ML19319B578

From kanterella
Jump to navigation Jump to search
LER 78-062/03L-0:on 780604,diesel Generator 1-1 Failed to Operate W/Proper Frequency & Voltage.Caused by Primary Potential Fuse Component Failure.Fuse Replaced
ML19319B578
Person / Time
Site: Davis Besse Cleveland Electric icon.png
Issue date: 06/28/1978
From: Beeler T
TOLEDO EDISON CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
Shared Package
ML19319B573 List:
References
LER-78-062-03L, LER-78-62-3L, NUDOCS 8001270103
Download: ML19319B578 (2)


Text

u.m em . ,- ,

LtdENSEE EVENT REPORT f-gv)

CONTr.0L BLOCK: l 1

l l l l 6

lh (PLE ASE PRINT OR T'. ELL RECUIRED INFORMATION) l 01 Hj Dl Bl Sl 1l@l0 l0 l- l0 l0 lN lP IF l IO l1-25l@!264 I 1UCENSE l 1 !TYPE 1 l JG1 lh!_ l SSl@

57 .;AT 7 3 LICENSEE CCDE 14 15 LICENSE NuMS ER CO lol11. ERCI I L l@l 0 15 10 l- 10 13 14 16 @ l0 16 [0 14 17 i8 l@l0l612181 64 63 EV ENT D ATg 74 75 REPORT QATE 80 I 8 60 61 COCKET NUMBER EVENT DESCRIPTION AND PROBABLE CONSEQUENCES h I o l 21 l On '6/4/78 while perforr.ing surveillance testing, Diesel Generator (DG) 1-1 failed to l

[o !al l Operate with proper frequency and voltage. The test was suspended and DG l-1 declaredl Io Ie 1 l inoperable. The unit was in Mode 6 at the ti=c of the occurrence. This incident is l Io isi I being reported as a component failure. There was no danger to the health and safety [

i l o 16 j l of the public or unit personnel. Diesel Generator 1-2 was operable had e=ergency (NP-33-78-74) l I O l 7 l l power been required.

I l o l e I 'l __ 80 CAUSE COMP. VALVE SYSTEM CAUSE CCOE SU8 CODE COMPONENT CODE SUSCCOE SUSCODE CODE lo191 lE l3 j @ lE l@ l A l@ lG lE IN lE IR l A lh lD lh l Zlh 12 18 19 20 7 8 9 10 ft 12 4EVISION SEOUENTI AL OCCURRENCE REPORT REPORT NO. CODE TYPE NC.

EVENT YEAR

  • O arg;s LE RtRO 17181

,_ 21 22 1-1 23 10 !6 l2 I 24 26 W27 I 01 31 23 29 W

30 1-l 31 I 0l 32 ME M HOURS 22 5 8 i C FOR 8. SUPPLi$ MANUFAC RER EN 'ACT ON CN PLANT

,)lAj@lZj@ l Z [g l36Z lg 3l10 l0 l0 l- 40 l lY lg 41 lY lg 42 l43A l@ lP l3 l1 [8 l]

64 47 33 34 35 CAUSE DESCRIPTION ANO CORRECTIVE ACTIONS f

ji joll The cause of this occurrence can be attributed to a cennonent failure of a ortra n lt ; i j l potential fuse for the diesel generator. The crimarv cotential fuse for DC 1-1 v w I

,,,7, l replaced. At 1515 hours0.0175 days <br />0.421 hours <br />0.0025 weeks <br />5.764575e-4 months <br /> on 6/4/78, the Diesel Generator Monthlv Test was ececleted I I

l3 ;3j l and the diesel generator declared operable.

I li !4 l l 7 8 9

% POWER OTHER STATUS O50 Y DtScoVERY DESCRIFTioN ST l

(1 ! *5l' l G lh l 0l Ol OlhlNA l l3l@lSurveillanceTestST 5031.07 so

' 12 n 4A . 45 46 ACTiv Tv Co'0 TENT AMOUNT CF ACTIVITY LOCATION OF RELEASE RELEASED OF RELEASE NA l l NA l

}1 l6l 7 8 9 l Zl@ lZ 10 11 A4 45 80 PERSONNEL EXPCSURES

  • NuveER TV8E DESCRIPTION 39

_ a g t,i l l1 l7ll0l0l0 lZ A PERSONNE L INJURIES Q Ag ge.,i p NUv9ER DESCRIPTION l

ii n i 10 ! Q i O t1l@l 12NA (\*,,.[ s:

7 (' % 9

( , w' ;r$== """ @ '

8oo127o/o3 l ms i Z igi NA 83 d 9 10 7

'U B L ICITY NRC USE CNLY ISSUED DE SC R f PTION l ll l l l Il III IIly}

l l 0 } l N l 44 'l NA 63 69 80 ,

10 .

7 a 3 ~

I F 3**19? PwCNE: 51 ~ 2 50- SOMI -

I- 2 '; '

, , , , , . 33, N AME 05 PREP t.R ER

.___ -- . _ - - .- - .- - . - . - . _ . - - _ . . - .__.=. _... ._ .

.. - z. .

G.,

=

TOLEDO EDISON COMPANY DAVIS-BESSE UNIT ONE NUCLEAR POWER STATION SUPPLEMENTAL INFORMATION FOR LER UP-33-78-74 l DATE OF EVENT: June 4, 1978 FACILITY: Davis-Besse Unit 1 ,

f

IDENTIFICATION OF OCCURRENCE
Diesel Generator 1-1 declared inoperable on June 4, 1978.

l l Conditions Prior to Occurrence: The unit was in Mode 6., with Power (5"I) = 0 and Load (M4E) = 0, a

Description of Occurrence: At 0545 hours0.00631 days <br />0.151 hours <br />9.011243e-4 weeks <br />2.073725e-4 months <br /> on June 4,1978, while performing Surveil-l

lance Test ST 5031.07, " Safety Features Actuation System (SFAS) 18 Month or Refuel-ing Test" Diesel Generator 1-1 came up to speed but the generator breaker did not j

close. The test was suspended at this point, and Surveillance Test ST 5081.01,

" Diesel Generator Monthly Test", was performed. Upon starting Diesel Generator 1-1, l l the frequency was' not stable and the generator voltage was icw. The test was sus- ,

pended at this point, and the diesel generator declared inoperable.

This occurrence did not place the unit in the Action Statement: of Technical Speci-fication 3.8.1.2 because the unit was in Mode 6, which requires only one diesel generator to be operable while in Modes 5 or 6. This incident is being reported as a component failyss.

Designation of Aeoarent Cause of Occurrence: The cause of this occurrence can be i attributed to a component failure of a primary potential fuse for the diesel generator.

Analysis of Occurrence: . There was no danger to the health and safety of the public or to unit personnel. Diesel Generator 1-1 was not required for emergency power during the period of time it was inoperable.- Diesel Generator 1-2 was operable had emergency power been required. ,

j Corrective Action: Under Maintenance Work Order 78-1332, the primary potential fuse for Diesel Generator 1-1 wcs replaced.

4 At 1515 hours0.0175 days <br />0.421 hours <br />0.0025 weeks <br />5.764575e-4 months <br /> on June 4,1978, Surveillance Test ST 5081.01, Diesel Generator Monthly Test, was completed and the diesel generator declared operable.

1 ,

Fa i lure Data: No previous si=ilar events have occurred.

4 LER #78-062

,,..-___,,_,,...-..y,.. , _ _ _ . , . m.___. , , , - . .,- ,,_,.,_,,._,,.,_._,,m.m_m,. ,_..,.,,,.,,,,..,#-.- - - . _ , . _ ..,.,m-