05000247/LER-2018-002, Manual Reactor Trip Due to Trip of Both Main Boiler Feedwater Pumps

From kanterella
(Redirected from ML18173A127)
Jump to navigation Jump to search
Manual Reactor Trip Due to Trip of Both Main Boiler Feedwater Pumps
ML18173A127
Person / Time
Site: Indian Point 
Issue date: 06/18/2018
From: Vitale A
Entergy Nuclear Northeast
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
NL-18-043 LER 2018-002-00
Download: ML18173A127 (6)


LER-2018-002, Manual Reactor Trip Due to Trip of Both Main Boiler Feedwater Pumps
Event date:
Report date:
Reporting criterion: 10 CFR 50.73(a)(2)(iv)(A), System Actuation

10 CFR 50.73(a)(2)(ii)(A), Seriously Degraded

10 CFR 50.73(a)(2)(viii)(A)

10 CFR 50.73(a)(2)(ii)(B), Unanalyzed Condition

10 CFR 50.73(a)(2)(viii)(B)

10 CFR 50.73(a)(2)(iii)

10 CFR 50.73(a)(2)(ix)(A)

10 CFR 50.73(a)(2)(x)

10 CFR 50.73(a)(2)(v)(A), Loss of Safety Function - Shutdown the Reactor

10 CFR 50.73(a)(2)(v)(B), Loss of Safety Function - Remove Residual Heat

10 CFR 50.73(a)(2)(v), Loss of Safety Function

10 CFR 50.73(a)(2)(i)(A), Completion of TS Shutdown

10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications

10 CFR 50.73(a)(2)(vii), Common Cause Inoperability

10 CFR 50.73(a)(2)(i)
2472018002R00 - NRC Website

text

A

  • ~*Entergx NL-18-043 June 18, 2018 U.S. Nuclear Regulatory Commission Attn: Document Control Desk Mail Stop O-P1-17 Washington, D.C. 20555-0001 Entergy Nuclear Northeast Indian Point Energy Center 450 Broadway, GSB P.O. Box 249 Buchanan, N.Y. 10511-0249 Tel (914) 254-6700 Anthony J Vitale Site Vice President SUBJECT: Licensee Event Report# 2018-002-00, "Manual Reactor Trip Due to Trip of Both Main Boiler Feedwater Pumps" Indian Point Unit No. 2 Docket No. 50-24 7 DPR-26

Dear Sir or Madam:

Pursuant to 10 CFR 50. 73(a)(1 ), Entergy Nuclear Operations Inc. (ENO) hereby provides Licensee Event Report (LER) 2018-002-00. The enclosed LER identifies an event where the reactor was manually tripped following an automatic trip of both Main Boiler Feedwater Pumps (MBFPs). This event is reportable under 10 CFR 50.73(a)(2)(iv)(A).

As a result of the MBFP trip, the Auxiliary Feedwater System was actuated, which is also reportable under 10 CFR 50. 73(a)(2)(iv)(A). The condition was recorded in the Entergy Corrective Action Program as Condition Report CR-IP2-2018-02806.

There are no new commitments identified in this letter. Should you have any questions regarding this submittal, please contact Mr. Robert Walpole, Manager, Regulatory Assurance at (914) 254-6710.

Sincerely, AJV/cdm cc:

Mr. David Lew, Acting Regional Administrator, NRC Region I NRC Resident Inspector's Office Ms. Bridget Frymire, New York State Public Service Commission J

NRCFORM 366 U.S. NUCLEAR REGULATORY COMMISSION APPROVED BY 0MB: NO. 3150-0104 EXPIRES: 03/31/2020 (02-2018)

, the NRG may not conduct or sponsor, and a oerson is not reouired to resoond to the information collection.

~.Page Indian Point 2 05000-247 1 OF5

4. Title Manual Reactor Trip Due to Trip of Both Main Boiler Feedwater Pumps
5. Event Date
6. LER Number
7. Report Date
8. Other Facilities Involved Sequential Rev Facility Name Docket Number Month Day Year Year Month Day Year Number No.

