L b
-i d
ATTACHMENT 1 ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT h-l 9904270098 990421 I
POR ADOCK 03000348 PDR L t
R o
i
4 W
W SOUTHERN NUCLEAR OPERATING COMPANY FARLEY-NUCLEAR PLANT UNIT NO. ONE LICENSE NO. NPF-2 AND FARLEY NUCLEAR PLANT UNIT NO. TWO LICENSE NO. NPF-8 I
ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT-CALENDAR YEAR 1998-i
[
J
E 1
FARLEY NUCLEAR PLANT ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT SECTION.
TITLE PAGE
1.0 INTRODUCTION
1 2.0 LIQUID EFFLUENTS 3
2.1' ODCM Limits 3
2.2 Measurements and Approximation 3
of Total Radioactivity 2.3 Abnormal Releases 4
2.4 Batch Releases 4
2.5 Release Summaries 9
2.5.1 Liquid Effluents - Summation of 9
All Releases 2.5.2 Liquid Effluents - Continuous 16 and Batch Releases 2.6 Radiological Impact 29 3.0 GASEOUS EFFLUENTS 39 3.1 -
ODCM Limits 39 3.2
. Measurements and Approximation 39 of Total Radioactivity 3.3 Abnormal Releases 41 3.4 Batch Releases 41 l
J
c FARLEY NUCLEAR PLANT ANNUAL RADIOACTIVE EFFLUENT
~
RELEASE REPORT SECTION TITLE PAGE 3.5 Release Summaries 50 3.5.1 Gaseous Effluents - Summation of 50 j
All Releases 3.5.2 Gaseous Effluents - Mixed Mode 57 Releases 3.5.3 Gaseous Effluents - Ground Mode 66 Releases 3.6 Radiological Impact 75
,.4.0 SOLID WASTE 85 5.0 ONSITE DOSES TO MEMBERS OF 90 THE PUBLIC 6.0 MISCELLANEOUS 97 6.1 Total Dose From Uranium Fuel Cycle 97 6.2 L'icensee Initiated Changes to 97 the ODCM-6.3 Program Deviations 97 6.4 Major Changes.to the Radwaste 97 Treatment Systems l
J
FARLEY NUCLEAR PLANT ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT TABLE LIST OF TABLES PAGE 1-4A Liquid Effluents - Batch Release 5
Summary, Unit 1 1-4B Liquid Effluents - Batch Release 7
Summary, Unit 2 f
1-1A Liquid Effluents - Summation of 10 All Releases, Unit 1 1-1B Liquid Effluents - Summation of 12 All Releases, Unit 2 1-1C Liquid Effluents - Summation of 14 All Releases, Site 1-2A Liquid Effluents - Continuous 17 and Batch Releases, Unit 1 1-2B Liquid Effluents - Continuous 21 and Batch Releases, Unit 2 1-2C Liquid Effluents - Continuous 25 and Batch Releases, Site 1-3A Doses to a MEMBER OF THE PUBLIC 30 Due to Liquid Releases, Unit 1 1-3B Doses to a MEMBER OF THE PUBLIC 32 Due to Liquid Releases, Unit 2 1-5 Typical Liquid MDC's Achieved 34 on Counting System 1-6A Liquid Effluents - Abnormal Release 35 Summary, Unit 1 1-6B Liquid Effluents - Abnornal Release 37 Summary, Unit 2 2-8A Gaseous Effluents - Abnormal Release 42 Summary, Unit 1 2-8B Gaseous Effluents - Abnormal Release 44 Summary, Unit 2 2-6A-Gaseous Effluents - Batch Release 46 Summary, Unit 1 2-6B Gaseous Effluents - Batch Release 48 Summ4ry, Unit 2 a
a FARLEY NUCLEAR PLANT ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT TABLE-LIST.OF TABLES
-PAGE 1A Gaseous-Effluents - Summation of-51 All Releases,. Unit 1 2-1B Gaseous Effluents - Summation of 53 All Releases, Unit 2 2-1C Gaseous Effluents - Summation of 55 All Releases, Site 2-2A Gaseous Effluents- Mixed Mode 58 Level Releases, Unit 1 2-2B Gaseous Effluents - Mixed Mode 61 Level Releases, Unit 2 2-2C' Gaseous Effluents - Mixed Mode 63 Level Releases, Site 2-3A Gaseous Effluents - Ground 67 Level Releases, Unit 1 2-3B Gaseous Effluents - Ground 70 Level' Releases, Unit 2 2-3C Gaseous Effluents - Ground 72 Level Releases, Site-2-4A Air Doses Due to Gaseous 76 Releases, Unit 1 2-4B Air Doses Due to Gaseous 78 Releases, Unit 2 2-5A Doses to a MEMBER OF THE PUBLIC 80 Due to Radiciodines, Tritium, and Particulates in Gaseous Releases, Unit 1 1
2-5B Doses to a MEMBER OF THE PUBLIC 82 Due to Radiciodines, Tritium, and Particulates in Gaseous Releases, Unit 2
.2-7 Typical Gaseous MDC's Achieved 84 on Counting. System j
1 3
Solid Waste and Irradiated 86 I
Fuel Shipments j
FARLEY NUCLEAR PLANT ANNUAL RADIOACTIVE EFFLUENT RELEASE' REPORT TABLE LIST OF TABLES PAGE 4-1 Doses to a MEMBER OF THE PUBLIC 91 Due to Activities Inside the Site Boundary, Site
l
1.0 INTRODUCTION
In accordance with Technical Specification (TS) 6.9.1.8 and 6.9.1.9 and Offsite Dose Calculation Manual
( DCM) 7.2, this O
Annual Radioactive Effluent Release Report covers the operations of the Farley Nuclear Plant (FNP) during 1998.
Information regarding the radioactive liquid and gaseous effluents and solid waste releases are summarized in formats similar to those provided in the Nuclear Regulatory Commission (NRC) Regulatory Guide 1.21, " Measuring, Evaluating, and Reporting j
Radioactivity in Solid Wastes and Releases of Radioactive Materials in Liquid and Gaseous Effluents from Light Water Cooled Nuclear Power Plants", Revision 1, June 1974. In addition the report includes required or appropriate information regarding meteorology, dose assessment and other pertinent matters.
Detailed information on liquid effluents is provided in Section 2.
The quantities of the radioactive effluents (including any unplanned releases) are summarized on a quarterly basis. A tabulation of the total body and organ doses which were calculated in accordance with ODCM 2.4 are presented to show conformance with the limits of ODCM
)
2.1.3.
Detailed information on gaseous effluents similar to that for liquid effluents is provided in Section 3. Tabulations are provided of the offsite air doses calculated in accordw.sce with ODCM 3.4.2 to show conformance with the limits of ODCM 3.1.3, and the offsite organ doses to a member of the public calculated in accordance with ODCM 3.4.3 to show conformance with the limits of ODCM 3.1.4.
{
Detailed information as specified by ODCM 7.2.2.4 on any solid radwastes shipped offsite is provided in Section 4. The data is summarized on a semiannual basis.
Assessments of the doses to members of the public due to their activities inside the site boundary are provided in Section 5.
These assessments are performed as specified by ODCM 6.2.
A number of miscellaneous matters are addressed in Section 6.
These are matters which require reporting only under certain conditions. The alphabetized list given below includes the conditional matters addressed.
A. An assessment of the radiation doses to the likely most exposed member of the public from reactor releases and other nearby uranium fuel cycle sources to show conformance with 40CFR190, should a determination be required by ODCM 5.1.2.
1
B. Any licansca initiated changc3 to the ODCM pursuant to TS 6.14 including changes to the campling locations in the Radiological Environmental Monitoring Program pursuant to ODCM 4.1.1.2.3 or 4.1.2.2.2, or changes in the location of the centrolling dose receptor identified in ODCM 3.4.3 pursuant to ODCM 4.1.2.2.1.
C. Discussions of deviations in the Radioactive Effluent Control Program pursuant to ODCM 7.2.2.6.
D. Any major changes to the liquid or gaseous radwaste treatment systems initiated by the licensee as required by ODCM 2.1.5 and 3.1.C, respectively, or to the solid radwaste treatment system pursuant to the Process Control Program (PCP) App. B section B.4.1.
Meteorological data are retained onsite; these data are available to the NRC upon request. The meteorological data include annual as well as quarterly summaries of hourly measurements of wind speed, wind direction and atmospheric stability in the form of joint i
frequency distribation tables.
l 2
E 2.0 LIQUID EFFLUENTS This section contains applicable ODCM limits for liquid effluents as well as the quantities of radioactive liquid effluents released during 1998. These quantities.are summarized on a quarterly basis-and include any unplanned releases. A tabulation of the total body i
and organ doses which were calculated in accordance with ODCM 2.4 i
are presented to show conformance with the limits of ODCM 2.1.3.
2.1 ODCM Limits In accordance with Technical Specifications 6.8.3.e(ii) and 1
6.8.3.e(iii), the concentration of radioactive material released 1
in liquid effluents to UNRESTRICTED AREAS (see ODCM Figure 10-1) shall be limited at all times to ten times the concentrations specified in 10CFR20, Appendix B, Table 2, Column 2 for radionuclides other than dissolved or entrained noble gases. For dissolved or entrained noble gases, the concentration shall be limited to 1E-04 uCi/ML total activity.
In accordance with Technical Specifications 6.8.3.e(iv) and 6.8.3.e(v), the dose or dose commitment to a MEMBER OF THE PUBLIC from radioactive materials in liquid. effluents released, from each unit, to UNRESTRICTED AREAS (see ODCM Figure 10-1) shall be limited:
- a. During any calendar quarter to less than or equal to 1.5 mrem to the total body and to less than or equal to 5 mrem to any organ, and
- b. During any calendar year to less than or equal to 3 mrem to the total body and to less than or equal to 10 mrem to any organ.
2.2 Measurements and Approximation of Total Radioactivity The radionuclides listed below are considered when evaluating liquid effluents:
MN-54 CS-134 FE-59 CS-137 CO-58 CE-141 CO-60 CE-144 ZN-65 MO-99 SR-89 FE-55 SR-90 H-3 I-131 i
3
Batch Relcases: Repre:entativa pre-release grab samples are obtained and analyzed in accordance with ODCM Table 2-3.
Isotopic analyses are performed using the computerized pulse height analysis system utilizing high resolution germanium detectors. Isotopic values thus obtained are used for release rate calculations as specified in the ODCM. Only those nuclides that are detected are used in the calculations. All Strontium and Iron-55 samples are sent offsite to the Georgia Power Environmental Laboratory for analysis. Gross beta and gross alpha determinations are made using 2 pi gas flow proportional counters. Tritium determinations are made using liquid scintillation techniques. Dissolved gases are determined employing grab sampling techniques and then counting on the pulse height analyzer.
l Continuous Releases: Continuous releases are analogous to batch releases except that they are analyzed on a weekly composite basis in accordance with ODCM Table 2-3.
The maximum error associated with volume and flow measurements, based upon plant calibration practice is estimated to be + or -
10%. The average error associated with counting is estimated to be less than + or - 15'e.
2.3 Abnormal Releases There were no abnormal liq 1 tid releases on either Unit 1 or Unit 2 during 1998.
Abnormal release information for Units 1 and 2 is summarized in the following tables:
Unit 1 1998 Liquid Abnormal Releases : Table 1-6A Unit 2 1998 Liquid Abnormal Releases : Table 1-6B 2.4 Batch Releases Batch release information for Units 1 and 2 is summarized in the following tables:
Unit 1 1998 Liquid Batch Releases : Table 1-4A Unit 2 1998 Liquid Batch Releases : Table 1-4B I
4 j
l
o
. TABLE 1-4A UOscph M.
Farley Nuclear Plant ANNUAL RADIO 2CTIVE EFFLUENT RELEASE REPORT - 1998 Liquid Effluents - Batch Release Summary Unit: 1 Starting :
1-Jan-1998 Ending : 30-Jun-1998 LIQUID RELEASES NUMBER OF BATCH RELEASES 115 TOTAL TIME PERIOD FOR BATCH RELEASES 10994.00 MINUTES MAXIMUM TIME PERIOD FOR A BATCH RELEASE 149.00 MI4UTES AVERAGE TIME PERIOD FOR BATCH RELEASES 95.60 MINUTES MINIMUM TIME PERIOD FOR A BATCH RELEASE 68.00 MINUTES AVERAGE STREAM FLOW DURING PERIODS OF
~ RELEASE OF LIQUID EFFLUENT INTO A FLOWING STREAM :
1.96E+04 CFS *
- Avarage River Flow Rate, taken at Walter F. George Lock and Dam, located 30.7 miles above Farley Nuclear Plant.
1 l
l 5
1
I I
TABLE 1-4A Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1998 Liquid Effluents - Batch Release Summary l
Unit: 1 Starting :
1-Jul-1998 Ending : 31-Dec-1998 LIQUID RELEASES NUMBER OF BATCH RELEASES 196 TOTAL TIME PERIOD FOR BATCH RELEASES 18838.73 MINUTES MAXIMUM TIME PERIOD FOR A BATCH RELEASE 147.00 MINUTES AVERAGE TIME PERIOD FOR BATCH RELEASES 96.12 MINUTES l
MINIMUM TIME PERIOD FOR A BATCH PELEASE 60.00 MINUTES AVERAGE STREAM FLOW DURING PERIO1 OF RELEASE OF LIQUID EFFLUENT INTO A FLOWING STREAM :
8.50E+03 CFS
- i
- Average River Flow Rate, taken at Walter F. George Lock and Dam, located 30.7 miles above Farley Nuclear Plant.
1 6
n j
TABLE 1-4B Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1998 Liquid Effluents-- Batch Release Summary Unit: 2 Starting :
1-Jan-1998 Ending : 30-Jun-1998
-LIQUID RELEASES j
NUMBER OF BATCH RELEASES 173 TOTAL TIME PERIOD FOR BATCH RELEASES 18246.63 MINUTES MAXIMUM TIME PERIOD FOR A BATCH RELEASE 129.00 MINUTES AVERAGE TIME PERIOD FOR BAi'CH RELEASES 105.47 MINUTES MINIMUM TIME PERIOD FOR A BATCH RELEASE 90.00 MINUTES AVERAGE STREAM FLOW DURING PERIODS OF RELEASE OF LIQUID EFFLUENT INTO A FLOWING STREAM :
1.96E+04 CFS * -
4 l
i i
- Average River Flow Rate, taken at Walter F. George Lock and Dam, located 30.7 miles above Farley Nuclear Plant.
i 7
TABLE 1-4B Joseph M.
Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1998 Liquid Effluents - Batch Release Summary Unit: 2 Starting :
1-Jul-1998 Ending : 31-Dec-1998 LIQUID RELEASES NUMBER OF BATCH RELEASES 97 TOTAL TIME PERIOD FOR BATCH RELEASES 10209.00 MINUTES MAXIMUM TIME PERIOD FOR A BATCH RELEASE 120.00 MINUTES AVERAGE TIME PERIOD FOR BATCH RELEASES 105.25 MINUTES MINIMUM TIME PERIOD FOR A BATCH RELEASE 95.00 MINUTES AVERAGE STREAM FLOW DURING PERIODS OF RELEASE OF LIQUID EFFLUENT INTO A FLOWING STREAM :
8.50E+03 CFS *
- Average River Flow Rate, taken at Walter F. George Lock and Dam, located 30.7 miles above Farley Nuclear Plant.
l i
8 i
1 2.5 Release Summaries l
This section contains the summaries of all radioactive liquid effluents released for Units 1 and 2 during 1998. Typical liquid Minimum Detectable Concentrations (MDC'S) for analyses are in Table 1-5 of this section. Regulatory Guide 1.21 Table 2A is found in this report as Tables 1-1A, 1-1B, and 1-1C. Regulatory Guide 1.21 Table 2B is found in this report as Tables 1-2A, 1-2B, and 1-2C.
2.5.1 Liquid Effluents - Summation of All Releases The summations of all liquid effluent releases are contained in the following tables:
j Unit 1 1998 Summation of All Releases : Table 1-1A i
Unit 2 1998 Summation of All Releases : Table 1-1B Site 1998 Summation of All Releases : Table 1-1C i
I i
9
TABLE 1-1A Joseph M.
Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1998 Liquid Effluents - Summation of All Releases Unit: 1 Starting :
1-Jan-1998 Ending : 30-Jun-1998 TYPE OF EFFLUENT UNIT 9 QUARTER 1 QUARTER 2 EST. TOT ERROR %
q i
~A.
FISSION & ACTIVATION PRODUCTS
- 1. TOTAL RELEASE (NOT INCLUDING TRITIUM, GASES, ALPHA)
CURIES 1.85E-02 1.09E-01 2.50E+01
- 2. AVERAGE DILUTED CONCENTRATION DURING PERIOD uCi/ML 1.13E-09 6.87E-09
)
3.
PERCENT OF APPLICABLE LIMIT j
B. TRITIUM
- 1. TOTAL RELEASE CURIES 1.67E+02 1.64E+02 2.50E+01 i
- 2. AVERAGE DILUTED CONCENTRATION DURING PERIOD uCi/ML 1.02E-05 1.04E-05 l
- 3. PERCENT OF APPLICABLE LIMIT C. DISSOLVED AND ENTRAINED GASES
- 1. TOTAL RELEASE CURIES 1.06E-04 1.07E-04 2.50E+01
- 2. AVERAGE DILUTED CONCENTRATION DURING PERIOD uCi/NL 6.47E-12 6.73E-12 1
- 3. PERCENT OF APPLICABLE LIMIT D. G.10SS ALPHA RADIOACTIVITY l
- 1. TOTAL RELEASE CURIES 5.36E-06 3.72E-05 2.50E+01 t
i l
E. WASTE VOL RELEASED (PRE-DILUTION)
LITERS 1.02E+08 8.36E+07 1.00E+01 1
F. VOLUME.0F DILUTION WATER USED LITERS 1.62E+10 1.58E+10 1.00E+01 Applicable limits are expressed in terms of dose.
See Tables 1-3A and 1-3B of this report.
10 L.
E 1
J TABLE 1-1A Jor:ph M.
Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1998 Liquid Effluents - Summation of All Releases j
Unit: 1 i
Starting :
1-Jul-1998 Ending : 31-Dec-1998 j
i TYPE OF EFFLUENT UNITS QUARTER 3 QUARTER 4 EST. TOT ERROR %
A.
FISSION & ACTIVATION PRODUCTS k$ Tbhkb kbbbkSb (hbT bhbLbbkhb
~
TRITIUM, GASES, ALPHA)
CURIES 5.46E-01 1.25E-01 2.50E+01
\\
- 2. AVERAGE DILUTED CONCENTRATION DURING PERIOD uCi/ML 3.08E-08 8.03E-09 3.
PERCENT OF APPLICABLE LIMIT 1
B. TRITIUM j
- 1. TOTAL RELEASE CURIES 2.95E+02 6.59E+01 2.50E+01
- 2. AVERAGE DILUTED CONCENTRATION DURING PERIOD uCi/ML 1.66E-05 4.25E-06 1
3.
PERCENT OF APPLICABLE LIMIT C. DISSOLVED AND ENTRAINED GASES
- 1. TOTAL RELEASE CURIES 4.24E-02 6.56E-03 2.50E+01
- 2. AVERAGE DILUTED CONCENTRATION DURING PERIOD uCi/ML 2.39E-09 4.23E-10
- 3. PERCENT OF APPLICABLE LIMIT D. GROSS ALPHA RADIOACTIVITY
- 1. TOTAL RELEASE CURIES 2.97E-05 1.04E-05 2.50E+01 E. WASTE VOL RELEASED (PRE-DILUTION)
LITERS 9.22E+07 3.83E+07 1.00E+01 F. VOLUME OF DILUTION WATER USED LITERS 1.77E+10 1.55E+10 1.00E+01 Applicable limits are expressed in terms of dose.
See Tables 1-3A and 1-3B of this report.
11
c 4
TABLE 1-1B Jo2cph M.
Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1998 l
Liquid Effluents - Summation of All Releases Unit: 2 l
Starting :
1-Jan-1998 Ending : 30-Jun-1998 1
TYPE OF. EFFLUENT UNITS QUARTER 1 QUARTER 2 EST. TOT ERROR %
)
1 i
A. FISSION &. ACTIVATION PRODUCTS l
- 1. TOTAL RELEASE (NOT INCLUDING i
TRITIUM, GASES, ALPHA)'
CURIES 3.84E-02 1.83E-01 2.50E+01 i
- 2. AVERAGE DILUTED CONCENTRATION i
DURING PERIOD uCi/ML 2.33E-09 1.46E-08
- 3. PERCENT OF APPLICABLE LIMIT B. TRITIUM
- 2. AVERAGE DILUTED CONCENTRATION DURING PERIOD uCi/ML 2.66E-05 8.96E-06 i
- 3. PERCENT OF APPLICABLE LIMIT C. DISSOLVED AND ENTRAINED GASES
- 1. TOTAL RELEASE CURIES 5.18E-04 3.52E-04 2.50E+01
]
- 2. AVERAGE DILUTED CONCENTRATION DURING PERIOD uCi/ML 3.15E-11 2.80E-11 i
i
- 3. PERCENT OF APPLICABLE LIMIT D. GROSS ALPHA RADIOACTIVITY
- 1. TOTAL RELEASE CURIES 3.04E-05 1.31E-04 2.50E+01 E. WASTE VOL RELEASED (PRE-DILUTION)
LITERS 5.38E+07 3.82E+07 1.00E+01 F, VOLUME OF DILUTION WATER USED LITERS 1.64E+10 1.25E+10 1.00E+01 Applicable limits are expressed in terms of dose.
See Tables 1-3A and 1-3B of this report.
12
i-1 TABLE 1-1B Joseph M. Farlcy Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1998 i
Liquid Effluents - Summation of All Releases Unit: 2 Starting :
1-Jul-1998 Ending : 31-Dec-1998 I
TYPE OF EFFLUENT.
UNITS QUARTER 3
' QUARTER 4 EST. TOT ERROR %
A. FISSION & ACTIVATION PRODUCTS-
- 1. TOTAL RELEASE (NOT INCLUDING TRITIUM, GASES, ALPHA)
CURIES 2.39E-02 3.41E-02 2.50E+01
- 2. AVERAGE DILUTED CONCENTRATION I
DURING PERIOD uCi/ML 1.40E-09 2.15E-09
- 3. PERCENT OF APPLICABLE LIMIT B. TRITIUM
- 1. TOTAL RELEASE CURIES 1.15E+02 1.29E+02 2.50E+01-
- 2. AVERAGE DILUTED CONCENTRATION DURING PERIOD uCi/ML 6.73E-06 8.15E-06
- 3. PERCENT OF APPLICABLE LIMIT l
f l
C. DISSOLVED AND ENTRAINED GASES i
1.
TOTAL RELEASE CURIES 2.90E-03 1.13E-03 2.50E+01
- 2. AVERAGE DILUTED CONCENTRATION DURING PERIOD uCi/ML 1.70E-10 7.17E-11
- 3. PERCENT OF APPLICABLE LIMIT 1
D. GROSS ALPHA RADIOACTIVITY
- 1. TOTAL RELEASE CURIES 7.18E-06 1.43E-05 2.50E+01 E.--WASTE VOL RELEASED (PRE-DILUTION)
LITERS 7.11E+07 6.60E+07 1.00E+01 F. VOLUME OF DILUTION WATER USED LITERS 1.69E+10 1.58E+10 1.00E+01 i
Applicable limits are expressed in terms of dose.
See Tables
- 3A and 1-3B of this report.
13
TABLE 1-1C Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1998 Liquid Effluents - Summation of All Releases Unit: Site Starting :
1-Jan-1998 Ending : 30-Jun-1998 TYPE OF EFFLUENT UNITS QUARTER 1 QUARTER 2 EST. TOT ERROR %
A. FISSION & ACTIVATION PRODUCTS
- 1. TOTAL RELEASE (NOT INCLUDING j
TRITIUM, GASES, ALPHA)
CURIES 5.68E-02 2.92E-01 2.50E+01
- 2. AVERAGE DILUTED CONCENTRATION DURING PERIOD uCi/ML 1.73E-09 1.03E-08
- 3. PERCENT OF APPLICABLE LIMIT i
j B. TRITIUM
- 1. TOTAL RELEASE CURIES 6.06E+02 2.77E+02 2.50E+01 i
i i
- 2. AVERAGE DILUTED CONCENTRATION DURING PERIOD uCi/ML 1.85E-05 9.75E-06 3.
PERCENT OF APPLICABLE LIMIT 1
C. DISSOLVED AND ENTRAINED GASES 1.' TOTAL RELEASE CURIES 6.24E-04 4.58E-04 2.50E+01
- 2. AVERAGE DILUTED CONCENTRATION DURING PERIOD uCi/ML 1.90E-11 1.61E-11
- 3. PERCENT OF APPLICABLE LIMIT D. GROSS ALPHA RADIOACTIVITY
- 1. TOTAL R3 LEASE CURIES 3.57E-05 1.69E-04 2.50E+01 E. WASTE VOL RELEASED (PRE-DILUTION)
LITERS 1.56E+08 1.22E+08 1.00E+01 h$VbbbMbbFbkbbTkbhhkTkkbbhb bkTbkb 5$h6kkb b$b5bkb 5$bbbb5 e
Applicable limits are expressed 11. terms of dose.
See Tables 1-3A and 1-3B of this report.
14
4 i
e TABLE 1-1C Joseph M.
Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1998
(
Liquid Effluents - Summation of All Releases Unit: Site Starting :
1-Jul-1998 Ending : 31-Dec-1998 TYPE OF EFFLUENT UNITS QUARTER 3 QUARTER 4 EST. TOT ERROR %
A.' FISSION & ACTIVATION PRODUCTS 1, TOTAL RELEASE (NOT INCLUDING TRITIUM, GASES, ALPHA)
CURIES 5.70E-01 1.59E-01 2.50E+01
- 2. AVERAGE DILUTED CONCENTRATION DURING PERIOD uCi/ML 1.64E-08 5.06E-09 1
3.. PERCENT OF APPLICABLE LIMIT i
__l__..__..................__.......___........._.............__.___....____..
B. TkITIUM i
- 1. TOTAL RELEASE CURIES 4.10E+02 1.95E+02 2.50E+01
- 2. AVERAGE DILUTED CONCENTRATION DURING PERIOD uCi/ML 1.18E-05 6.22E-06 1
- 3. PERCENT OF APPLICABLE LIMIT j
i C. DISSOLVED AND ENTRAINED GASES TOTAL RELEASE CURIES 4.53E-02 7.69E-03 2.50E+01
___1.
- 2. AVERAGE DILUTED CONCENTRATION DURING PERIOD uCi/ML 1.30E-09 2.45E-10 3.
PERCENT OF APPLICABLE LIMIT D. GROSS ALPHA RADIOACTIVITY
- 1. TOTAL RELEASE CURIES 3.69E-05 2.46E-05 2.50E+01 E. WASTE VOL RELEASED (PRE-DILUTION)
LITERS 1.63E+08 1.04E+08 1.00E+01 F. VOLUME OF DILUTION WATER USED LITERS 3.46E+10 3.12E+10 1.00E+01 Applicable limits are expressed in terms of dose.
See Tables 1-3A and 1-3B of this report.
15
p-
.,s 2.5.2 Liquid Effluents - Continuous and Batch Releases The continuous and batch release summaries of all liquid effluent releases (includes listing by nuclide) are contained in the.following tables:
Unit 1 1998 Continuous and Batch Releases : Table 1-2A.
' Unit 2 1998 Continuous and Batch Releases : Table 1-2B Site-1998 Continuous and Batch Releases : Table 1-2C 4
9 16 i
4 TABLE 1-2A*
Jo2 ph M.
Fnrley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1998 Liquid Effluents Unit: 1 Starting :
1-Jan-1998 Ending : 30-Jun-1998 j
l CONTINUOUS MODE l
BATCH MODE l
NUCLIDE l
UNIT l QUARTER 1 l QUARTER 2 l QUARTER 1 l QUARTER 2 l H-3 l
CURIES l 1.36E+00 l 1.12E+00 l 1.66E+02 l 1.63E+02 l FISSION & ACTIVATION PRODUCTS AG-110M CURIES 0.00E+00 0.00E+00 4.80E-04 4.48E-04 AS-76 CURIES 0.00E+00 0.00E+00 2.10E-06 0.00E+00 CO-57 CURIES 0.00E+00 0.00E+00 5.61E-05 2.33E-04 CO-58 CURIES 0.00E+00 1.35E-04 6.04E-03 7.52E-02 CO-60 CURIES 0.00E+00 0.00E+00 4.32E-03 4.07E-03 CR-51 CURIES 0.00E+00 0.00E+00 0.00E+00 1.39E-03 CS-134 CURIES 0.00E+00 0.00E+00 1.50E-05 0.00E+00 CS-137 CURIES 0.00E+00 0.00E+00 3.31E-04 6.88E-05 FE-55 CURIES 3.26E-09 7.68E-09 1.78E-03 4.47E-03 FE-59 CURIES 0.00E+00 0.00E+00 0.00E+00 1.73E-04 I-133 CURIES 2.67E-03 1.88E-02 0.00E+00 0.00E+00 MN-54 CURIES 0.00E+00 0.00E+00 1.34E-04 1.86E-04
,NB-95 CURIES 0.00E+00 0.00E+00 1.36E-05 1.46E-04 NB-97 CURIES 0.00E+00 0.00E+00 9.73E-05 1.36E-04 PR-144 CURIES 0.00E+00 0.00E+00 7.82E-05 0.00E+00 SB-124 CURIES 0.00E+00 0.00E+00 0.00E+00 1.71E-04 SB-125 CURIES 0.00E+00 0.00E+00 2.36E-03 2.42E-03 SR-89 CURIES 5.82E-11 5.82E-11 1.98E-05 8.89E-06 i
SR-90 CURIES 4.55E-12 4.59E-04 1.24E-07 2.03E-05 l
SR-92 CURIES 0.00E+00 0.00E+00 8.36E-06 1.58E-05 TC-99M CURIES 0.00E+00 0.00E+00 5.86E-06 0.00E+00 ZN-65 CURIES 0.00E+00 0.00E+00 4.45E-05 9.49E-05 ZR-95 CURIES 0.00E+00 0.00E+00 0.00E+00 4.43E-05 TOTALS l
CURIES l 2.67E-03 l 1.94E-02 l 1.58E-02 l 8.93E-02 l DISSOLVED AND ENTRAINED GASES XE-133 CURIES 0.00E+00 0.00E+00 1.00E-04 9.60E-05 XE-135 CURIES 0.00E+00 0.00E+00 0.00E+00 2.22E-06 TOTALS l
CURIES l 0.00E+00 l 0.00E+00 l 1.06E-04 l 1.07E-04 l 17
TABLE 1-2A*
Jo2cph M.
Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1998 Liquid Effluents Unit: 1 Starting :
1-Jan-1998 Ending : 30-Jun-1998 l CONTINUOUS MODE l
. BATCH MODE l
NUCLIDE l
UNIT l QUARTER 1 l QUARTER 2 l QUARTER 1 l QUARTER 2'l G-ALPHA l
CURIES l 5.82E-11 l 6.18E-11 l 5.36E-06 l 3.72E-05 l Zeroes in this table indicate that no radioactivity was present at detectable levels.
See Table 1-5 for typical minimum detectable concentrations.
i I
l i
18 l
TABLE 1-2A*
Joacph M.
Farley Nuclear Plant
~
ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1998 Liquid Effluents Unit: 1 Starting :
1-Jul-1998 Ending : 31-Dec-1998 l CONTINUOUS MODE l
BATCH MODE l
NUCLIDE l
UNIT l QUARTER 3 l QUARTER 4 l QUARTER 3 l QUARTER 4 l H-3 l
CURIES l 9.43E+00 l 8.79E+00 l 2.86E+02 l 5.71E+01 l FISSION & ACTIVATION PRODUCTS AG-110M CURIES 0.00E+00 0.00E+00 1.02E-03 1.63E-02 BA-140 CURIES 8.76E-03 0.00E+00 0.00E+00 0.00E+00 CO-57 CURIES 0.00E+00 0.00E+00 1.41E-04 1.56E-04 CO-58 CURIES 1.29E-02 7.65E-04 3.78E-02 3.69E-02 CO-60 CURIES 4.51E-04 1.22E-04 3.34E-03 7.12E-03 CR-51 CURIES 5.87E-04 0.00E+00 1.68E-04 2.88E-03 CS-134 CURIES 4.89E-04 1.88E-03 0.00E+00 6.92E-04 CS-137 CURIES 6.72E-04 2.26E-03 2.84E-04 1.47E-03 CS-138 CURIES 9.52E-03 0.00E+06 0.00E+00 0.00E+00 FE-55 CURIES 1.20E-03 6.84E-05 5.61E-03 1.19E-02 FE-59 CURIES 1.01E-04 0.00E+00 7.87E-05 3.40E-04 I-131 CURIES 4.95E-03 1.27E-03 0.00E+00 0.00E+00 I-132 CURIES 1.67E-02 0.00E+00 0.00E+00 3.80E-06 I-133 CURIES 2.67E-01 3.63E-02 4.56E-06 0.00E+00 I-134 CURIES 1.82E-02 0.00E+00 0.00E+00 0.00E+00 I-135 CURIES 2.84E-02 0.00E+00 0.00E+00 0.00E+00 LA-140 CURIES 1.41E-02 0.00E+00 0.00E+00 0.00E+00 MN-54 CURIES 9.77E-03 2.69E-04 7.88E-05 3.22E-04 NA-24 CURIES 4.63E-02 0.00E+00 0.00E+00 0.00E+00 NB-95 CURIES 2.11E-04 2.14E-04 7.80E-05 3.27E-04 NB-97 CURIES 0.00E+00 0.00E+00 2.12E-04 5.42E-05 PM-149 CURIES 1.59E-02 0.00E+00 0.00E+00 0.00E+00 RH-106 CURIES 5.63E-03 0.00E+00 0.00E+00 0.00E+00 RU-103 CURIES 0.00E+00 0.00E+00 4.41E-06 0.00E+00 RU-106 CURIES 5.63E-03 0.00E+00 0.00E+00 0.00E+00 SB-122 CURIES 0.00E+00 1.20E-04 0.00E+00 1.73E-06 SB-124 CURIES 0.00E+00 0.00E+00 4.53E-04 3.71E-06 I
SB-125 CURIES 0.00E+00 0.00E+00 6.20E-03 1.64E-03 SN-113 CURIES 0.00E+00 0.00E+00 0.00E+00 6.96E-05 SR-89 CURIES 2.42E-03 2.72E-04 7.63E-05 3.06E-05 SR-90 CURIES 2.75E-05 7.50E-12 5.02E-06 9.31E-06 I
SR-92 CURIES 0.00E+00 0.00E+00 7.46E-06 4.84E-04 TC-99M CURIES 5.32E-03 0.00E+00 0.00E+00 0.00E+00 19 l
1
E l
s TABLE 1-2Ae Joseph M. Farley Nuclear Plant I
ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1998 Liquid Effluents Unit: 1 Starting :
1-Jul-1998 Ending : 31-Dec-1998 l CONTINUOUS MODE l
BATCH MODE l
NUCLIDE l
UNIT l QUARTER 3 l QUARTER 4 l QUARTER 3 l QUARTER 4 l FISSION & ACTIVATION PRODUCTS TE-132 CURIES 0.00E+00 0.00E+00 0.00E+00 9.40E-06 ZN-65 CURIES-0.00E+00 0.00E+00 2.69E-06 0.00E+00 ZN-69M CURIES 1.52E-02 0.00E+00 0.00E+00 0.00E+00 ZR-95 CURIES 0.00E+00
.1.24E-04 2.05E-05 2.18E-04 TOTALS l
CURIES l 4.91E-01 l 4.36E-02 l 5.55E-02 l 8.09E-02 l DISSOLVED AND ENTRAINED GASES XE-133 CURIES 1.10E-03 1.58E-04 3.46E-03 1.04E-03 XE-135 CURIES 2.32E-02 1.82E-03 5.30E-06 0.00E+00 XE-135M CURIES 1.45E-02 3.54E-03 2.98E-06 0.00E+00 TOTALS l
CURIES. l 3.89E-02 l 5.52E-03 l 3.47E-03 l 1.04E-03 l G-ALPHA l
CURIES l 3.59E-11 l 1.32E-11 l 2.97E-05 l 1.04E-05 l l
1 1
Zeroes in this table indicate that no radioactivity was present at detectable levels.
