE 1-4B Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1997 Li' quid Effluents - Batch Release Summary Unit: 2 Starting : 1-Jan-1997 Ending : 30-Jun-1997 l
1 LIQUID RELEASES L NUMBER OF BATCH RELEASES : 112
'~
TOTAL TIME PERIOD FOR BATCH RELEASES : 11706.00 MINUTES MAXIMUM-TIME PERIOD FOR A BATCH RELEASE : 122.00 MINUTES AVERAGE' TIME PERIOD FOR BATCH RELEASES : 104.52 MINUTES
- MINIMUM TIME PERIOD FOR A BATCH RELEASE
- 92.00 MINUTES i AVERAGE STREAM FLOW DURING PERIODS OF l
RELEASE OF LIQUID EFFLUENT INTO A FLOWING STREAM : 1.22E+04 CFS
- 0 Average River Flow Rate, taken at Walter F. George Lock and Dam, located l
30.7 miles above Farley Nuclear Plant. i i
l 1
l-7 i
1.
i
[-
t.
TABLE 1-4B l Joseph.M. Farley Nuclear: Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1997 Liquid Effluents . Batch Release Summary Un'it: 2
)
Starting : 1-Jul-1997 Ending : 31-Dec-1997 I
_____________________________________________________________.. ________________ )
.________-_____________________________.________________________________________ 1 l
LIQUID RELEASES
{
' NUMBER OF BATCH RELEASES : 68 TOTAL TIME PERIOD FOR BATCH RELEASES. : 6970.73 ' MINUTES l
MAXIMUM TIME. PERIOD;FOR A BATCH RELEASE : 121.00 MINUTES xAVERAGE TIME PERIOD FOR BATCH RELEASES : 102.51 MINUTES 1 MINIMUM. TIME PERIOD FOR A BATCH RELEASE : 87.00 MINUTES I RVERAGE STREAM FLOW DURING PERIODS OF l RELEASE OF LIQUID EFFLUENT INTO A FLOWING STREAM : 9.09E+03- CFS
- I t
l I
i l
l.
l ll O' Average River Flow Rate, taken at Walter F. George Lock ana Dam, located 30.7 miles above Farley Nuclear Plant, i
i 8
l
~
2.5 Release Summaries This section contains the summaries of'all radioactive liquid effluents released for Units l'and 2 during 1997. Typical liquid i Minimum Detectable Concentrations (MDC'S) for analyses are l in Table-1-5 of this section. Regulatory Guide 1.21 Table =2A is found in this report as Tables 1-1A, 1-1B, and 1-1C. Regulatory i
! ' Guide 1.21-Table 2B is found'in this report as Tables 1-2A, 1-2B, l
and 1-2C.
, 2.5.1 Liquid' Effluents - Summation of All Releases i The summations of all liquid effluent releases are contained l
in the following tables l
. Unit 1 1997 Summation of'All Releases : Table'1-1A-j Unit 2 1997 Summation of All Releases : Table 1-1B Site 1997 Summation of All Releases : Table 1-1C l
i
~
l L
l 9
o I
TABLE 1-1A
-Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT ~- 1997 Liquid Effluents - Summation of All Releases Unit: 1:
Starting : 1-Jan-1997 Ending : 30-Jun-1997 TYPE OF EFFLUENT UNITS QUARTER 1 QUARTER 2 'EST. TOT
-ERROR % '
A. FISSION!& ACTIVATION PRODUCTS
-1. TOTAL-RELEASE (NOT INCLUDING
. TRITIUM,LGASES, ALPHA) CURIES 5.03E-02 4.18E-02 2.50E+01 2$kVbkkhbbkLbTbbbbhbbhTkkTkbh DURIJG PERIOD uCi/ML 3.01E-09 2.89E-09
- 3. PERCENT OF APPLICABLE LIMIT % *
- B. TRITIUM
- 1. TOTAL RELEASE CURIES 2.96E+02 2.40E+01- 2.50E+01
- 2. AVERAGE DILUTED CONCENTRATION DURING PERIOD uCi/ML 1.77E-05
____________________________________________________________1.66E-06~ ____________________
- 3. PERCENT OF APPLICABLE LIMIT % *
- __..____________ __________________________________.____________________________ 1 C. DISSOLVED AND ENTRAINED GASES
- 1. TOTAL' RELEASE CURIES 1.62E 1.94E-04 2.50E+01'
- 2. AVERAGE' DILUTED CONCENTRATION. !
DURING PERIOD' uCi/ML 9.71E-10 1.34E-11
- 3. PERCENT OF APPLICABLE LIMIT % *
- D.. GROSS ALPHA RADIOACTIVITY
- 1. TOTAL RELEASE CURIES 8.37E-06 2.85E-06 2.50E+01 E. WASTE VOL RELEASED (PRE-DILUTION) LITERS 8.31E+07 5.04E+07 1.00E+01 F. VOLUME OF DILUTION WATER USED LITERS 1.66E+10 1.44E+10 1.00E+01 o Applicable limits are expressed in terms of dose. See Tables 1-3A and 1-3B of thie report.
10
TABLE 1-1A Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1997 Liquid Effluents - Summation of All Releases Unit: 1-Starting : 1-Jul-1997 Ending : 31-Dec-1997 1
TYPE OF EFFLUENT UNITS QUARTER 3 QUARTER 4 EST. TOT ERROR %
.A. FISSION & ACTIVATION PRODUCTS
- 1. TOTAL RELEASE (NOT INCLUDING
______ TRITIUM, GASES, ALPHA) CURIES 2.10E-02 1.02E-02 2.50E+01
- 2. AVERAGE DILUTED CONCENTRATION DURING PERIOD uCi/ML 1.12E-09 6.47E-10
....._________________s .________________________________________ ______________ i PERCENT OF APPLICABLE LIMIT 1
- 3. % * * !
B. TRITIUM
- 1. TOTAL RELEASE CURIES 7.83E+01 1.27E+02 2.50E+01
- 2. AVERAGE DILUTED CONCENTRATION DURING PERIOD uCi/ML 4.16E-06 8.00E-06
- 3. PERCENT OF APPLICABLE LIMIT % *
- l C. DISSOLVED AND ENTRAINED GASES
- 1. TOTAL RELEASE CURIES 2.45E-05 6.60E-05 2.50E+01
- 2. AVERAGE DILUTED CONCENTRATION DURING PERIOD uCi/ML 1.30E-12 4.17E-12
- 3. PERCENT OF APPLICABLE LIMIT % *
- D. GROSS ALPHA RADIOACTIVITY
-1. TOTAL RELEASE CURIES 1.41E-06 4.04E-07 2.50E+01 E. WASTE VOL RELEASED (PRE-DILUTION) LITERS 9.73E+07 8.53E+07 1.00E+01 F. VOLUME OF DILUTION WATER USED LITERS 1.87E+10 1.57E+10 1.00E+01 o .. Applicable limits are expressed in terms of dose. See Tables 1-3A and 1-3B of this report.
11
r I
TABLE 1-1B ,
Joseph M. Farley Nuclear Plant i
ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1997
!' Liquid Effluents - Summation of All Releases Unit: 2 Starting : 1-Jan-1997 Ending : 30-Jun-1997 TYPE OF EFFLUENT UNITS QUARTER 1 QUARTER 2 EST. TOT 1 ERROR %
A. FISSION & ACTIVATION PRODUCTS.
l
- 1. TOTAL RELEASE (NOT INCLUDING TRITIUM, GASES, ALPHA) CURIES 1.72E-02 5.66E-03 2.50E+01
- 2. AVERAGE DILUTED CONCENTRATION DURING PERIOD uCi/ML 9.59E-10 3.27E-10
- 3. PERCENT OF APPLICABLE LIMIT- % *
- B. TRITIUM
- 2. AVERAGE DILUTED CONCENTRATION DURING PERIOD uCi/ML 5.74E-06 1.68E-06
- 3. PERCENT OF APPLICABLE LIMIT % *
- C. DISSOLVED AND ENTRAINED GASES t
- 1. TOTAL RELEASE CURIES 3.76E-03 2.18E-04 2.50E+01
- 2. AVERAGE DILUTED CONCENTRATION DURING PERIOD uCi/ML 5.44E-10 1.26E-11
- 3. PERCENT OF APPLICABLE LIMIT % *
- 1 D. GROSS ALPHA RADIOACTIVITY
-1. TOTAL RELEASE CURIES 0.00E+00 0.00E+00 2.50E+01 1 ._________________________________ ______________________________________________
i E. WASTE VOL. RELEASED (PRE-DILUTION)
LITERS 7.53E+07 7.49E+07 1.00E+01 F. VOLUME OF DILUTION WATER USED LITERS 1.79E+10 1.72E+10 1.00E+01
____m.__________________________________________________________________________
- Applicable limits are expressed in terms of dose. See Tables 1-3A and 1-3B of this report.
12
TABLE 1-1B Joseph M. Farley Nuclear Plant i
ANNUAL RADIOACTIVE EFFLUENT RELEASS REPORT - 1997 l Liquid Effluents - Summation of All Releases Unit: 2 <
Starting : 1-Jul-1997 Ending : 31-Dec-1997 ll l
i TYPE OF EFFLUENT i
UNITS QUARTER 3 QUARTER 4 EST. TOT j ERROR %
______________________________.________________________________________________ j si l
A. FISSION & ACTIVATION PRODUCTS s I
- 1. TOTAL RELEASE (NOT INCLUDING TRITIUM, GASES, ALPHA) CURIES 1.05E-02 1.56E-02 2.50E+01 l
- 2. AVERAGE DILUTED CONCENTRATION l DURING PERIOD uCi/ML 6.21E-10 9.22E-10
_______________________.________________________________________________________ l l
- 3. PERCENT OF APPLICABLE LIMIT % *
- B. TRITIUM
- 2. AVERAGE DILUTED CONCENTRATION DURING PERIOD uCi/ML 4.57E-06 1.37E-05
- 3. PERCENT OF APPLICABLE LIMIT % *
- C. DISSOLVED AND ENTRAINED GASES
- 1. TOTAL RELEASE CURIES 3.22E-05 1.41E-04 2.50E+01
- 2. AVERAGE DILUTED CONCENTRATION DURING PERIOD uCi/ML 1.90E-12 8.32E-12
- 3. PERCENT OF APPLICABLE LIMIT % *
- D. GROSS ALPHA RADIOACTIVITY
- 1. TOTAL RELEASE CURIES 0.00E+00 0.00E+00 2.50E+01 E. WASTE VOL RELEASED (PRE-DILUTION) LITERS 7.02E+07 6.98E+07 1.00E+01 l
F. VOLUME OF DILUTION WATER USED LITERS 1.69E+10 1.69E+10 1.00E+01 l
o Applicable limits are expressed in terms of dose. See Tables 1-3A and 1-3B of this report.
13 L
TABLE 1-1C Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1997 Liquid Effluents - Summation of All Releases Unit: Site Starting : 1-Jan-1997 Ending : 30-Jun-1997
. TYPE OF EFFLUENT UNITS . QUARTER 1 QUARTER 2 EST. TOT ERROR % i
.._____________________________________________________. _______________________. t A. FISSION & ACTIVATION PRODUCTS
- 1. TOTAL RELEASE (NOT INCLUDING TRITIUM, GASES, ALPHA) CURIES 6.75E-02 4.75E-02 2.50E+01
- 2. AVERAGE DILUTED CONCENTRATION DURING PERIOD uCi/ML 1.95E-09 1.49E-09
- 3. PERCENT OF APPLICABLE LIMIT % *
- B. TRITIUM
- 1. TOTAL RELEASE CURIES 3.99E+02 5.30E+01 2.50E+01
- 2. AVERAGE DILUTED CONCENTRATION DURING PERIOD uCi/ML 1.15E-05 1.67E-06
- 3. PERCENT OF APPLICABLE LIMIT % *
- C. DISSOLVED AND ENTRAINED GASES
- 1. TOTAL RELEASE CURIES 2.60E-02 4.12E-04 2.50E+01' l
~~~ ~ ~ -
~~~--------~~~~~~~~----------------
2! EVEEE55 55L5fs5 55s5isfREti6A DURING PERIOD uCi/ML 7.50E-10 1.30E-11
- 3. PERCENT OF APPLICABLE LIMIT % *
- D. GROSS ALPHA RADIOACTIVITY
- 1. TOTAL RELEASE CURIES 8.37E-06 2.85E-06 2.50E+01 E. WASTE VOL RELEASED (PRE-DILUTION) LITERS 1.58E+08 1.25E+08 1.00E+01 F. VOLUME OF DILUTION WATER USED LITERS 3.45E+10 3.16E+10 1.00E+01 Applicable limits are expressed in terms of dose. See Tables 1-3A and 1-3B of this report.
14
l l
i i
TABLE 1-1C i
Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1997 Liquid Effluents - Summation of All Releases Unit: Site Starting _: Jul-1997 Ending : 31-Dec-1997 l
- -TYPE OF EFFLUENT UNITS QUARTER 3 QUARTER 4 'EST. TOT l ERROR %-
A. FISSION & ACTIVATION PRODUCTS
! 1. TOTAL RELEASE (NOT INCLUDING
. TRITIUM, GASES, ALPHA) CURIES 3.16E-02 2.59E-02 2.50E+01
- 2. AVERAGE DILUTED CONCENTRATION DURING PERIOD uCi/ML 8.83E-10 7.90E-10
-3 . PERCENT OF APPLICABLE LIMIT % *
- 1 t
B. TRITIUM i
- 1. TOTAL RELEASE CURIES 1.56E+02 3.59E+02 2.50E+01 l
,2. AVERAGE DILUTED CONCENTRATION
.DURING PERIOD uCi/ML 4.36E-06 1.09E-05
- 3. PERCENT OF APPLICABLE LIMIT % * *
. ___________________________._____ 1
________________________________ ________ 4
.C. DISSOLVED AND ENTRAINED GASES
- 2. AVERAGE DILUTED CONCENTRATION j DURING~ PERIOD uCi/ML 1.59E-12 6.32E-12
- 3. PERCENT OF APPLICABLE LIMIT % *
- l- D. GROSS ALPHA RADIOACTIVITY t
- 1. TOTAL RELEASE CURIES 1.41E-06 4.04E-07 2.50E+01
-E.-WASTE VOL RELEASED (PRE-DILUTION) LITERS 1.67E+08 1.55E+08 1.00E+01 F. VOLUME OF DILUTION WATER USED LITERS 3.56E+10 3.26E+10 1.00E+01 o Applicable limits are expressed in terms of dose. See Tables 1-3A and 1-3B of this report.
