ML20113G569

From kanterella
Jump to navigation Jump to search
Rev 1 to Instructional Unit LO-IU-11202-007-01-C, Respond to Emergency Generator Alarms
ML20113G569
Person / Time
Site: Vogtle  
Issue date: 08/10/1989
From: Allison S, Craig T
GEORGIA POWER CO.
To:
Shared Package
ML20092F288 List: ... further results
References
CON-IIT05-192-000C-90, CON-IIT5-192-C-90, RTR-NUREG-1410 LO-IU-11202-007, LO-IU-11202-7, NUDOCS 9202210479
Download: ML20113G569 (16)


Text

r e

e 4

GEORGIA POWER i

POWER CENERATING DEPARTMENT

'~

YbCTLE ELECTRIC GENERATING PLANT INSTRUCTIONAL UNIT

'ITLE:

RFSPOND TO EMERCENCY OF;NERATOR NUMBER L0-10-11202-007-01-C CENERATOR ALARJts PROGRAM LICEh' SED OPERATOR REVISION 1

AUTHOR:

S. All.ISON DATE 7/31/89

((/d/[f APPROVEDI M

DATEt V0GTLE PROCEDURE 17035-1. ANNUNCIATOR RESPONSE PROCEDURES (REV 4) l 1.

R 9202210479 v20116 I

PDR ADOCK 05000424 V

S PDR

e L0-1U-11202-007-01-C1 Respond To Diesel Generator Generator Alaras PrKFORMANCE OBJECTIVE Given that a generator alarm associated with the diesel generator tas i

annunciated, respond to the diesel generator "generat.or" alarm.

All communication and activities niust be performed in accordance with current. approved procedures.

The alarm must be acknowledged and its validity determined.

A plant equipment operator must be dispatched to petform activities locally, as necessary.

The diesel generator must be returned to operational status if it becomes inoperable due to the alarmed condition.

INFORMATION in this instructional unit.. the following generatar ala.ms associated with the diesel generator are covered:

DGIA GENERATOR TROUBLE DGI A LOW VOLTAGE DCIA HIGH TEMP GEN CNTL PNL DGIA LOW EXCITATION DGIA TRIP GENERATOR PAULT DGIA TRIP GEN DIFF DCI A HIGH TDtP GEN BEARINGS DGI A GENERATOR UNDER FREQUENCY DGIA DISABLED GEN CONTROL PVR FAILURE (wes covered in previous clustrt with other DISABLED alarms)

Upon receipt of any one of the diesel generstor alarms, obtain Plant Vogtle Annunciator Response Procedure 17035-1, and acknowledge the alarm. Also depress the SII.ENCE push button to silence the alarm horn.

When responding to any one of the diesel generator alarms:

s 1.

Acknowledge the alarm.

When acknowledging the alarm note any other alarm that may have annunciated associated with this alarm.

2.

Investigate the alarm.

Perform the initial Cperator actions required for the appropriate alarm as listed in the procedure. Dispatch a PE0 to perform the local subsequent operator actions as listed in the procedure.

Determine the validit v of the alarm.

In most cases, the PE0's readings of local indicatn e will accomplish this.

3.

Take corrective action (s) to r ri.

rha condition causing the alarm.

After the condition has been torr

1. reset the alarm.

Ensure that the PE0 resets the alarm locall;

4' iate MW0s as needed. Note any 7-1

g 4

4 to-IU-ll202-007-01-Ci Respond to Diesel Generator Generator Alarms t

i change of alignment or switch positions that have been made to affect the operability of the diesel generator.

Ref er to Technical specif ications for the diesel generators where applicable.

Nutify mr sko of the situation.

4.

Log the activity.

Log all pertinent informat tort in the control room log.

E01 DGIA GENERATOR TROUBLE This alarm is caused by a generator protective relay actuating.

These relays are located on the panel just to the right of the generator control panel in the diesel generator room.

The relays that can cause the alarm are auxiliary (X) relays actuated by the following primary relays:

132 Reverse power Relay 140 Luss of Excitat. ion 146 Negative phar,e Sequence Relay 151V/A Voltage Restrained Overcurrent (OC) Relays for A Phate 151VfB Voltage Restrained Overcurrent (00) Relays for B Phase 151V/C Voltage Restrained Overcurrent (OC) Relays for C Phase 151N Neutral Ground Overcurrent Relay 159 Cenerator Bus overvoltage Relay 160 potent tal Transformer (PT) Tailure Relay Transformer 164 Cenerator Field Ground Relay 181 Underfrequency 127 Undervoltage on the primary relay for the above functions. a target wi.11 appear showing that the relay has " picked up" when it detects the condition. Jhe diesel generator does not respond in the same manner for all these relays.