See Table 1-5 for typical minimum detectable concentrations.
20
TABLE 1-2Bt Jo cph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1938 Liquid Effluents Unit: 2 l
Starting :
1-Jan-1998 Ending : 30-Jun-1998 l CONTINUOUS MODE l
BATCH MODE l
NUCLIDE l
UNIT l QUARTER 1 l QUARTER 2 l QUARTER 1 l QUARTER 2 l H-3 l
CURIES l 1.25E-01 l 2.66E-01 l 4.38E+02 l 1.12E+02 l FISSION & ACTIVATION PRODUCTS AG-110M CURIES 0.00E+00 0.00E+00 1.00E-04 6.35E-04 CO-57 CURIES 0.00E+00 0.00E+00 1.63E-04 5.60E-04 CO-58 CURIES 0.00E+00 1.12E-04 1.95E-02 1.66E-01 CO-60 CURIES 0.00E+00 0.00E+00 9.50E-03 5.60E-03 CR-51 CURIES 0.00E+00 0.00E+00 9.94E-05 1.14E-03 CS-134 CURIES 0.00E+00 0.00E+00 1.73E-05 0.00E+00 CS-137 CURIES 0.00E+00 0.00E+00 5.23E-04 3.86E-05 FE-55 CURIES 4.66E-09 2.80E-09 4.67E-03 7.31E-03 FE-59 CURIES 0.00E+00 0.00E+00 0.00E+00 2.16E-04 I-131 CURIES 0.00E+00 0.00E+00 3.39E-06 0.00E+00 I-133 CURIES 0.00E+00 0.00E+00 1.60E-05 0.00E+00 MN-54 CURIES 0.00E+00 0.00E+00 2.75E-04 1.13E-04 NA-24 CURIES 0.00E+00 0.00E+00 7.91E-05 0.00E+00 NB-95 CURIES 0.00E+00 0.00E+00 2.34E-05 6.98E-05 NB-97 CURIES 0.00E+00 0.00E+00 1.10E-04 9.39E-05 SB-122 CURIES 0.00E+00 0.00E+00 2.57E-06 0.00E+00 SB-124 CURIES 0.00E+00 0.00E+00 0.00E+00 2.27E-04 SB-125 CURIES 0.00E+00 0.00E+00 3.04E-03 7.59E-04 SN-113 CURIES 0.00E+00 0.00E+00 5.52E-07 0.00E+00 SR-89 CURIES 7.28E-11 4.38E-11 5.32E-05 2.84E-04 SR-90 CURIES 6.37E-12 5.46E-12 5.24E-06 7.53E-06 SR-92 CURIES 0.00E+00 0.00E+00 2.10E-05 2.32E-05 TC-99M CURIES 0.00E+00 0.00E+00 1.07E-05 0.00E+00 ZN-65 CURIES 0.00E+00 0.00E+00 1.22E-04 3.39E-04 TOTALS l
CURIES l 4.74E-09 l 1.12E-04 l 3.84E-02 l 1.83E-01 l 21
TABLE 1-2B*
Jo cph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1998 Liquid Effluents Unit: 2 Starting :
1-Jan-1998 Ending : 30-Jun-1998 l CONTINUOUS MODE l
BATCH MODE l
NUCLIDE l
UNIT l QUARTER 1 l QUARTER 2 l QUARTER 1 l QUARTER 2 l DISSOLVED AND ENTRAINED GASES AR-41 CURIES 0.00E+00 0.00E+00 5.29E-06 0.00E+00 XE-133 CURIES 0.00E+00 0.00E+00 4.94E-04 3.52E-04 XE-133M CURIES 0.00E+00 0.00E+00 7.85E-06 0.00E+00 XE-135 CURIES 0.00E+00 0.00E+00 1.14E-05 0.00E+00 TOTALS l
CURIES l 0.00E+00 l 0.00E+00 l 5.18E-04 l 3.52E-04 l G-ALPHA l
CURIES l 2.36E-11 l 1.09E-11 l 3.04E-05 l 1.31E-04 l Zeroes in this table indicate that no radioactivity was present at detectable levels.
See Table 1-5 for typical minimum detectable concentrations.
I 22
TABLE 1-2B*
Joacph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1998 Liquid Effluents Unit: 2 Starting :
1-Jul-1998 Ending : 31-Dec-1998 l CONTINUOUS MODE l
BATCH MODE l
NUCLIDE l
. UNIT l QUARTER 3 l QUARTER 4 l QUARTER 3 l QUARTER 4 l H-3 l
CURIES l 1.55E-01 l 2.61E-02 l 1.14E+02 l 1.29E+02 l FISSION & ACTIVATION PRODUCTS AG-110M-CURIES 0.00E+00 0.00E+00 4.09E-04 5.34E-03 CO-57 CURIES 0.00E+00 0.00E+00 6.77E-05 1.02E-04 CO-58 CURIES 0.00E+00 0.00E+00 1.47E-02 1.64E-02 l
CO-60 CURIES 0.00E+00 0.00E+00 1.19E-03 1.75E-03 CR-51 CURIES 0.00E+00 0.00E+00 6.40E-05 9.48E-04 CS-137 CURIES 0.00E+00 0.00E+00 1.48E-04 4.83E-05 FE-55 CURIES 5.64E-04 3.34E-05 1.94E-03 8.23E-03 FE-59 CURIES 0.00E+00 0.00E+00 1.34E-05 2.14E-04 I-132 CURIES 0.00E+00 0.00E+00 0.00E+00 6.02E-06 j
MN-54 CURIES 0.00E+00 0.00E+00 1.76E-05 9.34E-06 l
NA-24 CURIES 0.00E+00 0.00E+00 2.28E-06 0.00E+00 NB-95 CURIES 0.00E+00 0.00E+00 7.28E-06 0.00E+00 l
NB-97 CURIES 0.00E+00 0.00E+00 5.61E-05 2.75E-05 SB-124 CURIES 0.00E+00 0.00E+00 3.85E-04 0.00E+00 SB-125 CURIES 0.00E+00 0.00E+00 4.05E-03 4.63E-04 l
SN-113 CURIES 0.00E+00 0.00E+00 0.00E+00 1.12E-05 l
SR-89 CURIES 1.77E-04 3.63E-04 2.89E-05 2.95E-05 SR-90 CURIES 1.35E-11 8.41E-12 1.45E-06 2.81E-07 SR-92 CURIES 0.00E+00 0.00E+00 6.43E-05 1.16E-04 TE-132 CURIES 0.00E+00 0.00E+00 0.00E+00 6.00E-06 ZN-65 CURIES 0.00E+00 0.00E+00 1.30E-05 0.00E+00 ZR-95 CURIES 0.00E+00 0.00E+00 0.00E+00 1.46E-05 TOTALS l
CURIES l 7.40E-04 l 3.96E-04 l 2.32E-02 l 3.37E-02 l l
23
TABLE 1-2B*
Jo cph M. Farley Nuclear Plant j
ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1998 Liquio Effluents i
Unit: 2 i
Starting :
1-Jul-1998 Ending : 31-Dec-1998 l CONTINUOUS MODE l
BATCH MODE l
NUCLIDE l
UNIT l QUARTER 3 l QUARTER 4 l QUARTER 3 l QUARTER 4 l DISSOLVED AND ENTRAINED GASES XE-133 l
CURIES l 0.00E+00 l 0.00E+00 l 2.90E-03 l 1.13E-03 l TOTALS l
CURIES l 0.00E+00 l 0.00E+00 l 2.90E-03 l 1.13E-03 l G-ALPHA l
CURIES l 1.55E-11 l 2.18E-11 l 7.18E-06 l 1.43E-05 l Zeroes in this table indicate that no radioactivity was present o
at detectable levels.
See Table 1-5 for typical minimum i
detectable concentrations.
24
r l
I L
TABLE 1-2C*
Jo:cph M.
Farley Nuclear Plant l
ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1998 l
Liquid Effluents Unit: Site Starting :
1-Jan-1998 Ending : 30-Jun-1998 l
l l CONTINUOUS MODE l
BATCH MODE l
NUCLIDE l
UNIT l QUARTER 1 l QUARTER 2 l QUARTER 1 l QUARTER 2 l H-3 l
CURIES l 1.48E+00 l 1.39E+00 l 6.05E+02 l 2.76E+02 l FISSION & ACTIVATION PRODUCTS AG-110M CURIES 0.00E+00 0.00E+00 5.80E-04 1.08E-03 AS-76 CURIES 0.00E+00 0.09E+00 2.10E-06 0.00E+00 CO-57 CURIES 0.00E+00 0.00E+00 2.19E-04 7.93E-04 CO-58 CURIES 0.00E+00 2.47E-04 2.56E-02 2.41E-01 CO-60 CURIES 0.00E+00 0.00E+00 1.38E-02 9.68E-03 CR-51 CURIES 0.00E+00 0.00E+00 9.94E-05 2.54E-03 CS-134 CURIES 0.00E+00 0.00E+00 3.23E-05 0.00E+00 CS-137 CURIES 0.00E+00 0.00E+00 8.54E-04 1.07E-04 FE-55 CURIES 7.92E-09 1.05E-08 6.45E-03 1.18E-02 FE-59 CURIES 0.00E+00 0.00E+00 0.00E+00 3.89E-04 I-131 CURIES 0.00E+00 0.00E+00 3.39E-06 0.00E+00 j
I-133 CURIES 2.67E-03 1.88E-02 1.60E-05 0.00E+00 MN-54 CURIES 0.00E+00 0.00E+00 4.08E-04 2.99E-04 NA-24 CURIES 0.00E+00 0.00E+00 7.91E-05 0.00E+00 NB-95 CURIES 0.00E+00 0.00E+00 3.70E-05 2.16E-04 NB-97 CURIES 0.00E+00 0.00E+00 2.07E-04 2.30E-04 PR-144 CURIES 0.00E+00 0.00E+00 7.82E-05 0.00E+00 SB-122 CURIES 0.00E+00 0.00E+00 2.57E-06 0.00E+00 SB-124 CURIES 0.00E+00 0.00E+00 0.00E+00 3.98E-04 SB-125 CURIES 0.00E+00 0.00E+00 5.40E-03 3.18E-03 SN-113 CURIES 0.00E+00 0.00E+00 5.52E-07 0.00E+00 SR-89 CURIES 1.31E-10 1.02E-10 7.30E-05 2.93E-04 SR-90 CURIES 1.09E-11 4.59E-04 5.36E-06 2.79E-05 SR-92 CURIES 0.00E+00 0.00E+00 2.93E-05 3.90E-05 TC-99M CURIES 0.00E+00 0.00E+00 1.66E-05 0.00E+00 ZN-65 CURIES 0.00E+00 0.00E+00 1.67E-04 4.33E-04 ZR-95 CURIES 0.00E+00 0.00E+00 0.00E+00 4.43E-05 TOTALS l
CURIES l 2.67E-03 l 1.95E-02 l 5.42E-02 l 2.73E-01 l 25
)
TABLE 1-2C*
Jo ph M.
Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1998 Liquid Effluents Unit: Site Starting :
1-Jan-1998 Ending : 30-Jun-1998 l CONTINUOUS. MODE l
BATCH MODE l
NUCLIDE l
UNIT l QUARTER 1 l QUARTER 2 l QUARTER 1 l QUARTER 2 l DISSOLVED AND ENTRAINED GASES AR-41 CURIES 0.00E+00 0.00E+00 1.08E-05 8.31E-06 XE-133 CURIES 0.00E+00 0.00E+00 5.94E-04 4.48E-04 XE-133M CURIES 0.00E+00 0.00E+00 7.85E-06 0.00E+00 XE-135 CURIES 0.00E+00 0.00E+00 1.14E-05 2.22E-06 TOTALS l
CURIES l 0.00E+00 l 0.00E+00 l 6.24E-04 l 4.58E-04 l
)
G-ALPHA l
CURIES l 8.19E-11 l 7.28E-11 l 3.57E-05 l 1.69E-04 l i
I Zeroes in this table' indicate that no radioactivity was present at detectable levels.
See Table 1-5 for typical minimum detectable concentrations.
26
l TABLE 1-2C*
i Joseph M.
Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1998 Liquid Effluents Unit: Site Starting :
1-Jul-1990 Ending : 31-Dec-1998 l
fbbNTkhbbbS Mbbb f
bkTbh Mbbb f
NUCLIDE l
UNIT l QUARTER 3 l QUARTER 4 l QUARTER 3 l QUARTER 4 l l
CURIES l 9.58E+00 l 8.82E+00 l 4.00E+02 l 1.86E+02 l FISSION & ACTIVATION PRODUCTS AG-110M CURIES 0.00E+00 0.00E+00 1.43E-03 2.17E-02 BA-140 CURIES 8.76E-03 0.00E+00 0.00E+00 0.00E+00 CO-57 CURIES 0.00E+00 0.00E+00 2.09E-04 2.58E-04 CO-58 CURIES 1.29E-02 7.65E-04 5.25F 32 5.33E-02 CO-60 CURIES 4.51E-04 1.22E-04 4.512-03 8.87E-03 CR-51 CURIES 5.87E-04 0.00E+00 2.32E-04 3.83E-03 CS-134 CURIES 4.89E-04 1.88E-03 0.00E+00 6.92E-04 CS-137 CURIES 6.72E-04 2.26E-03 4.32E-04 1.52E-03 CS-138 CURIES 9.52E-03 0.00E+00 0.00E+00 0.00E+00 FE-55 CURIES 1.77E-03 1.02E-04 7.54E-03 2.01E-02 FE-59 CURIES 1.01E-04 0.00E+00 9.21E-05 5.54E-04 I-131 CURIES 4.95E-03 1.27E-03 0.00E+00 0.00E+00 I-132 CURIES 1.67E-02 0.00E+00 0.00E+00 9.82E-06 I-133 CURIES 2.67E-01 3.63E-02 4.56E-06 0.00E+00 I-134 CURIES 1.82E-02 0.00E+00 0.00E+00 0.00E+00 I-135 CURIES 2.84E-02 0.00E+00 0.00E+00 0.00E+00 LA-140 CURIES 1.41E-02 0.00E+00 0.00E+00 0.00E+00 MN-54 CURIES 9.77E-03 2.69E-04 9.65E-05 3.31E-04 NA-24 CURIES 4.63E-02 0.00E+00 2.28E-06 0.00E+00 NB-95 CURIES 2.11E-04 2.14E-04 8.53E-05 3.27E-04 NB-97 CURIES 0.00E+00 0.00E+00 2.68E-04 8.17E-05 P:M-149 CURIES 1.59E-02 0.00E+00 0.00E+00 0.00E+00 RH-106 CURIES 5.63E-03 0.00E+00 0.00E+00 0.00E+00 RU-103 CURIES 0.00E+00 0.00E+00 4.41E-06 0.00E+00 RU-106 CURIES 5.63E-03 0.00E+00 0.00E+00 0.00E+00 SB-122 CURIES 0.00E+00 1.20E-04 0.00E+00 1.73E-06 SB-124 CURIES 0.00E+00 0.00E+00 8.39E-04 3.71E-06 SB-125 CURIES 0.00E+00 0.00E+00 1.02E-02 2.10E-03 SN-113 CURIES 0.00E+00 0.00E+00 0.00E+00 8.08E-05 SR-89 CURIES 2.60E-03 6.35E-04 1.05E-04 6.02E-05 SR-90 CURIES 2.75E-05 1.59E-11 6.48E-06 9.59E-06 SR-92 CURIES 0.00E+00 0.00E+00 7.18E-05 6.01E-04 TC-99M CURIES 5.32E-03 0.00E+00 0.00E+00 0.00E+00 27
TABLE 1-2C*
Joseph M.
Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1998 Liquid Effluents Unit: Site Starting :
1-Jul-1998 Ending : 31-Dec-1998 l CONTINUOUS MODE l
BATCH MODE l
NUCLIDE l
UNIT l QUARTER 3 l QUARTER 4 l QUARTER 3 l QUARTER 4 l FISSION & ACTIVATION PRODUCTS
~ TE-132 CURIES 0.00E+00 0.00E+00 0.00E+00 1.54E-05 ZN-65 CURIES 0.00E+00 0.00E+00 1.57E-05 0.00E+00 ZN-69M CURIES 1.52E-02 0.00E+00 0.00E+00 0.00E+00 ZR-95 CURIES 0.00E+00 1.24E-04 2.05E-05 2.32E-04 TOTALS l
CURIES l 4.92E-01 l 4.40E-02 l 7.87E-02 l 1.15E-01 l DISSOLVED AND ENTRAINED GASES AR-41 CURIES 0.00E+00 0.00E+00 1.61E-06 0.00E+00 XE-133 CURIES 1.10E-03 1.58E-04 6.36E-03 2.17E-03 XE-135 CURIES 2.32E-02 1.82E-03 5.30E-06 0.00E+00 l
XE-135M _________.......__. CURIES 1.45E-02 3.54E-03 2.98E-06 0.00E+00 TOTALS l
CURIES l 3.89E-02 l 5.52E-03 l 6.37E-03 l 2.17E-03 l G-ALPHA l
CURIES l 5'14E-11 l 3.50E-11 l 3.69E-05 l 2.46E-05 l Zeroes in this table indicate that no radioactivity was present at detectable levels.
