Temporary Procedure to Rev 0 to Temporary Procedure T-ENG-90-14, Unit One Train B DCP 88-VIN0070 Sequencer Functional
ML20092G747
Person / Time
Site: Vogtle 
Issue date: 03/27/1990
From: Bockhold J
GEORGIA POWER CO.
To:
Shared Package
ML20092F288 List: ... further results
References
CON-IIT05-061-90, CON-IIT5-61-90, RTR-NUREG-1410 T-ENG-90-14, NUDOCS 9202200333
Download: ML20092G747 (14)


Text

\\ ;;,;;;,

l

4 PAOCEDURE NO o s' - G / - PO LEVISION FAGE NO VEGP 00053-C 3

12 of 13 2

TEMPORARY PR0('EDURE APPROVA! FORM TEMPORARY PROCEDURE NUMEER }.f/J6 '!C'/ V UNIT C N E TITLE Un,t Cne.hn B DLP G-YlfJDO70 Sf6dfNUR FUULTECNhL REV O

CIiE TIME USE ONLY:

YES,f NO: IF NO, TERMINATION DATE TiW! 2C/T PURPOSE:

Th is P.1 2dm. L. st Fu,u t.a.a b.1-A c.imin s e. n ia.le-6 ds.FCn. Nm B.h 6ue.ica-h, DC P%'R - Yt NCC';O PRB REVIEW REQUIRED:

>C YES NO ORIGINATED BY Du thw % 2

/3/U/7U ON-SITE X OFFSITE DATE COGNIZANT SUPERVISOR R.

't DATE 3 D DEPARTMENT mal.AGER/ SUPT _.

h, bh DATE 3' Oid

(

PRB REVIEW (if recuired),

MEETING NO, 3DM DATE 3/M/90 4

RECOMMEND:

(vfAPPROVAL

( ) DISAPPROVAL - Return to responsible department Mgr./ Supt.

j UNREVIEWED SAFETY QUESTION INVOLVED:YES ( )

NO (4 PRB CHAIRMAN d'7 htl%S GENERAL MANAGER - NUCLEAR PLANT (if required)

DISPOSITION:

(

APPROVED

( ) REJECTION REASON FOR REJECTIOff

/

bbkf b/27 SD v

GENERAL MANAGER - NUCLEAR PLANT DATE /

(N FIGURE 2 9202200333 920116 (Example)

.'I V I

I PDR ADDCK 05090424 S

PDR resus

- - - - - - ^

/EuP 0000S6-C Dev 9 E + :, a g 1/ of 19 LO Li'MINaiiLtN OF NLED F OP OAFETY EV ALUA 1 1014 6HE.E 1 i UF 2 Doc u,a r,t 1D No. T-ENG-90-14 Rev. 0 SEC T ! Uf J 1.0 1.1 Descraption of proposed change. test, n r. e x p er i.v.e r.t 1 This procedure will f unc ti onal l y test the U/V RESET OWITCH the remote U/V reset relay (K311), the D-G Brkr Fail To Close relay (K317), and the U/V Roset Enable relay (K306).

The Train B 4160V Switchgear will be de-energized and the D-G output breaker will be locked out during the performance of thi s: procedure. - The Train'B Sequencer will receive a U/V signal and will operate the sequencer output relays.

This test will prove that the Sequencer can be manually reset by the U/'s RESET SWITCH or relay K311 if the D-G output breaker does not close.

It will also prove that the Sequencer cannot be reset by the U/V RESET SWITCH or relay K311 while the D-G output breaker is closed and the Sequencer is cycling.

1.

w won for proponed change, test. or experiment:

This procedure is being performed as a functional test for modifications made by DCP 88-VlN0070.

1. :

Does the proposed change 2nvolve a change to Technical ipecit1catians?

Yes No X

L oim Mton:

This is a functional test of modifications made in the reset logic of the Sequencer and does not require a change to the. Technical Specifications.

Tech.

Spec. sections 3/4.3.2 and 4.8.1.1.2.h do not address testing of the sequencer with a de-energized buss.