The response of each depends on the conditlons under which the diesel generator was started.

i.e..

emergency start or normal start situation.

This can af fect whether the diesel generator cont inues to run or not.

Also, whether the diesel generator output breaker is open or closed can affect how the diesel generator responds to an actuation by certain relays.

Acknowledge the alarm When the alarm is received in the ennti 11 room. the operator should note other associated alarms which mav m nie pertinent information when investigating the cause of the alarm

'n il1 alarms have been noted. the alarm is acknowledged by depressine ' L i hhutton which silences the annunciator horn and changes the -unen

,mtow from a flashing light to a continuous light.

1 7-2

i i

10-1U-11?O2-007-DI-ci Respond To Diesel Generator Generator Alarms i

investigate _the a_larm.

On ofAB. note the phase current. t sie volt age between phases and chite monitor lights kilowatts (X 1.000). KVAR ineter. and frequency (lle ).

Ditect a cAo t o the diesel generator room to determine which relay (8) has been picked up by looking for targeta flags.

The OAO should make note of shat primarv telays and lockout relays have targets showlag, and report his' findings to you.

Take correctiv 3 tions.

Should the generator trouble alarm occur, dispatch an OAO to the generator panel to attempt to locate the difficulty.

This includes checking for d'opped target flags.

Take corrective actions for " generator trouble" alarms by relay numbers as follows:

a.

132 - !<EVERSE p0WER HELAY. The diesel generator output breaker will trip (after a delav upon start) unless corrected.

The diesel generator will have been paralleled.

Observe the KW meter.

If it is very low or zero. increase power.

b.

140 - LOSS OF FIELD EXCITATION. The diesel generator and output breaker will trip when this relay picks up unless the diesel generator was emergency started.

If the diesel generator did not trip. and it is the only available supply to that train's components. closely monitor the operation of that diesel generator and the components supplied by it.

If the 140 relay picked up yet the diesel generator and components continued to operate spuriously, coordinate actions with the SRO.

c.

146 - NEGATIVE PHASE SEQUENCE.

This relay responds to an imbalsace between phases.

After the " generator trouble" alarm occurs, check the voltage and current of each phase of the diesel generator.

If the diesel generator has been normally started and was paralleled, the diesel generator output breaker will open after a time delay.

If the relay picked up due to a blown pT fase, the tripping of the 186C should be blocked due to action of the 160 (pT failure) relay.

If the diesel generator has been emerge 1cy started (LOCA). the relays picking up will still cause the " generator trouble" alarm but will not trip the diesel generator or output breaker, d.

151V/A. 151V/8. 151V/C - PilASE OVERCURRENT RE!.AYS. Any of these relays picking up on a phase overcurrent will trip the output breaker and shut down the diesel generator except on an emergency start.

If one of these relays caused the " generator t rout,le "

alarm when the diesel generator was loaded in an e2iergency start, one or more phases on the phase ammeter would have been observed reading high.

If phase voltages are low. (less than 4160V) and current is high, increasing the voltage will cause the current to decrease as long as the loail (kilowatts) remains the same.

1 7-3

4 LO-1U-ll202-007-01-Ci Respond To Diesel Generator Generator Alarms i

e.

151H - NEtfinAL OVERCL'RRENT RELAY. This alarm will cause the diesel generator to trip and its output breaker to open if the diesel generator has been normally started.

On an emergency start, the relay will cause the " generator trouble" alarm. Once the OAO has found the target on the 151N relay dropped, notify the SRO and initiate an W o. The 151N relay,. when picked up.' has detected a phase-to-ground fault by detecting current returning to the generator via the neut ral ground, f.

160 - PT FA11URE. There are two 4200V to 120V P'fs (three phases each) and their associated primary and secondary fuses on the leads between the generator and its output breaker.

These pts measure voltages used for diesel generator monitoring (meters),

controls (governor), and protective devices (relays).

The 160 relay is normally balanced across the outputs of both sets of pts.

If a PT should fail (or a PT fuse blows), the 160 relay detects the imbalance causes the " generator trouble" alarm, and blocks the tripping of 186B or 1860 when certain relavs pick up due to the PT problems.

This prevents unnecessary tripping of the diesel generator due to blown PT fuses.