See Table 1-5 for typical minimum detectable concentrations.
i i
l l
i 28
- n...
a 2.6 Radiological Impact The total body and organ doses.for Units 1 and 2'are provided
~
in.the following tables in. order to show conformance with the limits of ODCM 2.1.3 :
Unit-1 1998 Liquid Doses : Table 1-3A Unit 2 1998 Liquid Doses : Table 1-3B l
l 29
i
)
a s
.i TABLE 1-3A Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1998 DOSES TO A MEMBER OF THE PUBLIC DUE TO LIQUID RELEASES Unit: 1 Starting: 01-Jan-1998 Ending: 30-Jun-1998
- Cumulative Doses per Quarter Organ ODCM Units Quarter
% of Quarter
% of Limit 1
ODCM 2
ODCM Limit Limit Bone 5.0 mrem 8.63E-04 1.73E-02 9.54E-03 1.91E-01 Liver 5.0 mrem 2.16E-03 4.32E-02 2.48E-03 4.95E-02 TBody 1.5 mrem 1.93E-03 1.29E-01 4.48E-03 2.99E-01 Thyroid 5.0 mrem 1.86E-03 3.72E-02 5.90E-03 1.18E-01 Kidney 5.0 mrem 1.47E-03 2.93E-02 1.31E-03 2.62E-02 i
Lung 5.0 mrem 1.32E-02 2.64E-01 1.31E-02 2.62E-01 GILLI 5.0 mrem 4.32E-03 8.64E-02 1.17E-02 2.35E-01 Cumulative Doses per Year Organ ODCM Units Year to
% of Limit Ending ODCM Date Limit Bone 10.0 mrem 1.04E-02 1.04E-01 Liver 10.0 mrem 4.64E-03 4.64E-02 TBody 3.0 mrem 6.41E-03 2.14E-01 Thyroid 10.0 mrem 7.76E-03 7.76E-02 Kidney 10.0 mrem 2.78E-03 2.78E-02 Lung 10.0 mrem 2.63E 2.63E-01 GILLI 10.0 mrem 1.61E-02 1.61E-01 i
30
l TABLE 1-3A Joseph M.
Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1998 DOSES TO A MEMBER OF THE PUBLIC DUE TO LIQUID RELEASES Unit: 1 Starting: 01-Jul-1998 Ending: 31-Dec-1998 Cumulative Doses per Quarter Organ ODCM Units Quarter
%.of Quarter
% of Limit 3
ODCM 4
ODCM Limit Limit Bone 5.0 mrem 7.35E-03 1.47E-01 9.66E-03 1.93E-01 Liver 5.0 mrem 7.77E-03 1.55E-01 1.54E-02 3.08E-01 TBody 1.5 mrem 6.68E-03' 4.45E-01 1.13E-02 7.52E-01 Thyroid 5.0 mrem 8.20E-02 1.64E+00 1.37E-02 2.73E-01 Kidney 5.0 mrem 4.82E-03 9.64E-02 5.41E-03 1.08E-01 Lung 5.0 mrem 3.22E-02 6.45E-01 1.11E-02 2.21E-01 GILLI 5.0 mrem 2.67E-02 5.34E-01 1.10E-02 2.20E-01 4
Cumulative Doses per Year Organ ODCM Units Year to
% of Limit Ending ODCM Date Limit Bonn 10.0 mrem 2.74E-02 2.74E-01 Liver 10.0 mrem 2.78E-02 2.78E-01 TBody-3.0 mrem 2.44E-02 8.13E-01 Thyroid 10.0 mrem 1.03E-01 1.03E+00 Kidney 10.0 mrem 1.30E-02 1.30E-01 t"nq 10.0 mrem 6.96E-02 6.96E-01
- . ;I 10.0 mrem 5.38E-02 5.38E-01 I
l l
l 31 v
l t
TABLE 1-3B Joseph M.
Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1998 DOSES TO A MEMBER OF THE PUBLIC DUE TO LIQUID RELEASES Unit: 2 Starting: 01-Jan-1998 Ending: 30-Jun-1998 Cumulative Doses per Quarter Organ ODCM Units Quarter
% of Quarter
% of Limit 1
ODCM 2
ODCM Limit Limit Bone 5.0 mrem 1.74E-03 3.47E-02 1.83E-03 3.67E-02 Liver 5.0 mrem 4.83E-03 9.65E-02 3.02E-03 6.05E-02 TBody 1.5 mrem 4.42E-03 2.95E-01 3.45E-03 2.30E-01 Thyroid 5.0 mrem 3.15E-03 6.30E-02 8.15E-04 1.63E-02 Kidney 5.0 mrem 3.42E-03 6.83E-02 8.61E-04 1.72E-02 Lung 5.0 mrem 1.77E-02 3.55E-01 4.97E-03 9.94E-02 GILLI 5.0 mrem 9.55E-03 1.91E-01 2.29E-02 4.58E-01 1
Cumulative Doses per Year Organ ODCM Units Year to
% of Limit Ending ODCM Date Limit i
Bone 10.0 mrem 3.57E-03 3.57E-02 Liver 10.0 htrem 7.85E-03 7.85E-02 TBody 3.0 mrem 7.87E-03 2.62E-01 Thyroid 10.0 mrem 3.97E-03 3.97E-02 Kidney 10.0 mrem 4.28E-03 4.28E-02 Lung 10.0 mrem 2.27E-02 2.27E-01 GILLI 10.0 mrem 3.25E-02 3.25E-01 32
e TABLE 1-3B Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1998 DOSES TO A MEMBER OF THE PUBLIC DUE TO LIQUID RELEASES Unit: 2 Starting: 01-Jul-1998 Ending: 31-Dec-1998 i
Cumulative Doses per Quarter Organ ODCM Units Quarter
% of Quarter
% of
)
Limit 3
ODCM 4
ODCM Limit Limit-Bons
'5.0 mrem 9.83E-04 1.97E-02 1.97E-03 3.94E-02 Livar 5.0 mrem 1.45E-03 2.90E-02 2.36E-03 4.73E-02 TBody 1.5 mrem 1.29E-93 8.58E-02 1.57E-03 1.05E-01' Thyroid 5.0 mrem 8.10E-04 1.62E-02 9.50E-04 1.90E-02 Kidney 5.0 mrem 8.85E-04 1.77E-02 9.86E-04 1.97E-02 Lung 5.0 mrem 2.04E-02 4.08E-01 3.72E-03 7.44E-02 GILLI 5.0 mrem 5.10E-03 1.02E-01 4.64E-03 9.27E-02 Cumulative Doses per Year Organ ODCM Units Year to
% of Limit Ending ODCM Date Limit Bone 10.0 mrem 6.52E-03 6.52E-02 Livor 10.0 mrem 1.17E-02 1.17E-01 i
TBody 3.0 mrem 1.07E-02 3.57E-01 1
Thyroid 10.0 mrem 5.72E-03 5.72E-02 Kidney 10.0 mrem 6.15E-03 6.15E-02 Lung 10.0 mrem 4.68E-02 4.68E-01
_GILLI 10.0 mrem 4.22E-02 4.22E-01 33
6%=
' fli v
TABLE 1-5
. Joseph M. Farley-Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1998 TYPICAL LIQUID MDC'S ACHIEVED ON COUNTING SYSTEM Nuclide MDC(uCi/ML)
MN-54 3.14E-08 CO-58 4.92E-08 i
FE-59 7.19E-08 CO-60 4.77E-08 ZN-65 8.11E-08 MO-99 1.29E-07 l
I-131 2.53E-08 CS-134 3.51E-08 CS-137 4.28E-08 CE-141 5.41E-08 CE-144 1.95E-07
[
(
l i
34 r
~ l i
t TABLE 1-6A.
Jo cph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1998 Liquid Effluents - Abnormal Release Summary Unit: 1 Starting :
1-Jan-1998 Ending : 30-Jun-1998 LIQUID RELEASES NUMBER OF RELEASES 0
TOTAL TIME FOR ALL RELEASES 0.00 MINUTES MAXIMUM TIMF FOR A RELEASE 0.00 MINUTES AVERAGE TIME FOR A RELEASE 0.00 MINUTES MINIMUM TIME FOR A RELEASE 0.00 MINUTES TOTAL-ACTIVITY FOR ALL RELEASES :
0.00E+00 CURIES 35 l
1 i
TABLE.1-6A Joseph M. Farley. Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1998 Liquid Effluents - Abnormal Release Summary Unit: 1 Starting :
1-Jul-1998 Lending : 31-Dec-1998
........................................a.......................................
l LIQUID RELEASES l
NUMBER OF RELEASES 0
TOTAL TIME FOR ALL RELEASES 0.00 MINUTES MAXIMUM TIME FOR A RELEASE 0.00 MINUTES AVERAGE TIME FOR A RELEASE 0.00 MINUTES I
MINIMUM TIME FOR A RELEASE 0.00 MINUTES TOTAL ACTIVITY FOR ALL RELEASES :
0.00E+00 CURIES I
l l
l l
l '.
l l
I I
I 36
i TABLE 1-6B Joseph M.
Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1998 Liquid Effluents - Abnormal Release Summary Unit: 2 Starting :
1-Jan-1998 Ending : 30-Jun-1998 l
l l
LIQUID RELEASES l
NUMBER OF RELEASES 0
TOTAL TIME FOR ALL RELEASES 0.00 MINUTES MAXIMUM TIME FOR A RELEASE 0.00 MINUTES l
AVERAGE TIME FOR A RELEASE 0.00 MINUTES MINIMUM TIME FOR A RELEASE 0.00 MINUTES TOTAL ACTIVITY FOR ALL RELEASES :
0.00E+00 CURIES m
1 I
l 37 l
1
i l
TABLE 1-6B Jonoph M.
Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1998 Liquid Effluents - Abnormal Release Summary
)
Unit: 2 i
Starting :
1-Jul-1998 Ending : 31-Dec-1998 LIQUID RELEASES NUMBER OF RELEASES 0
TOTAL TIME FOR ALL RELEASES 0.00 MINUTES MAXIMUM TIME FOR A RELEASE 0.00 MINUTES j
AVERAGE TIME FOR A RELEASE 0.00 MINUTES MINIMUM TIME FOR A RELEASE 0.00 MINUTES TOTAL ACTIVITY FOR ALL RELEASES :
O.00E+00 CURIES l
I i
1 i
i 38
3.0 GASEOUS EFFLUENTS This section contains applicable.ODCM limits for gaseous effluents as well as the quantities of radioactive gaseous effluents released during 1998. These quantities are summarized on a quarterly basis and include any unplanned releases. Tabulations are provided of the offsite air doses calculated in accordance with ODCM 3.4.2 to show conformance with the limits of ODCM 3.1.3, and the offsite organ doses to a member of the public calculated in accordance with ODCM 3.4.3 to show conformance with ODCM 3.1.4.
3.1 ODCM Limits In accordance with Technical Specifications 6.8.3.e(v) and 6.8.3.e(viii), the air dose due to noble gases released in gaseous effluents, from each reactor unit, to areas at and beyond the SITE BOUNDARY (see ODCM Figure 10-1) shall be limited to the following:
- a. During any calendar quarter: Less than or equal to 5 mrad for gamma radiation and less than or equal to 10 mrad for beta radiation, and
- b. During any calendar year: Less than or equal to 10 mrad for gamma radiation and less than or equal to 20 mrad for beta radiation.
In accordance with Technical Specifications 6.8.3.e(v) and 6.8.3.e(ix), the dose to a NEMbER OF THE PUBLIC from I-131, I-133, tritium, and all radionuclides in particulate form with half-lives greater than 8 days in gaseous effluents released, from each reactor unit, to areas at and beyond the SITE BOUNDARY (see ODCM Figure 10-1) shall be limited to the following:
- a. During any calendar quarter: Less than or equal to 7.5 mrem to any organ, and
- b. During any calendar year: Less than or equal to 15 mrem to any organ.
3.2 Measurements and Approximation of Total Radioactivity The following noble gases are considered in evaluating gaseous effluents:
KR-87 XE-133 KR-88 XE-135 XE-133M XE-138 39
r The following rcdioiodines cnd radioactiva materialo in particulato form cro rpecifically considered in evaluating gaseous effluents:
MN-54 MO-99 FE-59 I+131 CO-58 CS-134 CO-60 CS-137 ZN-65 CE-141 SR-89 CE-144 SR-90 H-3 Periodic grab samples from plant effluent streams are analyzed by a computerized pulse height analyzer system utilizing high itsolution germanium detectors. Samples are obtained and analyzed in accordance with ODCM Table 3-3.
Isotopic values thus obtained l
are used for release rate calculations as specified in ODCM 3.4.2 and ODCM 3.4.3. Only those nuclides which are detected are l
used in calculations. For radioiodines and particulates, in addition to the nuclides listed above other nuclides with half-lives greater than 8 days which are identified are also considered.
Continuous Releases: Continuous sampling is performed on the continuous releases points (i.e. the Plant Vent Stack, Containment Purge, and the Turbine Building Vent). Particulate material is collected by filtration. Periodically these filters are removed and analyzed on the pulse height analyzer to identify and quantify radioactive materials collected on the filters. Particulate filters are then analyzed for gross alpha and strontium as required. Gross alpha determinations are made using a 2 pi gas flow proportional J
counter. All Sr-69 and SR-90 samples are sent offsite to the i
Georgia Power Environmental Laboratory for analysis.
Batch Releases: The processing of batch type releases (from J
Containment or Waste Gas Decay Tanks) is analogous to continuous releases, except that the release is not commenced until samples have been obtained and analyzed.
The maximum errors associated with monitor readings, sample flow, vent flow, sample collection, monitor calibration and laboratory procedure are collectively estimated to be:
Fission and Activation Gases Iodine Particulates Tritium 75%
60%
50%
45%
The average error associated with counting is estimated to be:
Fission and Activation Gases Iodine Particulates Tritium 19%
28%
20%
8%
40
3.3 Abnormal kalenses There were 11 abnormal releases on Unit 1 during the first half of 1998 and 20 abnormal releases on Unit i during the second half of 1998. All but one of one these releases were due to
. releases via the Turbine Driven Auxiliary Feed Pump end the Atmospheric Relief Valves while a primary to secondary leak existed on Unit 1. The remaining abnormal release was due to a leaking KR-85 gas source which resulted in about 0.06 Curies of KR-85 being inadvertently released, this release is documented in Occurrence Report 98433.1. No limits were exceeded as a result of any of these abnormal releases.
There were no abnormal releases on Unit 2 during 1998.
Abnormal r dease information for Units 1 and 2 is summarized in the follot.uc tables:
Unit 1 1998 Gaseous Abnormal Releases : Table 2-8A Unit 2 1998 Gaseous Abnormal Releases : Table 2-8B 3.4 Batch Releases Batch release information for Units 1 and 2 is summarized in the following tables:
Unit 1 1998 Gaseous Batch Releases : Table 2-6A Unit 2 1998 Gaseous Batch Releases : Table 2-6B 1
i 41
TABLE 2-8A Joseph M.
Faricy Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1998 Gaseous Effluents - Abnormal Release Summary Unit: 1 Starting :
1-Jan-1998 Ending : 30-Jun-1998 GASEOUS RELEASES NUMBER OF RELEASES-11 TOTAL TIME FOR ALL RELEASES 3828.00 MINUTES MAXIMUM TIME FOR A RELEASE 3507.00 MINUTES AVERAGE TIME FOR A RELEASE 348.00 MINUTES MINIMUM TIME FOR A RELEASE 2.00 MINUTES TOTAL' ACTIVITY'FOR ALL RELEASES :
1.74E-03 CURIES i
42
TABLE 2-8A Jo:cph M.
Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1998 i
Gaseous Effluents - Abnormal Release Summary I
Unit: 1 Starting :
1-Jul-1998 Ending : 31-Dec-1998 1
I GASEOUS RELEASES NUMBER OF RELEASES 20 TOTAL TIME FOR ALL RELEASES 2166.00 MINUTES MAXIMUM TIME FOR A RELEASE 839.00 MINUTES AVERAGE TIME FOR A RELEASE 108.30 MINUTES MINIMUM TIME FOR A RELEASE 1.00 MINUTES TOTAL ACTIVITY FOR ALL RELEASES :
2.57E-01 CURIES 43
m 4
TABLE 2-8B Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1998 Gaseous Effluents - Abnormal Release Summary Unit: 2 Starting :
1-Jan-1998 Ending~: 30-Jun-1998 GASEOUS RELEASES NUMBER OF RELEASES 0
TOTAL TIME-FOR ALL RELEASES 0.00 MINUTES MAXIMUM TIME FOR A RELEASE 0.00 MINUTES AVERAGE TIME FOR A RELEASE 0.00 MINUTES MINIMUM TIME FOR A RELEASE 0.00 MINUTES TOTAL ACTIVITY FOR ALL RELEASES :
0.00E+00 CURIES 44
i i
TABLE 2-8B Joreph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1998 i
Gaseous Effluents - Abnormal Release Summary Unit: 2 Starting :
1-Jul-1b98 Ending : 31-Dec-1998 GASEOUS RELEASES NUMBER OF RELEASES 0
TOTAL TIME FOR ALL RELEASES 0.00 MINUTES i
MAXIMUM TIME FOR A RELEASE 0.00 MINUTES AVERAGE TIME FOR A RELEASE 0.00 MINUTES MINIMUM TIME FOR A RELEASE 0.00 MINUTES TOTAL ACTIVITY FOR ALL RELEASES :
0.00E+00 CURIES 45
TABLE 2-6A Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1998 Gaseous Effluents - Batch Release Summary I
Unit: 1 Starting :
1-Jan-1998 Ending : 30-Jun-1998 GASEOUS RELEASES NUMBER OF BATCH RELEASES 0
TOTAL TIME PERIOD FOR BATCH RELEASES 0.00 MINUTES MAXIMUM TIME PERIOD FOR A BATCH RELEASE :
0.00 MINUTES AVERAGE TIME PERIOD FOR BATCH RELEASES 0.00 MINUTES MINIMUM TIME FOR A BATCH RELEASE 0.00 MINUTES I
)
l 4
I l
1 l
1 46 l
m
rl' TABLE 2-6A Joseph M.
Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1998 Gaseous Effluents - Batch Release Summary Unit: 1 i
i Starting :
1-Jul-1998 Ending : 31-Dec-1998 l
GASEOUS RELEASES NUMBER OF BATCH RELEASES 32 TOTAL TIME PERIOD FOR BATCH RELEASES 11180.00 MINUTES MAXIMUM TIME PERIOD.FOR A BATCH RELEASE :
585.00 MINUTES AVERAGE TIME PERIOD FOR BATCH RELEASES 349.38 MINUTES L
MINIMUM. TIME FOR A BATCH RELEASE 69.00 MINUTES I
l
\\
l l
47 l
{
i
\\
l TABLE 2-6B Joseph M.
Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1998 Gaseous Effluents - Batch Release Summary
)
Unit: 2 Starting :
1-Jan-1998 Ending : 30-Jun-1998 1
GASEOUS RELEASES NUMBER OF BATCH RELEASES 6
TOTAL TIME PERIOD FOR BATCH RELEASES 2823.00 MINUTES MAXIMUM TIME PERIOD FOR A BATCH RELEASE :
839.00 MINUTES AVERAGE TIME PERIOD FOR BATCH RELEASES 470.50 MINUTES MINIMUM TIME FOR A BATCH RELEASE 306.00 MINUTES l
J i
48
r.
4 TABLE 2-6B Joseph M.
Farley Nuclear Plant
{
ANNUAL RADIOACTIVE. EFFLUENT RELEASE REPORT - 1998 l
Gaseous Effluents ~- Batch Release Summary Unit: 2 Starting :
1-Jul-1998 Ending : 31-Dec-1998
- GASEOUS RELEASES NUMBER OF-BATCH RELEASES 0
TOTAL TIME PERIOD FOR BATCH RELEASES 0.00 MINUTES MAXIMUM TIME PERIOD FOR A BATCH RELEASE :
0.00 MINUTES
' AVERAGE TIME PERIOD FOR BATCH RELEASES 0.00 MINUTES MINIMUM TIME FOR A BATCH RELEASE 0.00 MINUTES I
l l
i l
f:
49 i.
3.5 Release Summaries This section contains the summaries of all radioactive gaseous effluents released for Units 1 and 2 during 1998. Typical gaseous Miniumum Detectable Concentrations (MDC'S) for analyses are in Table 2-7 of this section. Regulatory Guide 1.21 Table 1A is found in this report as Tables 2-1A, 2-1B, and 2-1C. Regulatory Guide 1.21 Table 1B is found in this report as Tables 2-2A, 2-2B, and 2-2C. Regulatory Guide 1.21 Table 1C is found in this report as Tables 2-3A, 2-3B, and 2-3C.
3.5.1 Gaseous Effluents - Summation of All Releases The summations of all gaseous effluent releases are contained in the following tables:
Unit 1 1998 Summati'n of All Releases : Table 2-1A Unit 2 1998 Summation of All Releases : Table 2-1B Site 1998 Summation of All Releases : Table 2-1C 4
W 50
r TABLE 2-1A l
Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1998 Gaseous Effluents - Summation of All Releases L
Unit: 1 l
Starting :
1-Jan-1998
'Ending : 30 Jun-1998 TYPE OF EFFLUENT UNITS QUARTER 1 QUARTER 2 EST. TOT ERROR %
1 I
A. FISSION & ACTIVATION PRODUCTS
- 1. TOTAL RELEASE CURIES 7.72E+01 2.74E+01 9.40E+01
.......v...................__...............................................
- 2. AVERAGE RELEASE RATE FOR PERIOD uCi/Sec 9.93E+00 3.49E+00
- 3. PERCENT OF APPLICABLE LIMIT B. RADIOIODINES
- 1. TOT 7.L IODINE-131 CURIES 3.92E-07 0.00E+00 8.80E+01
- 2. AVFRAGE RELEASE RATE FOR PERIOD uCi/Sec 5.05E-08 0.00E+00
- 3. PERCENT OF APPLICABLE LIMIT C..PARTICULATES 1.
PARTICULATES(HALF-LIVES >8 DAYS)
CURIES 9.19E-06 6.31E.07 7.00E+01
- 2. AVERAGE RELEASE RATE FOR PERIOD uCi/Sec 1.18E-06 8.03E-08
- 3. PERCENT OF APPLICABLE LIMIT
- 4. GROSS ALPHA RADIOACTIVITY CURIES 1.51E-07 4.27E-07 D. TRITIUM
- 1. TOTAL RELEASE CURIES 3.69E+00 2.41E+00 5.30E+01
- 2. AVERAGE RELEASE RATE FOR PERIOD uCi/Sec 4.75E-01 3.06E-01
- 3. PERCENT OF APPLICABLE LIMIT
-Applicable limits are expressed-in terms of dose.
See Tables 2-4A, 2-4B, 2-5A, and 2-5B of this report.
51 I
1
4 TABLE 2-1A Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1998 Gaseous Effluents - Summation of All Releases Unit: 1 Starting :
1-Jul-1998 Ending : 31-Dec-1998 TYPE OF EFFLUENT UNITS QUARTER 3 QUARTER 4 EST. TOT ERROR %
A. FISSION & ACTIVATION PRODUCTS
- 1. TOTAL RELEASE CURIES 3.27E+01 6.21E+00 9.40E+01
- 2. AVERAGE RELEASE RATE FOR PERIOD uCi/Sec 4.12E+00 7.81E-01 3.
PERCENT OF APPLICABLE LIMIT B. RADIOIODINES
- 1. TOTAL IOD1NE-131 CURIES 2.77E-04 3.25E-04 8.80E+01
- 2. AVERAGE RELEASE RATE FOR PERIOD uCi/Sec 3.48E-05 4.09E-05
- 3. PERCENT OF APPLICABLE LIMIT C. PARTICULATES 1.
PARTICULATES(HALF-LIVES >8 DAYS)
CURIES 1.16E-03 1.92E-02 7.00E+01
- 2. AVERAGE RELEASE RATE FOR PERIOD uCi/Sec 1.46E-04 2.41E-03 3.
PERCENT OF APPLICABLE LIMIT 4.' GROSS ALPHA RADIOACTIVITY CURIES 2.05E-07 5.99E-08 D. TRITIUM l
- 1. TOTAL RELEASE CURIES 3.36E+00 1.22E+01 5.30E+01
- 2. AVERAGE RELEASE RATE FOR PERIOD uCi/Sec 4.22E-01 1.54E+00 l
- 3. PERCENT OF APPLICABLE LIMIT 1
Applicable limits are expressed in terms of dose.
See Tables 2-4A, 2 4B, 2-5A, and 2-5B of this report.
52
l TABLE 2-1B Joreph M. Farley Nuclear Plant ANNUAL' RADIOACTIVE EFFLUENT RELEASE REPORT - 1998
]
Gaseous Effluents - Summation of All Releases Unit: 2 Starting :
1-Jan-1998 Ending : 30-Jun-1998 TYPE OF EFFLUENT UNITS QUARTER 1 QUARTER 2 EST. TOT ERROR %
A. FISSION & ACTIVATION PRODUCTS
- 1. TOTAL RELEASE CURIES 9.89E+00 6.34E+00 9.40E+01
- 2. AVERAGE RELEASE RATE FOR PERIOD uCi/Sec 1.27E+00 8.06E-01
- 3. PERCENT OF APPLICABLE LIMIT B. RADIOIODINES
- 1. TOTAL IODINE-131 CURIES 2.45E-06 1.33E-06 8.80E+01
- 2. AVERAGE RELEASE RATE FOR PERIOD uCi/Sec 3.15E-07 1.69E-07
- 3. PERCENT OF APPLICABLE LIMIT C. PARTICULATES i
1.
PARTICULATES(HALF-LIVES >8 DAYS)
CURIES 0.00E+00 5.07E-06 7.00E+01 I
- 2. AVERAGE RELEASE RATE FOR PERIOD uCi/Sec 0.00E+00 6.45E-07
- 3. PERCENT OF APPLICABLE LIMIT
- 4. GROSS ALPHA RADIOACTIVITY CURIES 7.11E-08 9.89E-08 D. TRITIUM
- 1. TOTAL RELEASE CURIES 1.03E+01 3.29E+00 5.30E+01
- 2. AVERAGE RELEASE RATE FOR PERIOD uCi/Sec 1.32E+00 4.19E-01
- 3. PERCENT OF APPLICABLE LIMIT Applicable limits are expressed in terms of dose.
See Tables 2-4A, 2-4B, 2-5A, and 2-5B of this report, i
2 53
4 4
TABLE 2-1B Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1998 Gaseous Effluents - Summation of All Releases Unit: 2 Starting :
1-Jul-1998 Ending : 31-Dec-1998
)
TYPE OF EFFLUENT UNITS QUARTER 3 QUARTER 4 EST. TOT ERROR %
A. FISSION & ACTIVATION PRODUCTS
- 1. TOTAL RELEASE CURIES 8.37E+00 1.84E+01 9.40E+01
- 2. AVERAGE RELEASE RATE FOR PERIOD uCi/Sec 1.05E+00 2.32E+00
- 3. PERCENT OF APPLICABLE LIMIT 1
B. RADIOIODINES
- 1. TOTAL IODINE-131 CURIES 0.00E+00 0.00E+00 8.80E+01
- 2. AVERAGE RELEASE RATE FOR PERIOD uCi/Sec 0.00E+00 0.00E+00
- 3. PERCENT OF APPLICABLE. LIMIT k
C. PARTICULATES j
1.
PARTICULATES(HALF-LIVES >8 DAYS)- CURIES 3.97E-08 5.81E-09 7.00E+01 l
i
- 2. AVERAGE RELEASE RATE FOR PERIOD uCi/Sec 4.99E-09 7.30E-10
- 3. PERCENT OF APPLICABLE LIMIT i
- 4. GR"3S ALPHA RADIOACTIVITY CURIES 7.05E-08 1.23E-07 I
D. TRITIUM
- 1. TOTAL RELEASE CURIES 2.86E+00 1.54E+01 5.30E+01
- 2. AVERAGE RELEASE RATE FOR PERIOD uCi/Sec 3.60E-01 1.94E+00 3.
PERCENT OF APPLICABLE LIMIT Applicable limits are expressed in terms of dose.
See Tables 2-4A, 2-4B, 2-5A, and 2-5B of this report.
54
TABLE 2-1C Jomoph M.
Farley. Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1998 Gaseous Effluents - Summation of All Releases Unit: Site Starting :
1-Jan-1998 Ending : 30-Jun-1998 TYPE OF EFFLUENT UNITS.
QUARTER 1 QUARTER 2 EST. TOT ERROR %
A. FISSION & ACTIVATION PRODUCTS
- 1. TOTAL RELEASE CURIES 8.71E+01 3.37E+01 9.40E+01
)
- 2. AVERAGE RELEASE RATE.FOR PERIOD _uCi/Sec 1.12E+01 4.29E+00-
- 3. PERCENT OF APPLICABLE LIMIT B. RADIOIODINES
- 1. TOTAL IODINE-131 CURIES 2.84E-06 1.33E-06 8.80E+01 2~.
AVERAGE RELEASE RATE FOR PERIOD uCi/Sec 3.65E-07 1.69E-07
- 3. PERCENT OF APPLICABLE LIMIT C. PARTICULATES 1.
PARTICULATES(HALF-LIVES >8 DAYS)
CURIES 9.19E-06 5.70E-06 7.00E+01
-2. AVERAGE RELEASE RATE FOR PERIOD uCi/Sec 1.18E-06 7.25E-07 I
1
- 3. PERCENT OF APPLICABLE LIMIT l
- 4. GROSS ALPHA RADIOACTIVITY CURIES 2.22E-07 5.26E-07 D. TRITIUM
- 1. TOTAL RELEASE CURIES 1.40E+01 5.70E+00 5.30E+01
- 2. AVERAGE RELEASE RATE FOR PERIOD uCi/Sec 1.80E+00 7.25E-01 3.
PERCENT OF APPLICABLE LIMIT Applicable limits are expressed in terms of dose.
See Tables 2-4A, 2-4B, 2-5A, and 2-5B of this report.
55
1 i
I
~
l l
TABLE 2-1C Joseph M.
Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1998 Gaseous Effluents - Summation of All Releases Unit: Site Starting :
1-Jul-1998 Ending : 31-Dec-1998 TYPE OF EFFLUENT UNITS QUARTER 3 QUARTER 4 EST. TOT ERROR %
A.
FISSION & ACTIVATION PRODUCTS
- 1. TOTAL RELEASE CURIES 4.11E+01 2.46E+01 9.40E+01
- 2. AVERAGE RELEASE RATE FOR PERIOD uCi/Sec 5.17E+00 3.10E+00 1
- 3. PERCENT OF APPLICABLE LIMIT i
i B. RADIOIODINES
- 1. TOTAL IODINE-131 CURIES 2.77E-04 3.25E-04 8.80E+01 l
- 2. AVERAGE RELEASE RATE FOR PERIOD uCi/Sec 3.48E-05 4.09E-05
- 3. PERCENT OF APPLICABLE LIMIT C.
PARTICULATES 1
1.
PARTICULATES(HALF-LIVES >8 DAYS)
CURIES 1.16E-03 1.92E-02 7.00E+01
- 2. AVERAGE RELEASE RATE FOR PERIOD uCi/Sec 1.46E-04 2.41E-03
- 3. PERCENT OF APPLICABLE LIMIT
- 4. GROSS ALPHA RADIOACTIVITY CURIES 2.76E-07 1.82E-07 D. TRITIUM
- 1. TOTAL RELEASE CURIES 6.22E+00 2.76E+01 5.30E+01
- 2. AVERAGE RELEASE RATE FOR PERIOD uCi/Sec 7.82E-01 3.47E+00
- 3. PERCENT OF APPLICABLE LIMIT Applicable limits are expressed in terms of dose.
See Tables o
2-4A, 2-4B, 2-5A, and 2-5B of this report.
56
l
(
\\
3.5.2 G2ccous Effluents - Mixtd Moda_Relea2cp.
The summaries of all-gaseous effluent mixed mode
. releases (includes listing by nuclide) are contained in the following tables :
Unit 1 1998 Mixed Mode' Summary : Table 2-2A Unit 2 1998 Mixed Mode Summary :. Table 2-2B Site 1998 Mixed Mode Summary : Table 2-2C i
I 57
r-TABLE 2-2A*
Joseph M._Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1998 Gaseous Effluents-Mixed-Mode Level Releases Unit: 1 Starting :
1-Jan-1998 Ending : 30-Jun-1998 l
l l
CONTINUOUS MODE l
BATCH MODE l
NUCLIDES RELEASED l
UNIT l QUARTER 1 l QUARTER 2 l QUARTER 1 l QUARTER 2 l FISSION GASES AR-41 CURIES 7.26E+01 1.57E+01 0.00E+00 0.00E+00 XE-135 CURIES 1.33E+00 7.47E+00 0.00E+00 0.00E+00 XE-133 CURIES 3.23E+00 4.20E+00 0.00E+00-0.00E+00 TOTAL FOR PERIOD l
CURIES l 7.72E+01 j 2.74E+01 l 0.00E+00 l 0.00E+00 l IODINES I-131 l
CURIES l 3.92E-07 l 0.00E+00 l 0.00E+00 l 0.00E+00 l TOTAL FOR PERIOD l
CURIES l 3.92E-07 l 0.00E+00 j 0.00E+00 l 0.00E+00 l PARTICULATES SR-89 CURIES 3.17E-07 2.42E-08 0.00E+00 0.00E+00 CO-58 CURIES 0.00E+00 5.90E-07 0.00E+00 0.00E+00 SR-90 CURIES 0.00E+00 1.67E-08 0.00E+00 0.00E+00 TOTAL FOR PERIOD l
CURIES l 3.17E-07 l 6.31E-07 j'O.00E+00 l 0.00E+00 l H-3 CURIES 3.69E+00 2.41E+00 0.00E+00 0.00E+00 G-ALPHA CURIES 1.51E-07 4.27E-07 0.00E+00 0.00E+00 Zeroes in this table indicate that no radioactivity was present at detectable levels.
See Table 2-7 for typical minimum detectable concentrations.
l 58
?
j TABLE 2-2A*
Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1998 Gaseous Effluents-Mixed-Mode Level Releases i
Unit: 1 Starting :
1-Jul-1998 Ending : 31-Dec-1998-l CONTINUOUS MODE l
BATCH MODE l
NUCLIDES RELEASED l
UNIT-l QUARTER 3 l QUARTER 4 l QUARTER 3 l QUARTER 4 l FISSION GASES AR-41 CURIES ~
1.22E+01 3.11E+00 8.02E-03 0.00E+00 KR-85M CURIES 0.00E+00 0.00E+00 1.57E-03 0.00E+00 XE-135 CURIES 3.05E+00 1.17E+00 3.01E-02 2.83E-C2 XE-133M CURIES 0.00E+00 0.00E+00 2.16E-02 3.15E-02 XE-133 CURIES 1.47E+01 5.80E-02 1.86E+00 1.51E+00 XE-131M CURIES 0.00E+00 0.00E+00 1.61E-02 8.29E-03 KR-85 CURIES 0.00E+00 0.00E+00 3.23E-01 3.20E-02 TOTAL FOR PERIOD l
CURIES l 2.99E+01'j 4.34E+00 l 2.26E+00 l 1.61E+00 l IODINES I-132 CUE 7"9 0.00E+00 0.00E+00 4.63E-08 4.68E-07
'I-133 CU' 0.00E+00 1.55E-06 9.22E-08 1.40E-06 I-131-CL 0.00E+00 7.20E-05 1.94E-06 6.91E-06 TOTAL FOR PERIOD l
CUR 1ES l 0.00E+00 l 7.35E-05 l 2.08E-06 l 8.78E-06 l
)
1 I
Zeroes in this table indicate that no radioactivity was present at detectable levels.
See Table 2-7 for typical minimum detectable concentrations.
59
TABLE 2-2A*
Jo:cph M.
Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1998 Gaseous Effluents-Mixed-Mode Level Releases Unit: 1 Starting :
1-Jul-1998 Ending : 31-Dec-1998 l
CONTINUOUS MODE l
BATCH MODE l
NUCLIDES RELEASED l
UNIT
'l QUARTER 3 l QUARTER 4 l QUARTER 3 l QUARTER 4 l PARTICULATES CR-51 CURIES 0.00E+00 4.04E-06 0.00E+00 0.00E+00 NB-95 CURIES 0.00E+00 6.80E-07
-0.00E+00 0.00E+00 SR-89 CURIES 1.1S5-07 1.66E-07 0.00E+00 0.00E+00 CO-58 CURIES 0.00E+00 5.35E-06 9.53E-09 0.00E+00 Y-88 CURIES 0.00E+00 0.00E+00 3.57E-05 0.00E+00 SN-113 CURIES 0.00E&OO 0.00E+00 1.38E-07 5.28E-08 CO-60 CURIES 0.00E+00 5.75E-07 0.00E+00 0.00E+00 SR-90 CURIES 1.19E-09 0.00E+00 0.00E+00 0.00E+00
-TOTAL FOR PERIOD l
CURIES l 1.17E-07 l 1.08E-05 l 3.59E-05 l 5.28E-08 l H-3 CURIES 3.11E+00 1.22E+01 0.00E+00 0.00E+00 G-ALPHA.
CURIES 2.05E-07 5.99E-08 0.00E+00 0.00E+00 Zeroes in this table indicate that no radioactivity was present at detectable levels.
See Table 2-7 for typical minimum detectable concentrations.
I 60
)
1
F TABLE 2-2B*
Joseph M.
Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1998 Gaseous Effluents-Mixed-Mode Level Releases Unit: 2 Starting :
1-Jan-1998 Ending : 30-Jun-1998 l
CONTINUOUS MODE l
BATCH MODE l
NUCLIDES RELEASED l
UNIT l QUARTER 1 l QUARTER 2 l QUARTER 1 l QUARTER 2 l FISSION GASES AR-41 CURIES 9.44E+00 5.47E+00 0.00E+00 0.00E+00 XE-135 CURIES 2.24E-01 8.38E-01 0.00E+00 0.00E+00 XE-133 CURIES-2.27E-01 0.00E+00 7.86E-05 2.52E-02 TOTAL FOR PERIOD l
CURIES l 9.89E+00 l 6.31E+00 l 7.86E-05 l 2.52E-02 l IODINES I-133 CURIES 2.86E-05 0.00E+00 0.00E+00 0.00E+00 I-131 CURIES 2.45E-06 1.30E-06 0.00E+00 2.26E-08 TOTAL FOR PERIOD l
CURIES l 3.11E-05 l 1.30E-06 l 0.00E+00 l 2.26E-08 l PARTICULATES CO-58 CURIES 0.00E+00 4.78E-06 0.00E+00 2.59E-07 CO-60 CURIES 0.00E+00 0.00E+00 0.00E+00 1.97E-08 SR-90 CURIES 0.00E+00 5.75E-09 0.00E+00 0.00E+00 TOTAL FOR PERIOD l
CURIES l 0.00E+00 l 4.79E-06 l 0.00E+00 l 2.79E-07 l H-3 CURIES 1.03E+01 3.29E+00 0.00E+00 0.00E+00 G-ALPHA CURIES 7.11E-08 9.89E-08 0.00E+00 0.00E+00 Zeroes in this table indicate that no radioactivity was present at detectable levels.
See Table 2-7 for typical minimum detectable concentrations.
61
TABLE 2-2B*
Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1998 Gaseous Effluents-Mixed-Mode Level Releases Unit: 2 Starting :
1-Jul-1998 Ending : 31-Dec-1998 l
CONTINUOUS MODE l
BATCH MODE l
NUCLIDES RELEASED l
UNIT l QUARTER 3 l QUARTER 4 l QUARTER 3 l QUARTER 4 l FISSION GASES AR-41 CURIES 7.69E+00 1.84E+01 0.00E+00 0.00E+00 XE-135 CURIES 2.56E-01 0.00E+00 0.00E+00 0.00E+00 XE-133 CURIES 4.20E-01 0.00E+00 0.00E+00 0.00E+00 TOTAL FOR PERIOD l
CURIES l 8.37E+00 l 1.84E+01 l 0.00E+00 l 0.00E+00 l IODINES TOTAL FOR PERIOD l
CURIES l 0.00E+00 l-0.00E+00 l 0.00E+00 l 0.00E+00 l PARTICULATES SR-89 CURIES 8.81E-09 5.81E-09 0.00E+00 0.00E+00 SR CURIES 6.05E-11 8.33E-17 0.00E+00 0.00E+00 l
1 TOTAL FOR PERIOD l
CURIES l 8.87E-09 l 5.81E-09 l 0.00E+00 l 0.00E+00 l i
H-3 CURIES 2.86E+00 1.54E+01 0.00E+00 0.00E+00 G-ALPHA CURIES 7.05E-08 1.23E-07 0.00E+00 0.00E+00 Zeroes in this table indicate that no radioactivity was present at detectable levels.
See Table 2-7 for typical minimum detectable concentrations.
62
D TABLE 2-2C*
l Joseph M.
Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1998 Gaseous Effluents-Mixed-Mode Level Releases Unit: Site Starting :- 1-Jan-1998 Ending : 30-Jun-1998 l
CONTINUOUS MODE l
BATCH MODE l
NUCLIDES RELEASED l
UNIT l QUARTER 1 l QUARTER 2 l QUARTER 1 l QUARTER 2 l FISSION GASES AR-41 CURIES 8.21E+01-2.12E+01 0.00E+00 0.00E+00 XE-135 CURIES 1.56E+00 8.30E+00 0.00E+00 0.00E+00 XE-133 CURIES 3.46E+00 4.20E+00 7.86E-05 2.52E-02 TOTAL FOR PERIOD l
CURIES l 8.71E+01 l 3.37E+01 l 7.86E-05 l 2.52E-02 l IODINES I-133 CURIES 2.86E-05 0.00E+00 0.00E+00 0.00E+00 I-131 CURIES 2.84E-06 1.30E-06 0.00E+00 2.26E-08 TOTAL FOR PERIOD l
CURIES l 3.15E-05 l 1.30E-06 l 0.00E+00 l 2.26E-08 l PARTICULATES SR-89 CURIES 3.17E-07 2.42E-08 0.00E+00 0.00E+00 CO-58 CURIES 0.00E+00 5.37E-06 0.00E+00 2.59E-07 CO-60 CURIES 0.00E+00 0.00E+00 0.00E+00 1.97E-08 SR-90 CURIES 0.00E+00 2.24E-08 0.00E+00 0.00E+00 TOTAL FOR PERIOD l
CURIES l'3.17E-07 l 5.42E-06 l 0.00E+00 l 2.79E-07 l H-3 CURIES 1.40E+01 5.70E+00 0.00E+00 0.00E+00 G-ALPHA CURIES 2.22E-07 5.26E-07 0.00E+00 0.00E+00 Zeroes in this table indicate that no radioactivity was present at detectable levels.
See Table 2-7 for typical minimum detectable concentrations.
63
7 TABLE 2-2C#
Joseph M.
Parley-Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1998 Gaseous Effluents-Mixed-Mode Level Releases Unit: Site Starting :
1-Jul-1998 Ending : 31-Dec-1998 l
CONTINUOUS MODE l
BATCH MODE l
NUCLIDES RELEASED l
UNIT l QUARTER 3 l QUARTER 4 l QUARTER 3 l QUARTER 4 l FISSION GASES AR-41 CURIES 1.98E+01 2.16E+01 8.02E-03 0.00E+00 KR-85M CURIES 0.00E+00 0.00E+00 1.57E-03 0.00E+00 XE-135 C'URIES 3.30E+00 1.17E+00 3.01E-02 2.83E-02 XE-133M CURIES 0.00E+00 0.00E+00 2.16E-02 3.15E-02 XE-133 CURIES 1.51E+01 5.80E-02 1.86E+00 1.51E+00 XE-131M CURIES 0.00E+00 0.00E+00 1.61E-02 8.29E-03 KR-85 CURIES 0.00E+00 0.00E+00 3.23E-01 3.20E-02 TOTAL FOR PERIOD l
CURIES l 3.82E+01 l 2.28E+01 l 2.26E+00 l 1.61E+00 l IODINES I-132 CURIES 0.00E+00 0.00E+00 4.63E-08 4.68E-07 I-133 CURIES 0.00E+00 1.55E-06 9.22E-08 1.40E-06 I-131 CURIES 0.00E+00 7.20E-05 1.94E-06 6.91E-06 TOTAL FOR PERIOD l
CUEIES l 0.00E+00 l 7.35E-05 l 2.08E-06 l 8.78E-06 l 1
PARTICULATES 3
CR-51 CURIES 0.00E+00 4.04E-06 0.00E+00 0.00E+00 NB-95 CURIES 0.00E+00 6.80E-07 0.00E+00 0.00E+00 SR-89 CURIES 1.24E-07 1.72E-07 0.00E+00 0.00E+00 CO-58 CURIES 0.00E+00 5.35E-06 9.53E-09 0.00E+00 Y-88 CURIES 0.00E+00 0.00E+00 3.57E-05 0.00E+00 SN-113 CURIES 0.00E+00 0.00E+00 1.38E-07 S.28E-08 CO-60 CURIES 0.00E+00 5.75E-07 0.00E+00 0.00E+00 SR-90 CURIES 1.25E-09 8.33E-17 0.00E+00 0.00E+00 TOTAL FOR PERIOD l
CURIES l 1.26E-07 l 1.08E-05 l 3.59E-05 l 5.28E-08 l Zeroes in this table indicate that no radioactivity was present at detectable levels.
See Table 2-7 for typical minimum detectable concentrations.
64
T
\\
j TABLE 2-2C#
Jo:cph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1998 Gaseous Effluents-Mixed-Mode Level Releases Unit: Site Starting :
1-Jul-1998 Ending : 31-Dec-1998 l
CONTINUOUS MODE l
BATCH MODE l
NUCLIDES RELEASED l.
UNIT l QUARTER 3 l QUARTER 4 l QUARTER 3 l QUARTER 4 l
)
H-3 CURIES 5.97E+00 2.76E+01 0.00E+00 0.00E+00 G-ALPHA
,URIES 2.76E 1.82E-07 0.00E+00 0.00E+00 l
i 1
l Zeroes in this table indicate that no radioactivity was present I
at detectable levels.
See Table 2-7 for typical minimum detectable concentrations.
65
n
~
3.5.3 G2stous Effluents - Ground ModeRoleasep The summaries of all gaseous effluent ground mode-
. releases.(includes listing by nuclide) are contained in the following tables :
' UnitL1 1998. Ground Mode Summary : Table 2-3A
-Unit 2 J1998 Ground Mode Summary : Table'2-3B Site 1998' Ground Mode Summary : _ Table 2-3C I
1 i
4 l
66 I
p 4
TABLE 2-3A*
JoIcph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1998 Gaseous Effluents-Ground Level Releases Unit: 1 Starting :
1-Jan-1998 Ending : 30-Jun-1998 l
CONTINUOUS MODE l
BATCH MODE l
)
NUCLIDES RELEASED l
UNIT l QUARTER 1 l QUARTER 2 l QUARTER 1 l QUARTER 2 l FISSION GASES XE-135M CURIES 0.00E+00 0.00E+00 8.39E-07 7.32E-08 AR-41 CURIES 0.00E+00 0.00E+00 6.23E-06 1.49E-07 XE-135 CURIES 3.57E-03 8.93E-03 6.32E-08 3.51E-07 RA-226 CURIES 0.00E+00 0.00E+00 2.07E-06 0.00E+00 TOTAL FOR PERIOD l
CURIES l 3.57E-03 l 8.93E-03 l 9.20E-06 l 5.74E-07 l 1
I IODINES I-134 CURIES 0.00E+00 0.00E+00 3.18E-06 7.88E-06 I-132 CURIES 0.00E+00 0.00E+00 1.06E-05 1.27E-05 I-133 CURIES 0.00E+00 1.95E-07 8.55E-06 9.78E-06 TOTAL FOR PERIOD l
CURIES l 0.00E+00 l 1.95E-07 l 2.23E-05 l 3.04E-05 l PARTICULATES RH-106 CURIES 0.00E+00 0.00E+00 4.43E-06 0.00E+00 RU-106 CURIES 0.00E+00 0.00E+00 4.43E-06 0.00E+00 TOTAL FOR PERIOD l
CURIES l 0.00E+00 l 0.00E+00 l 8.87E-06 l 0.00E+00 l H-3
]
CURIES l 3.51E-04 l 2.18E-04 l 8.49E-04 l 8.16E-04 l 1
i l
i Zeroes in this table indicate that no radioactivity was present at detectable levels.
See Table 2-7 for typical minimum detectable concentrations, i
1 1
67 1
y TABLE 2-3A*
Joseph M.
Farley Nuclear Plant
^
ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1998 Gaseous Effluents-Ground Level Releases Unit: 1 Starting :
1-Jul-1998 Ending : 31-Dec-1998 l
CONTINUOUS MODE l
BATCH MODE l
- NUCLIDES RELEASED l
. UNIT l QUARTER 3 l QUARTER 4 l QUARTER 3 l QUARTER 4 l FISSION GASES XE-138 CURIES 2.02E-02 0.00E+00 0.00E+00 0.00E+00 XE-135M CURIES 6.82E-02 4.36E-02 9.75E-06 3.95E-03
- KR-87 CURIES 7.98E-03 0.00E+00 0.00E+00 0.00E+00
-AR-41 CURIES 1.77E-01 1.06E-01 0.00E+00 0.00E+00 KR-88 CURIES 2.55E-03 0.00E+00 0.00E+00 0.00E+00 KR-85M CURIES 1.70E-02 1.94E-02 0.00E+00 0.00E+00 XE-135 CURIES 1.01E-01 2.26E-02 1.06E-06 3.54E-04
- XE-133 CURIES 1.95E-01 0.00E+00 0.00E+00 0.00E+00 XE-131M CURIES 0.00E+00 0.00E+00 0.00E+00 5.84E-08 KR-85 CURIES 0.00E+00 0.00E+00 0.00E+00 6.00E-02 TOTAL FOR PERIOD l
CURIES l 5.88E-01 l 1.91E-01 l 1.08E-05 l 6.43E-02 l IODINES I-134 CURIES 0.00E+00 0.00E+00 8.93E-06 4.66E-03 I-132' CURIES 0.00E+00 0.00E+00 9.54E-06 4.18E-03 I-130 CURIES 0.00E+00 0.00E+00 0.00E+00 2.65E-07 I-133 CURIES 2.96E-07 0.00E+00 2.53E-05 3.32E-03 I-131 CURIES 5.21E-09 0.00E+00 2.72E-04 2.46E-04 TOTAL.FOR PERIOD-l CURIES l 3.01E-07 l 0.00E+00 l 3.15E-04 l 1.24E-02 l Zeroes in this table indicate that no radioactivity was present at detectable levels.
See Table 2-7 for typical minimum detectable' concentrations.
68 l
TABLE 2-3A*
Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1998 Gaseous Effluents-Ground Level Releases Unit: 1 Starting :
1-Jul-1998 Ending : 31-Dec-1998 l
CONTINUOUS MODE l
BATCH MODE l
NUCLIDES RELEASED l
UNIT l QUARTER 3 l QUARTER 4 l QUARTER 3 l QUARTER 4 l 1
PARTICULATES I-131 CURIES 0.00E+00 0.00E+00 3.32E-06 0.00E+00 NB-95 CURIES 0.00E+00 0.00E+00 5.33E-06 0.00E+00 ZR-95 CURIES 0.00E+00 0.00E+00 3.38E-06 0.00E+00 CO-58 CURIES 0.00E+00 0.00E+00 3.78E-04 0.00E+00 TE-127M CURIES 0.00E+00 0.00E+00 9.52E-06 1.92E-02 i
MN-54 CURIES 0.00E+00 0.00E+00 1.41E-04 3.32E-09 RH-106 CURIES 0.00E+00 0.00E+00 2.87E-06 0.00E+00 RU-106 CURIES 0.00E+00 0.00E+00 2.87E-06 0.00E+00 CS-134 CURIES 0.00E+00 0.00E+00 2.31E-04 4.52E-06 CS-137 CURIES 0.00E+00 0.00E+00 3.47E-04 4.90E-06 TOTAL'FOR PERIOD l
CURIES l 0.00E+00 l_0.00E+00 l 1.12E-03 l 1.92E-02 l H l CURIES l 1.32E-01 l 3.02E-04 l 1.19E-01 l 3.18E-02 l Zeroes in this table indicate that no radioactivity was present at detectable levels.
See Table 2-7 for typical minimum detectable concentrations.
69
F.
TABLE 2-3B*
-Joseph M.
Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1998 Gaseous Effluents-Ground Level Releases l
Unit: 2 Starting :
1-Jan-1998 Ending : 30-Jun-1998 t
i l
CONTINUOUS MODE l
BATCH MODE l
NUCLIDES RELEASED l
UNIT l QUARTER 1 l QUARTER 2 l QUARTER 1 l QUARTER 2 l FISSION GASES TOTAL FOR-PERIOD l
CURIES l 0.00E+00 l 0.00E+00 l 0.00E+00 l 0.00E+00 l IODINES i
TOTAL FOR PERIOD l
CURIES l 0.00E+00 l 0.00E+00 l 0.00E+00 l 0.00E+00 l PARTICULATES l
TOTAL FOR PERIOD l
CURIES l 0.00E+00 l 0.00E+00 l 0.00E+00 l 0.00E+00 l H-3 l'
CURIES l 1.90E-03 l 2.38E-05 l 0.00E+00 l 0.00E+00 l-Zeroes in this table indicate that no radioactivity was present at detectable levels.
See Table 2-7 for typical minimum detectable concentrations.
