ML18219B526

From kanterella
Jump to navigation Jump to search
05/24/1978 Letter Abnormal Environmental Occurrence Involving Circulating Water Increasing in Temperature Past Limit
ML18219B526
Person / Time
Site: Cook  American Electric Power icon.png
Issue date: 05/24/1978
From: Shaller D
American Electrtic Power System, Indiana Michigan Power Co, (Formerly Indiana & Michigan Power Co)
To: James Keppler
NRC/IE, NRC/RGN-III
References
LER 1978-002-04X
Download: ML18219B526 (5)


Text

L L' V

0 6/(/78 REGUI ATORY INFORMATION DISTRIBUTION SYSTEM (RIDS)

DISTRIBUTION FOR INCOMING MATERIAL 50-316 REC: KEPPl ER J G ORG: SHALLER D V DOCDATE: 05/24/78 NRC IN 4 MI PWR DATE RCVD: 06l05f 78 DOCTVPE: LETTER NOTARIZED: NG COPIES RECEIVED

SUBJECT:

LTR 1 ENCL 0 LICENSEF. EVFNT REPT (RO 50-316/78-002) CONCERNING CIRCULATING WATER T GN UNIT 2 INCREASED TO 19. 5 DEGREES F VIOLATING APPENDIX B TECH SPEC LIMIT OF 17 DEGREES F + 1 DEGREES F.

PLANT NAME: COOK UNIT 2 REVIEWER INITIAL: XJM DISTRIBUTOR INITIAL:

DISTRIBUTION OF THIS MATERIAL IS AS FOLLOWS NOTES:

SEND 3 COPIES OF ALL MATERIAL TO I@E ED REEVES-1 CY ALL MATERIAI ENVIRONMENTAL EVENTNBNORMAL OCCURENCE (DISTRIBUTION CODE C003) QAJ(Q(. l.'tQ, Q0>Q f.TR FOR IICTION: BR CIIIEF L~

s~edl BC>" LTR ONLY~ Sf.A>88 f-W 4- Le< ~~.

INTERNAL: RFA Tl f=e>>f T I NRC PDR>>>>LTR ONLY(1)

I 4 L>>>>l TR ONLY(2) GELD>>>>LTR ONLY<1)

HANAUER>>>>LTR ONLY(1) MIPC>>>>LTR ONLY(1)

EEB>>>>LTR ONLY(i) L CROCKER>>>>LTR ONLY< 1)

ENV IRO SPFC BR>>>>LTR ONLY ( 1 > EFFI UEhlT TREAT SYS>>>>LTR ONLY( 1)

F. XTFRNAL: LPDR'S ST. JOSEPH. MI>>>>LTR ONLY( 1)

TIC>>>>LTR ONLY(1>

NSIC>>>>LTR ONLY(i)

ACRS CAT B>>>>LTR ONLY(1>

DISTRIBUTION: LTR 22 EN('.L 0 CONTROL NBI: 78i.570. 99 SIZE: 2P THE FND

~

)

INDIANA 8 MICHIGANPOPOVER COMPANY DONALD C. COOK NUCLEAR PLANT P.O. Box 458, Bridgman, Michigan 49106 May 24, 1978 Ct'-

Mr. J. G. Keppler, Regional Director Office of Inspection and Enforcement United States Nuclear Regulatory Commission r g Region III Ag-S 799 Roosevelt Road Glen Ellyn, IL 60137 Operating License DPR-74 Docket 850-3'@

AEO 878-02/OPR-0

Dear Mr. Keppler:

This report is submitted as required by Appendix B Technical Specification Section 5.4.2.1 relating to an Abnormal Environmental Occurrence, notifica-tion of which was given you on May 17, 1978.

This occurrence concerned the circulating water bT on Unit 2 having increased to 19.5 F in violation of the Appendix B Technical Specification limit of 17 F + loF. This condition prevailed for approximately 10 hours1.157407e-4 days <br />0.00278 hours <br />1.653439e-5 weeks <br />3.805e-6 months <br />.

The condenser discharge valves had been partially closed to assist in maintaining the circulating water side of the condensers full of water.

After the discharge valves had been adjusted, closer monitoring of the AT was not initiated.

The alarm point for the circulating water aT was improperly set, having been adjusted for 22 F (which is the limit for Unit 1) instead of the required 17 F for Unit 2. The Technical Specification limit was not listed on the log form used for recording circul.ating water temperature.

No adverse effects resulted from this occurrence. In the event of a circulating water pump malfunction Unit 2 is allowed to operate for up to 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br />, providing the hT does not exceed 20 F. In this instance, all four circulating water pumps were operating and the AT did not exceed 20 F.

...... continued

-v( '

b

'I V

J. G. Keppler Nay 24, 1978 Page 2 The circulating water AT was reduced to less than 17 F in less than ten minutes after discovery. The log form was revised to include the Technical Specification limit to serve as a reminder to the operator each time readings are taken. The aT alarm has been adjusted to its proper Unit 2 setting.

D. V. Shaller Plant flanager