05000 06 18 2018 Facility Name Docket Number 04 19 2018 2018

- 002
- 00 05000
9. Operating Mode
11. This Reoort is Submitted Pursuant to the Requirements of 10 CFR §: (Check all that aoofv)

D 20.2201(b)

D 20.2203(a)(3)(i)

D 50.73(a)(2)(ii)(A)

D 50.73(a)(2)(viii)(A) 1 D 20.2201 (d)

D 20.2203(a)(3)(ii)

D 50.73(a)(2)(ii)(B)

D 50.73(a)(2)(viii)(B)

D 20.2203(a)(1)

D 20.2203(a)(4)

D 50.73(a)(2)(iii)

D 50.73(a)(2)(ix)(A)

D 20.2203(a)(2)(i)

D 50.36(c)(1)(i)(A)

~ 50.73(a)(2)(iv)(A)

D 50.73(a)(2)(x)

10. Power level D 20.2203(a)(2)(ii)

D 50.36(c)(1)(ii)(A)

D 50.73(a)(2)(v)(A)

D 73.71 (a)(4)

D 20.2203(a)(2)(iii)

D 50.36(c)(2)

D 50.73(a)(2)(v)(B)

D 73.71(a)(5) 8 D 20.2203(a)(2)(iv)

D 50.46(a)(3)(ii)

D 50.73(a)(2)(v)(C)

D 73.77(a)(1)

D 20.2203(a)(2)(v)

D 50.73(a)(2)(i)(A)

D 50.73(a)(2)(v)(D)

D 73.77(a)(2)(ii)

D 20.2203(a)(2)(vi)

D 50.73(a)(2)(i)(B)

D 50.73(a)(2)(vii)

D 73.77(a)(2)(iii)

D 50.73(a)(2)(i)(C)

D Other (Specify in Abstract below or in NRC Form 366A

12. Licensee Contact for this LER Licensee Contact relephone Number (Include Area Code)

Christopher Bohren, Manager, Operations Support I (914) 254.2911 Cause System Component Manufacturer Reportable To ICES

Cause

System Component Manufacturer Reportable To ICES D

TG SHV W351 y

14. Supplemental Report Expected Month Day Year D Yes (If yes, complete 15. Expected Submission Date) ~ No
15. Expected Submission Date Abstract (Limit to 1400 spaces, i.e., approximately 14 single-spaced typewritten lines)

On April 19, 2018, at 2100 hours0.0243 days <br />0.583 hours <br />0.00347 weeks <br />7.9905e-4 months <br />, during initial plant startup following the Spring 2018 refueling outage (2R23), Indian Point Unit 2 commenced performance of the main turbine generator startup procedure to conduct turbine overspeed testing. At 2107 hours0.0244 days <br />0.585 hours <br />0.00348 weeks <br />8.017135e-4 months <br />, the control room received main feedwater supervisory and panel alarms, and the main turbine control valves were observed to have opened rapidly. The unexpected rapid opening of the turbine control valves caused steam flow to increase, which in turn, caused all four steam generator water levels to swell. The high steam generator levels initiated an automatic main feedwater isolation and main turbine trip, with both Main Boiler Feedwater Pumps (MBFPs) tripping on closure of their discharge valves as part of the main feedwater isolation actuation. At 2108 hours0.0244 days <br />0.586 hours <br />0.00349 weeks <br />8.02094e-4 months <br />, with reactor power at 8 percent and no MBFPs running, a manual reactor trip was inserted by the control board operators in accordance with the abnormal operating procedure for loss of main feedwater. All control rods fully inserted and all required safety systems functioned properly. The plant was stabilized in hot standby with decay heat being removed by the main condenser. The Auxiliary Feedwater System (AFWS) automatically started as expected on the tripping of the MBFPs to maintain steam generator inventory. The direct cause of the event was main turbine control oil stop valve LO-Z being out of its required position (closed instead of open). The root cause was main turbine generator startup procedure (2-SOP-26.4) provided a weak barrier to maintain the proper configuration of the main turbine control oil system. Corrective actions primarily involved the resolution of configuration control and management vulnerabilities.

h"his event had no effect on the public health and safety. The event was reported to the Nuclear Regulatory Commission on

~oril 19, 2018 under 10 CFR 50.72(b)(2)(iv)(B) and 50.72(b)(3)(iv)(A).

NRC FORM 366 (02-2018)

Note: The Energy Industry Identification System Codes are identified within the brackets { }.