70 l-l
i n
TABLE 2-3B*
Jo eph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1998 i
Gaseous Effluents-Ground Level Releases Unit: 2 Starting :
1-Jul-1998 Ending : 31-Dec-1998 j
l CONTINUOUS MODE l
BATCH MODE l
j NUCLIDES RELEASED l
~ UNIT l QUARTER 3 l QUARTER 4 l QUARTER 3 l QUARTER 4 l FISSION GASES I
1
' TOTAL FOR PERIOD l
CURIES l 0.00E+00 l 0.00E+00 l 0.00E+00 l 0.00E+00 l IODINES I
I f6ii'~i6i~iiii66~~~~~~~~i'~C6iiiS~~i~6:56i+66i~6:66i+66i~6:56i+56i6:66i'66'il
+
PARTICULATES CO-58 l
CURIES l 3.08E-08 l 0.00E+00 l 0.00E+00 l 0.00E+00 l TOTAL FOR PERIOD l
CURIES l 3.08E-08 l 0.00E+00 l 0.00E+00 l 0.00E+00 l i
CURIES l 4.19E-04 l 1.30E-03 l 0.00E+00 l 0.00E+00 l Zeroes in this table indicate that no radioactivity was present at detectable levels.
See Table 2-7 for typical minimum detectable concentrations.
)
71
F TABLE 2-3C*
Joseph M.
Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1998 Gaseous Effluents-Ground Level Releases
)
Unit: Site
)
Starting :
1-Jan-1998 Ending : 30-Jun-1998 l
CONTINUOUS MODE l
BATCH MODE l
NUCLIDES RELEASED l
UNIT l QUARTER 1 l QUARTER 2 l QUARTER 1 l QUARTER 2 l I
FISSION GASES 1
AR-41 CURIES 0.00E+00 0.00E+00 6.23E-06 1.49E-07 XE-135 CURIES 3.57E-03 8.93E-03 6.32E-08 3.51E-07 RA-226 CURIES 0.00E+00 0.00E+00 2.07E-06 0.00E+00 TbhkLhbkPbkkbb f
bbkkhb f b$bhb bb f b$bbb5bb f b$bbb bb f b$hkb5bh f i
IODINES I-134 CURIES 0.00E+00 0.00E+00 3.18E-06 7.88E-06 I-132 CURIES 0.00E+00 0.00E+00 1.06E-05 1.27E-05 I-133 CURIES 0.00E+00 1.95E-07 8.55E-06 9.78E-06 TOTAL FOR PERIOD l
CURIES l 0.00E+00 l 1.95E-07 l 2.23E-05 l 3.04E-05 l PARTICULATES RH-106 CURIES 0.00E+00 0.00E+00 4.43E-06 0.00E+00 RU-106 CURIES 0.00E+00 0.00E+00 4.43E-06 0.00E+00 TbhkLhbkPbkkbb f
bbkkhb f b$bbb bb f b$bbb+bb f b$bhb bb f b$bbb bb f H-3 l
CURIES l 2.25E-03 l 2.41E-04 l 8.49E-04 l 8.16E-04 l Zeroes in this table indicate that no radioactivity was present at detectable levels.
See Table 2-7 for typical minimum detectable concentrations.
l l
72
?
TABLE 2-3C*
Joacph M.
Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1998 Gaseous Effluents-Ground Level Releases Unit: Site Starting.:
1-Jul-1998 Ending : 31-Dec-1998 l
CONTINUOUS MODE l
BATCH MODE l
NUCLIDES RELEASED l
UNIT l QUARTER 3 l QUARTER 4 l QUARTER 3 l QUARTER 4 l FISSION GASES XE-138 CURIES 2.02E-02 0.00E+00 0.00E+00 0.00E+00 XE-135M CURIES 6.82E-02 4.36E-02 9.75E-06 3.95E-03 KR-87 CURIES 7.98E-03 0.00E+00 0.00E+00 0.00E+00 AR-41 CURIES 1.77E-01 1.06E-01 0.00E+00 0.00E+00 KR-88 CURIES 2.55E-03 0.00E+00 0.00E+00 0.00E+00 KR-85M CURIES 1.70E-02 1.94E-02 0.00E+00 0.00E+00 XE-135 CURIES 1.01E-01 2.26E-02 1.06E-06 3.54E-04 XE-133
' CURIES 1.95E-01 0.00E+00 0.00E+00 0.00E+00 XE-131M CURIES 0.00E+00 0.00E+00 0.00E+00 5.84E-08 KR-85 CURIES 0.00E+00 0.00E+00 0.00E+00 6.00E-02 TOTAL FOR PERIOD l' CURIES l 5.88E-01 l 1.91E-01 l 1.08E-05 l 6.43E-02.l IODINES I-134 CURIES 0.00E+00 0.00E+00 8.93E-06 4.66E-03
'I-132 CURIES 0.00E+00
-0.00E+00 9.54E-06 4.18E-03 I-130 CURIES 0.00E+00 0.00E+00 0.00E+00 2.65E-07 I-133 CURIES 2.96E-07 0.00E+00 2.53E-05 3.32E-03
.I-131 CURIES 5.21E-09 0.00E+00 2.72E-04 2.46E-04 TOTAL FOR PERIOD l
CURIES l 3.01E-07 l 0.00E+00 l 3.15E-04 l 1.24E-02 l Zeroes in this table indicate that no radioactivity was present at detectable levels.
See Table 2-7 for typical minimum detectable concentrations.
73
~'
TABLE 2-3C*
Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1998 Gaseous Effluents-Ground Level Releases Unit: Site Starting :
1-Jul-1998 Ending : 31-Dec-1998 l
l l
CONTINUOUS MODE l
BATCH MODE l
NUCLIDES RELEASED l
UNIT l QUARTER 3 l QUARTER 4 l QUARTER 3 l QUARTER 4 l l
PARTICULATES I-131 CURIES 0.00E+00 0.00E+00 3.32E-06 0.00E+00 l
l l
NB-95 CURIES 0.00E+00 0.00E+00 5.33E-06 0.00E+00 l
ZR-95 CURIES 0.00E+00 0.00E+00 3.38E-06 0.00E+00 CO-58 CURIES 3.08E-08 0.00E+00 3.78E-04 0.00E+00 TE-127M CURIES 0.00E+00 0.00E+00 9.52E-06 1.92E-02 MN-54 CURIES 0.00E+00 0.00E+00 1.41E-04 3.32E-09 l
RH-106 CURIES 0.00E+00 0.00E+00 2.87E-06 0.00E+00 l
RU-106 CURIES 0.00E+00 0.00E+00 2.87E-06 0.00E+00
'CS-134 CURIES 0.00E+00 0.00E+00 2.31E-04 4.52E-06 CS-137 CURIES 0.00E+00 0.00E+00 3.47E-04 4.90E-06 TOTAL FOR PERIOD l
CURIES l 3.08E-08 l 0.00E+00 l 1.12E-03 l 1.92E-02 l H-3 l
CURIES l 1.33E-01 l 1.60E-03 l 1.19E-01 l 3.18E-02 l l
l Zeroes in this table indicate that no radioactivity was present at detectable levels.
See Table 2-7 for typical minimum detectable concentrations.
l l
l l
l t
1 1
74
l j
3.6_Radiologicol Impact The air doses and organ doses due to gaseous' effluents for
' Units 1 and-2 are provided in the following tables in order I
to show conformance with the limits of ODCM 3.1.3 and ODCM 3'1.4 :
i Unit 1 1998 Air Doses
- Table 2-4A Unit 2 1998 Air Doses
- Table 2-4B Unit 1 19981 Organ Doses : Table 2-5A Unit 2 1998 Organ Doses : Table 2-5B l
l 75
4 TABLE 2-4A Joseph M. Farley Nuclear-Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1998 AIR DOSES DUE TO GASEOUS RELEASES Unit: 1 Starting: 01-Jan-1998 Ending: 30-Jun-1998 Cumulative Doses per Quarter Type ODCM Units Quarter
% of Quarter
% of of Limit 1
ODCM 2
ODCM Radi-Limit Limit otion Gamma 5.0 mrad 2.33E-02 4.65E-01 5.58E-03 1.12E-01 Bata 10.0 mrad 8.40E-03 8.40E-02 2.58E-03 2.58E-02 Cumulative Doses per Year Type ODCM Units Year to
% of of Limit Ending ODCM Redi-Date Limit ation Gamma 10.0 mrad 2.88E-02 2.88E-01 Beta 20.0 mrad 1.10E-02 5.49E-02 I
l l
1 76
['
F TABLE 2-4A Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1998 AIR DOSES DUE TO GASE9US RELEASES Unit: 1 Starting: 01-Jul-1998 Ending: 31-Dec-1998 Cumulative Doses per Quarter Typs ODCM Units Quarter
% of Quarter
% of of Limit 3
ODCM 4
ODCM Radi-Limit Limit etion Gamma 5.?
mrad 8.03E-03 1.61E-01 2.96E-03 5.92E-02 B:ta 10.0 mrad 4.25E-03 4.25E-02 1.43E-03 1.43E-02 Cumulative Doses per Year Typ3 ODCM Units Year to
% of of Limit Ending ODCM Rcdi-Date Limit ation Gamma 10.0 mrad 3.98E-02 3.98E-01 Bata 20.0 mrad 1.67E-02 8.33E-02 M
77
r TABLE 2-4B Joseph M. Farley Nuclear Plant i
ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1998 AIR DOSES DUE TO GASEOUS RELEASES Unit: 2 Starting: 01-Jan-1998 Ending: 30-Jun-1998 Cumulative Doses per Quarter Typ3
'ODCM Units Quarter
% of Quarter
% of of.
Limit 1
ODCM 2
ODCM Rcdi-Limit Limit ation Gamma 5.0 mrad 3.02E-03 6.05E-02 1.80E-03 3.60E-02 Bata 10.0 mrad 1.09E-03 1.09E-02 6.86E-04 6.86E-03 I
Cumulative Doses per Year Typ3 ODCM Units Year to
% of of -
Limit Ending ODCM REdi-Date Limit etion i
Gamma 10.0-mrad 4.82E-03 4.82E-02 B:ta 20.0 mrad 1.77E-03 8.86E-03 I
i l
t
{
i l
78
)
I TABLE 2-4B Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1998 AIR DOSES DUE TO GASEOUS RELEASES l
Unit: 2 Starting: 01-Jul-1998 Ending: 31-Dec-1998 Cumulative Doses per Quarter Type rOCM Units Quarter
% of Quarter
% of of
_lmit 3
ODCM 4
ODCM Radi-Limit Limit ation Gamma 5.0 mrad 2.47E-03 4.94E-02 5.87E-03 1.17E-01 Bata 10.0 mrad 9.01E-04' 9.01E-03 2.07E-03 2.07E-02 Cumulative Doses per Year Typ3 ODCM Units Year to
% of of Limit Ending ODCM Radi-Date Limit etion Gamma 10.0 mrad 1.32E-02 1.32E-01 Bsta 20.0 mrad 4.74E-03 2.37E-02 79
o e
TABLE 2-5A Joseph M.
Farley Nuclear Plant
)
ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1998 DOSES'TO A MEMBER OF THE PUBLIC DUE TO RADIOIODINES, TRITIUM, AND PARTICULATES IN GASEOUS RELEASES Unit: 1 Starting: 01-Jan-1998 Ending: 30-Jun-1998 Cumulative Doses per Quarter Organ ODCM Unit Quarter
% of Quarter
% of Limit 1
ODCM 2
ODCM Limit Limit Bone 7.5 mrem 2.49E-05 3.33E-0\\
7.44E-06 9.92E-05 Liver 7.5 mrem 5.08E-04 6.77E-03 3.30E-04 4.40E-03 TBody 7.5 mrem 5.10E-04 6.80E-03 3.32E-04 4.43E-03 Thyroid 7.5 mrem 5.30E-04 7.06E-03 3.48E-04 4.63E-03 Kidney 7.5 mrem 5.34E-04 7.12E-03 3.30E-04 4.40E-03 Lung 7.5 mrem 5.25E-04 7.00E-03 3.30E-04 4.40E-03 GILLI 7.5 mrem 8.08E-04 1.08E-02 3.30E-04 4.41E-03 Cumulative Doses per Year Organ ODCM Units Year to
% of Limit Ending ODCM Date Limit Bone 15.0 mrem 3.24E-05 2.16E-04 Liver 15.0 mrem 8.38E-04 5.59E-03 TBody 15.0 mrem 8.42E-04 5.61E-03 Thyroid 15.0 mrem 8.77E-04 5.85E-03 Kidney 15.0 mrem 8.64E-04 5.76E-03 Lung 15.0 mrem 8.55E-04 5.70E-03 GILLI 15.0 mrem 1.14E-03 7.59E-03 80
I TABLE 2-5A Joseph M.
Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1998 DOSES TO A MEMBER OF THE PUBLIC DUE TO RADIOIODINES, TRITIUM, AND PARTICULATES IN GASEOUS RELEASES Unit: 1 Starting: 01-Jul-1998 Ending: 31-Dec-1998 Cumulative Doses per Quarter Organ ODCM Unit Quarter
% of Quarter
% of Limit 3
ODCM 4
ODCM Limit Limit Bone 7.5 mrem 2.54E-02 2.05E-01 5.01E-02 6.68E-01 Liver 7.5 mrem 1.81E-02 2.41E-01 1.55E-02 2.07E-01
.TBody 7.5 mrem 7.72E-03 1.03E-01 7.78E-03 1.04E-01 Thyroid 7.5 mrem 1.87E-02 2.50E-01 3.30E-02 4.39E-01 Kidney 7.5 mrem 9.57E-03 1.28E-01 1.44E-01 1.92E+00
. Lung 7.5 mrem.
7.03E-03 9.37E-02 9.68E-03 1.29E-01 GILLI 7.5 mrem 5.92E-03 7.90E-02 4.24E-02 5.65E-01 Cumulative Doses per Year Organ ODCM Units Year to
% of Limit Ending ODCM Date Limit Bone 15.0 mrem.
6.55E-02 4.37E-01 Liver 15.0 mrem 3.44E-02 2.29E-01 TBody 15.0 mrem 1.63E-02 1.09E-01 4
Thyroid 15.0 mrem 5.26E-02 3.51E-01 Kidney 15.0 mrem 1.54E-01 1.03E+00 Lung 15.0 mrem 1.76E-02 1.17E-01 GILLI 15.0 mrem 4.95E-02 3.30E-01 l
1 81
h
)
t' 4
I' TABLE 2-5B Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1998 DOSES TO A MEMBER OF THE PUBLIC DUE TO RADIOIODINES, TRITIUM, L
AND PARTICULATES IN GASEOUS RELEASES l
Unit: 2 Starting: 01-Jan-1998 Ending: 30-Jun-1998 1
Cumulative Doses per Quarter Organ ODCM Unit Quarter
% of Quarter
% of Limit 1
ODCM 2
ODCM Limit Limit Bone 7.5 mrem 2.16E-07 2.88E-06 3.26E-06 4.35E-05 Liver 7.5 mrem 1.41E-03 1.87E-02 4.51E-04 6.01E-03 T3ody 7.5 mrem 1.41E-03 1.87F-02 4.52E-04 6.02E-03 Thyroid 7.5 mrem 1.46E-03 1.95E-02 4.74E-04 6.33E-03 Kidney 7.5 mrem 1.41E-03 1.87E-02 4.51E-04 6.01E-03 Lung 7.5-mrem 1.41E-03 1.87E-02 4.51E-04 6.01E-03 GILLI 7.5 mrem 1.41E-03 1.87E-02 4.51E-04 6.02E-03 Cumulative Doses per Year Organ ODCM Units Year to
% of Limit Ending ODOM Date Limit Bonn 15.0 mrem 3.48E-06 2.32E-05 i
Liver 15.0 mrem 1.86E-03 1.24E-02 TBody 15.0 mrem 1.86E-03 1.24E-02 i
Thyroid 15.0 mrem 1.93E-03 1.29E-02
' Kidney 15.0 mrem 1.86E-03 1.24E-02 Lung 15.0 mrem 1.86E-03 1.24E-02 GILLI 15.0 mrem 1.86E-03 1.24E-02 i
82 l
4 TABLE 2-5B Joseph M.
Farley Nuclear Plant ANNUAL RADIOACTIVE. EFFLUENT RELEASE REPORT - 1998 DOSES TO A MEMBER OF THE PUBLIC DUE TO RADIOIODINES, TRITIUM, AND PARTICULATES IN GASEOUS RELEASES Unit: 2 Starting: 01-Jul-1998 Ending: 31-Dec-1998 Cumulative Doses per Quarter Organ ODCM' Unit Quarter
% of Quarter
% of Limit 3
ODCM 4
ODCM Limit Limit Bono 7.5 mrem-1.42E-07 1.90E-06 1.10E-07 1.47E-06
'Livar 7.5 mrem 3.91E-04 5.21E-03 2.10E-03 2.80E-02 i
TPody 7.5 mrem 3.91E-04 5.21E-03 2.10E-03 2.80E-02 Thyroid 7.5 mrem 3.91E-04 5.21E-03 2.10E-03 2.80E-02 Kidney 7.5 mrem 3.91E-04 5.21E-03 2.10E-03 2.80E-02
)
L:ung 7.5 mrem 3.91E-04 5.21E-03 2.10E-03 2.80E-02 GILLI 7.5 mrem 3.91E-04 5.21E-03 2.10E-03 2.80E-02 Cumulative Doses per Year.
Organ ODCM Units Year to
% cf Limit Ending ODCM
.Date Limit Bonn 15.0 mrem 3.73E-06 2.49E-05 Liver 15.0 mrem 4.35E-03 2.90E-02 TBody 15.0 mrem 4.35E-03 2.90E-02 Thyroid 15.0 mrem 4.43E-03 2.95E-02 Kidney 15.0 mrem 4.35E-03 2.90E-02 Lung 15.0 mrem 4.35E-03 2.90E-02 GILLI 15.0 mrem 4.35E-03 2.90E-02 83
T l
TABLE 2-7 L
Jo cph M.
Ferley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1998 f^
TYPICAL GASEOUS MDC'S ACHIEVED ON COUNTING SYSTEM l
Nuclide MDC (uCi/ML)
MN-54 3.21E-15 CO-58 1.53E-14 i
FE-59 7.96E-15 CO-60 1.95E-14 ZN-65 2.34E-14 MO-99 1.81E-13 CS-134 1.41E-14 CS-137 7.83E-15 CE-141 6.
