Text
.
Apoendix 3 NOTICE OF DEVIATION I'nion Electric Company Dockt: No. 50-483 3ased en the resul:s of an NRC inspection conducted on January 10-13, 23, February 2-3, and 6, IF 23, i: appears : hat :wo of your activicies are not being conducted in ;onfor=ance wi:h your coc:ments to the Co=-
=ission in Bechtel Topical Report SC-TOP-5A.
The following two items are deviations.
1.
Contrary to 3C-!0P-5A, See: ion CC-3534, concrete Crack control (whi:h s:ates, " Reinforcing bars :ensidered as face reinforcement shall not be more than 1/5 of the total section thickness from the concrete face." ) f ace reinforce =ent is be'ing placed at a
dis:ance greater than the design maxi =um distance from the concrete face.
['
O.
Contrary to 3C-TCP-5A, See: ion CC-3533, Reinforceing Steel Cover and Spacing Require =ents, Subsection CC-3533-l', Cover (which scates in part, "the following minimum concrete cover shall be proviced for reinforcing bars.
No. 6 through No. 18 bars
. exposed :o earth or weather.
. minimum cover two inches.") reinforcement bars are being placed wi:h a concrete cover of less chan two inches.
=