DESCRIPTION OF EVENT

SEQUENTIAL NUMBER

- 002 REV NO.
- 00 On April 19, 2018, at approximately 2100 hours0.0243 days <br />0.583 hours <br />0.00347 weeks <br />7.9905e-4 months <br />, during initial plant startup following the Spring 2018 refueling outage (2R23), Indian Point Unit 2 (IP2) commenced performance of main turbine generator {TA, TB} startup procedure 2-SOP-26.4 to conduct turbine overspeed testing. When the main turbine is offline, two Load Limit controllers {TG, PC}

function to modulate the main turbine control valves {SB, FCV}. The Load Limit controller with the lower control oil pressure controls modulation of the turbine control valves. The Load Limit 2 controller (Load Limit 2) was selected to raise turbine speed. Unknown to the operators, turbine control oil stop valve LO-Z {TG, SHV} was incorrectly positioned to the closed position. With LO-Z closed, Load Limit 2 was isolated from the common control oil line, which removed its ability to modulate the turbine control valves. The Load Limit 2 control oil pressure was at minimum as expected (control board indication read 0.3 pounds per square inch gauge (psig)). However, with Load Limit 2 isolated and effectively out of service, the Load Limit 1 controller (Load Limit 1) was in control of the turbine control valves.

This was an undetected abnormal condition that caused the turbine control valves to respond uncharacteristically when the control room operators raised Load Limit 1 control oil pressure in accordance with 2-SOP-26.4 to ensure Load Limit 2 was in control.

At approximately 2107 hours0.0244 days <br />0.585 hours <br />0.00348 weeks <br />8.017135e-4 months <br />, the control room received main feedwater {SJ} supervisory and panel alarms {18},

including the steam generator level control deviation {XA}, heater drain high/low level {LA}, and moisture separator drain tank high level {LA} alarms. Also at this time, the main turbine control valves were observed to have opened rapidly. With the main turbine stop valves {SB, SHV} opened previously per procedure 2-SOP-26.4, the unexpected rapid opening of the main turbine control valves caused steam flow to the high pressure turbine to increase from 0 pounds mass per hour (lbm/hr) to 1. OE6 lbm/hr in 17 seconds. This step increase in steam flow caused all four steam generator {AB, SG} water levels to swell (increase) from approximately 38 percent to 73 percent narrow range level.

The high steam generator levels initiated an automatic main feedwater isolation and main turbine trip. Both Main Boiler Feedwater Pumps (MBFPs) {SJ, P} tripped on closure of their discharge valves {SJ, 20} as part of the main feedwater isolation actuation. Operations entered abnormal operating procedure (AOP) 2-AOP-FW-1 for loss of main feedwater.

At approximately 2108 hours0.0244 days <br />0.586 hours <br />0.00349 weeks <br />8.02094e-4 months <br />, with reactor power at 8 percent and no MBFPs running, a manual reactor trip was inserted by the control board operators in accordance with 2-AOP-FW-1. Emergency operating procedure (EOP) 2-E-O was entered for the reactor trip to assess plant conditions and identify the appropriate recovery actions. All control rods {AA} were verified fully inserted and all required safety systems functioned properly. The plant was stabilized in hot standby with decay heat being removed by the main condenser {SG}. Pressurizer and steam generator pressures and levels, and Reactor Coolant System (RCS) {AB} temperature were being maintained within their normal bands.

There was no radiation release. The emergency diesel generators {EK, DG} did not start, as offsite power remained available and stable. The Auxiliary Feedwater System (AFWS) {BA} motor-driven auxiliary boiler feedwater pumps

{BA, P} automatically started as expected on the tripping of the MBFPs. Indian Point Unit 3 (IP3) was unaffected and remained at 100 percent reactor power.

As required, on April 19, 2018, at 2341 hours0.0271 days <br />0.65 hours <br />0.00387 weeks <br />8.907505e-4 months <br />, the reactor trip event was reported to the Nuclear Regulatory Commission (NRC) in a 4-hour non-emergency notification under 10 CFR 50. 72(b)(2)(iv)(B) for an actuation of the Reactor Protection System (RPS) {JC} when the reactor is critical, and included an 8-hour notification for valid actuations of the RPS and AFWS under 1 O CFR 50. 72(b )(3)(iv)(A) (Event Log No. 53348). The event was recorded in the Indian Point Energy Center (IPEC) Corrective Action Program (CAP) as CR-IP2-2018-02806.