15 l
I
F i
2.5.2' Liquid Effluents ~- Continuous and Batch. Releases -
~
l The continuous and batch release summaries of all'ljauid -
effluent releases. (includes listing by nuclide) are contained in'the following-tables:
Unit 1 1997 Continuous and. Batch Releases : Table 1-2A-
! Unit 2'1997 Continuous and Batch-Releases : Table 1-2B Site 1997 Continuous and Batch Releases : Table 1-2C l'
I 4
l-I l
i I !
i 16
TABLE 1-2AO I Joseph'M. Farley Nuclear Plant j ANNUAL RADIOACTIVE. EFFLUENT. RELEASE REPORT - 1997 '
Liquid Effluents Unit: 1 Starting : 1-Jan-1997 Ending :.30-Jun-1997 i
-l CONTINUOUS MODE l BATCH . MODE l i
.__..___________. _______________________________________...___________________. R MUCLIDE l UNIT l QUARTER 1 l QUARTER 2 l QUARTER 1 l QUARTER 2-l H-3: l ' CURIES ll.1.70E-01-l 2.98E-07-l 2.96E+02 l'2.40E+01 l.
l FISSION & ACTIVATION PRODUCTS AG-110M CURIES 0.00E+00 0.00E+00 2.73E a.. l 2.69E-03 CO-57 CURIES 0.00E+00 0.00E+00 4.96E N 7.74E-05 CO-58 CURIES 0.00E+00 0.00E+00 1.85E-u2 2.~42E-02 CO-60 CURIES 0.00E+00 -0.00E+00 1.05E-02 2.63E-03 CR CURIES 0.00E+00 -0.00E+00 1.77E-03 2.16E-03 CS-134 CURIES 0.00E+00 0.00E+00 4.16E-05 6.35E-05 CS-136 CURIES 0.00E+00 0.00E+00 6.02E 0.00E+00 CS-137 CURIES- 0.00E+00 0.00E+00 6.94E-04 4.03E-04 FE-55 CURIES 0.00E+00 0.00E+00 9.74E-03 5.01E-03 FE-59 CURIES 0.00E+00 0.00E+00 1.06E-04 1.00E-04
- I-131 CURIES 0.00E+00 0.00E+00 7.62E-06 0.00E+00 I-132 CURIES 0.00E+00 0.00E+00 7.44E-05 0.00E+00 I-133 CURIES 1.41E-03 0.00E+00 3.43E-05 0.00E+00 I-135 CURIES 0.00E+00 0.00E+00 2.52E-05 0.00E+00 MN-54 CURIES 0.00E+00 0.00E+00 2.59E-04 ~4.08E-04 NA-24. CURIES 0.00E+00 0.00E+00 1.34E-05 1.36E-05 NB-95 CURIES 0.00E+00- 0.00E+00 1.38E-04 3.13E-04 NB-97 CURIES 0.00E+00 0.00E+00 l'.47E-04 1.39E-04
'RB-86. CURIES 0.00E+00 0.00E+00 1.34E-05 6.32E-05 RU-103 CURIES 0.00E+00 0.00E+00 1.59E-05 3.66E-06
-SB-122 CURIES 0.00E+00 0.00E+00 0.00E+00 2.77E-06.
SB-124 CURIES 0.00E+00 0.00E+00 1.31E-04 1.60E 'SB-125 CURIES 0.00E+00 0.00E+00 3~.10E-03 1.92E-03 l SN-117M CURIES 0.00E+00 0.00E+00 0.00E+00 1.19E-05 SR-89 CURIES 0.00E+00 0.00E+00 3.78E-05 1.36E-05 SR-90 CURIES 0.00E+00 0.00E+00 1.35E-05 7.56E-06
-SR-92= CURIES 0.00E+00 0.00E+00 4.41E-05 1.90E-05 TC-99M CURIES 0.00E+00 0.00E+00 2.00E-05 0.00E+00 TE-125M CURIES 0.00E+00 0.00E+00 0.00E+00 1.20E-03 TE-132 CURIES 0.00E+00- 0.00E+00 5.84E-05 0.00E+00 l
17
TABLE.1-2A0 Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1997 Liquid Effluents Unit: 1 Starting : 1-Jan-1997 Ending : 30-Jun-1997 l CONTINUOUS MODE l BATCH. MODE -
__...__-_________.._______ ______________.______ ___.__.__'__ _ __________________l NUCLIDE <
l UNIT l QUARTER 1 l QUARTER 2-l QUARTER 1 l QUARTER 2
_..._______________________________________________________._. ________ ._______l J
FISSION & ACTIVATION PRODUCTS (
ZN-65' CURIES 0.00E+00 0.00E+00 '7.63E-05 4.33E-06 ZN-69M CURIES 0.00E+00 0.00E+00 9.72E-06 0.00E+00
" ZR-95 CURIES 0.00E+00 0.00E+00 5.47E-05 1.70E-04 TOTALS CURIES l l 1.41E-03 l 0.00E+00 l 4.89E-02-l 4.18E-02'
________________.___________._____________________.._____________...._________l-
DISSOLVED AND ENTRAINED GASES
'AR-41' CURIES 0.00E+00 0.00E+00 1.17E-05 2.64E-05' XE-133 CURIES 0.00E+00 0.00E+00 1.61E-02 1.68E-04 XE-133M CURIES 'O.00E+00 0.00E+00 4.15E-05 0.00E+00 XE-135 CURIES 0.00E+00 0.00E+00 1.94E-05 0.00E+00
. TOTALS CURIES l l 0.00E+00 l 0.00E+00 l 1.62E-02 l 1.94E-04
.._____________.._l G-ALPHA l CURIES- l 0.00E+00 l 0.00E+00 l 8.37E-06 l 2.85E-06 l
- o. Zeroes in'this table indicate that no radioactivity was present at detectable. levels ^. See Table 1-5 for typical minimum detectable concentrations.
18
. TABLE 1-2A*
Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1997 Liquid Effluents Unit: 1 Starting : 1-Jul-1997 Ending : 31-Dec-1997 l CONTINUOUS MODE l BATCH MODE l NUCLIDE l UNIT lQUARTER 3 l QUARTER 4 l QUARTER 3-l QUARTER 4 l H-3 l CURIES l 1.50E-01 l 5.10E-01 l 7.81E+01 l-1.26E+02 l FISSION & ACTIVATION PRODUCTS AG-110M CURIES 0.00E+00 0.00E+00 8.08E-05 2.93E-05 CO-57 CURIES 0.00E+00 0.00E+00 5.87E-06 1.22E-06 CO-58' CURIES 0.00E+00 0.00E+00 2.57E-03 3.79E-04 CO-60. CURIES 0.00E+00 0.00E+00 1.59E-03 7.57E-04
-CR-51 CURIES 0.00E+00 0.00E+00 1.55E-04 1.80E-04 CS-134 CURIES 0.00E+00 0.00E+00 9.00E-06 0.00E+00 CS-137 CURIES 0.00E+00 0.00E+00 5.14E 2.52E-04 FE-55 CURIES 0.00E+00 0.00E+00 3.70E-03 1.48E-03 I-130 CURIES 0.00E+00 0.00E+00 l'. 6 4 E- 0 5 0.00E+00 MN-54 CURIES 0.00E+00 0.00E+00 1.04E-04 5.47E-05 NA-24 CURIES 0.00E+00 0.00E+00 3.49E-05 0.00E+00 NB-95 CURIES- 0.00E+00 0.00E+00 6.69E-05 2.16E-05 NB-97 CURIES 0.00E+00 0.00E+00 1.48E-04 6.78E-05 RB CURIES 0.00E+00 0.00E+00 2.52E-05 0.00E+00 SB-124 CURIES 0.00E+00 0.00E+00 3.20E-04 0.00E+00 SB-125 CURIES 0.00E+00 0.00E+00 1.09E-02 6.78E-03 SR-89 CURIES 8.94E-05 2.25E-04 5.77E-06 6.29E-06 SR-90 CURIES 0.00E+00 0.00E+00 3.75E-06 1.30E-06 SR-92 CURIES 0.00E+00 0.00E+00 1.10E-05 4.15E-06 TC-101 CURIES 0.00E+00- 0.00E+00 2.24E-06 0.00E+00 ZN-65 CURIES 0.00E+00 0.00E+00 6.58E-04 0.00E+00 ZR-95' CURIES 0.00E+00 0.00E+00 5.41E-06 .0.00E+00 TOTALS l CURIES l 8.94E-05 l 2.25E-04-l 2.09E-02 l 1.00E-02 l 19
l 1
1 l
TABLE 1-2A*
Joseph M. .Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT '1997 l Liquid Effluents 1
. Unit: 1 l Starting : 1-Jul-1997 Ending : 31-Dec-1997 i
ll CONTINUOUS MODE l BATCH MODE ~l NUCLIDE l UNIT l QUARTER 3 l QUARTER 4 l QUARTER 3.l QUARTER 4 'l' i
i DISSOLVED AND-ENTRAINED GASES-
...____.____.__ __ _..____________________..____..______________ __ __ __________ l AR-41 CURIES -0.00E+00 0.00E+00 8.85E-06 0.00E+00 !
!-XE-133 CURIES 0.00E+00 0.00E+00 9.26E-06 6.60E-05 l L XE-135M CURIES 0.00E+00 0.00E+00 6.35E-06 0.00E+00 TOTALS. CURIES l l 0.00E+00 l 0.00E+00 l 2.45E-05 l 6.60E-05 l
G-ALPHA l CURIES l;0.00E+00 l 0.00E+00 l 1.41E-06 l 4.03E-07 l -1 1
i 1
Zeroes in this table indicate that no radioactivity was present
! at detectable levels. See Table 1-5 for typical minimum.
l detectable concentrations.
i j;
I l
l l
20
I[
TABLE 1-2B0 Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1997-Liquid Effluents Unit: 2 Starting : 1-Jan-1997 Ending : 30-Jun-1997 l
l l l CONTINUOUS MODE 'l BATCH MODE l l l NUCLIDE l UNIT l QUARTER l'l QUARTER'2 l QUARTER 1 l QUARTER 2 l l
l l ------_--_---------------_----_----_----_-------------------_----_-_---.......--
H-3 CURIES l l 2.38E-06 l12.09E-06 l 1.03E+02 l 2.90E+01 l
l l FISSION & ACTIVATION PRODUCTS AG-110M CURIES 0.00E+00 0.00E+00 1.52E-04 2.38E-04 l CO-57 CURIES 0.00E+00 0.00E+00 5.35E-05 7.66E-05 CO-58 CURIES 0.00E+00 0.00E+00 1.18E-02 2.79E-03 CO-60 CURIES 0.00E+00 0.00E+00 -1.78E-03 6.29E-04 CR-51 CURIES 0.00E+00 0.00E+00 6.55E-05 6.57E-05
- CS-137 CURIES 0.00E+00 0.00E+00 1.48E-04 6.04E-05 L FE-55 CURIES 0.00E+00 0.00E+00 1.79E-03 1.23E , HG-203 CURIES 0.00E+00 0.00E+00 0.00E+00 6.13E-07 MN-54 CURIES 0.00E+00 0.00E+00 1.58E-04 2.17E-05 MO-90 CURIES 0.00E+00 0.00E+00 1.00E-06 0.00E+00 NB-95 CURIES 0.00E+00 0.00E+00 2.70E-06 5.98E-06
.NB-97 CURIES 0.00E+00 0.00E+00 8.44E-05 4.66E-05 SB-124 CURIES 0.00E+00 0.00E+00 5.87E-05 2.95E-05 SB-125 CURIES 0.00E+00 0.00E+00 1.03E-03 4.58E-04 SN-117M CURIES 0.00E+00 0.00E+00 0.00E+00 1.89E SR-89 CURIES 0.00E+00 0.00E+00 2.90E-06 0.00E+00 SR-90 CURIES- 0.00E+00 0.00E+00 1.38E 0.00E+00 SR-92 CURIES 0.00E+00 0.00E+00 6.18E-06 1.62E-06 ZN CURIES 0.00E+00 0.00E+00 3.40E-05 6.35E-06 TOTALS 'l CURIES l 0.00E+00 l 0.00E+00 l 1.72E-02-l 5.66E-03 l 4 I
l 21
l l
TABLE 1-2B* 1 Joseph M. Farley Nuclear Plant I i.
ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1997 Liquid Effluents !
Unit: 2 Starting-: 1-Jan-1997 Ending : 30-Jun-1997
]
l CONTINUOUS MODE l BATCH MODE' l NUCLIDE
~
l UNIT l QUARTER 1 l QUARTER 2 l QUARTER 1 l QUARTER 2 l L
' DISSOLVED AND ENTRAINED GASES e
' XE-133M CURIES- 0.00E+00 0.00E+00 3.18E-05 0.00E+00
! XE-135 CURIES- 0.00E+00 0.00E+00 1.47E-06 0.00E+00-l ._______________________________________________________ ______________________.
l . TOTALS l CURIES l 0.00E+00 l_0.00E+00 l 9.76E-03 l~2.18E-04 l l .______________________ _________~_______________________________________________
lG-ALPHA l CURIES l 0.00E+00 l 0.00E+00'l 0.00E+00'l 0.00E+00 l 1
I P
I l
l I'
i' i
I..
1 I
b' l
I 22
TABLE 1-2B*
Joseph M. Farley Nuclear. Plant ANNUAL RADIOACTIVE' EFFLUENT RELEASE REPORT - 1997-Liquid Effluents Unit: 2 Starting : 1-Jul-1997 Ending : 31-Dec-1997 l CONTINUOUS MODE l BATCH MODE NUCLIDE l UNIT l QUARTER 3 l QUARTER 4.l QUARTER 3 l QUARTER'4
'H CURIES l l 1.67E-06-l 1.34E-06 l 7.76E+01 l.2.32E+02 l FISSION & ACTIVATION PRODUCTS
.AG-110M CURIES 0.00E+00 0.00E+00 9.04E-06 4.58E-05 CO-57 CURIES 0.00E+00 0.00E+00 2.04E-05 2.08E-05 CO-58 CURIES 5.42E-05 0.00E+00 1.45E-03. 8.24E-04 CO-60 CURIES 0.00E+00 1.91E-04 9.44E-04 1.42E-03 CR-51 CURIES 0.00E+00 .0.00E+00 3.65E-05 2.22E-04 CS-13'? CURIES 0.00E+00 0.00E+00 1.21E-04 2.98E-04 FE-55 CURIES 0.00E+00 0.00E+00 2.38E-03 l'90E-03 LA-141 CURIES 0.00E+00 0.00E+00 3.24E-05 0.00E+00 MN-54 CURIES 0.00E+00 0.00E+00 4.91E-05 4.82E-05 Nr.- 2 4 - CURIES 0.00E+00 0.00E+00 9.94E-07 3.74E-06 NB-95 CURIES 0.00E+00 0.00E+00 ~4.28E-06 0.00E+00
-NB-97 CURIES 0.00E+00 0.00E+00 5.50E-05. 4.26E-05 SB-124 CURIES 0.00E+00 0.00E+00 2.01E-04 0.00E+00 SB-125 CURIES 0.00E+00 0.00E+00 5.03E-03 9.98E-03 SR-89 CURIES 7.86E-05 5.78E-04 5.00E-06 3.37E-06 SR-90 CURIES 0.00E+00 0.00E+00 6.99E-07 0.00E+00-SR CURIES 0.00E+00 0.00E+00 7.44E-06 2.20E-06 ZN-65: CURIES 0.00E+00 0.00E+00 6.31E-05 4.96E-05 TOTALS CURIES l l 1.33E-04 l~7.68E-04 l 1.04E-02 l 1.49E-02:l.
23
1 J
~ TABLE 1-2B*
' Joseph M. Farley Nuclear. Plant ANNUAL RADIOACTIVE EFFLUENT-RELEASE REPORT - 1997' Liquid Effluents l
l Unit: 2 l Starting : 1-Jul-1997 Ending : 31-Dec-1997 l CONTINUOUS: MODE l BATCH' MODE.
NUCLIDE -l. UNIT -l QUARTER 3 l QUARTER 4-l QUARTER-3 l QUARTER 4
-DISSOLVED'AND ENTRAINED GASES XE-133 CURIES '
.l . l
....____'O.00E+00'-l 0.00E+00 l 3.22E-05'-l 1.41E-04:l-
' TOTALS l~ CURIES l 0.00E+00~l 0.00E+00 l 3.22E-05 l'1.41E-04 l.
_.___________.____....______________________________________________________- q G-ALPHA' CURIES l l 0.00E+00.l 0.00E+00 l 0.00E+00Ll 0.00E+00.l.
...____________________________________________________________________________. l Zeroes in this table indicate that.no radioactivity was present at detectable levels. See Table 1-5 for typical minimum detectable concentrations. ;
24
I TABLE 1-2C0 Joseph M. Farley Nuclear Plant i
ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1997 Liquid Effluents Unit: Site Starting : 1-Jan-1997 Ending : 30-Jun-1997 l CONTINUOUS MODE l BATCH MODE l NUCLIDE l UNIT l QUARTER 1 l QUARTER 2 l QUARTER 1 l QUARTER 2 l H-3 l CURIES l 1.70E-01 l 2.38E-06 l 3.99E+02 l 5.30E+01 l FISSION & ACTIVATION PRODUCTS AG-110M CURIES 0.00E+00 0.00E+00 2.88E-03 2.93E-03 CO-57 CURIES 0.00E+00 0.00E+00 5.50E-04 1.54E-04 CO-58 CURIES 0.00E+00 0.00E+00 3.03E-02 2.70E-02 CO-60 CURIES 0.00E+00 0.00E+00 1.23E-02 3.26E-03 )
'CR-51 CURIES 0.00E+00 0.00E+00 1.83E-03 2.23E-03 !