1.4 Dces the proposed chanae lino)vu a change in the f aci it y es described in the F 9WJ Yes No X

! - p i vu m t l on :

This procedure does not involve a change in the facility as described in FSAR secti ons 8. 3.1.1.2.K or 8.3.1.1.3.F.

The Sequencer is not discussed in this l e.v el of detail in the FSAR.

l l

l l

' A U. E r et 1 '.

!_<m<

t !,.

ti op

_+ u t t, t i n j +.

ira O!,

c h d i o s.. In pr, E rj i

  • s u.

.m a t;i

,,'s

.c N,

X L> p l oric ti ot.:

This procedure does not involve a change in procedures as described in Section 8. 3.1.1. 3. H. 3 or Chapter 13 of the FSAR.

1.

a:

tra pr a d rta n.; i n,ul e n

':e

,r

- i pet 2 m ot t

<-t W

s ta ci li.

h_

! ~; ~J ve Uc.

X

E2plsi,

.i; This procedure does not inval ve a test or experiment not described in the FSAR.

This procedure will cycle the Sequencer as in tests outlined in FSAP Sections 8.3.1.1.3.H.3.a and b except this test will not operate any major plant equipment due to buss 1DA03 being de-energ1:ed,

+ $h toj;

,r M

i 4

Date 3 - 2. 7

  • /u... -

a.- { ;

r D+th_

os e m.r,.

..- -.,- _ e,

_n

~l mat.: !ind,

'11 D t-r p 3 r 1 i st 6 r.

,i L.

1=i -e

,.i MOD i i ( - t i O r, 2,O aa ; -.. )

~

t>

F.-

.;q I 4:a !

'ri.

i a

@RoCEDUAE No REvlsioN PaGE NQ VEGP 00056-C 9

19 c f 19 ENVikONMENTAL EVALUATION DETERMIFATION Document ID: T. 24

'n ~

/-/

Revision No.:

O 1.

Could implementation of this document pose adverse environmental effects of any type either directly or indirectly?

(Unit 1 and Unit 2 Operating License, Appendix B)

Check a or b

()

a.

Possibly.

(Explain):

e pl b.

No.

The nature of this document is such that it will not result in a condition which significantly alters the impact of the station on the environment.

l Evaluator 7/ 1 /,, [ c [ ~ M [.

Date M 7/

Supervisor I

o Date bd"/d 2.

If an environmental question is posed (item la is checked) the document will not be approved until evaluated.

Forward the package to the Health Physics / Chemistry Department for an environmental review, i

3.

Attach completed environmental review and return to the l

evaluator (item 1) for continued processing.

P FIGURE 2 e

-. _.. _ _. _ _.... _... _ _ _... _ _... _... _ _ _. _..... ~... _ _. _.

F, 1

1 a

i i

t i

1 1.

i i

i T-ENG-90-14 l

Rev 0 i

UNIT ONE TRAIN B-l DCP 88-V1N0070 SEQUENCER-FUNCTIONAL-TEST-I D.W.

HINES

+

l Expiration Date April 20,_1990 i

= Approval:

/

WI[Ph 27 fO-iDate: 2 i.

1' l

T-ENG-90-14 PAGE 2 OF 9

1.0 PURPOSE

This procedure will test the U/V RESET SWITCH and the remote U/V reset relay (K311) installed in Unit One Train B Sequencer. A Sequencer Operability Check along with this procedure will complete the functional test requirements of DCP 88-V3N0070 for Train B. The DG Brkr Fail To Close relay (K317) and the U/V Reset Enable relay (K306) will also be tested in this procedure.

2.0 PRECAUTIONS AND LIMITATIONS:

2.1 This test, once begun, shall be carried through to completion. If the test must be interrupted, then a detailed explanation of the interruption must be entered into the log.

2.2 Operator assistance should be obtained to operate equipment as required.

2.3 Observe all appropriate precautions and limitations in the plant operating procedures for the equipment operated during this test.

2.4 Prior to the start of the test, the Responsible Engineer shall review the Prerequisites and Initial Conditions, Section 4.0.