The main turbine control oil system {TG} utilizes three controllers {TG, PC} to control high pressure steam flow to the Page 2 of 5 (04-2017)

U.S. NUCLEAR REGULATORY COMMISSION APPROVED BY 0MB: NO. 3150-0104 EXPIRES: 3/31/2020 LICENSEE EVENT REPORT (LER)

CONTINUATION SHEET (See NUREG-1022, R.3 for instruction and guidance for completing this form http://www.nrc.gov/read inq-rm/doc-collections/nuregs/staff/sr1 022/r3D

, the NRG may not conduct or sponsor, and a person is not required to respond to, the information collection.

3. LERNUMBER YEAR Indian Point 2 05000-247 2018 SEQUENTIAL NUMBER
- 002 REV NO.
- 00 turbine by modulating the main turbine control valves. Two Load Limit controllers are used to modulate the control valves when the turbine is offline and not at rated speed. The Load Limit controllers share a common oil line, which sends a hydraulic signal based on control oil pressure to modulate the control valves. Normally, the control valves stroke with a common control oil pressure of approximately 18 pounds per square inch (psi) (valves full closed) to 45 psi (valves full open). With the use of internal check valves, the Load Limit controller with the lower pressure signal maintains overall control of the position of the control valves. The third controller is the main turbine governor {TA, 65},

which functions as a controller {TG, TC} when the turbine is close to normal operating speed (greater than approximately 1650 revolutions per minute (rpm)). The governor uses a turbine shaft mounted impeller to adjust the common control oil pressure based on turbine speed. As such, the governor impeller oil pressure provides the modulating control signals to the turbine control valves during normal operation.

A modification of the main turbine control oil system was performed when Consolidated Edison Company owned IP2.

The modification installed new oil piping and valves into the system to allow testing of the main turbine governor with the turbine offline and not at rated speed. The new piping configuration allows oil from Load Limit 2 to flow into the governor impeller oil supply line to simulate a governor impeller pressure. This allows the governor to modulate the turbine control valves during outages for testing purposes. The modification included the addition of stop ball valve LO-Z to the common control oil line upstream of the internal check valve for Load Limit 2. The modification also added stop ball valve LO-Y {TG, SHV} and associated piping to connect the Load Limit 2 common control oil supply line to the governor impeller oil supply line to the governor. For governor testing, valve LO-Z would be closed to isolate Load Limit 2 from the common control oil circuit to prevent interference with the oil pressure supplied to the governor. Valve LO-Y would be opened during the testing to allow the Load Limit 2 control oil supply to flow to the governor.

The investigation following the April 19, 2018 reactor trip resulted in the discovery of valve LO-Z being out of position.

The valve was closed (instead of open) during the performance of main turbine generator startup procedure 2-SOP-26.4. With valve LO-Z in the closed position, Load Limit 2 was isolated from the common control oil line. This removed the ability of Load Limit 2 to modulate the main turbine control valves, and also affected the hydraulics of the common control oil circuit by reducing the volume of oil and effectively removing the Load Limit 2 oil drain and internal check valve from the circuit. This, in turn, changed the main turbine control valve zero (opening) and span (stroke range) settings, which would cause the valves to stroke in an uncharacteristic manner. Thus, when the control room operators raised Load Limit 1 control oil pressure in accordance with 2-SOP-26.4, the control valves opened unexpectedly, causing a rapid increase in steam flow to the high pressure turbine, and this resulted in water level swell (increase) in all four steam generators. The high steam generator levels initiated an automatic main feedwater isolation and main turbine trip that caused both MBFPs to trip, and necessitated the insertion of a manual reactor trip by the control board operators. The time period during which valve LO-Z was out of its required position was determined to be between 1218 hours0.0141 days <br />0.338 hours <br />0.00201 weeks <br />4.63449e-4 months <br /> on April 16, 2018 and 2107 hours0.0244 days <br />0.585 hours <br />0.00348 weeks <br />8.017135e-4 months <br /> on April 19, 2018 (turbine trip). However, no Work Orders, procedures, or other activities performed or occurring during this period were found that directed operation of valve LO-Z, nor was the valve on any protective tagouts (PTOs), and there was no evidence of tampering.

Consequently, the investigation into how the valve LO-Z became mispositioned was inconclusive.

