LER 79-007/03L-0 on 790109:during Sys Component Test, Residual Heat Removal Pump D Would Not Start.Caused by Motor Switch Being in Off Position
ML19261B204
Person / Time
Site: Brunswick Duke Energy icon.png
Issue date: 02/07/1979
From: Tollison A
CAROLINA POWER & LIGHT CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
Shared Package
ML19261B202 List:
References
LER-79-007-03L, LER-79-7-3L, NUDOCS 7902140165
Download: ML19261B204 (2)


Text

(7 77)

LICENSEE EVENT REPORT g CONTR0L BLOCK: l

. i l l l l e

lh (PLE ASE PRINT OR TYPE ALL REQUIRED INFORMATION) l 0 1 F 9 NlC B LICENSEE CODE E

Pl1l@l0 0l-l0 14 15 0 l0 0 l 0 l - l - l - l@l 4 l1 l1 l1 l1 l@l l LICENSE NUMBER 26 26 LICENSE TYPE JO 57 LAT $8 CON'T o i 8

3[]"' l L l@l 610 l 5 l 0DOCKET - l 0 l 3 l 2 15 68l@l 690 l 1 EVENT 9 l 7 9 l@LO 2]

l 0 l DATE 74 75 0l 7l 7l 980 @

REPORT D ATE

? 60 NUMBER EVENT DESCRIPTION AND PROB ABLE CONSEQUENCES h o 7 l RHR pump "D" would not start during the LPCI/RHR System Component Test (P.T. 8.1.3).

o 3  ; The Motor Control Center (MCC) circuit breaker was found in the open circuit positionI o 4 I without the charging spring compressed. This would not allow the breaker to close 1 o s ; and the motor to start. (Technical Specification 3.5.3.2) l o e l l o 7 I l o e I 80 7 6 9 SYSTEM CAUSE CAUSE COMP. VALVE CODE CODE SUBCODE COMPONENT CODE SUBCODE SUBCODE o 9 lC Fj @ lX l @ lZ l@ l C l Kl T l B l R l K l@ y@ Zl@

7 8 9 10 11 12 13 18 19 20

_ SE QUE NTI AL OCCUR R ENCE REPORT REVISION EVENT YE AR REPORT NO CODE TYPE NC.

LER RO

@ REPORT l7 l9 l l_l l 0l 0l 7l jfl 0l3l lL l 30 l- l0l 32

_2' 22 23 24 26 27 28 29 31 AKE ACT ON ON PLANT ME H HOURS SB i D FOP B. SUPP LI MANUFAC URER ln JJ l@lZ 34 l@ U@ U@

35 36 3/

oln o of 40 l v l@

di W@ W@ lGl0l8l0l@

42 43 44 47 CAUSE DESCRIPTION AND CORRECTIVE ACTIONS h i o l A switch controlling the small electric motor which is used to compress the breake*

l i 13 ) ; charging spring was found in the off position. The charcine sprine is used m nukk1vi

, 7 l close the breaker contacts, therefore providing power to the circuit. The charcine I i 3 l motor switch was turned on, and the Periodic Test completed sar*j actorils. Fire I i 4 l protection modifications are being installed in the MCC breaker area by (Cont'd.) l 7 8 9 80 STA S  % POWER OTHE R ST ATUS otSCO RY DISCOVERY DESCRIPTION i 5 lE l@ 0l9l6l@l NA l lBl@l Periodic Test i ACTIVITY CO TENT RELE ASED OF RELE ASE AMOUNT OF ACTIVITY LOCATION oF RELEASE 7

i c 8 9 lZ l @ Ugl 10 11 NA 44 l

45 NA 80 l

PERSONNEL E XPOSURES NUMBER i 7 l0l0 0 l@lZTYPE ' "

@lDESCW NA TION - "

l 7 *

  • PErsONNe'L iN;u' RIES 2

N UV8 E R DESCRIPTION 7

1 P 8 9 l0l0l0l@l 11 12 NA 80 l

LOSS OF OR D AV AGE TO F ACILITY TYPE DE SCRIPTION l

7 i 9 8 9 lZl@l 10 NA 80 PUB L ICITY NRC USE ONLY

, , IsyE gg,otscm"'oN , 79021401G r ,

68 69

, , , ,,,,,,,,,ij BC 5 7 g 9 to 7-4-tM j g PREPARER . C. Tollison, Jr. PHONE: 919-457-6701 {

1 LER CONTINUATION -- RO# 1-79-7 Facility: BSEP Unit #1 Event Date 1/9/79 construction personnel. It is believed the charging motor switch had inadvertently been turned off . Construction personnel have been asked to be extremely aware of their surroundings while working. This is considered an isolated event, and no further corrective action is required.