2.5 All procedural steps may be signed off by the Responsible Engineer, Shift Supervisor, or designated individual.

2.6 All switches and lights are located on the Unit One Train B Sequencer Test Panel unless otherwise stated.

2.7 Train A 4160Vac (1AA02) is meeting the electrical needs of Unit One. Train B 4160Vac (lBA03)

.switchgear will be de-energized during this procedure.

2.8 Alarms generated during performance of this procedure may be reset at the discretion of the Responsible Engineer.

2.9 Relay K311 may be removed to connect and disconnect the temporary power supply.

t T-ENG-90-14 PAGE 3 OF 9 3.0 MEASUREMENT AND Tf.ST EQUIPMENT 3.1 Volt-ohm meter,Simpson model 260 or equivalent, for monitoring a K317 spare normally open contact.

This meter will check the operation of K317 relay and will be referred to as relay K317 in this procedure.

3.2 Volt-ohm meter,Simpson model 260 or equivalent, for monitoring a K306 spare normally open contact.

This meter will check the operation of K306 relay and will be referred to as relay K306 in this procedure.

3.3 Stop Watch. The stop watch will be used to check 4

the approximate time of relay and light operation.

3.4 A 48Vdc power supply to operate the remote U/V reset relay K306.

3.5 A switched jumper that will be used to simulate DG1B breaker (1BA0319) is closed.

4.0 PREREQUISITES OR INITIAL CONDITIONS:

4.1 The Responsible Engineer has reviewed Section 2.0

/

4.2 The Unit One Train B Sequencer is in normal operating mode.

/

4.3 The Diesel Generator Output Brkr, 1BA0319, is open.

1 4.4 Establish communications, using sound powered phones, from the Unit One Train B Gequencer panel to the control room.

/

T-ENG-90-14 PAGE 4 OF 9 4.5 The Unit one Shift Supervisor has given permission to nerform this test.

J'

}

SS Signature Date Time 5.0 TEST SECTION 5.1 Initial Setup 5.1.1 Connect a VOM across a spare normally open contact, 8 and 9, of relay K317.

/_

5.1.2 Connect a VOM across a spare normally open contact, 4 and 5, of relay K306.

/

5.1.3 Set the DC voltage supply for approximately 48Vdc.

/

5.1.4 Connect a 48Vdc supply, supply turned off, across the coil, 6 and 7, of relay K311.

/-

Section 5.1 Complete

/

sign date 5.2 SEQUENCER TEST - U/V RESET WITH DE-ENERGIZED BUSS AND DIESEL GENERATOR 1B NOT RUNNING 5.2.1 Place DG1B OUTPUT BRKR (HS-1BA0319 at QEAB) into PTL.

/

5.2.2 Place the DG1B in the LOCAL MAINTENANCE mode.

/

T-ENG-90 14 PAGE 5 OF 9 NOTE THE FOLLOWING STEP WILL DE-ENERG128 BUBS 1BA03.

5.2.3 Open the PRFP NORM INCM BRKR (1BA0301)

J 5.2.4 Wait 60 seconds for time delay relays to operate.

/

R 5.2.5 Using the toggle switch located on the card in slot A4-2, reset the "3 UV in 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br />" card.

One of the lights on this card should illuminate after reset.

]

/

5.2.6 Verify relays K317 and K306 are energized.

/

5.2.7 Verify the UV RESET SWITCH is illuminated.

/

NOTE Step 5.2.11 will cccur approximately 15 seconds after step 5.2.8 is performed. Start the stopwatch at step 5.2.8 5.2.8 Depress the UV RESET SWITCH.

/

5.2.9 Verify relays K317 and K306 de-energize.

/

5.2.10 Verify the UV RESET SWITCH is not illuminated.

/

f T-ENG-90-14 PAGE 6 OF 9 5.2.11 Verify relay K317 energizes approximately 15 seconds after the UV RESET SWITCH was depressed.

/ __

5.2.12 Verify relay K306 energizes and the UV RESET SWITCH illuminates approximately 60 seconds after the UV RESET SWITCH was depressed.