If the diesel generator is running and loaded end a PT fuse blows causing the " generator trouble" alarm, observe the status of the diesel generator controls.

The phase ammeter should still indicate normal current.

Check the voltages between phases.

Note the kilowatt meter and KVAR meter.

The indicators will respond differently depending on which PT fuse blew.

If the voltage between any of the phases shows zero and a DGIA LOW VOLTAGE alarm is also present. a blown PT fuse is the usual cause.

Since one of the pts inputs to the exciter regulator and governor. closely monitor the phase current meters.

If operating conditions allow. shut d an the diesel generator. Direct the OAO to observe the 160 relay.

Initiate an MWO to have the pts and fuses checked and conditions corrected.

g, 164 - FIEl.D GROUND. This relay causes the " generator trouble" alarm when a ground is detected by the 164 relay on the generator field. Direct the OAO to observe the 164 relay for indications.

If operational conditions allow, shut down the diesel generator.

Initiate an HWO to have the condition investigated and corrected, h.

159 - Generator bus overvoltage. Ar. overvoltage on the generator bus will cause the generator trouble alarm without tripping the 186B or 186G lockout. In determining that an overvoltage condition caused the generat or t rouble alarm to 'come in, note the voltage for the bus and receive the report from the OAO that the 159 relay is showiue a ilrnpped target. If a higher voltage is noted. lower t he-M voltage to 4160V. Direct the OAO to reset the relay target. M

.he annunciator and direct the OA0 to do the same.

i.

181'- GENERATOR UNDERFREOn V

nitiates alarm only 7-4

4 LO-to-ll202-007-01-ci Respond To Diesel Generator Generator Alatms i.

127 - CENERATOR l'NDERVOLTAGE - initiates alatin only initi<te an MWO for Maintenance to investigate and repair malfunctioning equipment.

Notify the SS of the situation and get pe rmi n t ort to rnset the tatget on the teley or lockout relay.

Direct the OA0 to press the "telay target, reset" pushbutton on the genetator control panel.

Direct the OAO to reset the orange target indicator on the primary relay.

Before resetting the lockout relay. the OAO tuuut verify that the primary relay did not pick up again and that targets did not drop.

Direct the OAO to turn the handle on the lockout relay to the RESET position.

release it. and verify the red light for that 186 relay is lit.

Communicate with the OAO khile ne is resetting the TRIP-RESET handle on the lockout relay.

Log the activity.

Log the activity in the control toom log.

This must be done af ter the cause of the alarm is determined and action is taken to correct the condition causing the alarm.

Direct the OAC to call you before resetting any target flag on the DG's relay panel.

VEGP Procedure 10007-C states who may reset relavs.

the permissitn required, and certain exceptions.

E02 DGIA LOW VOLTAGE-Acknowledge the alarm When the alarm is received In the control room, the operator should note other associated alarms which may provide pertinent inforination when investigating the cause of the alarm. When all alarms have been noted, the alarm is acknowledged by depressing the ACK pushbutton which silences the annunciator horn and changes the annunciator window from a flashing light to a~ continuous light.

Investicate the alarm.

Direct the OA0 to check local instrumentation at the generator control

. panel and determine the cause of the alarm.

Observe the voltmeter and, if the output breaker is closed, obsesse i he KVAR meter. The ' alarms occurs at 3780V A0 decreasing.

Take corrective action.

Increase voltage using the DGI A V01 T im cnNTROL RAISE pushbutton on QEAB to bring the voltage back to normal ! y r, s en it elv 4160V).

If this does not appear to return the voltage to no' lifect the OAO to check the field voltmeter, the field ammeter. and '

m phases of busses.

Direct the OAO to ensure the auto regulator i-

- bv observing white lights

-illuminated above the voltage con'-

the generator control a

panel.

If the GENERATOR TR0l'BLE lit. check for voltage i

7-5

i LO-!U-ll202-007-01-Ci Respond To Diesel Generator Generator Alarms s

between phases.

If one phase shows no voltage, suspect PT problems such as a blown pT futu.

NOTE: Be alert for this alarm when the diesa! generator automatically starts.

The voltage control circuits r,ht.uld be automatically preset to the proper setting prior to start up.

I f t he. DGI A voltmet er reads low, increase the voltas'e to normal approximately 4160V. If the DC is running and powering the 4160V IE bus in response to a loss of off(ite power and the cenerator failed to develop adequate voltage during startup due to a voltage regulator malfunction. refer to procedure 13145-1 for instructions on OAO actions.