3E-15 CE-144 3.47E-14 KR-87 8.18E-07 KR-88 3.94E-08 XE-133 4.30E-08 XE-133M 4.82E-08 XE-135 1.78E-08 XE-138
. 99E-07 I-131 9.67E-15 I 2.n 1.80E-13 i
84
4.0 SOLID WASTE This section contains information regarding the types and
{
quantities of solid radioactive waste shipped offsite during 1998 as required in ODCM 7.2.2.4. This information is presented in Table 3.
l The error involved in determining tha contents of solid radwaste shipments is estimated to be less than + or - 15%.
l i
85
TABLE 3 Joseph M.
Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1998 SOLID WASTE AND IRRADIATED FUEL SHIPMENTS Starting: 01-Jan-1998 Ending: 30-Jun-1998 A. SOLID WASTE SHIPPED OFFSITE FOR BURIAL GR DISPOSAL (not irradiated fuel)
- 1. Type of Waste.
UNITS 6-Months 3
- a. Spent _ resins, Filter sludges, m
7.691E+00
~
evaporator bottoms, etc.
Ci*
6.180E+02 3
- b. Dry compressible waste, contaminated m
7.637E+00 equipment, etc.
Ci*
1.816E-01 3
- c. Irradiated components, control m
None rods, etc.
Ci*
None i
3
- d. Other (describe) m None Ci*
None
- 2. Estimate of major nuclide composition ( hy type of waste ).
- a. NI-63 61.2%
CO-60 28.3%
FE-55 6.5%
- b. FE-55 45.0%
CO-58 19.0%
CO-60 15.3%
NI-63 12.5%
CR-51 2.1%
NB-95 1.3%
C-14 1.2%
- 3. Solid Waste Disposition Number of Shipments Mode of Transportation Destination 12 Highway Chem-Nuclear Systems, Inc.
Barnwell, South Carolina.
- Measured and/or estimated by correlations in accordance with 10CFR61.55.
86
r-TABLE 3 Joacph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1998
' SOLID WASTE AND IRRADIATED FUEb SHIPMENTS Starting: 01-Jan-1998-Ending: 30-Jun-1998 (continued)
- 4. Type of. Containers (Shipped offsite for burial / processing)
Container Type of Number Container 3
Description Container of Volume (m
)
Containers
- a. RADLOK 500 High Integrity 3
3.850E+00 Container
- b. 20' Seavan Strong Tight 5
2.945E+01 Container 40' Seavail-Strong Tight 2
5.890E+01 Container 55 Gallon Drum Strong Tight 59 2.100E-01 Container 85 Gallon Drum Strong Tight 1
3.400E-01 Container Metal Box Strong Tight 14 2.590E+00 Container
- 5. Solidification Agent
- a. None
- b. None B.
IRRADIATED FUEL SHIPMENTS (Disposition)
Number of Shipments Mode of Transportation Destination None N/A N/A
/
87 1
TABLE 3 1
Joseph M.
Farley Nuclear Plant I
ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1998 SOLID WASTE AND IRRADIATED FUEL SHIPMENTS Starting: 01-Jul-1998 Ending: 31-Dec-1998 A.
SOLID WASTE SHIPPED OFFSITE FOR BURIAL OR DISPOSAL (not irradiated fuel)
- 1. Type of Waste.
UNITS 6-Months 3
- a. Spent resins, Filter sludges, m
4.690E-01 g
evaporator bottoms, etc.
Ci*
6.169E+00 3
- b. Dry compressible waste, contaminated m
1.503E+01 equipment, etc.
Ci*
1.967E+00 3
- c. Irradiated components, control m
None rods, etc.
Ci*
None 3
- d. Other (describe) m None Ci*
None
- 2. Estimate of major nuclide composition ( by type of waste ).
- a. FE-55 37.2%
NI-63 26.3%
CO-60 22.8%
C-14 6.0%
CS-137 2.6%
- b. FE-55 52.4%
CO-60 15.7%
NI-63 14.7%
CO-58 7.8%
MN-54 1.5%
C-14 1.3%
ZR-95 1.3%
- Measured and/or estimated by correlations in accordance with 10CFR61.55.
88
TABLE 3 Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1998 SOLID WASTE AND IRRADIATED FUEL SHIPMENTS Starting: 01-Jul-1998 Ending: 31-Dec-1998 (continued)
- 3. Solid Waste Disposition Number of Shipments Mode of Transportation Destination 40 Highway Chem-Nuclear Systems, Inc.
Barnwell, South Carolina.
- 4. Type of Containers (Shipped offsite for burial / processing)
Container Type of Number Container 3
Description Container of Volume (m
)
Containers
- a. RADLOK 500 High Integrity 2
3.850E+00 Container HN-100 Strong Tight 2
4.890E+00 Container
- b. 40' Seavan Strong Tight 2
5.890E+01 Container
- 5. Solidification Agent
- a. None
- b. None i
B. IRRADIATED FUEL SHIPMENTS (Disposition)
Number of Shipments Mode of Transportation Destination None N/A N/A 89
l 5.0-ONSITE DOSES TO MEMBERS OF THE.PUBLIC l
Current FNP effluent controls as established by ODCM 6.1 do not L
require assessment of the radiation doses from radioactive liquid L
and gaseous effluents to MEMBERS OF THE PUBLIC due to their i
activities inside the SITE BOUNDARY (ODCM Figure 10-1). However, l.
thic assessment has been performed for 1998 using the methods described in ODCM 6.2 and is included in this section as
. Table 4-1.
4 90
TABLE 4-1 Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1998 DOSE TO A MEMBER OF THE PUBLIC DUE TO ACTIVITIES INSIDE THE SITE BOUNDARY Unit: Site Starting: 01-Jan-1998 Ending: 30-Jun-1998 Page:
1 Location Name VISITOR LOCATION 1 (VIS. CENTER)
Distance (kilometers) 3.06E-01 Sector WSW Occupancy Factor 1.37E-03 (1.20E+01 hr/yr)
.Aga Group CHILD Ground Level Releases:
Noble Gas X/Q (sec/m3) 1.04E-04 Particulate X/Q (sec/m3) 1.04E-04 Particulate D/Q (m-2) 4.80E-07 Mixed Mode Releases:
Noble Gas X/Q (sec/m3) 8.80E-06 Particulate X/Q (sec/m3) 8.80E-06 Particulate D/Q (m-2) 6.20E-08 Elevated Releases:
Noble Gas X/Q (sec/m3)
N/A Particulate X/Q (sec/m3)
N/A Particulate D/Q (m-2)
N/A Units Quarter 1 Quarter 2 Quarters Year to 1-and 2 Ending Dace Bone mrem 2.83E-04 7.77E-05 3.61E-04 3.61E-04 Liver mrem 2.89E-04 8.02E-05 3.70E-04 3.70E-04 TBody mrem 2.89E-04 8.02E-05 3.70E-04 3.70E-04 Thyroid mrem 2.90E-04 8.04E-05 3.70E-04 3.70E-04 Kidney mrem 2.89E-04 8.02E-05 3.70E-04 3.70E-04 Lung mrem 2.90E-04 8.02E-05 3.70E-04 3.70E-04 GI-LLI mrem 2.89E-04 8.02E-05 3.70E-04 3.70E-04 91
1
's TABLE 4-1 Joseph M. Farley Nuclear Plant I
ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1998 DOSE TO A MEMBER OF THE PUBLIC DUE TO ACTIVITIES INSIDE THE SITE BOUNDARY Unit: Site Starting: 01-Jan-1998 Ending: 30-Jun-1998 Page:
2 Location Name VISITOR LOCATION 2 (SW POND)
Distance (kilometers) 9.66E-01 Sector SSW Occupancy Factor 7.53E-03 (6.60E+01 hr/yr)
Age Group CHILD Ground Level Releases:
Noble Gas X/Q (sec/m3) 4.74E-05 Particulate X/Q (sec/nG) 4.74E-05 Particulate D/Q (m-2) 1.31E-07 Mixed Mcde Releases:
Noble Gas X/Q (sec/nG) 9.75E-07 Particulate X/Q (sec/nG) 9.75E-07 Particulate D/Q (m-2) 2.78E-08 Elevated Releases:
Noble Gas X/Q (sec/m3)
N/A Particulate X/Q (sec/m3)
N/A Particulate D/Q (m-2)
N/A Units Quarter'1 Quarter 2 Quarters Year to 1 and 2 Ending Date Bone mrem 1.73E-04 4.74E-05 2.20E-04 2.20E-04 Liver mrem 1.76E-04 4.90E-05 2.25E-04 2.25E-04 TBody-mrem 1.76E-04 4.90E-05 2.25E-04 2.25E-04 i
Thyroid mrem 1.77E-04 4.94E-05 2.26E-04 2.26E-04 Kidney mrem 1.76E-04 4.90E-05 2.25E-04 2.25E-04 I
Lung mrem 1.77E-04 4.90E-05 2.26E-04 2.26E-04 GI-LLI mrem 1.76E-04 4.90E-05 2.25E-04 2.25E-04 l
92
1 TABLE'4-1 Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1998 DOSE TO A MEMBER OF THE PUBLIC DUE TO ACTIVITIES INSIDE THE SITE BOUNDARY Unit: Site
-Starting: 01-Jan-1998 Ending: 30-Jun-1998 2
Page:
3 i
I Location Name VISITOR LOCATION 3 ' (IUf DISCH. )
Dictance (kilometers) 1.64E+00
)
Sector SE
. Occupancy Factor 1.14E-02 (9.99E+01 hr/yr)
Aga Group CHILD Ground Level Releases:
Noble Gas X/Q (sec/nG) 1.63E-05 Particulate X/Q (sec/m3) 1.63E-05 Particulate D/Q (m-2) 4.55E-08 i
Mixed Mode Releases:-
l Noble Gas X/Q (sec/m3) 7.05E-07 Particulate X/Q (sec/m3) 7.05E-07 Particulate D/Q (m-2) 1.39E-08 Elevated Releases:
Noble Gas X/Q _ (sec/m3)
N/A Particulate X/Q (sec/m3)
N/A Particulate D/Q (m-2)
N/A i
Units Quarter 1 Quarter 2 Quarters Year to 1 and 2 Ending Date Bone mrem 1.89E-04 5.19E-05 2.41E-04 2.41E-04 Liver mrem 1.93E 5.35E-05 2.47E-04 2.47E-04 TBody mrem 1.93E-04 5.35E-05 2.47E-04 2.47E-04 Thyroid mrem 1.93E-04 5.37E-05 2.47E-04 2.47E-04 Kidney mrem 1.93E-04 5.35E-05 2.47E-04 2.47E-04 Lung mrem 1.93E-04 5.35E-05 2.47E-04 2.47E-04 GI-LLI mrem 1.93E-04 5.35E-05 2.47E-04 2.47E-04 93
TABLE 4-1 Joseph M.
Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1998 DOSE TO A MEMBER OF THE PUBLIC DUE TO ACTIVITIES INSIDE THE SITE BOUNDARY Unit: Site Starting: 01-Jul-1998 Ending: 31-Dec-1998 Page:
1 Location Name VISITOR LOCATION 1 (VIS. CENTER)
Dictance (kilometers) 3.06E-01 Sector WSW Occupancy Factor 1.37E-03 (1.20E+01 hr/yr)
Ago Group CHILD Ground Level Releases:
Noble Gas X/Q (sec/m3) 1.04E-04 Particulate X/Q (sec/m3) 1.04E-04 Particulate D/Q (m-2) 4.80E-07 Mix d Mode Releases:
doble Gas X/O (sec/m3) 8.80E-06 Particulate X/O (sec/m3) 8.80E-06 Particulate D/Q (m-2) 6.20E-08 Elevated Releases:
Noble Gas X/Q (sec/m3)
N/A Particulate X/Q (sec/m3)
N/A Particulate D/Q (m-2)
N/A Units Quarter 3 Quarter 4 Quarters Year to
)
3 and 4 Ending Date Bone mrem 2.00E-04 7.74E-05 2.78E-04 6.39E-04 Liver mrem 2.05E-04 8.79E-05 2.92E-04 6.62E-04 TBody mrem 2.03E-04 8.71E-05 2.90E-04 6 59E-04 Thyroid mrem 2.22E-04 1.64E-04 3.86E-04 7.56E-04 Kidney mrem 2.03E-04 9.28E-05 2.96E-04 6.65E-04 Lung mrem 2.06E-04 2.15E-04 4.20E-04 7.90E-04 GI-LLI mrem 2.02E-04 9.30E-05 2.95E-04 6.65E-04 I
94
TABLE 4-1 Joseph M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1998 DOSE -TO A MEMBER OF. THE PUBLIC DUE TO ACTIVITIES INSIDE.THE SITE BOUNDARY Unit: Site Starting: 01-Jul-1998 Ending: 31-Dec-1998 Page:
2 Location Name VISITOR LOCATION 2 (SW POND)
Distance (kilometers) 9.66E-01 Sector SSW Occupancy Factor 7.53E-03 (6.60E+01 hr/yr)
Ago Group CHILD Ground Level Releases:
Noble Gas X/Q (sec/m3) 4.74E-05 Particulate X/Q (sec/m3) 4.74E-05 Particulate D/Q (m-2) 1.31E-07 Mixed Mode Releases:
Noble Gas X/Q (sec/m3) 9.75E-07 Particulate X/Q (sec/m3) 9.75E-07 Particulate D/Q (m-2) 2.78E-08 Elevated Releases:
1 Noble Gas X/Q (sec/m3)
N/A Particulate X/Q (sec/m3)
N/A Particulate D/Q (m-2)
N/A Units Quarter 3 Quarter 4 Quarters Year to 3 and 4 Ending Date Bone mrem 2.52E-04 5.95E-05 3.12E-04 5.32E-04 Liver mrem 2.57E-04 6.36E-05 3.21E-04 5.46E-04 l
TBody mrem 2.53E-04 6.18E-05 3.14E-04 5.40E-04 Thyroid mrem 3.02E-04 2.52E-04 5.54E-04 7.81E-04 Kidney mrem 2.54E-04 7.61E-05 3.30E-04 5.55E-04
. Lung mrem 2.60E-04 3.82E-04 6.42E-04 8.68E-04 GI-LLI mrem 2.52E-04 7.65E-05 3.28E-04 5.53E-04 95
TABLE 4-1 Joseph-M. Farley Nuclear Plant ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT - 1998 DOSE TO A MEMBER OF THE PUBLIC DUE TO ACTIVITIES INSIDE THE SITE BOUNDARY Unit: Site Starting: 01-Jul-1998-Ending: 31-Dec-1998 Page:
3 Location'Name Dictance (kilometers).
VISITOR' LOCATION 3 (RW DISCH.)
1.64E+00 Sector SE Occupancy Factor 1.14E-02 (9.99E+01 hr/yr)
Age Group CHILD Ground Level Releases:
Noble Gas X/Q (sec/m3) 1.63E-05 Particulate X/Q (sec/m3) 1.63E-05 Particulate D/Q (m-2) 4.55E-08 Mixed-Mode Releases:
Noble Gas'X/Q (sec/nd) 7.05E-07 Particulate X/Q (sec/m3) 7.05E-07 Particulate D/Q (m-2) 1.39E-08 Elevated Releases:
Noble Gas X/Q (sec/m3)
N/A Particulate X/Q (sec/nG)
N/A Particulate D/Q (m-2)
N/A Units Quarter 3 Quarter 4 Quarters Year to 3 and 4 Ending Date Bone mrem 1.57E-04 5.54E-05 2.12E-04 4.53E-04 Liver-mrem 1.61E-04.
6.16E-05 2.22E-04 4.69E-04 TBody mrem 1.58E-04 6.07E-05 2.19E-04 4.65E-04 Thyroid
' mrem 1.84E-04 1.60E-04 3.44E-04 5.91E-04 Kidney mrem 1.59E-04 6.81E-05 2.27E-04 4.73E-04 Lung mrem 1.62E-04 2.27E-04 3.89E-04 6.36E-04 GI-LLI mrem 1.58E-04 6.83E-05 2.26E-04 4.72E-04 96
6.0 MISCELLANEOUS This section contains several items which are only required to be reported under certain conditions. These include radiation dose assessments to show conformance with 40CFR190 (if required by ODCM 5.1.2), licensee initiated changes to the ODCM within the last year, deviations in the Radioactive Effluent Control Program within the last year pursuant to ODCM 7.2.2.6, major changes to the liquid or gaseous radwaste treatment systems as required by ODCM 2.1.5 and 3.1.6, and any changes to the solid radwaste_ treatment system pursuant to the Process Control Program (PCP).
6.1 Total Dose From Uranium Fuel Cycle In accordance with Technical Specification 6.8.3.e(x), the dose or dose commitment to any MEMBER OF THE PUBLIC over a calendar year, due to releases of radioactivity and to radiation from uranium fuel cycle sources, shall be limited to less than or equal to 25 mrem to the total body or to any organ, except the thyroid, which shall be limited to less than or equal to 75 mrem (as stated in ODCM 5.1).
With the calculated doses from the release of radioactive materials in liquid or gaseous effluents exceeding twice the limits of ODCM 2.1.3, 3.1.3, or 3.1.4, calculations shall be made according to ODCM 5.2 methods to determine whether the above (ODCM 5.1) limits have been exceeded (as stated in ODCM 5.1.2).
Since none of the ODCM 2.1.3, 3.1.3, or 3.1.4 limits were exceeded during 1998, no calculations were required.
6.2 Licensee Initiated Changes to the ODCM There were three revisions to the ODCM during 1998. These revisions were generally comprised of changes to various environmental sampling locations and environmental sampling j
frequencies, including the addition of a new dairy sampling location. These revisions are included as an Attachment to this Annual Radioactive Effluent Release Report, along with the corresponding procedure request forms and evaluations.
6.3 Program Deviations This section contains any deviations from the composite sampling or MDC requirements included in ODCM Tables 2-3 and 3-3.
There were no deviations during 1998.
6.4 Nhjor Changes to the Radwaste Treatment Systems There were no major changes to the Radwaste Treatment Systems during 1998.