ML20107A786
Text
,..
e 1
UNITED ST ATES J.'N',*h.
?
ATOMIC ENERGY COMMISSION oincerOnaTr Or arcuu TOHV OPr R AYlON5 j
..s.
neciOu i
. 4.,
enamemamresemensx hW Mm 631 Park Ave.
King of Prueste, Pa.
19406 October 3, 1973 Mr. Schuyler Mott, Librarian Docket Ocean County Library 50-363 15 Hooper Avenue Toms River, New Jersey 08753 Gentlemen:
Enclosed are copies of correspondence between Region I, Directorate of Regulatory Operations, and Jersey Central Power and Light Company (JCP&L).
This correspondence is submitted pursuant to arrangements made with the Public Proceedings Branch, Office of the Secretary for j
use by the public.
Where possible, these materials should be punched and filed in a folder labeled as follows-Correspondence to and from Applicant or Licensee
-(Excluding Enviro.nmental & Antitrust)
Sincerely, e
Joe E. Sefth Administrt.tive Officer I
Enclosures:
p\\j\\
1.
Abaemal Desarrence to B0:I dtd 9/10/73 rpt me. 73-19.
1 2.
Absemal Occurrence to RD I dtd 9/10/73 rpt me. 73-20/
j 3.
Abnernal Osourrense to n0:1 dtd 9/10/73 rpt me. 73-22.
4.
Abnomal Oseurrence to E0:1 dtd 9/10/73 rpt so. 73-22.
5.
Ltr fr Jersey Central Poeer & Light Co. to 30:I dtd 8/31/73.
6.
30 I ltr to Jersey Central Power & Light Co. dtd 8/23/73 w/rpt 50-219/73 06.
7.
R0:1 Itr to Jersey Central Power & Light Co.eded 8/29/73 w/rpt 50-363/73-03.
8.
R0:1 Itr to Jersey Central Power & Light Co. dtd 8/29/73 w/rpt 50-363/73-04 cc:
Central Mail 6 Files Unit, Document Roce Cler w/o enc 1.
9604150120 960213 PDR FOIA DEKOK95-259 PDR
l JD, Jerscy CenthI Power & Light C )mpany, e
kd' . g
- m.,s M AolSoN AVENU E AT PUNCH BOWL Ro Ao e MoRRisToWN. N.J. 07960 e s39 6111 cp (n
%cd @ o October 3, 1973 4
i 9-Op 'Ibb k,'/ o.r..s o J
a Mr. A. Giambusso cy%
N J2 Deputy Director for Reactor Projects 9
- R,. ' ' '. ' cr i
Directorate of Licensing 8/Ar United States Atomic Energy Commission If
/
Washington, D. C. 20545
.,43 p
Dear Mr. Giambusso:
Subj ect:
Oyster Creek Station 4
Docket No. 50-219 Differential Pressure Switch Failure
[
The purpose of this Ictter is to report a failure of differential pressure switch DPS66A to trip and thereby actuate the reactor building to torus vacuum breaker block valves, V-26-16 and 18.
This event is considered to be an abnonm 1 occurrence as defined in the Technical Specifications, paragraph 1.15.D.
Notification of this event as required by the Technical Specifications, paragraph 6.6.2.a., was made to AEC Region 1, D'irectorate of Regulatory Operations by tele-phone on Sept ember 24, 19'3 and by telecopier on Septeuber 25, 1973.
h'hile per' forming routine surveillance testing as required by the Tech-nical Specificat. ions, paragraph 4.5'.1.5., diff' rential pressure switch DPS66A i
e failed to trip.
The cause for this failure was determined to be due to excess friction in the linkage pivots.
1 The switch wcs removed, disassembled and c1 caned.
After reasscubly and insta11ction, the unit was satisfactorily trip-tested twenty times and roturned to service.
Details of the switch are:
Manufacturer:
Dwyer Mo, del Number:
163512 y
llistory of Failures:
No previous failures.
/
--ted in the Technical Specifications, "The absorption chamber-a-
reactor building vacuum relief system assures that the primary containment is not opernted at a negative pressure relative to its surroundings.
The vacuun re-
- lief systen is a redundant system and full capacity is availabic through either valve,"
1:urther, the differential pressure switches are themselves redundant in that either pressure switch will actuate both block valves.
In this case, since one of the r.wi t ches was operable, full relief capacity would have been provided through yin s o, A r 2 >
Osvvu - -
- ~
ff.
..,s..,,
A
/H ))
.4
.M g
h
,) -
s' 4
t' Mr.. Gi ninbus so October 3, 1973 l
.cither valvo since' both would have.bcen available. The significance of this event then is the loss of redundancy of the actuating switches.
Th'c redundant different.
pressure switch DP566B will be disassembled
)
and c] caned. No further action is planned at this time since this is believed to be an 1solated occurrence based on four (4) years of satisfactory performance,from these switches.
Enclosed are forty (40) copies of this report.