/

NOTE Step 5.2.16 will occur approximately 15 seconds after step 5.2.13 is performed. Start the stopwatch at step 5.2.13.

5.2.13 Momentarily energize relay K311.

/

5.2.14 Verify relays E317 and K306 de-energize.

/

5.2.15 Verify the UV RESET SWITCH is not illuminated.

/

5.2.16 Verify relay K317 energizes approximately 15 seconds after relay K311 is energized.

5.2.17 Verify relay K306 energizes and the UV RESET SWITCH illuminates approximately 60 seconds after relay K311 is energized.

-/

T-ENG-90-14 PAGE 7 OF 9 5.2.18 Using the toggle switch located on the card in slot A4-2, reset the "3 UV in 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br />" card.

One of the lights on this card should illuminate after reset.

/_

Saction 5.2 Completed

/

sign date 5.3 SEQUENCER TEST - U/V WILL NOT RESET WHILE SEQUENCER IS CYCLING 1;OTE The following steps must be performed before the Sequencer step timer completes the sequence steps (approximately 30 seconds).

The sequence will begin when step 5.3.1 is performed.

5.3.1 Place a jumper from 1TB51-1 to 1TB51-3

/

5.3.2 Verify the Sequencer begins to sequence by observing the Elapsed Timer is running.

/

5.3.3 Depress the UV RESET SWITCH.

/

5.3.4 Verify that the Sequencer does not reset by observing the Elapsed Timer does not restart from O.

/

5.3.5 Momentarily energize relay K311.

/

i l

- -)

T-ENG-90-14 PAGE 8 OF 9 5.3.6 Verify that the Sequencer does not reset by observing the Elapsed Timer does not restart from O.

/

5.3.7 Remove the jumper from 1TB51-1 to 1TB51-3.

/

/

IVOR Section 5.3 Complete

/

sign date i

6.0 RESTORATION 6.1 Remove all test equipment.

1) VOM connected to relay K317

/

/

IVOR

2) VOM connected to relay K306

/

4

/

IVOR

3) Power supply connected to relay K311

/

/

IVOR 6.2 Verify K311 is installed ccrrectly.

/

/

IVOR

T-ENG-90-14 PAGE 9 OF 9 6.3 Inform the Unit One Shift Supervisor of the completion of this test and 1BA03 may be returned to service.

/

7.0 ACCEPTANCE CRITERIA 7.1 All steps have been completed satisfactorily.

/

l i

l

v PROC / REY. NO. TEtJ Cf - Go -pf O f-C ) - 3 {.

T0:

M W flue ( on PRB C0fMENT REVIEW SHEET I

Page of

.THRU:

PRB 90-W Date N27/90 The PRB has reviewed the attached procedure and recossmends approval with comments as noted below.

Nndatory (H) consnents shall be incorporated prior to approval of the procedure.

If not incorporated the procedure shall be resubadtted to the-board.

You have the responsibility to determine whether the Optional (0) comments should be included at this time, saved for later inclusion, or otherwise resolved.

This procedure does not constitute an unreviewed safety of;estion.

No.

Section M/0 PR8 Inif.ials Conuments Resolutions i

M at,A Er, sttre-

! Mods u&cead w W Ct ; 4 r t M ;;i Q pa,ce w e ne a accorcot-,a 1 e- " - ~ -

~"

LD L fl.-

DD3b]-(_

wesprpo 0

2-nA L<)he r, us aun Vokf. Sh m f</ s k f-c

$* n.. <a.. c noo & f r$trrobee or W)LuvaLcr,+.

3 SO.Q"'

b1 C,EF

' C hu.cc. 57.9 h 5 2 %. ChtCL Y

L ~ ~:M wt.W pirc.cs u, proct b re 7,

1 l

1 j

=

Changes to this procedure other than those addressing the board's cosaments will require resubssittal to the board. Upon resolution of the above comments, the procedure should be forwarded.to the General mnager for approval. Upon approval' the procedure should be returned to the PR8 Secretary for further processing.

PRB Chainr.an T417 kdu

^

Attachment