CS-134 CURIES 0.00E+00 0.00E+00 4.16E-05 6.35E-05 CS-136 CURIES 0.00E+00 0.00E+00 6.02E-06 0.00E+00 ]
CS-137 CURIES 0.00E+00 0.00E+00 8.41E-04 4.64E-04 FE-55 CURIES 0.00E+00 0.00E+00 1.15E-02 6.24E-03 FE-59 CURIES 0.00E+00 0.00E+00 1.06E-04 1.00E-04 HG-203 CURIES 0.00E+00 0.00E+00 0.00E+00 6.13E-07 I-131 CURIES 0.00E+00 0.00E+00 7.62E-06 0.00E+00 I-132 CURIES 0.00E+00 0.00E+00 7.44E-05 0.00E+00 I-133 CURIES 1.41E-03 0.00E+00 3.43E-05 0.00E+00 I-135 CURIES 0.00E+00 0.00E+00 2.52E-05 0.00E+00 MN-54 CURIES 0.00E+00 0.00E+00 4.17E-04 4.30E-04 MO-90 CURIES 0.00E+00 0.00E+00 1.00E-06 0.00E+00 NA-34 CURIES 0.00E+00 0.00E+00 1.34E-05 1.36E-05 NB-95 CURIES 0.00E+00 0.00E+00 1.41E-04 3.19E-04 NB-97 CURIES 0.00E+00 0.00E+00 2.32E-04 1.86E-04 RB-86 CURIES 0.00E+00 0.00E+00 1.34E-05 6.32E-05 RU-103 CURIES 0.00E+00 0.00E+00 1.59E-05 3.66E-06 SB-132 CURIES 0.00E+00 0.00E+00 0.00E+00 2.77E-06 SB-124 CURIES 0.00E+00 0.00E+00 1.89E-04 1.90E-04 SB-125 CURIES 0.00E+00 0.00E+00 4.13E-03 2.38E-03 SN-117M CURIES 0.00E+00 0.00E+00 0.00E+00 1.38E-05 SR-89 CURIES 0.00E+00 0.00E+00 4.07E-05 1.36E-05 SR-90 CURIES 0.00E+00 0.00E+00 1.49E-05 7.56E-06 SR-92 CURIES 0.00E+00 0.00E+00 5.03E-05 2.06E-05 TC-99M CURIES 0.00E+00 0.00E+00 2.00E-05 0.00E+00 TE-125M CURIES 0.00E+00 0.00E+00 0.00E+00 1.20E-03 TE-132 CURIES 0.00E+00 0.00E+00 5.84E-05 0.00E+00 ZN-65 CURIES 0.00E+00 0.00E+00 1.10E-04 1.07E-05 25
I TABLE 1-2C*
Joseph M. Farley Nuclear Plant i
ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1997 LLiquid Effluents Unit: Site Starting : 1-Jan-1997 Ending : 30-Jun-1997 l l CONTINUOUS MODE l BATCH MODE l l NUCLIDE .l- UNIT l QUARTER 1 l QUARTER 2 l QUARTER 1 l QUARTER 2 l i
' FISSION & ACTIVATION PRODUCTS 1
___. . ___ __________..___-.._____________________________________________________ I
.ZN-69M CURIES 0.00E+00 0'.00E+00 9.72E-06 0.00E+00 ZR-95 CURIES 0.00E+00 -0.00E+00 5.47E-05 1.70E-04 TOTALS CURIES l l l 1.41E-03 l 0.00E+00 l 6.61E-02 l 4.75E-02 l
_________________________________.___________ __________.______________________. 1 i
DISSOLVED AND ENTRAINED GASES ;
AR-41 CURIES 0.00E+00 0.00E+00 1.17E-05 2.64E-05
, XE-133 CURIES 0.00E+00 0.00E+00 2.59E-02 3.86E-04 l XE-133M CURIES 0.00E+00 0.00E+00 7.33E-05 0.00E+00 i XE-135 CURIES 0.00E+00 0.00E+00 2.09E-05 0.00E+00
! TOTALS l CURIES 'l 0.00E+00 l 0.00E+00 l 2.60E-02 l 4.12E-04 l G-ALPHA -l CURIES l 0.00E+00 l 0.00E+00 l 8.37E-06 l 2.85E-06.l
!
- Zeroes in this table indicate that no radioactivity was present at detectable-levels. See Table 1-5 for typical minimum detectable concentrations.
t i
I' 26
TABLE 1-2C0 Joseph M. Farley Nuclear Plant l- ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1997 l Liquid Effluents Unit: Site Starting : 1-Jul-1997 Ending : 31-Dec-1997 l l CONTINUOUS MODE ] BATCH MODE 'l NUCLIDE l UNIT l QUARTER 3 l QUARTER 4 l QUARTER 3 l QUARTER 4'l H-3 CURIES l l l11.50E-01 l 5.10E-01 l 1.56E+02 l 3.58E+02 l j FISSION & ACTIVATION PRODUCTS i
! CO-57 CURIES 0.00E+00 0.00E+00 2.62E-05 2.20E-05 CO-58 CURIES 5.42E-05 0.00E+00 4.0'L-03 1.20E-03 CO-60 CURIES 0.00E+00 1.91E-04 2 63E-03 2.18E ,
CR-51 CURIES 0.00E+00 0.00E+00 1.92E-04 4.02E-04 CS-134 CURIES 0.00E+00 0.00E+00 9.00E-06 0.00E+00
! -CS-137 CURIES 0.00E+00 0.00E+00 6.34E-04 5.50E-04 l FE-55 CURIES 0.00E+00 0.00E+00 6.08E-03 3.39E-03 L I-130 CURIES 0.00E+00 0.00E+00 1.64E-05 0.00E+00 LA-141 CURIES 0.00E+00 0.00E+00 3.24E-05 0.00E+00 MN-54 CURIES 0.00E+00 0.00E+00 1.53E-04 1.03E-04 MA-24 CURIES 0.00E+00 0.00E+00 3.59E-05 3.74E-06 NB-95 CURIES 0.00E+00 0.00E+00 7.12E-05 2.16E-05 L NB-97 CURIES 0.00E+001 '0.00E+00 2.03E-04 1.10E-04 RB-86 CURIES 0.00E+00 0.00E+00 2.52E-05 0.00E+00 SB-124 CURIES 0.00E+00 0.00E+00 5.21E-04 0.00E+00 SB-125 CURIES 0.00E+00 0.00E+00 1.59E-02 1.68E-02 SR-89 CURIES 1.68E-04 8.02E-04 1.08E-05 9.66E-06 l- SR-90 CURIES 0.00E+00 0.00E+00 4.45E-06 1.30E-06 SR-92 CURIES 0.00E+00 0.00E+00 1.84E-05 6.35E-06 TC-101 CURIES 0.00E+00 0.00E+00 2.24E-06 0.00E+00 ZN-65 CURIES 0.00E+00 0.00E+00 7.22E-04 4.96E-05
'ZR-95 CURIES 0.00E+00 0.00E+00- 5.41E-06 0.00E+00
. TOTALS l CURIES l 2.22E-04 l 9.93E-04 l 3.14E-02 l 2.49E-02,l l
l 27 i
l
TABLE 1-2C0 Joseph.M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT -'1997' Liquid Effluents Unit: Site Starting : 1-Jul-1997 Ending : 31-Dec-1997 l CONTINUOUS MODE. 'l BATCH MODE MUCLIDE .l UNIT
~
l QUARTER 3 l QUARTER 4 l QUARTER 3 l QUARTER 4 l DISSOLVED AND ENTRAINED GASES
'AR-41 CURIES 0.00E+00 0.00E+00 8.85E-06 '0.00E+00 XE-133- CURIES -0.00E+00 0.00E+00 4.15E-05 2.07E-04 XE-135M CURIES 0.00E+00 0.00E+00 6.35E-06 0.00E+00 TOTALS j CURIES l 0.00E+00 l
___________________________________________'0.00E+00 l 5.67E-05 l 2.07E-04: l G-ALPHA l CURIES l 0.00E+00 l 0.00E+00 l 1.41E-06 l.4.04E-07 o Zeroes in this table indicate that no radioactivity was present at detectable levels. See Table 1-5 for typical minimum detectable concentrations.
l 28
I 2.6 Radiological Impact i
The total body and organ doses for Units 1 and 2 are provided in the following tables in order to show conformance with the limits of ODCM 2.1.3 :
Unit 1 1997 Liquid Doses : Table 1-3A Unit 2 1997 Liquid Doses : Table 1-3B l
l 1
i l
l 1
1 1
1 1
l l
l 29 l
1 l
! i l l l
j.
- . TABLE 1-3A Joseph M. Farley Nuclear Plant j ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1997 ;
' DOSES TOiA MEMBER OF THE PUBLIC DUE TO LIQUID RELEASES l Unit: 1 l Starling: 01-Jan-1997 Ending: 30-Jun-1997
^
1 Cumulative Doses per Quarter l
!. Organ ODCM Units Quarter. % of Quarter ~ % of l Limit 1 ODCM 2 .ODCM i
Limit Limit l Bone 5.0 mrem 3.09E-03 6.18E-02 1.83E-03 3.66E-02 i Liver 5.0 mrem 5.03E-03 '1.01E-01 1.86E 3.73E-02 I l TBody- . 1.5 mrem 4.01E-03 2.67E-01 1.23E-03 8.23E-02 I l Thyroid 5.0 mrem 2.67E-03 5.35E-02 2.54E-04 5.08E-03 i Kidney 5.0 mrem 2.73E-03 5.47E-02_ 1.74E-03 _3.47E-02 l Lung- 5.0 mrem 1.93E-02 3.85E-01 9.33E-03 1.87E-01 GZLLI 5.0 mrem 1.03E-02 2.05E-01 6.08E-03 1.22E-01 L
Cumulative Doses per Year l i
Organ ODCM Units Year to % of 1 l Limit Ending ODCM l
Date Limit l _ _ _ ,
l Bone 10.0 mrem 4.92E-03 4.92E-02 Liver 10.0 mrem 6.89E-03 6.89E-02
-TBody 3.0 ' mrem 5.24E-03 1.75E-01
' Thyroid 10.0 mrem 2.93E-03 2.93E-02
! Kidney 10.0 mrem 4.47E-03 4.47E-02
' Lung 10.0 mrem 2.86E-02 2.86E-01 GILLI 10.0 mrem 1.63E-02 1.63E-01 l
I t !
30
1 i
l 1
TABLE 1-3A l Joseph M. Farley Nuclear Plant
)
ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1997 l DOSES TO A MEMBER OF THE PUBLIC DUE TO LIQUID RELEASES l Unit: 1 Starting: 01-Jul-1997 Ending: 31-Dec-1997-1' Cumulative Doses'.per Quarter.
l Organ ODCM Units Quarter.' .%,of Quarter % of Limit ~3 ODCM' 4 ODCM Limit Limit i i
_________. ___.__________ ________________________________________________ a l
-Bone 5.0 mrem- 1.85E-03 3.70E-02 1.07E-03 2.14E-02
~ Liver 5.0 mrem 1.93E-03 3.87E-02 1.54E-03 3.09E-02 l TBody- 1.5 mrem 1.41E-03 9.38E-02 1.35E-03 8.97E-02 j
- Thyroid- 5.0 mrem 5.45E-04 1.09E-02 9.45E-04 1.89E-02
-Kidney 5.0 . mrem 8.43E-04 1.69E-02 1.08E-03 2 .15 E - D'i Lung 5.0 mrem 5.13E-02 1.03E+00 3.45E-02 6.89E-61 GILLI 5.0 mrem 6.34E-03 1.27E-01 4.17E-03 8. 3 4 E- 02
.___________________________________________..______________.._____________ i Cumulative Doses per Year
-Organ ODCM Units Year to % of Limit Ending ODCM.
Date Limit Bone 10.0 mrem 7.83E-03 7.83E-02
. Liver 10.0 mrem 1.04E-02 1.04E-01
- TBody. 3.0 mrem 8.00E-03 2.67E-01 1 Thyroid 10.0 mrem 4.42E-03 '4.42E l Kidney 10.0 mrem 6.39E-03 6.39E-02 j Lung 10.0 mrem 1.14E-01 1.14E+00 '
GILLI 10.0 mrem 2.68E-02 2.68E-01 31
l TABLE 1-3B i Joseph M. Farley Nuclear Plant
! ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1997 DOSES TO A MEMBER OF THE PUBLIC DUE TO LIQUID RELEASES Unit: 2 Starting: 01-Jan-1997 Ending: 30-Jun-1997 i
Cumulative Doses per Quarter Organ ODCM- Units Quarter % of Quarter % of Limit 1 ODCM 2 ODCM Limit Limit Bone 5.0 mrem 5.24E-04 1.05E-02 2.95E-04 5.91E-03 Liver 5.0 mrem 1.19E-03 2.38E-02 4.45E-04 8.91E-03 TBody 1.5 mrem 1.06E-03 7.09E-02 3.35E-04 2.23E-02 Thyroid 5.0 mrem 6.94E-04 1.39E-02 1.91E-04 3.83E-03 Kidney 5.0 mrem 7.64E-04 1.53E-02 2.21E-04 4.41E-03 Lung 5.0 mrem 5.39E-03 1.08E-01 2.39E-03 4.78E-02 GILLI 5.0 mrem 2.84E-03 5.67E-02 9.40E-04 1.88E-02 Cumulative Doses per Year Organ ODCM Units Year to % of l Limit Ending ODCM Date Limit Bone 10.0 mrem 8.19E-04 8.19E-03 Liver 10.0 mrem 1.63E-03 1.63E-02 TBody 3.0 mrem 1.40E-03 4.66E-02 Thyroid 10.G mrem 8.86E-04 8.86E-03 Kidney 10.0 mrem 9.85E-04 9.85E-03 Lung 10.0 mrem 7.78E-03 7.78E-02 GILLI 10.0 mrem 3.78E-03 3.78E-02 32
o
- TABLE 1-3B j Joseph M. Farley Nuclear Plant ANNUAL-RADIOACTIVE EFFLUENT RELEASE REPORT - 1997
. DOSES TO A MEMBER OF THE PUBLIC DUE TO LIQUID RELEASES Unit: 2
- Starting
- 01-Jul-1997 Ending: 31-Dec-1997 L
i
- Cumulative Doses per Quarter
! Organ ODCM Units Quarter % of Quarter % of L Limit 3 ODCM 4 ODCM l Limit Limit
' Bone 5.0 mrem- -8.45E-04 1.69E-02 1.47E-03 2.94E-02 l Liver 5.0 mrem 1.04E-03 2.07E-02 2.32E-03 4.63E-02 l' TBody 1.5 mrem 8.28E-04 5.52E-02 2.11E-03 1.41E-01
! Thyroid 5.0 mrem 5.35E-04 1.07E-02 1.61E-03 3.23E-02 Kidney 5.0. mrem 5.98E-04 1.20E-02 1.76E-03 3.52E-02 Lung 5.0 mrem 2.36E-02 4.71E-01 4.86E-02 9.72E-01 GILLI 5.0 mrem 3.47E-03 6.93E-02 6.30E-03 1.26E-01 l
t I
l Cumulative Doses per Year L Organ ODCM Units Year to % of l Limit Ending ODCM
(. Date Limit i
L Bone- 10.0 mrem 3.14E-03 3.14E-02 Liver 10.0 mrem 4.99E-03 4.99E-02 TBody 3.0 mrem 4.34E-03 1.45E-01 Thyroid 10.0 mrem 3.03E 3.03E-02 Kidney 10.0 mrem 3.34E-03 3.34E-02 Lung- 10.0 . mrem 8.00E-02 8.00E-01 j GILLI 10.0 mrem 1.35E-02 1.35E-01 l
l l
33 5
I i
i TABLE 1-5 Joseph M.:Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT..-'1997 TYPICAL LIQUID MDC'S ACHIEVED ON COUNTING SYSTEM L ,
l i
I Nuclide- MDC(uCi/ML) 1 1
MN-54 3.14E-08
'CO-58' 4.92E- 8 FE-59 7.19E-08
! l CO-60 4.77E-08 I f-ZN-65 8.11E-08 MO-99 1.29E-07 l I-131 2.53E-08 I
CS-134' 3.51E-08 CS-137 4.28E-08 CE-141 5.41E-08 CE-144 1.95E-07 l
l L !
