MONTHYEARML20137H9751997-03-25025 March 1997 NPDES Noncompliance Notification:On 970215 Discharge Monitoring Point 203 Exceeded Allowable Monthly Average of 30 Mg/L for Total Suspended Solids ML20101K8061996-03-21021 March 1996 NPDES Noncompliance Notification:Epa Discharge 008 Exceeded Allowable Monthly Average of 30 Mg/L for Total Suspended Solids ML20083D7361991-09-16016 September 1991 NPDES Noncompliance Notification:On 910805,Discharge 101 Exceeded Max Spec.Maint Insp Revealed Damaged Protective Liner in Regernerant Storage Tank Which Allowed Corrosion to Occur & Affect Effluent Quality ML20082R7831991-08-23023 August 1991 NPDES Noncompliance Notification:On 910703,Unit 1 Chemical Waste Sump at Discharge 101 Exceeded Daily Max Spec of 100.00 mg/1 Total Suspended Solids.Regenerant Hold Tanks Inspected for Excessive Corrosion ML20247N3841989-07-18018 July 1989 NPDES Noncompliance Notification:Monitoring for Chlorine Residual at Discharge 001 Discovered Being Performed by Daily Grab Samples Rather than Required Chlorine Analyzer. New Chlorine Analyzer Scheduled to Be in Svc 891231 ML20246C1791989-06-27027 June 1989 NPDES Noncompliance Notification:On 890503,oil/water Separator Out of Spec for Daily Max of Oil & Grease. Separator Removed from Svc,Baffle Plates Removed & Cleaned & Separator Reassembled & Returned to Svc ML20133D2671985-07-0909 July 1985 NPDES Noncompliance Notification:On 850604,sample Taken of Discharge 113 from Sewage Treatment Plant Out of Spec in Fecal Coliform Bacteria Count.Caused by Low Chlorine Residual in Effluent Stream.Chlorine Pellets Added ML20081E0141983-10-0404 October 1983 NPDES Noncompliance Notification:On 830930,EPA Discharge 013 Sewage Treatment Plant Found Out of Spec in Total Suspended Solids.Caused by Excessive Solid Buildup in Clarifier Coupled W/High Flowrate.Solids Removed 1997-03-25
[Table view] Category:TEXT-ENVIRONMENTAL REPORTS
MONTHYEARL-99-147, NPDES Discharge Monitoring Rept for Aug 1999 for Bvps,Units 1 & 2. with1999-08-31031 August 1999 NPDES Discharge Monitoring Rept for Aug 1999 for Bvps,Units 1 & 2. with L-99-133, NPDES Monthly Discharge Monitoring Rept for July 1999 for Bvps,Units 1 & 2. with1999-07-31031 July 1999 NPDES Monthly Discharge Monitoring Rept for July 1999 for Bvps,Units 1 & 2. with L-99-123, NPDES Discharge Monitoring Rept for June 1999 for BVPS, Units 1 & 2. with1999-06-30030 June 1999 NPDES Discharge Monitoring Rept for June 1999 for BVPS, Units 1 & 2. with ML20196H4401999-05-31031 May 1999 NPDES Discharge Monitoring Rept for May 1999 for Bvps,Units 1 & 2.With ML20195B9431999-04-30030 April 1999 NPDES Discharge Monitoring Rept for Apr 1999. with ML20206E8611999-03-31031 March 1999 NPDES Discharge Monitoring Rept for Mar 1999 for Bvps,Units 1 & 2. with ML20205C3571999-02-28028 February 1999 NPDES Monthly Rept Discharge Monitoring Rept for Feb 1999, for Bvps,Units 1 & 2.With ML20207A6371999-01-31031 January 1999 NPDES Discharge Monitoring Rept for Jan 1999 for Bvps,Units 1 & 2. with ML20206G3451998-12-31031 December 1998 1998 Annual Environ Rept,Non-Radiological ML20206G3391998-12-31031 December 1998 1998 Annual Environ Rept,Radiological ML20205F6911998-12-31031 December 1998 Bvps,Units 1 & 2 Annual Radioactive Effluent Release Rept for CY98 ML20206P1891998-11-30030 November 1998 NPDES Discharge Monitoring Rept, for Nov 1998 for Bvnp Units 1 & 2.With ML20155D0961998-09-30030 September 1998 NPDES Discharge Monitoring Rept for BVPS Units 1 & 2 for Sept 1998. with ML20154B0171998-08-31031 August 1998 NPDES Discharge Monitoring Repts for Aug 1998 for BVPS, Units 1 & 2. with ML20151T8211998-07-31031 July 1998 NPDES Discharge Monitoring Repts for July 1998 for BVPS, Units 1 & 2 ML20236V4261998-06-30030 June 1998 NPDES Discharge Monitoring Rept for June 1998 ML20236F4441998-05-31031 May 1998 NPDES Monthly Rept for May 1998 for Beaver Valley Power Station,Units 1 & 2 ML20248D2101998-04-30030 April 1998 NPDES Discharge Monitoring Rept for Apr 1998 for Bvps,Units 1 & 2 ML20217P6901998-03-31031 March 1998 NPDES Discharge Monitoring Rept for Mar 1998, for Beaver Valley Power Station,Units 1 & 2 ML20217J4051998-02-28028 February 1998 NPDES Monthly Rept for Feb 1998 ML20203L3381998-01-31031 January 1998 NPDES Discharge Monitoring Rept for Jan 1998 for Bvps,Units 1 & 2 ML20217K0291997-12-31031 December 1997 Annual Effluent Release Rept for 1997 L-98-011, Annual Rept of Number of Personnel Receiving Greater than 100 Mrem & Associated Exposure by Work Function at BVPS for CY971997-12-31031 December 1997 Annual Rept of Number of Personnel Receiving Greater than 100 Mrem & Associated Exposure by Work Function at BVPS for CY97 ML20217Q4841997-12-31031 December 1997 1997 Annual Environ Rept,Non-Radiological,BVPS,Units 1 & 2 ML20217E3851997-12-31031 December 1997 BVPS Annual Exposure Rept for 1997 ML20217Q4761997-12-31031 December 1997 Bvps,Units 1 & 2,1997 Annual Environ Rept,Radiological ML20199J4291997-12-31031 December 1997 NPDES Monthly Rept for Jan 1998 for Bvps,Units 1 & 2 ML20198C4781997-11-30030 November 1997 NPDES Discharge Monitoring Rept for Nov 1997, for BVPS Units 1 & 2 ML20203B0681997-10-31031 October 1997 NPDES Monthly Discharge Rept for Oct 1997 for Bvps,Units 1 & 2 ML20212F5041997-09-30030 September 1997 NPDES Monthly Rept for Sept 1997 for Bvps,Units 1 & 2 ML20211F7901997-08-31031 August 1997 NPDES Discharge Monitoring Rept for Aug 1997 for Bvps,Units 1 & 2 ML20217R1841997-07-31031 July 1997 NPDES Monthly Rept for July 1997 ML20196J4801997-06-30030 June 1997 Discharge Monitoring Rept for June 1997 ML20148T4421997-05-31031 May 1997 NPDES Monthly Rept for May 1997 for Beaver Valley Power Station,Units 1 & 2 ML20140A6471997-04-30030 April 1997 NPDES Monthly Repts for Apr 1997 for Beaver Valley Power Station,Unit 1 & 2 ML20138G1701997-03-31031 March 1997 NPDES Monthly Rept for Mar 1997 for Beaver Valley Power Station Units 1 & 2 ML20137H9751997-03-25025 March 1997 NPDES Noncompliance Notification:On 970215 Discharge Monitoring Point 203 Exceeded Allowable Monthly Average of 30 Mg/L for Total Suspended Solids ML20136B8441997-01-31031 January 1997 NPDES Monthly Rept for Jan 1997 ML20137J0601996-12-31031 December 1996 Annual Radioactive Effluent Release Rept - 1996 ML20138J0161996-12-31031 December 1996 NPDES Discharge Monitoring Rept for Dec 1996 ML20138C6601996-12-31031 December 1996 1996 Annual Environ Rept,Radiological, for Beaver Valley Power Station,Units 1 & 2 ML20138D3621996-12-31031 December 1996 Annual Exposure Rept 1996. W/Two Diskettes ML20138C6791996-12-31031 December 1996 1996 Annual Environ Rept,Non-Radiological, for Beaver Valley Power Station,Units 1 & 2 ML20134L2171996-12-31031 December 1996 Annual Man-Rem Rept for 1996 ML20147B3051996-11-30030 November 1996 NPDES Discharge Monitoring Rept for Nov 1996 for BVPS, Units 1 & 2 ML20135B9221996-10-31031 October 1996 Discharge Monitoring Rept Suppl Sewage Sludge Rept for Oct 1996 ML20134E2651996-09-30030 September 1996 NPDES Discharge Monitoring Rept for Period of Sept 1996 ML20129E7021996-08-31031 August 1996 NPDES Monthly Rept,Epa Permit No. PA0025615 for Aug 1996 ML20117G3121996-07-31031 July 1996 NPDES Monthly Rept for Jul 1996 for Bvps,Units 1 & 2 ML20116C9841996-06-30030 June 1996 NPDES Discharge Monitoring Rept for June 1996 for Beaver Valley Power Station 1999-08-31
[Table view] |
Text
,
"F 4T Telephone (412) 3934000 Nuclear Division P.O. Box 4 Shippingport, PA 15077-0004 October 4,1983 '
NDIRCC:0875 T-y t EPA Permit No. 0025615 Reportable Occurrence United States Environmental Protection Agency Region III Compliance Office 6th and Walnut Streets' "
Philadelphia, Pennsylvania 19106
Dear Sir:
As required by EPA Permit No. 0025615, the following information is provided in regard to a reportable occurrence at Beaver Valley Power Station, Unit #1:
EPA Discharge #013, Unit #2 Sewage Treatment Plant, was found to be out of specification in total suspended solids (79.4 pounds / day) on September 30, 1983. A sample taken on October 3,1983, was within specification.-
The problem was determined to be caused by excessive solid build-up in the plant clarifier coupled with a high flowrate. The following corrective actions have been taken:
(1) The clarifier settling tank will have its solids , removed by a licensed hauler on a more frequent basis.
(2) Operation of the aeration pumps shall be. changed so that there is at least one pump running at all times. This shall insure continuous operation of the clarifier skimmers.
If you have any further questions regarding this report, please feel free to contact me.
Very truly yours, o24 f & h. AM O.S h$$$$8g2ggjof R
g Richard J. Swiderski Manager - Nuclear Construction BVPS #2 VJL/md cc: J. J. Carey G. F. Hickel T. D. Jones M. Coppula L. W. Johnson L. G. Schad -
J. W. McIntire l A. C. Mazunka Shift Supervisor (3)
V. J. Linnenbom i
W. G. Logan J. G. Randall S. L. Pernick Central File (2)