This involves:

--checking for tripped relays

- flashing the field manually

--transferring t.he generator bridge

--manually operating the voltage res;ulator Init.inte MW0s as needed for malfunctioning equipment, 1,og the activity.

Los the activity in the control room log.

E03 DGIA 111011 TEMP GEN CNTL PNL This alarm is functional when the diesel generator is operating and can be caused by:

1.

Overheating of exciter components.

2.

Rising temperature in the diesel generator room.

3.

Loss of HVAC.

Acknowledge the alarm When the alars is received in the control room. the operator should note other associated alares which may provide pertinent information when investigating the cause of the alarm.

When all alarms have been noted. the alarm is acknowledged by depressing the ACF pushbutton which silences the annunciator horn and changes the annunciator window from a flashing itsht to a continuous light.

Investigate the alarm.

This alarm occurs at 122 degrees F.

Direct the OA0 to check for high t.emperature in the diesel generatoi check the fire monitor panel for im alarms in the DG building.

The OAD met immediately report back to the control room if a fire is suspected.

Pit"rt the OA0 to check the generator panel for high temperature.

Direct . mn to ensure the generator conr+ol panel and the diesel generator toon b mitelv ventilated.

This alarm l

is functional when the DG is runnio

- 1;F fans (upstairs) should maintain DG room IIVAC.

i

LO-1U-11202-007-01-C; Respnui To Diesel Generator Generator Alarms Take corret, h:e ac t,lon.

11 the rinse of the high temperature cannot be determined, initiate an MWO for Maintenance to investigate and correct the condition.

If a fire is suspected activate the fire alarm announce the fire throughout the plant.

and notify the fire brigade per 92005-C. ' Tire Response procedure. "

4 tog the activitv.

Log the act tvity in the control room log.

E04 DGIA LOW EXCITATION This alarm could be caused by a problem with the exciter regulator or by the generator being operated with a leading reactive power.

Acknowledge the alarm When the alarm is received in the control room, the operator should note other associated alarms which may provide pertinent information when e

investigating the cause of the alarm.

When all alarms have been noted, the alarm is acknowledged by depressing the ACK pushbutton which silences the annunciator horn and changes the annunciator window from a flashing itght to a continuous light.

investigate the alarm.

Observe the incoming EW.Rs.

If the diesel generator is being operated parallel with an of f-site feedar.. increase reactive power.

Take corrective action.

Initiate positive VARS loading by placing the voltage control switch in the RAISE position.

If the problem appears to be a malfunction and the operating conditions allow (refer to Tech Specs), shut down the DG and initiate an MWO.

Log the activity.

Log the activity in the control room log. Notify the SS of the situation.

E06 DG1A TRIP GENERATOR FAlli Acknowledge ghe alarm When the alarm is received in the o nttot room, the operator should note other associated alarms which may pinvide pertinent information when investigating the cause of the alarm W n all alarms have been noted, the alarm is acknowledged by depressirr ' N-

\\rK pushbutton which silences the annunciator horn and changes the annu ido window from a flashing light to a continuous light.

1 7-7

-4 4

1.0-It!-11202-007-01-C; Respond To Diesel Generator Generator Alarms investigate the alarm.

Ibi7 ildtm will tprear when the 1868 and 186C trip and lockout relays have t ri pp-i, This alarm is similar to the generator trouble alarm.

but indicates primarily that the 186B or 1860 has tripped in response to a genent or pr obl+m.

186B will trip on currents on:

1.

loss of field 140 relay, 2.

phase ove cutient 151VA, 151VB. and 151VC.

3.

neutral ground overcurrent 151N.

186C will trip after a time delay if the following occurs:

1.

Reverse power telay 132, 2.

Negative phase sequence telay 146.

Direct the OAO to determine which 186 lockout relay has tripped by locating the relays on the generator control panel and noting which relays have targets showing, llad the 186B tripped and locked out, the DG would have stopped and the breaker would have tripped unless the DG was running for an emergency start. If the DG had been rutming in parallel with tb e normal supply from the RAT. the 1860 will trip the DG breaker: the engine keeps t urming.

Take corrective action.

When the OA0 reports which lockout tripped and which protective relay has targets. record this information.

The SS will make decisions involving resetting the relay targets.or lockout relay. When a DC lockout relay is tripped, its red pilot light is off. When it is reset, the red pilot light indicates continuity through the 186 trip coil.