1 1
34 l
l
i i
.1 TABLE 1-6A J Joseph' M. .Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT-RELEASE REPORT - 1997 Liquid Effluents - Abnormal Release Summary.
Unit: 1 Starting : 1-Jan-1997 -Ending': 30-Jun-1997 l
LIQUID RELEASES
____._____________________________________________.______________________________ i l NUMBER OF RELEASES : 0 l TOTAL TIME FOR'ALL RELEASES : 0.00 MINUTES !
! . MAXIMUM TIME'FOR A RELEASE : 0.00 MINUTES.
l RVERAGE TIME FOR A RELEASE : 0.00 MINUTES
, MINIMUM TIME FOR A. RELEASE : 0.00 MINUTES l E TOTAL ACTIVITY FOR ALL RELEASES : 0.00E+00 CURIES
, _____________________________-___._-______-___________________________.. ... ____ I l-1 l
I l
l
- i. l i
TABLE.1-6A Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1997 l ' Liquid Effluents - Abnormal Release Summary
. Unit:'1 Starting : 1-Jul-1997 Ending : 31-Dec-1997 l
i ..
i I
LIQUID RELEASES NUMBER OF RELEASES : 0 i 1 TOTAL TIME FOR ALL RELEASES : 0.00 MINUTES
' MAXIMUM TIME FOR A RELEASE : 0.00' MINUTES
' AVERAGE TIME FOR A RELEASE : 0.00 -MINUTES
. MINIMUM TIME FOR A RELEASE : 0.00 MINUTES .
I TOTAL ACTIVITY FOR ALL RELEASES : 0.00E+00 CURIES l i i L
1 t
. 1 i
t i
i t
l l
I' l
l L
36
TABLE 1-6B Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1997 Liquid Effluents - Abnormal Release Summary Unit: 2 Starting': 1-Jan-1997 Ending : 30-Jun-1997 j ________________________________________________________________________________
l l~
LIQUID RELEASES i ___ ____________________________________________________________________________
NUMBER OF' RELEASES : 0 iTOTAL TIME FOR ALL RELEASES- : 0.00 MINUTES 1
MAXIMUM TIME FOR A RELEASE : 0.00 MINUTES AVERAGE TIME FOR A-RELEASE
- 0.00 MINUTES-MINIMUM TIME FOR A RELEASE : 0.00 MINUTES TOTAL ACTIVITY FOR ALL RELEASES : 0.00E+00 CURIES J
l ._._____________________.__ ________________.____________________________________ j 1
l l
{
1 I
i- i l
1 I
i l
l f'
l l
l 37 i.
1 I
i TABLE 1-6B- 5 Joseph M. Farley Nuclear. Plant ANNUAL-RADIOACTIVE EFFLUENT RELEASE' REPORT --1997 Liquid Effluents - Abnormal Release Summary Unit: 2
. Starting-: 1-Jul-1997 Ending : 31-Dec-1997 LIQUID RELEASES NUMBER OF RELEASES : 0 TOTAL TIME FOR ALL RELEASES : 0.00 MINUTES MAXIMUM TIME FOR A RELEASE : 0.00- MINUTES AVERAGE TIME FOR A RELEASE : 0.00 MINUTES MINIMUM TIME FOR A RELEASE : 0.00 MINUTES TOTAL ACTIVITY FOR~ALL RELEASES : 0.00E+00 CURIES I
l l
38 j 1
1 I
3.0 GASEOUS EFFLUENTS I This section contains applicable ODCM limits for gaseous effluents as well as the quantities of radioactive gaseous effluents released during 1997. These quantities are summarized on a quarterly basis and include any unplanned releases. Tabulations are provided of the 1 offsite air doses calculated in accordance with ODCM 3.4.2 to show conformance with the limits of ODCM 3.1.3, and the offsite organ j
doses to a member of the public calculated in accordance with ODCM {
3.4.3 to show conformance with ODCM 3.1.4.
3.1 ODCM Limits In accordance ' with Technical Specifications 6.8.3.e (v) and I 6 . 8 . 3 . e (viii) , the air dose.due to noble gases released in gaseous. effluents, from each reactor unit, to areas at and beyond the SITE BOUNDARY (see ODCM Figure 10-1) shall be limited to the following:
- a. During any calendar quarter: Less than or equal to 5 mrad for gamma radiation and less than or equal to 10 mrad for beta radiation, and a
- b. During any calendar year: Less than or equal to 10 mrad-for gamma radiation and less than or equal to 20 mrad for beta radiation.
In accordance ' with Technical Specifications 6. 8.3.e (v) and
- 6. 8. 3. e (ix) , the dose to a MEMBER OF THE PUBLIC from I-131, I-133, tritium, and all radionuclides in particulate form with half-lives greater than 8 days in gaseous effluents released, from each reactor unit, to areas at and beyond the SITE BOUNDARY (see ODCM Figure 10-1) shall be limited to the following:
- a. During any calendar quarter: Less than or equal to 7.5 mrem to any organ, and
- b. During any calendar year: Less than or equal to 15 mrem to any organ.
3.2 Measurements and Approximation of Total Radioactivity The following noble gases are considered in evaluating gaseous effluents:
KR-87 XE-133 KR-88 XE-135 XE-133M XE-138 39
I l
1 The following radiciodines and radioactive materials in l particulate form are specifically considered in evaluating '
gaseous' effluents:
.CO-58 CS-134 CO-60 CS-137 ZN-65 CE-141
.SR-89 CE-144 SR-90 H-3 Periodic grab samples from plant effluent streams are analyzed l by a computerized pulse height analyzer system utilizing high '
resolution germanium detectors. Samples are obtained and analyzed in accordance with ODCM Table 3-3. Isotopic values thus obtained are used for release rate calculations as specified in ODCM-3.4.2 and ODCM-3.4.3. Only those nuclides which are detected are
.used in calculations. For radioiodines and particulates, in addition to the nuclides listed above other nuclides with half-lives greater than 8 days which are identified are also considered.
Continuous Releases: Continuous sampling is performed on the I continuous releases points (i.e. the Plant Vent Stack, Containment j Purge, and the Turbine Building Vent). Particulate material is collected by filtration. Periodically these filters are removed and analyzed on the pulse height analyzer to identify and quantify )
radioactive materials collected on the filters. Particulate filters are then analyzed for gross alpha and strontium as required. Gross I alpha determinations are made using a 2 pi gas flow proportional counter. All Sr-89 and SR-90 samples are sent offsite to the Georgia Power Environmental Laboratory for analysis.
Batch Releases: The processing of batch type releases (from ;
Containment or Waste Gas Decay Tanks) is analogous to continuous releases, except that the release is not commenced until samples have been obtained and analyzed.
The maximum errors associated with monitor readings, sample flow, vent flow, sample collection, monitor calibration and laboratory procedure are collectively estimated to be:
, Fission and i Activation Gases Iodine Particulates Tritium 75% 60% 50% 45%'
The average error associated with counting is estimated to be:
Fission and Activation Gases Iodine Particulates Tritium 19% 28% 20% 8%
f 40 i
1 l
1 3.3 Abnormal Releases i i There were 6 abnormal releases on Unit 1 during:the first half I.
' of 1997 and 6 abnormal releases on Unit 1 during the second half of 1997..These releases were due to releases via the Turbine Driven Auxiliary Feed Pump and.the Atmospheric Relief Valves while a small (.a, proximately 2 GPD ) primary to i
secondary leak existed on Unit .1 .
There were no abnormal releases on Unit 2 during'1997.
Abnormal release information for Units 1 and 2 is summarized in the following tables:
Unit 1 1997 Gaseous Abnormal Releases : Table 2-8A 1 j Unit ~2 1997 Gaseous Abnormal Releases : Table 2-8B 3.4 Batch Releases i
j_
Batch release information for Units 1 and 2 is summarized in the
'following. tables:
l
! Unit'1 1997 Gaseous Batch Releases : Table 2-6A Unit 2 1997 Gaseous Batch Releases.: Table 2-6B l
t I
l.
l )
t 1
}
l 41 !
i l
i v i i
TABLE 2-8A Joseph M. Farley Nuclear Plant.
ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1997 Gaseous' Effluents.- Abnormal. Release Summary Unit: 1 i
Starting : 1-Jan-1997 Ending : 30-Jun_1997-
- GASEOUS RELEASES NUMBER OF RELEASES : 6 TOTAL TIME FOR ALL RELEASES- : 2337.00 MINUTES MAXIMUM TIME ~FOR A RELEASE' : 1648.00 MINUTES AVERAGE TIME FOR A RELEASE : 389.50 MINUTES !
MINIMUM TIME FOR'A RELEASE : 3.00 MINUTES TOTAL ACTIVITY FOR ALL RELEASES : 4.85E CURIES l
l 42
-TABLE 2-8A l
Joseph M. Farley Nuclear Plant ANNUAL' RADIOACTIVE EFFLUENT RELEASE REPORT - 1997 l ' Gaseous Effluents - Abnormal Release. Summary Unit: 1 Starting : 1-Jt11 - 19 97 Ending : 31-Dec-1997 GASEOUS RELEASES l NUMBER OF RELEASES : 6 1 TOTAL TIME FOR.ALL RELEASES : 424.00 MINUTES MAXIMUM TIME'FOR A RELEASE : 219.00 MINUTES-
, . AVERAGE TIME FOR A RELEASE : 70.67 MINUTES MINIMUM TIME FOR A RELEASE : 2.00 MINUTES TOTAL-ACTIVITY FOR ALL. RELEASES : 6.01E-04 CURIES
(
i I
I i:
l l
l i
l 43 I
I
TABLE 2-8B Joseph.M. Farley Nuclear' Plant' .
ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1997 '
! -Gaseous Effluents - Abnormal Release Summary Unit: 2 l Starting : l'-Jan-1997 Ending : 30-Jun-1997 i
,i GASEOUS RELEASES l NUMBER OF RELEASES : 0 TOTAL TIME FOR ALL RELEASES : 0.00 MINUTES L MAXIMUM TIME FOR A RELEASE : 0.00 MINUTES j AVERAGE TIME FOR A RELEASE : 0.00' MINUTES
- MINIMUM TIME FOR A RELEASE
- 0.00 MINUTES
- TOTAL ACTIVITY FOR ALL RELEASES
- 0.00E+00 CURIES I l
l l
)
i i
i 1
1 l
l l
! 44
TABLE 2-8B l --
Joseph,M. Farley Nuclear. Plant.
ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1997 Gaseous Effluents - Abnormal Release Summary Unit: 2 Starting : 1-Jul-1997 Ending : 31-Dec-1997 1
I GASEOUS. RELEASES l NUMBER OF RELEASES : 0 TOTAL TIME FOR ALL' RELEASES : 0.00 MINUTES MJOCIMUM TIME FOR ^A RELEASE : 0.00 MINUTES
- RVERAGE TIME FOR A RELEASE
- 0.00 MINUTES MINIMUM TIME FOR A. RELEASE : 0.00 MINUTES TOTAL ACTIVITY FOR ALL RELEASES : 0.00E+00 CURIES i
i l
l l'
l 45 l-f l
TABLE 2-6A Joseph M. Farley Nuclear-Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1997 Gaseous Effluents - Batch Release Summary.
Unit: l' .
Starting : 1-Jan-1997 Ending : 30-Jun-1997 !
_______________________.________.__________________.__..___________________ ...._ l I
GASEOUS RELEASES NUMBER OF BATCH RELEASES : 17 TOTAL TIME PERIOD-FOR-BATCH RELEASES : 5270.00 MINUTES MAXIMUM TIME PERIOD FORJA BATCH RELEASE : 478.00 MINUTES .
AVERAGE' TIME. PERIOD FOR BATCH RELEASES : 310.00 MINUTES l MINIMUM TIME FOR A BATCH RELEASE : 179.00 MINUTES ,
1
________________________________________________________________________________ 1 1
l 46
TABLE 2-6A Joseph M. Farley Nuclear Plant-ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1997 Gaseous Effluents - Batch Release Summary Unit: 1 Starting : 1-Jul-1997 Ending : 31-Dec-1997 l
i l
l-
~
GASEOUS RELEASES NUMBER OF BATCH, RELEASES : 5 L TOTAL TIME PERIOD FOR BATCH RELEASES : 1359.00 MINUTES.
L ' MAXIMUM TIME PERIOD FOR A BATCH RELEASE 1
- 391.00 MINUTES AVERAGE. TIME PERIOD FOR BATCH RELEASES : 271.80 MINUTES MINIMUM TIME FOR A BATCH RELEASE : 2.00 MINUTES y _____________________________________________________________________________.__
?
I i
l l
)
t 1
1 1
47 l-
i-i o
TABLE'2-6B l Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT.- 1997 l Gaseous Effluents - Batch Release' Summary' i Unit: 2-Starting : 1-Jan-1997 Ending : 30-Jun-1997
)
________________________________________________________________________________ i i
I GASEOUS RELEASES NUMBER OF BATCH RELEASES ~ : 0 TOTAL TIME PERIOD FOR BATCH RELEASES : 0.00' MINUTES MAXIMUM TIME PERIOD FOR A BATCH RELEASE : 0.00 ~ MINUTES AVERAGE TIME PERIOD FOR BATCH' RELEASES : 0.00- MINUTES MINIMUM TIME FOR A BATCH RELEASE : 0.00 MINUTES f
h I
48
1 1
TABLE 2-6B j Joseph M. Farley Nuclear Plant ;
ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1997' J Gaseous Effluents - Batch' Release Summary.
Unit: 2 Starting : 1-Jul-1997 Ending : 31-Dec-1997 )
I
_______________________________________________________________________________. 3
.J GASEOUS RELEASES NUMBER'OF BATCH RELEASES : -0 TOTAL TIME PERIOD.FOR BATCH RELEASES : 0.00 MINUTES MAXIMUM' TIME PERIOD'FOR A. BATCH RELEASE : 0.00 MINUTES AVERAGE TIME PERIOD FOR BATCH RELEASES : 0.00 MINUTES MINIMUM TIME FOR A' BATCH RELEASE : 0.00 MINUTES l
.______ ___________._____________.___________________.___________________________ l 1
l 1
l
'1 i
49 i ,
I
-3.5 Release Summaries l This section contains the-summaries of'all radioactive gaseous effluents ~ released for Units-1 and 2 during 1997. Typical gaseous ,
Miniumum Detectable-Concentrations (MDC'S) for analyses are )
in Table;2-7 of this section. Regulatory Guide 1.21 Table 1A is !
found in this report as Tables 2-1A, 2-1B, and 2-1C. Regulatory Guide l'.21-Table 1B is found in this report as Tables 2-2A, 2-2B, and 2-2C.' Regulatory Guide 1.21 Table 1C is found in this report as Tables 2-3A,.2-3B, and 2-3C.
