Septcober 14, 1977 g f () Q Q Mr. J. G. Keppler, Director Region III Office of Inspectica and B1forcerent thited States hbclear Regulatory Comission 799 Roosevelt Road Glen Ellyn, IL 60157
Dear Mr. Keppler:
IDNTICEZ,10 MELF.Ut CENERATING PIANT Dacket No. 50-263 License hb. DPR-22 On Setenber 13, 1977, local leak rate testing of the Core Spray Inboard Isola-l tion Gieck Valve, AD 14-13B indicated that the Icakage execeded ~ the Tecimical Specification acceptance en,teria for individual isolation valves. The nea-sured Icakaga was approxinately 226 SCIH. The total testable penetration and isolation valve leaksge rate acceptance criteria specified by the Technical Specification.s was also exceeded when this valve was tested. On Septerber 14, 1977, local leah rate testing of the RCIC Tsaust Line Isolation Check Vahe, RCIC-9, indicated that the leakage exceeded the acceptance criteria for' individual isolation valves. The cause of the high leakage rates is being in-vestigated.
Yours very truly, kY f$A$l
~
L. R. Elikson Plant Manager IE/5d3 cc: Director, Office of Mmagement Infomation G Progran-Control G. Otarnoff
~
Minnesota Pollution Control Agency Attn:
J. K. Perman File Copy sent by telecopier to Keppler.