An extent of condition (EOC) analysis was performed to determine where the same or similar conditions may exist.

For this event, the EOC was limited to control oil system valves for the IP2 and IP3 main turbine generators and MBFPs where a valve misposition, valve leak, or incorrectly installed valve could lead to either an automatic or manual reactor trip. The EOC analysis concluded that there was a low EOC risk level for control oil system valves installed incorrectly or developing a leak large enough to require an automatic or manual reactor trip, and no corrective actions were required. The EOC analysis for control oil system valves being left out of position concluded that there was a medium EOC risk level due to the higher frequency that these valves are manipulated, which creates more opportunities and a higher probability for mispositioning the valves. The EOC corrective actions to address the medium risk of control oil system valves being left out of position are: (1) revise shutdown risk assessment procedure Page 3 of 5 (04-2017)

U.S. NUCLEAR REGULATORY COMMISSION APPROVED BY 0MB: NO. 3150-0104 EXPIRES: 3/31/2020 LICENSEE EVENT REPORT (LER)

CONTINUATION SHEET (See NUREG-1022, R.3 for instruction and guidance for completing this form http://www.nrc.gov/readinq-rm/doc-collections/nuregs/staff/sr1022/r3D

, the NRC may not conduct or sponsor, and a person is not required to respond to, the information collection.

3. LERNUMBER YEAR Indian Point 2 05000-247 2018 SEQUENTIAL NUMBER
- 002 REV NO.
- 00 IP-SMM-OU-104 to include a risk and work scope informed recommendation in the pre-outage risk assessment for which check off lists (COLs) should be performed at the end of an outage and (2) revise mode change checklists (Mode 3 to Mode 2) 2-PT-V053E and 3-PT-V053E to require partial performance of the MBFP and main turbine control oil system COLs.

CAUSE OF EVENT

The direct cause of the event was main turbine control oil stop valve LO-Z being out of its required position (closed instead of open). Valve LO-Z being closed led to the observed uncharacteristic turbine control valve operation and unexpected rapid increase in steam flow that caused all four steam generator water levels to swell. The high steam generator levels initiated an automatic main feedwater isolation and main turbine trip, which in turn, caused both MBFPs to trip, and culminated in the insertion of a manual reactor trip in accordance with 2-AOP-FW-1.

The root cause of the event was main turbine generator startup procedure (2-SOP-26.4) provided a weak barrier to maintain the proper configuration of the main turbine control oil system. Procedure 2-SOP-26.4 was determined to be weak because the procedure steps for startup of the main turbine generator do not reference the required positions for turbine control oil stop valves LO-Zand LO-Y. In addition, having the main turbine lube oil system aligned per the COL (2-COL-26.1) was not listed as a prerequisite in 2-SOP-26.4. This caused valve LO-Z to be out of its required position by allowing the turbine generator startup to be performed without ensuring valves LO-Zand LO-Y were properly aligned for startup.

Contributing causes

1. Weakness in the implementation of the site configuration control process. The weakness in configuration control allowed main turbine control oil stop valve LO-Z to be left out of its required position. Although the investigation was inconclusive, the valve was likely repositioned without proper documentation or configuration tracking. A stronger site configuration control process could have mitigated the risk of valve LO-Z being left out of position.
2. Weakness in the process used to determine which CO Ls are performed at the end of an outage. The main turbine lube oil system COL was not performed at the end of the IP2 Spring 2018 refueling outage (2R23), nor was it required to be performed. Not performing the COL contributed to the event because its performance could have mitigated the risk of valve LO-Z being left out of position at the time of startup.

CORRECTIVE ACTIONS

The following corrective actions have been or will be performed under the Entergy CAP to address the causes of this event.