3.5.1 Gaseous' Effluents - Summation of All' Releases The-summations of all gaseous effluent releases are contained in the following tables:
Unit 1 1997 Summation of All Releases : Table 2-1A Unit 2 1997 Summation of All Releases : Table 2-1B LSite 1997 Summation of All Releases : Table 2-1C i
l i
l I
50 l
l l
1 I
TABLE 2-1A Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1997 Gaseous Effluents - Summation of All Releases Unit: 1 Starting : 1-Jan-1997 Ending : 30-Jun-1997 TYPE OF EFFLUENT UNITS QUARTER 1 QUARTER 2 EST. TOT ERROR %
A. FISSION & ACTIVATION PRODUCTS
- 1. TOTAL RELEASE CURIES 3.01E+01 3.61E+01 9.40E+01
- 2. AVERAGE RELEASE RATE FOR PERIOD uCi/Sec 3.87E+00 4.59E+00
- 3. PERCENT OF APPLICABLE LIMIT % *
- B. RADIOIODINES
- 1. TOTAL IODINE-131 CURIES 1.12E-04 1.43E-05 8.80E+01
- 2. AVERAGE RELEASE RATE FOR PERIOD uCi/Sec 1.44E-05 1.82E-06
- 3. PERCENT OF APPLICABLE LIMIT % *
- C. PARTICULATES
- 1. PARTICULATES(HALF-LIVES >8 DAYS) CURIES 4.44E-07 5.31E-06 7.00E+01
- 2. AVERAGE RELEASE RATE FOR PERIOD uCi/Sec 5.70E-08 6.75E-07
- 3. PERCENT OF APPLICABLE LIMIT % * *
- 4. GROSS ALPHA RADIOACTIVITY CURIES 7.70E-08 1.64E-08 D. TRITIUM
- 1. TOTAL RELEASE CURIES 3.65E+00 3.21E+00 5.30E+01
- 2. AVERAGE RELEASE RATE FOR PERIOD uCi/Sec 4.69E-01 4.08E-01
- 3. PERCENT OF APPLICABLE LIMIT % *
- t l
l i
o Applicable limits are expressed in terms of dose. See Tables 2-4A, 2-4B, 2-5A, and 2-5B of this report.
51
f '
l
. TABLE 2-1R Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE' EFFLUENT RELEASE-REPORT - 1997' f-I Gaseous. Effluents Summation of'All~ Releases-Unit: 1 Starting : 1-Jul-1997- -Ending : 31-Dec-1997 ITYPE OF. EFFLUENT UNITS QUARTER 3 QUARTER 4 EST. TOT ERROR'%
i A. FISSION & ACTIVATION PRODUCTS 1..TCXUUL RELEASE CURIES 1,64E+01- 1.60E+01 9.40E+01 2.-AVERAGE-RELEASE RATE FOR-PERIOD 'uCi/Sec 2.07E+00 2.01E+00 g ____.________..._____________________________.._______....___..________________.
- 3. PERCENT OF APPLICABLE LIMIT % *
- l l
t B. RADIOIODINES
- 1. TOTAL IODINE-131 CURIES 6.62E-07 0.00E+00 8.80E+01
- 2. AVERAGE RELEASE RATE FOR PERIOD uCi/Sec 8.33E-08 0.00E+00'
- 3. PERCENT OF APPLICABLE LIMIT % '*
- C. PARTICULATES
- 1. PARTICULATES(HALF-LIVES >8 DAYS) CURIES 8.54E-08 4.18E-07 7.00E+01-2.. AVERAGE RELEASE RATE FOR-PERIOD uCi/Sec 1.07E-08 5.25E-08
- 3. PERCENT OF APPLICABLE LIMI1 %- * *
- 4. GROSS ALPHA RADIOACTIVITY CURIES 5.41E-07 2.87E-07 D. TRITIUM
- 1. TOTAL RELEASE CURIES 2.95E+00 4.62E+00 5.30E+01
- 2. AVERAGE RELEASE RATE FOR PERIOD uCi/Sec 3.71E-01 5.81E-01 L -3. PERCENT OF APPLICABLE LIMIT % *
- h o Applicable limits are expressed in terms of dose. See Tables 2-4A,'2-4B, 2-5A, and 2-5B of this report. !
52 1
I l
TABLE 2-1B Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1997 Gaseous Effluents - Summation of All Releases Unit: 2 Starting : 1-Jan-1997 Ending : 30-Jun-1997 TYPE OF EFFLUENT UNITS QUARTER 1 QUARTER 2 EST. TOT i ERROR %
A.-FISSION & ACTIVATION PRODUCTS
- 1. TOTAL RELEASE CURIES 7.95E+00 1.00E+01 9.40E+01
- 2. AVERAGE RELEASE RATE FOR PERIOD uCi/Sec 1.02E+00 1.28E+00
~
3I'hbRbbhT bb kPPb bkbbb LEkkT h *
- B. RADIOIODINES i
- 1. TOTAL IODINE-131 CURIES 6.95E-07 9.90E-07 8.80E+01
________________________________________________________________________________ \
- 2. AVERAGE RELEASE RATE FOR PERIOD uCi/Sec 8.94E-08 1.26E-07
- 3. PERCENT OF APPLICABLE LIMIT % *
- C. PARTICULATES
- 1. PARTICULATES(HALF-LIVES >8 DAYS) CURIES 2.66E-08 9.63E-08 7.00E+01
- 2. AVERAGE RELEASE RATE FOR PERIOD uCi/Sec 3.42E-09 1.22E-08
- 3. PERCENT OF APPLICABLE LIMIT % * *
- 4. GROSS ALPHA RADIOACTIVITY CURIES 6.22E-08 4.98E-08 D. TRITIUM
- 1. TOTAL RELEASE CURIES 1.11E+01 2.49E+01 5.30E+01
- 2. AVERAGE RELEASE RATE FOR PERIOD uCi/Sec 1.43E+00 3.17E+00 l 3. PERCENT OF APPLICABLE LIMIT % *
- l l
l
- Applicable limits are expressed in terms of dose. See Tables 2-4A, 2-4B, 2-5A, and 2-5B of this report.
53
a TABLE 2-1B Joseph M. Farley Nuclear Plant 1 ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1997 1 Gaseous Effluents - Summation of All Releases Unit: 2 Starting : 1-Jul-1997 Ending : 31-Dec-1997 l l
1 I
TYPE OF EFFLUENT UNITS QUARTER 3 QUARTER 4 EST. TOT ERROR %
A. FISSION & ACTIVATION PRODUCTS
________________________________________________________________________________ 1
- 1. TOTAL RELEASE CURIES 9.93E+00 1.44E+01 9.40E+01 1
i 1
- 2. AVERAGE RELEASE RATE FOR PERIOD uCi/Sec 1.25E+00 1.81E+00
- 3. PERCENT OF APPLICABLE LIMIT % *
- B. RADIOIODINES i l
- 1. TOTAL IODINE-131 CURIES 1.15E-06 1.94E-06 8.80E+01
- 2. AVERAGE RELEASE RATE FOR PERIOD uCi/Sec 1.45E_07 2.45E-07 '
- 3. PERCENT OF APPLICABLE LIMIT % * * .
1 l
C. PARTICULATES
- 1. PARTICULATES (HALF-LIVES >8 DAYS) CURIES 4.98E-09 1.42E-09 7.00E+01
- 2. AVERAGE RELEASE RATE FOR PERIOD uCi/Sec 6.27E-10 1.78E-10
- 3. PERCENT OF APPLICABLE LIMIT % * *
- 4. GROSS ALPHA RADIOACTIVITY CURIES 1.68E-08 5.69E-07 D. TRITIUM
- 1. TOTAL RELEASE CURIES 1.9?E+01 2.12E+01 5.30E+01
- 2. AVERAGE RELEASE RATE FOR PERIOD uCi/Sec 2.42E+00 2.67E+00
- 3. PERCENT OF APPLICABLE LIMIT %
- l o Applicable limits are expressed in terms of dose. See Tables 2-4A, 2-4B, 2-5A, and 2-5B of this report.
54 f
I
TABLE 2-1C Joseph M. Farley Nuclear Plant
' ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1997 i Gaseous Effluents - Summation of All Releases '
Unit: Site Starting-: 1-Jan-1997 Ending : 30-Jun-1997 TYPE ~OF-EFFLUENT UNITS QUARTER 1 QUARTER 2 EST. TOT i i
ERROR % I A. FISSION & ACTIVATION PRODUCTS
- 1. TOTAL RELEASE CURIES 3.80E+01 4.61E+01 9.40E+01
- 2. AVERAGE uCi/Sec 4.89E+00 5.87E+00 RELEASE RATE FOR PERIOD
- 3. PERCENT OF APPLICABLE LIMIT % *
- ________________________________________________________________________________ 1 B. RADIOIODINES 1, TOTAL IODINE-131 CURIES 1.13E-04 1.53E-05 8.80E+01 l
- 2. AVERAGB RELEASE RATE FOR PERIOD uCi/Sec 1.45E-05 . 1.95E-06
- 3. PERCENT OF APPLICABLE LIMIT % *
- ________________________________________________________________________________ l
-C. PARTICULATES
- 1. PARTICULATES(HALF-LIVES >8 DAYS) CURIES 4.70E-07 5.40E-06 7.00E+01 '
,2. AVERAGE RELEASE RATE FOR PERIOD uCi/Sec 6.05E-08 6.87E-07
- 3. PERCENT OF APPLICABLE LIMIT % * *
- 4. GROSS ALPHA RADIOACTIVITY CURIES 1.39E-07 6.62E-08
'D . TRITIUM l
l
- 1. TOTAL RELEASE CURIES 1.48E+01 2.81E+01 5.30E+01
! 2. AVERAGE RELEASE RATE FOR PERIOD uCi/Sec 1.90E+00 3.57E+00 3.' PERCENT OF APPLICABLE LIMIT % *
- o Applicable limits are expressed in terms of dose. See Tables 2-4A, 2-4B, 2-5A, and 2-5B of this report.
l 55 l
1 i
I l
l TABLE 2-1C Joseph M. Farley Nuclear Plant ANI.'UAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1997 daseous Effluents - Summation of All Releases Unit: Site Starting : 1-Jul-1997 Ending : 31-Dec-1997 TYPE OF EFFLUENT UNITS QUARTER 3 QUARTER 4 EST. TOT l ERROR %
A. FISSION & ACTIVATION PRODUCTS
- 1. TOTAL RELEASE CURIES 2.64E+01 3.04E+01 9.40E+01 l
________________________________________________________________________________ l
- 2. AVERAGE RELEASE RATE FOR PERIOD uCi/Sec 3.32E+00 3.82E+00
_________________.______________________________________________________________ l
- 3. PERCENT OF APPLICABLE LIMIT % *
- B. RADIOIODINES
____________m._________________________ ________________________________________ 1
- 1. TOTAL IODINE-131 CURIES 1.81E-06 1.94E-06 8.80E+01' i
- 2. AVERAGE RELEASE RATE FOR PERIOD uCi/Sec 2.28E-07 2.45E-07
- 3. PERCENT OF APPLICABLE LIMIT % *
- l C. PARTICULATES
- 1. PARTICULATES(HALF-LIVES >8 DAYS) CURIES 9.04E-08 4.19E-07 7.00E+01
- 2. AVERAGE RELEASE RATE FOR PERIOD uCi/Sec 1.14E-08 5.27E-08
- 3. PERCENT OF APPLICABLE LIMIT % * *
- 4. GROSS ALPHA RADIOACTIVITY CURIES 5.58E-07 8.55E-07 D. TRITIUM
- 1. TOTAL RELEASE CURIES 2.22E+01 2.58E+01 5.30E+01 !
i
- 2. AVERAGE RELEASE RATE FOR PERIOD uCi/Sec 2.79E+00 3.25E+00
- 3. PERCENT OF APPLICABLE LIMIT % * *
__-____---___________________________________________. ________ j i
1 o l l Applicable limits are expressed in terms of dose. See Tables i l 2-4A, 2-4B, 2-5A, and 2-5B of this report.
56 l
l l
l
E l
3.5.2 Gaseous Effluents - Mixed Mode Releases t The summaries of'all gaseous effluent mixed mode
! releases (includes listing by nuclide) are contained in the following tables :
Unit 1 1997 Mixed Mode Summary : Table 2-2A Unit 2 1997 Mixed Mode Summary : Table 2-2B Site 1997 Mixed Mode Summary : Table 2-2C l
2 57 I
i
TABLE 2-2A*
Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1997 Gaseous Effluents-Mixed-Mode Level Releases Unit: 1 Starting : 1-Jan-1997 Ending : 30-Jun-1997 l CONTINUOUS MODE l BATCH MODE l NUCLIDES RELEASED l UNIT l QUARTER 1 l QUARTER 2 l QUARTER 1 l QUARTER 2 l FISSION GASES AR-41 CURIES 8.35E+00 2.72E+00 0.00E+00 0.00E+00 XE-135 CURIES 2.52E+00 3.81E-02 8.63E-04 0.00E+00 XE-133 CURIES 6.41E+00 0.00E+00 2.98E-03 1.45E-03 XE-131M CURIES 1.27E+01 3.33E+01 0.00E+00 0.00E+00
. KR-85 CURIES 0.00E+00 0.00E+00 7.89E-02 0.00E+00 TOTAL FOR PERIOD CURIES l l 3.00E+01 l 3.61E+01 l 8.27E-02 l 1.45E-03 l
IODINES I-133 CURIES 4.36E-06 0.00E+00 0.00E+00 0.00E+00 I-131 CURIES 1.40E-05 1.43E-05 0.00E+00 0.00E+00 TOTAL FOR PERIOD l CURIES l 1.84E-05 l 1.43E-05 l 0.00E+00 l 0.00E+00 l PARTICULATES SR-89 CURIES 2.50E-15 0.00E+00 0.00E+00 0.00E+00 CO-58 CURIES 4.37E-07 4.94E-06 0.00E+00 0.00E+00 SN-113 CURIES 0.00E+00- 0.00E+00 1.37E-09 1.61E-07 CO-60 CURIES 0.00E+00 1.24E-07 0.00E+00 0.00E+00 SR-90 CURIES 5.50E-09 0.00E+00 0.00E+00 0.00E+00 CS-137 CURIES 0.00E+00 7.87E-08 0.00E+00 0.00E+00 TOTAL FOR PERIOD l CURIES l 4.42E-07 l 5.14E-06 l 1.37E-09 l 1.61E-07 l H-3 CURIES 3.65E+00 3.20E+00 0.00E+00 0.00E+00 G-ALPHA CURIES 7.70E-08 1.64E-08 0.00E+00 0.00E+00 )
- Zeroes in this table indicate that no radioactivity was present at detectable levels. See Table 2-7 for typical minimum detectable concentrations. I 58
1 i
l TABLE 2-2AO Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT -'1997 Gaseous Effluents-Mixed-Mode' Level Releases f Unit: 1 Starting : 1-Jul-1997 Ending : 31-Dec-1997 l CONTINUOUS MODE l BATCH MODE EOCLIDES RELEASED l UNIT l QUARTER 3 l QUARTER 4 l QUARTER 3 l QUARTER 4
________________________________________________,_______________________________l .
FISSION GASES:
AR CURIES 1.50E+01 1.53E+01 0.00E+00 0.00E+00 KR-85M CURIES 0.00E+00 4.41E-02 0.00E+00 0.00E+00 XE-135- CURIES 1.44E+00 5.85E-01 0.00E+00 0.00E+00
- XE-133 .
CURIES -3.71E-02 6.79E-02 0.00E+00 0.00E+00 TOTAL FOR PERIOD CURIES l l 1.64E+01 l 1.60E+01 l 0.00E+00 l 0.00E+00 l l
IODINES i
I-133 CURIES 6.90E-06 0.00E+00 0.00E+00 0.00E+00 I-131 CURIES 6.62E-07 0.00E+00 0.00E+00 0.00E+00 TOTAL FOR PERIOD CURIES l l 7.56E-06 l 0.00E+00 l 0.00E+00 l 0.00E+00 l
i PARTICULATES SR-89 CURIES 0.00E+00 -0.00E+00 0.00E+00 0.00E+00 -;
SN-113 CURIES 0.00E+00 0.00E+00 8.54E-08 0.00E+00 TIOTAL FOR PERIOD l CURIES l 0.00E+00'l 0.00E+00 l 8.54E-08 l 0.00E+00'l H-3 CURIES 2.95E+00 4.62E+00 0.00E+00 0.00E+00 G-ALPHA CURIES 5.41E-07 2.87E-07 0.00E+00 0.00E+00 o Zeroes in this table indicate that no radioactivity was present at-detectable levels. See Table 2-7 for typical minimum detectable concentrations.