Initiate an MWO for Maintenance to investigate the tripped relay if equipment problems are suspected. Direct the OA0 to reset the relay target.

Log the activity.

Log the activity in the control room lag.

E07 TRIP GEN DIFF Acknowledge the alarm When the alarm is received in the control nom. the operator should note other associated alarms which may provide pertinent information wheti investigating the cause of the alarm.

When all alarms have been noted, the alarm is acknowledged by depressing the ACK pushbutton which stlences the annunciator horn and changes the annunciator window from a flashing light to a continuous light.

Investigate the alarm.

The probable cause for this alarm k inv one or more of the three 187 differential relays sensing differeatla1 cutrent.

A 187 relay is designed to be a sensitive relay that protects th. genetatut by causing the diesel 7-8

. ~.

-. _ ~. - - -

4 LO-U-ll202-007-01-C: Respond To Diesel Generator Generator Alartas engine and excitation to shut dom and the generator breaker to open should a phue-to-phase vvercurrent occur.

.A 187 telay picking up will cause the trippine functie u to initiate.

This diesel generator trip is available even daing emetgency startups.

Ensure that the diesel generator shuts down.

Direct the OAD to look at the generator f tom the outside and check for hot spots, smoke. fire. odors of burning. or burning electrical insulation.

Direct the OAO to make notes of t elay target s showing at the generator cont rol panel.

Direct the OAD to check other 186 lockout relays which nuty have tripped and teport his findings.

Take corrective action.

Direct Electrical Maintenance to investigate the ttip.

Refer to Technical Specifications. since the diesel generator will be out of service until repairs have been made.

Notify the SRO of the situation. A situation like this will also involve opetability tests before the DG can be declared I

operable again.

NOTE: Do not, attempt to restart the diesel generator untti the cause of the trip has been determined.

If the condition causing the trip

- i has been corrected and approval from the SR0 has been obtained. direct the OAO to depress the target reset pushbut ton on the generatoe control panel, reset differential relay target flags. then reset 186A.

The emergency trip reset pushbutton can be reset once the 186A lockout has been reset.

Log the activity.

1 Log the activity in the control room log.

On an actual generator differential situation the DG will be inoperable for investigation.

repairs. and operability testing.

E08 DGh A HIGli TEMP GEN BEARINGS

. Acknowledge the, alarm When the alarm is received in the control room, the operator should note other associated alarms which may pr ovide pertinent information when investigating the cause of the alarm.

When all alarms, have been noted, the alarm is acknowledged by depressing the \\cK pushbutton which silences the annunciator horn and changes the annunciator window from a flashing light to a continuous light.

investigate the alarm.

This alarm occurs at approximatelv 1d W teen F at the generator bearings and is usually caused by low oil b i failure of the generator pedestal bearings.

1-n

-i...,_.-w.-

.-..,-.._,,,,..,._..,,...,..r.-,,m...m.,,,,m-,,

.,._,-,-_e.~._-

,...,__e,_,.

-.,.,.,~,.,,.r

m.

LO lU-ll;'02-007-01-C Respond To Diesel Generator Generator Alarms Direct the OA0 to check the bearing oil temperatute and level locally.

The bearine tempe:4ture is indicated on a digital rendout on PDG1 (pDG3) and the ati level should be visible through a round sightalass. Direct the OAO to look for oil leaks or s,moke at the pedestal bearings.

f Take corrective action.

If the oil level is low and temperature is confirmed as being high. shut down the DC and initiate an MWO for Maintenance to add oil or to investigate any leak.

If the alarm appears to be caused by a generator hearing. refer to Technical Specifications since the DG would be inoperable. The other D0 and its train of safeguard equipment. will have to be fully operable. Notify the SRO of the situation,

!og the activitv.

Log the activit y in the control room log.

D0ti-DGI A GENERATOR UNDER FREQl'ENCY Acknowledge the alarm When the alarm is received in the control toom, the operator r.hould note other associated alarms which may provide pertinent information shen

-investigating the cause of the alarm.

When all alarms have been noted the alarm is acknowledged by depressing the ACK pushbutton which silences the annunciator horn and changes the annunciator window f roir, a flashing light to a continuous light.

Investigate ihe alarm.

This alarm is caused by underfrequency conditions when the diesel generatnr is running.

If not corrected the 186G lockout relay will trip.

This will trip the breaker after a time dela* if the diesel generator is running.

parallel with an off site feed.

If the DG is running isolated (unit)._ the alarm may occur with DG starting, stopping, or frequency deviations to 59.5 lia due to loads.