  • Restored main turbine control oil stop valve LO-Z to its proper position and performed the main turbine lube oil system COL (2-COL-26.1) before the subsequent successful plant startup.
  • Revised procedure 2-SOP-26.4 to verify valves LO-Y and LO-Z are in the desired position prior to latching the main turbine.
  • Revise procedure IP-SMM-OU-104 to include a risk and work scope informed recommendation in the pre-outage risk assessment for which COLs should be performed at the end of the outage.
  • Review procedure revisions from 2001 to 2007 for System Operating Procedures (SOPs) related to main turbine and MBFP control oil systems and determine if applicable changes were captured for both IP2 and IP3. If changes were not captured then revise procedures as necessary.
  • Add main turbine control oil stop valves LO-Zand LO-Y to the Asset Suite (AS) equipment database for IP2 and IP3, and label the valves in the field to match the equipment database designation. Page 4 of 5 (04-2017)

U.S. NUCLEAR REGULATORY COMMISSION APPROVED BY 0MB: NO. 3150-0104 EXPIRES: 3/31/2020 LICENSEE EVENT REPORT (LER)

CONTINUATION SHEET (See NUREG-1022, R.3 for instruction and guidance for completing this form http://www.nrc.gov/reading-rm/doc-collections/nuregs/staff/sr1022/r3D

, the NRG may not conduct or sponsor, and a person is not required to respond to, the information collection.

3. LER NUMBER YEAR Indian Point 2 05000-247 2018 SEQUENTIAL NUMBER
- 002 REV NO.
- 00
  • Determine the valves to be included in the partial scope performance of the MBFP and main turbine control oil system mode change (Mode 3 to Mode 2) checklists and revise 2-PT-V53E and 3-PT-V53E to require partial performance of the MBFP and main turbine control oil system COLs.

EVENT ANALYSIS

The event is reportable under 10 CFR 50. 73(a)(2)(iv)(A). The licensee shall report any event or condition that resulted in manual or automatic actuation of any of the systems listed under 10 CFR 50. 73(a)(2)(iv)(B). Systems to which the requirements of 10 CFR 50.73(a)(2)(iv)(A) apply for this event include the RPS, including reactor trip, and AFWS actuation. This event meets the reporting criteria because a manual reactor trip was initiated on April 19, 2018 at 2108 hours0.0244 days <br />0.586 hours <br />0.00349 weeks <br />8.02094e-4 months <br />, and the AFWS was automatically actuated in response to the tripping of the MBFPs as part of the main feedwater isolation actuation. An investigation into the cause of the event and a post transient evaluation were initiated and completed. The root cause evaluation for this event was presented to the Performance Improvement Review Group and the post transient evaluation was presented to the Onsite Safety Review Committee. Both evaluations were approved.

PAST SIMILAR EVENTS A review was performed of the past three years for IP2 and IP3 Licensee Event Reports (LERs) that reported a reactor trip resulting from a component being out of its required position. The review identified a past similar event that was reported in IP2 LER 2016-009 for an automatic reactor trip event which occurred on July 6, 2016. The reactor trip resulted from an Instrument and Control (l&C) technician operating the Channel B RPS bypass key out of sequence and without procedural guidance. The root cause of this event was that fundamental standards and expectations, such as procedure use and adherence, were not being maintained. While the 2016 event was caused by an individual deviating from a procedure, the event reported in this LER was the result of procedures that provided inadequate configuration controls.

SAFETY SIGNIFICANCE

This event had no effect on the health and safety of the public. There were no actual safety consequences for the event because it was an uncomplicated manual reactor trip. The automatic main feedwater isolation and turbine trip on high steam generator levels functioned as designed to terminate the steam flow and feedwater flow transients, and allowed steam generator water levels to be restored to normal. The tripping of the MBFPs was an expected response since the MBFPs are steam-driven, and not designed to operate following a reactor trip. The AFWS motor-driven auxiliary boiler feedwater pumps automatically started to supply high pressure feedwater to the steam generators to maintain water inventory. The AFWS is designed to support the removal of decay heat energy from the RCS by secondary-side steam release when the Main Feedwater System {SJ} is not operable. This condition is bounded by the analyzed event described in IP2 Updated Final Safety Analysis Report (UFSAR) Section 14.1.9, Loss of Normal Feedwater. The AFWS has adequate redundancy to provide the minimum required flow assuming a single failure.

The UFSAR analysis demonstrates that the AFWS is capable of removing the stored and residual heat plus reactor coolant pump {AB, P} waste heat following a loss of normal feedwater event, thereby preventing over-pressurization of the RCS and preserving reactor coolant inventory. For this event, all control rods inserted as required upon initiation of the reactor trip. Following the reactor trip, the plant was stabilized in hot standby with decay heat being removed by the main condenser. Pressurizer and steam generator pressures and levels, and RCS temperature were being maintained within their normal bands. Page 5 of 5