59
l TABLE 2-2B0 I Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1997-Gaseous Effluents-Mixed-Mode Level Releases )
Unit: 2 Starting : 1-Jan-1997 Ending : 30-Jun-1997 l 1
1 l CONTINUOUS MODE BATCH MODE l l
_________________________________________________________________________l -
NUCLIDES RELEASED l UNIT. l QUARTER 1 l QUARTER 2 l QUARTER 1 l QUARTER 2 l
' FISSION GASES k l
_______,.________. ______________________________________________________________ j AR-41 CURIES 7.89E+00 1.00E+01 0.00E+00- 0.00E+00 J XE-135 CURIES 5.79E-02 0.00E+00 0.00E+00 0.00E+00 TOTAL FOR PERIOD _ CURIES l l 7.95E+00 l 1.00E+01 l 0.00E+00 l 0.00E+00 l
_______________________________________...._____________________________________ l IODINES I-133 CURIES 1.14E-05 1.84E-05 0.00E+00 0.00E+00 I-131 CURIES 6.95E-07 9.90E-07 0.00E+00 0.00E+00 TOTAL FOR PERIOD CURIES l l 1.21E-05 l 1.93E-05 l 0.00E+00 l 0.00Es00 l-PARTICULATES SR-89 l CURIES l 2.66E-08 l 9.63E-08 l 0.00E+00 l 0.00E+00 l TbTELFbkPbkkbb f CbkkbS fb$bbb5b8 f 9$bbb$bb f bIbbb bb f b)bbk bb f-H-3 CURIES 1.11E+01 2.49E+01 0.00E+00 0.00E+00 G-ALPHA CURIES 6.22E-08 4.98E-08 0.00E+00 0.00E+00 o Zeroes _in this table indicate that no radioactivity was present at detectable levels. See Table 2-7 for typical minimum detectable concentrations.
l 60 i I
k
r f
l
'TRBLE 2-280 Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1997 L Gaseous Effluents-Mixed-Mode Level Releases Unit: 2 Starting : 1-Jul-1997 Ending : L31-Dec-1997 l CONTINUOUS MODE l BATCH MODE l l NUCLIDES RELEASED l UNIT l QUARTER 3 l QUARTER 4 l QUARTER 3 l QUARTER 4 l FISSION. GASES-
._____________________________________________________________________________.a AR-41 CURIES 9.93E+00~ 1.42E+01 0.00E+00 0.00E+00 XE-135 -CURIES 0.00E+00 4.59E-02 0.00E+00 0.00E+00 XE-133 CURIES 0.00E+00 1.61E-01 0.00E+00 0.00E+00 ,
__________.____________________._______________.________________________.___.__.- l TOTAL'FOR PERIOD l CURIES l 9.93E+00 l 1.44E+01 l 0.00E+00 l 0.00E+00 l i
IODINES i I-133 CURIES 2.04E-05 2.83E-05 0.00E+00 0.00E+00 I-131' CURIES 1.15E-06 1.94E-06 0.00E+00 0.00E+00 TOTAL FOR PERIOD l CURIES l 2.16E-05 l 3.03E-05 l 0.00E+00 l 0.00E+00'l PARTICULATES
-SR-89 l CURIES l 4.98E-09 l l 0.00E+00 l 0.00E+00 l
....____________________________________________1.42E-09 ________________________________q TOTAL FOR PERIOD l CURIES: l 4.98E-09 l'1.42E-09 l 0.00E+00'l 0.00E+00 l
.H-3 CURIES 1.93E+01 2.12E+01 0.00E+00 0.00E+00 G-ALPHA CURIES 1.68E-08 5.69E-07 0.00E+00 0.00E+00 0- Zeroes in this table indicate that no radioactivity was present at detectable levels. See Table 2-7 for typical minimum detectable concentrations.
r i
61
TABLE 2-2C0 l Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1997 Gaseous Effluents-Mixed-Mode Level Releases !
Unit: Site i
Starting : 1-Jan-1997 Ending : 30-Jun-1997 l l CONTINUOUS MODE l BATCH-MODE l l
..__.______ ___________ __________~________________________ ....._________._____ '
.NUCLIDES RELEASED l UNIT l QUARTER 1 l QUARTER 2 l QUARTJ .1 l QUARTER 2 l
. .________.___..__________________________ _____________-______.___________--.___ \
FISSION GASES AR-41 CURIES 1.62E+01 1.28E+01 0.00E+00 0.00E+00 1
XE-135 CURIES 2.58E+00 3.81E ^' 8.63E-04 0.00E+00 XE-133 CURIES 6.41E+00 0.00E+00 2.98E-03 1.45E-03 XE-131M CURIES 1.27E+01 3.33E+01 0.00E+00 0.00E+00 KR-85 CURIES 0.00E+00 0.00E+00 7.89E-02 0.00E+00 TOTAL.FOR PERIOD CURIES l l 3.80E+01 l 4.61E+01 l 8.27E-02 l 1.45E-03 l'
- I-133 CURIES 1.58E-05 1.84E-05 0.00E+00 0.00E+00 I-131 CURIES 1.47E-05 1.53E-05 0.00E+00 0.00E+00 TOTAL FOR PERIOD l CURIES l 3.05E-05 l 3.36E -05 l 0.00E+00 l.0.00E+00 l PARTICULATES SR-89 CURIES 2.66E-08 9.63E-08 0.00E+00 410 0n+ 00 :
- CO-58 CURIES 4.37E-07 -4.94E-06 0.00E+00 SN-113 CURIES 0.00 h -A80ETUI n DOET10 1.37E-09 1.61E-07
.C0-60 .
~ ~~~~~CURTW 0.00E+00 1.24E-07 0.00E+00 0.00E+00 l SR-90 CURIES 5.50E-09 0.00E+00 0.00E+00 0.00E+00 1
-CS-137 CURIES 0.00E+00 7.87E-08 0.00E+00 0.00E+00 I 1
TOTAL FOR PERIOD l CURIES l 4.69E-07 l 5.24E-06 l 1.37E-09 l 1.61E-07 l ;
._ ____...__ _______________________.__________________.______________________.. 1
- H-3 CURIES 1.48E+01 2.81E+01 0.00E+00 0.00E+00 I
G-ALPHA CURIES 3.39E-07 6.62E-08 0.00E+00 0.00E+00 o Zeroes in this table indicate that no radioactivity was present at detectable levels. See Table 2-7 for typical minimum detectable concentrations.
62
TABLE 2-2C0 Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1997 Gaseous Effluents-Mixed-Mode Level Releases Unit: Site Starting : 1.Jul-1997 Ending : 31-Dec-1997 l CONTINUOUS MODE l BATCH MODE l NUCLIDES RELEASED l UNIT '
l QUARTER 3 l QUARTER 4 l QUARTER 3 l QUARTER 4 FISSION GASES AR-41 CURIES 2.49E+01 2.95E+01 0.00E+00 0.00E+00 KR-85M CURIES 0.00E+00 4.41E-02 0.00E+00 0.00E+00 XE-135 CURIES 1.44E+00 6.31E-01 0.000+00 0.00E+00 XE-133 CURIES 3.71E-02 2.29E-01 0.00E+00 0.00E+00 TOTAL FOR PERIOD CURIES l l 2.64E+01 l 3.04E+01 l 0.00E+00 l 0.00E+00 l
___________________________________________________________________-____________ 1 IODINES
__________________________________________-______-__________________________-___ 1 I-133 CURIES 2.73E-05 2.83E-05 0.00E+00 0.00E+00 l I-131 CURIES 1.81E-06 1.94E-06 0.00E+00 0.00E+00 TOTAL FOR PERIOD l CURIES l 2.91E-05 l 3.03E-05 l 0.00E+00 l 0.00E+00 l
>-PAATICULATES SR-89 CURIES -4.98E-09 1.42E-09 0.00E+00 0.00E+00 SN-113 CURIES 0.00E+00 0.00E+00 8.54E-08 0.00E+00 TOTAL FOR PERIOD l CURIES l 4.98E-09 l 1.42E-09 j 8.54E-08 l 0.00E+00 l H-3 CURIES 2.22E+01 2.58E+01 0.00E+00 0.00E+00 G-ALPHA CURIES 5.58E-07 8.55E-07 0.00E+00 0.00E+00 o Zeroes in this table indicate that no radioactivity was present at detectable levels. See Table 2-7 for typical minimum detectable concentrations.
63
7 3.5.3 Gaseous Effluents - Ground Mode Releases The summaries of all gaseous effluent ground mode releases (includes listing by nuclide) are contained in the following tables :
Unit 1 1997 Ground Mode Summary : Table 2-3A Unit 2 1997 Ground Mode Summary : Table 2-3B Site 1997 Ground Mode Summary : Table 2-3C 64
I.
3 TABLE 2-3A*
Joseph M. Farley Nuclear Plant ANNUAL RACIOACTIVE EFFLUENT RELEASE REPORT - 1997 Gaseous Effluents-Ground Level Releases Unit: 1 !
Starting : 1-Jan-1997 Ending : 30-Jun-1997 i l CONTINUOUS' MODE l BATCH MODE l
__._____________ ..________.________ _____________________________________..____- 1 NUCLIDES RELEASED. l UNIT. l QUARTER 1 l QUARTER 2 l QUARTER 1 l QUARTER 2.l .
l FISSION GASES
-XE-135 CURIES 0.00E+00 0.00E+00 0.00E+00 1.98E-08 l
l
~XE-133- CURIES 0.00E+00 0.00E+00 8.22E-04 0.00E+00 l TOTAL.FOR PERIOD l CURIES l 0.00E+00 l 0.00E+00 l 8.22E-04 1.98E-08 i ..
l
________.______________.__________.. _______________________________.l..______
__..______.____.____.._______.________________._____........____________________ \
l I-132 CURIES 0.00E+00 0.00E+00 3.48E-04 0.00E+00 ,
I-133 CURIES 0.00E+00 0.00E+00 4.41E-04 6.24E-08 I I-131' CURIES 0.00E+00 1.52E-08 9.80E-05 0.00E+00 i TOTAL'FOR PERIOD -l CURIES l 0.00E+00 l 1.52E-08 l 8.87E-04 l 6.24E-08 l 1
l H-3 l CURIES -l 1.64E-03 l 2.22E-03 l 3.14E-03 l 2.97E-08 l Zeroes in this table indicate that no radioactivity was present 1 at detectable levels. See Table 2-7 for typical minimum detectable concentrations.
l i
I 65 l
i TABLE 2-3A0 l Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1997 Gaseous Effluents-Ground Level Releases Unit: 1 Starting : 1-Jul-1997 Ending : 31-Dec-1997 l CONTINUOUS MODE l BATCH MODE NUCLIDES RELEASED l UNIT l QUARTER 3 l QUARTER 4 l QUARTER 3 QUARTER 4
_____________________________________________________________________l l ___________
FISSION GASES XE-135 CURIES l l 0.00E+00 l 0.00E+00 l 2.95E-07 l 0.00E+00 TOTAL FOR PERIOD CURIES l l 0.00E+00 l 0.00E+00 l 2.95E-07 l 0.00E+00 IODINES I-132 CURIES 0.00E+00 0.00E+00 0.00E+00 2.53E-06 X-133 CURIES 0.00E+00 0.00E+00 2.09E-08 2.30E-06 TOTAL FOR PERIOD CURIES l l 0.00E+00 l 0.00E+00 l 2.09E-08 l 4.83E-06 l l
PARTICULATES TE-127M CURIES l l 0.00E+00 l 0.00E+00 l 0.00E+00 l 4.18E-07 l TOTAL FOR PERIOD CURIES l l 0.00E+00 l 0.00E+00 l 0.00E+00 l 4.18E-07 l H-3 CURIES l l 1.00E-03 l 6.99E-04 l 9.89E-05 l 5.00E-04 l o Zeroes in this table indicate that no radioactivity was present at detectable levels. See Table 2-7 for typical minimum detectable concentrations.
1 I
66
TABLE 2-3B*
Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1997 Gaseous Effluents-Ground Level Releases Unit: 2 Starting': 1-Jan-1997 Ending : 30-Jun-1997 l CONTINUOUS MODE l BATCH MODE 'l NUCLIDES RELEASED l UNIT l QUARTER 1 l QUARTER 2 l QUARTER 1 QUARTER 2 l
_________________________________ .__________________________________l __________.
FISSION GASES
_____ ..________________________________ .______.._________________________..___ l TOTAL'FOR PERIOD CURIES l l 0.00E+00 l 0.00E+00 l 0.00E+00 l 0.00E+00
______________________________________________.._____________l IODINES.
TOTAL FOR PERIOD CURIES l l 0.00E+00 l 0.00E+00 l 0.00E+00 l 0.00E+00
..___________________________________________________..__________________.._____l PARTICULATES TOTAL FOR PERIOD CURIES l l 0.00E+00'l 0.00E+00 l 0.00E+00 l 0.00E+00
______________________._______..___.___________________________________________.l
'H-3 l- CURIES l 4.71E-04' l 5.02E-04 l 0.00E+00 l~0.00E+00
_______________....____________________________....____________________________.l
- ~
Zeroes in this table indicate that no radioactivity was present at detectable levels. See Table 2-7 for typical minimum detectable concentrations.
67
TABLE 2-3B0
-Joseph.M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPOR'l - 1997 Gaseous. Effluents _ Ground Level Releases.
Unit: 2 Starting : 1-Jul-1997 Ending : 31-Dec-1997 l CONTINUOUS MODE l BATCH MODE'
__--__-._---_-___.--_____--___.--__---___-_.-l.'
. NUCLIDES RELEASED l . UNIT .l QUARTER 3 l QUARTER 4 l QUARTER 3 l QUARTER'4-l FISSION GASES-1 TOTAL-FOR PERIOD CURIES l l 0.00E+00 l 0.00E+00 l 0.00E+00 l 0.00E+00.l
' IODINES TOTAL'FOR PERIOD l CURIES l 0.00E+00 l 0.00E+00 l 0.00E+00 l 0.00E+00 l PARTICULATES TOTAL FOR PERIOD- l. CURIES l 0.00E+00 l 0.00E+00 l 0.00E+00 l 0.00E+00 j' H-3 l CURIES l 3.45E-04 l 1.15E-03 l 0.00E+00 l 0.00E+00 l o Zeroes in this table indicate that no radioactivity was present at detectable levels. See Table 2-7 for typical minimum detectable concentrations.