Take corrective action.

If the diesel generator is running in the Unit Mode (not paralleled to the normal ESF bus supply breaker). biine the frequency back to 60 Hz by pressing the RAISE speed pushbutton, if the diesel generator is tunning in the Parallel Mode with underf requem s uut an of f-site power causes the generator output breaker to open, st -. the diesel generator and notify the SRO. Do not try to parallel the diewl avain until the off-site (system) frequency has returned to normal

( t o !I.+ ).

When the frequency has been returned to normal. direct the OAO -

!--et the underfrequency relay.

Log the activitv.

Log the activity in the control ro,'

b

.r,m..~.

a m e r-

.twm.

. r m e +

=e+e-"m-~~wM

i 10-Iti-11202-007 01-Ci Respond To Diesel Generator Generator Alaims 1

i i

PERFORMANCE GUIDE i

)

Follow these steps to respond to the renerator alatms associented with the i

i diesel genetator.

[

1.

Acknowledge the generator alat'm associated with the diesel.,enerator.

l

(,

2.

Xnvestigate the alarm, i

3.

Take corrective action.

4.

Log the activity.

c k

c

. -T I

4 a

L 4

L'.

f-B f

)

)

i I

2 1

4 9

7.[t m

... 2.-

r 6

LO-IU-11202-007-01,-C Respond To Diesel Generator Generator Alarms SELF-TFST Before proteeding to the Task Practice, answer the following questions.

1.

List the primary relays which can cause the GENERATOR TROUBLE alarm.

2.

State the primary purposes of the 186B and 186C lockout relays, and how the diesel engine and output breaker respond to the tripping of each type at lockout relay.

4 h

4 L

g i,..=-,.f, e-e

,s-.w

+.-v..,,.._,-e se v,

--r.

r., - ---w,-

,-s-

..w---a,-,-rm_.

, - -. ~, =,.. -

.-w,.-,--.

3.- - -,,-.-- --

e-

.t LO-Itt-11202-007 01-C: Respond To Diesel Generator Generator Alarms o

AN %T P4 1,

4. 132 Revdrse power telay
b. 140 loss. of excitation relay
c. 146 Negat(ve phase sequence relay
d. 1$1VA. 1$1VB. 1$1VC voltage restrained overcurrent relay for each phase 1$1N Neutral ground overcurrent relay e.

f 159 Cenerator bus overvoltage relay

g. 160 Potential transformer f ailure relay h.-164 Generator field ground relay
1. 181 Underfrequency relay 2.

The primary function of the 186B-lockout relay is to trip the DSL GEN l

output breaker and shut dwn the diesel engine and generator. except in safety injection conditions.

The primary function of the 186C lockout relay is to trip the DSL CEN output breaker when the diesel engine is operating in parallel with the preferred power source, The diesel engine continues to run after the 186C lockout relay has tripped.

F 0 -

7.---- -,.. a.-

--, u. -. : -

e 4

i 5

- 1,0-1U-11202-007 C 1 Respond To Diesel Generator Generator Alarms TASK PRACTICr.

7 Before proceedfug to the' Performance Test. complete the following Ta,sk Practice exeteise(s).

i 1;

Review Procedure 17035-1.

Be sure that you understand all precautions. limitations, and steps associated with responding to DG

" Generator" alarms.

2.

Take this instructional unit and Procedure 17035-1 to the control room or simulator.

He sure that you can locate all instrumentation

{

associated with responding to DG " Generator" alarms.

-3.

In the-control room or simulator. Simulate responding to DG

" Generator" alarms.

If possible, have a fellow trainee evaluate your performance using Procedure 17035-1 and this instructional unit.

t i

P e

h

.h 5

s t


..n

- - - ~ - - - - = -

?

t k

I,0-10-11202-007-01-C1 Respond To Diesel Generator Generator Alarms s

I FFEDtlACK ON TASK PRACTICE

}

-l 1.

If you have any questions about the piecautions. limitations. or. steps in Procedure 17035-1. ask your instructor.

l 2.

You should have been able to locate all instrumentation a ssricia t ed l

with responding to DG " Generator" alarms.

If you had any difficulty.

ask your instructor for help.

t 3.

You Should have simulated the steps necessary to tespond to diesel

'{

generator " Generator" alarms.

If you had any difficulty. te-read the pertinent sections of this instructional unit and the procedure.

Resolve any questions with your instructor.

j.

.l l

=

i

~i a

7-1~

. ~. -. -..

.