ML20080Q724

From kanterella
Jump to navigation Jump to search
Forwards Chemical Engineering Branch Proposed License Condition Re TMI Item II.B.3, Post-Accident Sampling Sys. Contents of Draft SER Should Be Used for SER
ML20080Q724
Person / Time
Site: Harris  
Issue date: 10/06/1983
From: Johnston W
Office of Nuclear Reactor Regulation
To: Novak T
Office of Nuclear Reactor Regulation
Shared Package
ML20079F427 List:
References
FOIA-84-35, TASK-2.B.3, TASK-TM NUDOCS 8310170095
Download: ML20080Q724 (3)


Text

_ _ _ _ _ _ _ _ - _ _ _ _ _

li, UMT E D sT AT ES

=

[ %,, q' NUCLEAR REGULATORY COMMISSION WA$mNGTON. D. C. 20555 DCT 6 1983 Docket Hos. 50-400/401 MEMORANDUM FOR:

Thomas M. Novak, Assistant Director i

for Licensing Divisicn of Licensing FROM:

William V. Johnston, Assistant Director Materials, Chemical & Environmental Technology l

Division of Engineering

SUBJECT:

SAFETY EVAULATION FOR SHEARON HARRIS NUCLEAR POWER PLANT, UNITS 1 & 2 (OL), CAROLINA POWER & LIGHT COMPANY, DOCKET N05. 50-400/401 l

Plant Name:

Shearon Harris Nuclear Power Plant, Units 1 & 2 Suppliers:

i'estinghouse; Carolina Power & Light Company Licensing Stage:

OL I

Docket Nos.:

50-400/401 Responsible Branch and Project Managers:

LB #3; E. Licitra, P. Kadambi Reviewers:

B. Turovlin; J. Wing Description of Task:

Operating License Review Status of Review:

Safety Evaluation Complete On November 17,' 1982, the Chemical Engineering Branch submitted a Dra't Safety Evaluation.

In the DSER, we concluded that Sections 6.1.1, 6.i.2,

6. 5. 2, 9.1.2, 9.1 4, 9.3.2. A. 9. 3.4. 10. 3. 5, 10.4. 6, and 10.4.8 were acceptable.

Section 9.3.2.B, Post-Accident Sampling System, partially v t the guidelines of Item II.B.3 in NUREG-0737.

We recommended that the license be conditioned for completion of the review of the remaining II.B.3 items.

~By letters dated May 23 and June 30, 1983, the applicant provided additional information on the Post-Accident Sampling System.

However, the information in these two submittals do not change our conclusions in the DSER.

Accordingly, the contents of the DSER should be used for the SER.

Attached is the proposed license condition.

l XA Copy Has Been Sent to PDR k.. j.g A.

.. t

.-k...-> L..s William V. Johnston, Assistant Director Materials, Chemical & Environmental

'3 /o/ 70095 y

oiM n" PEngineering

Attachment:

As stated cc:

See next page Contacts:

J. Wing B. Turovlin x27278 x28556

L..

OCT 6 1983 j

Thomas M. Novak.

cc:

w/ enclosure R. Vollmer D. Eisenhut G.'Knighton E.. Licitra B. D. Liaw

.;P. Xadambi

. :V. Benaroya

~

J. Weeks, BNL C.*McCracken f:27m%

!6B.:Turovlin I

R. Houston L. Hulman A. Chu

(

l I.

1 3

i i

1

(

I l

L

d *..

License Condition l

Prior to exceeding 5% power operation, Carolina Power & Light Company shall have installed and operational the Post-Accident Sampling System.

1 Prior to 5% power operation, t,he applicant:

(1) shall submit for NRC approval a core damage assessment procedure which incorporates, as a minimum, hydrogen levels, reactor coolant system pressure, core exit l

thermocouple temperatures and containment radiation levels in addition to r.adionuclide data; (2) shall demonstrate applicab.ility of procedures and, instrumentation'in ths pos,t-accident water chemistry and radiation l

environment, and retraining of operators on semi-annual basis; (3) shall prov'ide the plant procedures for chemical analyses and shall provide the

]

accuracy, range, and sensitivity of each of the radionuclide and chemical J

I analyses.

1 l

i 1i i 1 1

i

{

l l.

I i

J" nf k

<s 1