68
TABLE 2-3Co Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1997 Gaseous Effluents-Ground Level Releases Unit: Site Starting : 1-Jan-1997 Ending : 30-Jun-1997 l CONTINUOUS MODE l BATCH MODE NUCLIDES RELEASED j UNIT l QUARTER 1 l QUARTER 2 l QUARTER 1 l QUARTER 2 l FISSION GASES XE-135 CURIES 0.00E+00 0.00E+00 0.00E+00 1.98E-08 XE-133 CURIES 0.00E+00 0.00E+00 8.22E-04 0.00E+00 TOTAL FOR PERIOD CURIES l
l 0.00E+00 l 0.00E+00 l 8.22E-04 l 1.98E-08 l IODINES I-132 CURIES 0.00E+00 0.00E+00 3.48E-04 0.00E+00 I-133 CURIES 0.00E+00 0.00E+00 4.41E-04 6.24E-08 I-131 CURIES 0.00E+00 1.52E-08 9.80E-05 0.00E+00 TOTAL FOR PERIOD CURIES l
l 0.00E+00 l 1.52E-08 l 8.87E-04 l 6.24E-08 l PARTICULATES N TOTAL FOR PERIOD CURIES l
l 0.00E+00 l 0.00E+00 l 0.00E+00 l 0.00E+00 l H-3 CURIES l
l 2.11E-03 l 2.72E-03 l 3.14E-03 l 2.97E-08 l o
Zeroes in this table indicate that no radioactivity was present at detectable levels. See Table 2-7 for typical minimum detectable concentrations.
i 69
TABLE 2-3C0 Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1997 Gaseous Effluents-Ground Level Releases Unit: Site Starting : 1-Jul-1997 Ending : 31-Dec-1997 l CONTINUOUS MODE l BATCH MODE l NUCLIDES RELEASED' l UNIT l QUARTER 3 l QUARTER 4-l QUARTER 3-_l QUARTER 4 l
- FISSION GASES XE-135 l CURIES l 0.00E+00 l 0.00E+00 l 2.95E-07 l 0.00E+00 l TOTAL FOR PERIOD l CURIES l 0.00E+00 l 0.00E+00 l 2.95E-07 l 0.00E+00 l IODINES I-133 CURIES 0.00E+00 0.00E+00 2.09E-08 2.30E-06 TOTAL FOR PERIOD l CURIES l 0.00E+00 l 0.00E+00 l 2.09E-08 l 4.83E-06 l PARTICULATES' TE-127M' l CURIES l 0.00E+00 l 0.00E+00 l 0.00E+00 l 4.18E-07 l
..._______________________________________....._______________....._____________ i TOTAL FOR PERIOD l CURIES l 0.00E+00 l 0.00E+00_l 0.00E+00 l 4.18E-07 l H-3 l CURIES l'1.34E-03 l 1.85E-03 l 9.89E-05 l 5.00E-04 l 0 Zeroes in this table indicate that no radioactivity was present at detectable levels. See Table 2-7 for typical minimum detectable concentrations.
70
i
! 3.6 Radiological Impact The air doses and organ doses due to gaseous effluents for '
Units 1 and 2 are provided in the following tables in order to show conformance with the limits of ODCM 3.1.3 and ODCM 3.1.4 :
Unit 1 1997 Air Doses : Table 2-4A Unit 2 1997 Air Doses : Table 2-4B Unit 1 1997 Organ Doses : Table 2-5A Unit 2 1997 Organ Doses : Table 2-5B i
l l
! 71 l
TABLE 2-4A Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1997 AIR DOSES DUE TO GASEOUS RELEASES Unit: 1 Starting 01-Jan-1997 Ending: 30-Jun-1997 Cumulative Doses per Quarter Type ODCM Units Quarter % of Quarter % of of Limit 1 ODCM 2 ODCM Radi- Limit Limit ation Gamma 5.0 mrad 2.97E-03 5.94E-02 1.05E-03 2.09E-02 Beta 10.0 mrad 1.87E-03 1.87E-02 1.58E-03 1.58E-02
\
l Cumulative Doses per Year Type ODCM Units Year to % of of Limit Ending ODCM Radi- Date Limit ation Gamma 10.0 mrad 4.02E-03 4.02E-02 Beta 20.0 mrad 3.45E-03 1.72E-02 72
l
~l 3
TABLE 2-4A. l Joseph M. Farley Nuclear Plant '
ANNUAL' RADIOACTIVE. EFFLUENT RELEASE. REPORT - 1997 AIR DOSES DUE TO GASEOUS RELEASES Unit: 1 Starting: 01-Jul-1997 .Ending: 31-Dec-1997 I
' Cumulative _ Doses per Quarter Type ODCM Units Quarter % of Quarter % of of Limit '3 ODCM 4 ODCM Radi- Limit Limit j ation
, Gamma 5.0 mrad '4.86E-03 9.72E-02 4.91E-03 9.83E-02 Beta 10.0 mrad 1.80E-03 1.80E-02 1.77E-03 '1.77E-02 Cumulative Doses per Year Type' ODCM Units Year to % of of Limit Ending ODCM Radi- Date Limit ation
. Gamma 10.0 mrad 1.38E-02 1.38E-01 Beta 20.0 mrad 7.02E-03 3.51E-02 73
l-l l
TADLE 2-4B Joseph M. Farley Nuclear Plant i ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1997 (
AIR DOSES DUE TO GASEOUS RELEASES I Unit: 2 )
Starting: 01-Jan-1997 Ending: 30-Jun-1997 l
Cumulative Doses per Quarter Type ODCM Units Quarter % of Quarter % of of Limit 1 ODCM 2 ODCM Radi- Limit Limit ation Gamma 5.0 mrad 2.52E-03 5.03E-02 3.20E-03 6.39E-02 l Beta 10.0 mrad 8.91E-04 8.91E-03 1.13E-03 1.13E-02
______________________ ______________ __..________..__________________..__ l l
l Cumulative Doses per Year l
-_____________ ___________._____________________ _________________________ 1 Type ODCM Units Year to % of of Limit Ending ODCM Radi- Date Limit ation Gamma 10.0 mrad 5.71E-03 5.71E-02 Beta 20.0 mrad 2.02E-03 1.01E-02 74
TABLE 2-4B Joseph M. Farley.Wuclear' Plant-ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1997 1
-AIR DOSES DUE TO GASEOUS RELEASES l Unit: 2 Starting: 01-Jul-1997 Ending: 31-Dec-1997 l 1 i
Cumulative Doses per Quarter l Type' ODCM Units Quarter % of. Quarter % of I of Limit 3 ODCM 4 ODCM Radi . Limit Limit ation Gamma 5.0 mrad' 3.16E-03 6.33E-02 4.52E-03 9.03E-02 i
l Beta 10.0 mrad 1.12E-03 1.12E-02 1.60E-03 1.60E-02 Cumulative. Doses per Year
__.n.
l Type ODCM Units Year to % of I of Limit Ending ODCM Radi- Date Limit ation Gamma- 10.0 mrad 1.34E-02 1.34E-01 Beta 20.0 mrad 4.73E-03 .2.37E-02 75 l
l
TABLE 2-5A -
Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1997 i: DOSES TO A MEMBER OF THE PUBLIC DUE TO'RADIOIODINES, TRITIUM, l AND PARTICULATES IN GASEOUS RELEASES Unit: 1 l Starting: 01-Jan-1997 Ending: 30-Jun-1997 6 .
I J l
l Cumulative Doles per Quarter-
, Organ ODCM Unit Quarter % of Quarter % of-Limit 1 ODCM 2 ODCM Limit Limit-l Bone 7.5 mrem 2.32E-05 3.10E-04 3.30E-06 4.40E-05 Liver 7.5 mrem 5.27E-04 7.02E-03' 4.44E-04 5.92E-03 TBody 7.5 mrem 5.18E-04 6.91E-03 4.44E-04 5.91E-03 Thyroid 7.5 mrem 6.32E-03 8.42E-02 7.02E-04 9.35E-03 Kidney 7.5 mrem 5.39E-04 7.19E-03 4.44E-04 5 ^. 92E-03 l Lung 7.5 mrem 5.07E-04 6.77E-03 4.43E-04 5.90E-03 GILLI 7.5 mrem 5.10E-04 6.80E-03 4.43E-04 5.91E-03 Cumulative Doses per Year l __________________________________________________________________________
Organ ODCM Units Year to % of Limit Ending ODCM Date Limit
>Done 15.0 mrem 2.65E-05 1.77E-04 -i i Liver 15.0 mrem 9.71E-04 6.47E-03 l TBody 15.0 mrem 9.62E-04 6.41E-03 !
Thyroid 15.0 mrem 7.02E-03 4.68E-02 l Kidney 15.0 mrem 9.83E-04 6.55E-03
, . Lung 15.0 mrem 9.50E-04 6.33E-03 l GILLI 15.0- mrem 9.54E-04 6.36E-03 i
i 76 t
TABLE 2-5A-Joseph M. Farley Nuclear Plant-ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1997
, DOSES TO A MEMBER OF THE PUBLIC DUE TO RADIOIODINES, TRITIUM, AND PARTICULATES IN GASEOUS RELEASES Unit: 1 Starting: 01-Jul-1997 Ending: 31-Dec-1997 Cumulative Doses per Quarter Organ- ODCM Unit Quarter % of -Quarter- % of Limit 3 ODCM. 4 ODCM Limit Limit Bone 7.5 mrem 5.66E-08 7.55E-07 1.14E-06 1.52E-05 Liver 7.5 mrem 4.04E-04 5.39E-03 6.33E-04 8.44E-03 TBody 7.5 rrem 4.04E-04 5.39E-03 6.33E-04~ 8.43E-03
. Thyroid 7.5 mrem 4.19E-04 5.58E-03 6.37E-04 8.49E-03 Kidney 7.5 mrem 4.04E-04 5.39E-03 6.36E-04 8.47E-03 Lung 7.5 mrem '4.04E-04 5.39E-03 6.33E-04 8.43E-03
-GILLI 7.5 mrem 4.04E-04 5.39E-03 6.33E-04 8.44E-03 Cumulative Doses per. Year
~
..o___________________..__________________________ .______________________
Organ ODCM Units Year to % of Limit Ending ODCM Date Limit Dons 15.0 mrem 2.77E-05 1;85E-04 Liver 15.0 mrem 2.01E-03 1.34E-02 TBody -15.0 mrem 2.00E 1~33E-02 Thyroid 15.0 mrem 8.07E-03 5.38E-02 Kidney 15.0 mrem 2.02E-03 1.35E-02 l
.ung 15.0 mrem- 1.99E-03 1.32E-02 ;
"JILLI 15.0 mrem 1.99E-03 1.33E-02 77
I l
t TABLE 2-5B Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1997 DOSES TO A MEMBER OF THE PUBLIC DUE TO RADIOIODINES, TRITIUM, AND PARTICULATES IN GASEOUS RELEASES i Unit: 2 i Starting: 01-Jan-1997 Ending: 30-Jun-1997 I l
?
l l Cumulative Doses per Quarter i l Organ ODCM Unit Quarter % of Quarter % of Limit 1 ODCM 2 ODCM Limit Limit i Bone 7.5 mrem 4.04E-07 5.38E-06 1.27E-06 1.70E-05 l
Liver 7.5 mrem 1.52E-03 2.0'E-02 3.40E-03 4.53E-02 TBody 7.5 mrem 1.52E-03 2.03E-02 3.40E-03 4.53E-02
)
Thyroid 7.5 mrem 1.54E-03 2.05E-02 3.43E-03 4.57E-02 Kidney 7.5 mrem 1.52E-03 2.03E-02 3.40E-03 4.53E-02 Lung 7.5 mrem 1.52E-03 2.03E-02 3.40E-03 4.53E-02 :
GILLI 7.5 mrem 1.52E-03 2.03E-02 3.40E-03 4.53E-02 i
Cumulative Doses per Year Organ ODCM Units Year to % of Limit Ending ODCM Date Limit Bone 15.0 mrem 1.68E-06 1.12E-05 Liver 15.0 mrem 4.92E-03 3.28E-02 TBody 15.0 mrem 4.92E-03 3.28E-02 Thyroid 15.0 mrem 4.96E-03 3.31E-02 Kidney 15.0 mrem 4.92E-03 3.28E-02 Lung 15.0 mrem 4.92E-03 3.28E-02 GILLI 15.0 mrem 4.92E-03 3.28E-02 78
l' TABLE 2-5D Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1997 DOSES TO A MEMBER OF THE PUBLIC DUE TO RADIOIODINES,' TRITIUM, AND PARTICULATES IN GASEOUS RELEASES Unit: 2 Starting: 01-Jul-1997 Ending: 31-Dec-1997 Cumulative Doses per Quarter
. Organ ODCM Unit Quarter % of Quarter % of Limit 1 ODCM 2 ODCM-Limit Limit l Bone 7.5 mrem 1.98E-07 2.64E-06 2.14E 2.85E-06 l Liver 7.5 mrem 2.63E-03 3.51E-02 2.90E-03 3.86E-02 i TBody 7.5 mrem 2.63E-03 3.51E-02 2.90E-03 3.86E-02 l Thyroid 7.5 mrem 2.66E-03 3.54E-02 2.94E-03 3.92E-02 Kidney 7.5 mrem 2.63E-03 3.51E-02 2.90E-03 3.86E-02 Lung 7.5 mrem 2.63E-03 3.51E-02 2.90E-03 3.86E-02 L 'GILLI 7.5 mrem 2.63E-03 3.51E-02 2.90E-03 3.86E-02 Cumulative Doses per Year l Organ ODCM Units Year to % of ,
- i. Limit Ending ODCM 1
( Date Limit l
l ______ __.__________.__ -_____________________.____________....___________
l Bone 15.0 mrem 2.09E-06 1.39E-05 l Liver 15.0 mrem 1.04E-02 6.97E-02 TBody 15.0 mrem 1.04E-02 6.97E-02 Thyroid 15.0 mrem 1.06E-02 7.04E-02 l Kidney 15.0 mrem 1.04E-02 6.97E-02 L Lung 15.0 mrem 1.04E-02 6.97E-02 GILLI 15.0 mrem 1.04E-02 6.97E-02 l ____.___________________________________..____________________________-___
l l.
l-79
TABLE 2-7 Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1997 TYPICAL GASEOUS MDC'S ACHIEVED ON COUNTING SYSTEM
)
i Nuclide MDC(uCi/ML)
MN-54 3.21E-15 CO-58 1.53E-14 FE-59 7.~96E-15 CO-60 1.95E-14 ZN-65 2.34E-14 MO 1.81E-13 CS-134 1.41E-14 I CS-137 7.83E-15 CE-141 6.96E-15 CE-144 3.47E-14 !
4 KR-87 8.18E-07 KR-88 3.94E-08 !
XE-133 4.30E XE-133M 4.82E-08 XE-135 1.78E-08 XE-138 1.99E-07 I-131- 9.67E-15 I-133 1.80E-13 80
l -4.O SOLID WASTE This section contains information regarding the types and quantities of solid radioactive waste shipped offsite during l 1997 as required in ODCM 7.2.2.4. This information is presented t
in Table 3.
The error involved in determining the contents of solid radwaste shipments is estimated to be less than + or - 15%. I 1 l l
' I l
l l
l l
81 l
l
! TABLE 3 l Joseph M. Farley Wuclear Plant L
ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1997 i
SOLID WASTE AND IRRADIATED FUEL SHIPMENTS Starting: 01-Jan-1997 Ending: 30-Jun-1997' l
i A. SOLID WASTE SHIPPED OFFSITE FOR BURIAL OR DISPOSAL !
'(not irradiated fuel) -
- 1. Type of Waste. UNITS 6-Months 3
a.' Spent resins, Filter sludges, m None evaporator bottoms, etc. Ci* None 3
- b. Dry compressible waste, contaminated m 1.211E+01 i equipment, etc. Ci* 3.240E+00 3
- c. Irradiated components, control m None rods, etc. Ci* None 3
- d. Other (describe) m None Ci* None
- 2. Estimate of major nuclide composition,
- b. FE-55 33.5%
CO 28.1%
CR-51 9.5%
NI-63 8.9%
CO-60 8.1%
MN-54' 2.9% !
u H-3 2.6%
CS-137 2.4%
NB-95 1.1%
- 3. Solid Waste Disposition Number of Shipments Mode of Transportation Destination 26 Highway Chem-Nuclear Systems, Inc.
l Barnwell, South j Carolina.
- Measured and/or estimated by correlations in accordance with 10CFR61.55.
82
r TABLE 3 Joseph M. Farley__ Nuclear Plant -
ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1997 SOLID WASTE AND IRRADIATED FUEL SHIPMENTS Starting: 01-Jan-1997 Ending: 30-Jun-1997-(continued)
- 4. Type of Container (1b)'
' Strong Tight Containers.
l
- 5. Solidification Agent (1b) l None B. IRRADIATED FUEL SHIPMENTS (Disposition) l
. Number of Shipments Mode of Transportation Destination 1
None N/A- 'N/A j I
1 1
i t;
83
TABLE 3
' Joseph M. Farley Nuclear' Plant l ANNUAL RADIOACTIVE EFFLU"J"r RELEASE REPORT - 1997 l SOLID WASTE AND IRRAL1ATED FUEL SHIPMENTS !
Starting: 01-Jul-1997 'Ending: 31-Dec-1997 1
A. SOLID WASTE SHIPPED OFFSITE FOR BURIAL OR DISPOSAL !
(not irradiated. fuel) l
- 1. Type of Waste. : UNITS 6-Months 3
- a. Spent resins, Filter sludges, m None evaporator bottoms, etc. Ci* None 3 l
- b. Dry compressible waste, contaminated m 6.240E+00 equipment, etc. Ci* 6.200E-01' 3 l
- c. Irradiated components, control m None rods, etc. Ci* None 3 1
- d. Other (describe) m None 1 Ci* None 1
- 2. Estimate of major nuclide composition,
- b. FE-55 39.1%
CO-58 26.9%
NI-63 10.4%
CO-60 9.4%
NB-95 4.1%
CR-51 3.0%
ZR-95 2.4%
- 3. Solid Waste Disposition Number of Shipments Mode of Transportation Destination 16 Highway Chem-Nuclear Systems, Inc.
Barnwell, South Carolina.
- Measured and/or estimated by correlations in accordance with 10CFR61.55.
84
r
^
l' TABLE-3 Joseph-M. Farley Nuclear Plant-
)
,, ANNUAL' RADIOACTIVE EFFLUENT RELEASE REPORT-- 1997 !
SOLID WASTE'AND IRRADIATED FUEL SHIPMENTS i Starting: 01-Jul-1997 Ending: 31-Dec-1997 (continued)
, i
- 4. Type of Container (1b)
' Strong Tight Containers.
L l
- 5. Solidification Agent (1b)
None i
B. IRRADIATED FUEL SHIPMENTS (Disposition)
Number of Shipments Mode'of Transportation Destination-None N/A- N/A i
l l
l f-85
5.0 .ONSXTE DOSES-TO MEMBERS OF-THE PUBLIC Current FNP effluent controls as established by_ODCM 6.1-do not require assessment of the radiation doses from radioactive liquid and' gaseous effluents to MEMBERS OF THE PUBLIC due.to their activities.inside the SITE BOUNDARY (ODCM Figure 10-1). However,.
this assessment has been performed for 1997 using'the methods described in ODCM 6.2 and is included'in this section as Table 4-1..
-l I
86
)
1 l
TABLE 4-1 I l Joseph M. Farley Nuclear Plant i
ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1997 DOSE TO A MEMBER OF THE PUBLIC !
-DUE TO ACTIVITIES INSIDE THE SITE BOUNDARY Unit: Site I Starting: 01-Jan-1997 Ending: 30-Jun-1997 Page: 1
. Location Name VISITOR LOCATION 1 (VIS. CENTER)-
Distance (kilometers) 3.06E-01 Sector WSW Occupancy Factor- 1.37E-03 (1.20E+01 hr/yr)
Age Group. CHILD Ground Level Releases:
Noble Gas X/Q L (sec/m3) 1.04E-04 1 Particulate X/Q (sec/m3) 1.04E-04 Particulate D/Q (m-2) 4.80E-07 I Mixed Mode Releases:
Noble Gas X/Q (sec/m3) 8.80E-06 Particulate X/Q (sec/m3). 8.80E-06 Particulate D/Q (m-2) 6.20E-08 i 1
Elevated Releases:
Noble Gas X/Q (sec/m3) N/A )
Particulate X/Q (sec/m3) N/A !
Particulate D/Q (m-2)- N/A l
\
Units Quarter 1 Quarter 2 Quarters Year to 1 and 2 Ending Date Bone mrem ~ 5.84E-05 4.44E-05 1.03E-04 1.03E-04 l Liver mrem 6.50E-05 5.64E-05 1.21E-04 1.21E-04 ~
TBody mrem 6.49E-05 5.64E-05 1.21E-04 1.21E-04 l
< Thyroid mrem 7.99E-05 5.66E-05 1.36E-04 1.36E-04 l Kidney mrem 6.50E-05 5.64E-05 1.21E-04 1.21E-04
. Lung mrem. 6.49E-05 5.64E-05 1.21E-04 1.21E-04 GI-LLI mrem 6.49E-05 5.64E-05 1.21E-04 1.21E-04 I
l l
87
TABLE 4-1 Joseph M. Farley' Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1997 DOSE TO A MEMBER OF THE-PUBLIC DUE TO ACTIVITIES INSIDE THE SITE BOUNDARY Unit: Site Starting: 01-Jan-1997 Ending: 30-Jun-1997l Page: 2
-Location Name VISITOR LOCATION 2 (SW POND)
Distance (kilometers) 9.66E-01 Sector SSW Occupancy-Factor. 7.53E-03 '(6. 60E+01 hr/yr)
-Age Group CHILD Ground Level Releases:
Noble. Gas X/Q (sec/m3) 4.74E-05 Particulate X/O (sec/m3) 4.74E-05 Particulate D/Q (m-2) 1.31E-07 Mixed Mode Releases:
Noble Gas X/Q (sec/m3) 9.75E-07
' Particulate X/Q - (sec/m3) 9.75E-07 Particulate D/Q (m-2) 2.78E-08 Elevated Releases:
Noble Gas X/Q (sec/m3) N/A Particulate X/Q (sec/m3) N/A Particulate D/Q (m-2) N/A Units Quarter 1 Quarter 2 Quarters Year to 1 and 2 Ending Date Bone mrem 3.57E-05 2.70E-05 6.28E-05 6.28E-05 Liver mrem 3.98E-05 3.44E-05 7.42E-05 7.42E-05 TBody mrem 3.97E-05 3.44E-05 7.41E-05 7.41E-05 Thyroid mrem 7.69E-05 3.45E-05 1.11E-04 1.11E-04 !
Kidney mrem 3.99E-05 3.44E-05 7.43E-05 7.43E-05 Lung mrem 3.96E-05 3.44E-05 7.41E-05 7.41E-05 ,
GI-LLI mrem 3.97E-05 3.44E-05 7.41E-05 7.41E-05 88
TABLE 4-1
. Joseph M. Farley Nuclear Plant l ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1997 i
' DOSE TO A MEMBER OF THE PUBLIC DUE TO ACTIVITIES INSIDE THE SITE BOUNDARY Unit: Site
. Starting: '01-Jan-1997 Ending: 30-Jun-1997 L Page: 3 l
l Location.Name: VISITOR LOCATION 3 (RW DISCH.)
Distance (kilometers) 1.64E+00 Sector' SE Occupancy. Factor l'.14 E- 02 (9.99E+01 hr/yr)
Age Group CHILD Ground Level Releases:
- Noble Gas' X/Q (sec/m3) 1.63E-05 Particulate X/Q (sec/m3) 1.63E-05 Particulate D/Q (m-2) 4.55E-08 Mixed Mode Releases:
Noble' Gas X/Q (sec/m3) 7.05E-07
' Particulate X/Q (sec/m3)
~
7.05E-07 Particulate D/Q (m-2) 1.39E-08 Elevated Releases:
Noble Gas X/Q (sec/m3) N/A L Particulate X/Q (sec/m3) N/A Particulate D/Q (m-2) N/A Units Quarter 1 Quarter 2 Quarters Year to
- 1 and 2 Ending Date Done mrem 3.90E-05 2.96E-05 6.86E-05 6.86E-05 Liver mrem 4.34E-05 3.77E-05 8.10E-05 8.10E-05 l' TBody mrem 4.33E-05 3.77E-05 8.10E-05 8.10E-05 l Thyroid mrem 6.27E-05 3.77E-05 1.00E-04 1.00E-04 Kidney mrem 4.34E-05 3.77E-05 8.11E-05 8.11E-05
- Lung mrem 4.33E-05 3.77E-05 8.09E-05 8.09E-05 GI-LLI- mrem 4.33E-05 3.76E-05 8.10E-05 8.10E-05 i ..
)
89
! i
TABLE 4-1 l Joseph M. Farley Nuclear Plant
! ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1997 1 DOSE TO A MEMBER OF THE PUBLIC j
( DUE TO ACTIVITIES INSIDE THE SITE BOUNDARY Unit: Site Starting: 01-Jul-1997 Ending: 31-Dec-1997 i Page: 1 '
Location Name VISITOR LOCATION 1 (VIS. CENTER)
Distance (kilometers) i 3.06E-01 '
Sector WSW Occupancy Factor 1.37E-03 (1.20E+01 hr/yr)
Age Group CHILD Ground Level Releases: j Noble Gas X/Q (sec/m3) 1.04E-04 Particulate X/Q (sec/m3) 1.04E-04 Particulate D/Q (m-2) 4.80E-07 i
Mixed Mode Releases: l Noble Gas X/Q (sec/m3) 8.80E-06 i Particulate X/Q (sec/m3) 8.80E-06 I Particulate D/Q (m-2) 6.20E-08 i
Elevated Releases:
Noble Gas X/Q (sec/m3) N/A Particulate X/Q (sec/m3) N/A ,
Particulate D/O (m-2) N/A i l
I Units Quarter 3 Quarter 4 Quarters Year to I 3 and 4 Ending i Date Bone mrem 8.73E-05 9.73E-05 1.85E-04 2.87E-04 l Liver mrem 9.67E-05 1.08E-04 2.05E-04 3.26E-04 !
TBody mrem 9.67E-05 1.08E-04 2.05E-04 3.26E-04 Thyroid mrem 9.67E-05 1.08E-04 2.05E-04 3.42E-04 .;
Kidney mrem 9.67E-05 1.08E-04 2.05E-04 3.26E-04 i Lung mrem 9.67E-05 1.08E-04 2.05E-04 3.26E-04 )
GI-LLI mrem 9.67E-05 1.08E-04 2.05E-04 3.26E-04
__________..__________________________________________________________________ ]
l i
I 90
TABLE 4-1 Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1997 DOSE TO A MEMBER OF THE PUBLIC DUE TO ACTIVITIES INSIDE THE SITE BOUNDARY Unit: Site Starting: 01-Jul-1997 -Ending: 31-Dec-1997 Page: 2 LLocation Name- VISITOR LOCATION 2 (SW POND)
Distance (kilometers) 9.66E-01 Sector SSW i
Occupancy Factor 7.53E-03 (6.60E+01 hr/yr)-
Age Group CHILD
-Ground Level Releases: ~l i
r Noble Gas X/Q (sec/m3) 4.74E-05
- l. Particulate X/Q (sec/m3). 4.74E-05 Particulate D/Q (m-2) 1.31E-07 i
, Mixed Mode Releases: ]
l Noble Gas X/Q (sec/m3) 9.75E-07 l Particulate X/Q (sec/m3) 9.75E-07 Particulate D/Q (m-2) 2.78E-08 ]
- 1
- i 1
-Elevated Releases:
Noble Gas X/Q (sec/m3)
N/A Particulate X/Q (sec/m3) N/A Particulate D/Q (m-2) N/A
..___________________________________________________________________________ l l
Units Quarter 3 Quarter 4 Quarters ' Year to 3 and 4 Ending Date l Bone mrem 5.32E-05 5.~93E-05 1.12E-04 1.75E-04 '
l Liver mrem 5.89E-05 6.60E-05 1.25E-04 1.99E-04 j
'TBody- mrem 5.89E-05 6.60E-05 1.25E-04 1.99E-04 Thyroid- mrem 5.89E-05 6.61E-05 1.25E-04 2.36E-04 Kidney mrem 5.89E-05 6.60E-05 1.25E-04 1.99E-04 Lung mrem. 5.89E-05 6.60E-05 1.25E-04 1.99E-04 l
GI-LLI mrem 5.89E-05 6.60E-05 1.25E-04 1.99E-04 .
I l
i 91
1 i
(
L l l
TABLE 4-1 i~ Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1997 i L
DOSE TO A MEMBER OF 7EE PUBLIC f DUE TO ACTIVITIES INSIDE Th'O SITE BOUNDARY !
Unit: Site Starting: 01-Jul-1997 Ending: 31-Dec-1997 Page: 3 Location Name VISITOR LOCATION'3 (RW DISCH.) I Distance (kilometers) 1.64E+00 Sector SE l Occupancy' Factor 1.14E-02 (9. 99E+01 hr/yr) )
Age Group CHILD Ground' Level Releases:
' Noble Gas ' X/Q (sec/m3) 1.63E-05 Particulate X/Q (sec/m3) 1.63E-05 Particulate D/Q (m-2) 4.55E-08 Mixed Mode: Releases:
Noble Gas X/O (sec/m3) 7.05E-07 I Particulate X/Q (sec/m3) 7.05E-07 Particulate D/Q (m-2) 1.39E-08 )
Elevated Releases: j Noble Gas X/Q (sec/m3) N/A -]
Particulate X/Q (sec/m3) N/A Particulate D/Q (m-2) N/A
__~__________________________________________________________________________
Units Quarter 3 Quarter 4 Quarters Year to 3 and 4 Ending Date Bone mrem 5.82E-05 6.49E-05 1.23E-04 1.92E-04
- Liver mrem 6.45E-05 7.22E-05 1.37E-04 2.18E-04 TBody mrem 6.45E-05 7.22E-0E 1.37E-04 2.18E-04 Thyroid mrem 6.45E-05 7.23E-05 1.37E-04 2.37E-04
-Kidney mrem 6.45E-05 7.22E-05 1.37E-04 2.18E-04 Lung mrem 6.45E-05 7.22E-05 1.37E-04 2.18E-04 GI-LLI mrem 6.45E-05 7.22E-05 1.37E-04 2.18E-04 l
l 92
6.0 MISCELLANECUS i
This section contains several items which are only required to be reported under certain conditions. These include radiation dose assessments to show conformance with 40CFR190 (if required by ODCM 5.1.2), licensee initiated changes to the ODCM within the i last year, deviations in the Radioactive Effluent Control j Program within the last year pursuant to ODCM 7.2.2.6, major I changes to the liquid or gaseous radwaste treatment systems as required by ODCM 2.1.5 and 3.1.6, and any changes to the solid radwaste treatment system pursuant to the Process Control Progr4m (PCP).
6.1 Total Dose From Uranium Fuel Cycle In accordance with Technical Specification 6.8.3.e(x), the dose or dose commitment to any MEMBER OF THE PUBLIC over a calendar year, due to releases of radioactivity and to radiation from uranium fuel cycle sources, shall be limited to less than or equal to 25 mrem to the total body or to any organ, except the i thyroid, which shall be limited to less than or equal to 75 mrem (as stated in ODCM 5.1).
With the calculated doses from the release of radioactive materials in liquid or gaseous effluents exceeding twice the limits of ODCM 2.1.3, 3.1.3, or 3.1.4, calculations shall be ,
made according to ODCM 5.2 methods to determine whether the <
above (ODCM 5.1) limits have been exceeded (as stated in ODCM 5.1.2).
i Since none of the ODCM 2.1.3, 3.1.3, or 3.1.4 limits were exceeded during 1997, no calculations were required.
6.2 Licensee Initiated Changes to the ODCM There were no revisions to the ODCM during 1997.
6.3 Program Deviations This section contains any deviations from the composite sampling or MDC requirements included in ODCM Tables 2-3 and 3-3.
There was a deviation from gaseous effluent sampling requirements on both Unit 1 and Unit 2 during the second half of 1997 in that contJnuous containment Purge iodine and particulate samples were not obtained while required sample system modifications were being made. The Unit 1 sample system was out of service for approximately six days, and the Unit 2 sample system was out of service for approximately three days. Sample results from prior to and after the missed sample period were used to estimate the l Curies and doses released during these time frames.
l k 93
There was a deviation from the requirements of'ODCM Table 3-1 on Unit i during the second half ~of 1997 in~that the Auxiliary Building ventilation-lineup was not recorded once per four hours during a. period'when the Plant Vent' Stack flowrate recorder and its backup were inoperable. This occurred due to personnel failing to recognize the requirement to estimate flow once per four hours 1when the flowrate monitor was inoperable. There were no changes to the Auxiliary Building ventilation during this time period, and flowrates from prior to and after.the affected time period were used to estimate the flow during this time span.
6.4 Major Changes to the Radwaste Treatment. Systems There were no major changes to the Radwaste Treatment Systems during 1997.
1 i
l l
I l
94