ML18150A146 UNITED STATES
NUCLEAR REGULATORY COMMISSION
OFFICE OF NUCLEAR REACTOR REGULATION
OFFICE OF NEW REACTORS
WASHINGTON, DC 20555-0001
August 10, 2018
NRC INFORMATION NOTICE 2018-09:
ELECTRICAL ARC FLASH CAUSED BY
FOREIGN MATERIAL DAMAGES FIRE DOOR
ADDRESSEES
All holders of an operating license or construction permit for a nuclear power reactor under
Title 10 of the Code of Federal Regulations (10 CFR) Part 50, Domestic Licensing of
Production and Utilization Facilities, except those who have permanently ceased operations
and have certified that fuel has been permanently removed from the reactor vessel.
All holders of and applicants for a combined license under 10 CFR Part 52, Licenses, Certifications, and Approvals for Nuclear Power Plants.
PURPOSE
The U.S. Nuclear Regulatory Commission (NRC) is issuing this information notice (IN) to inform
addressees of an event involving an electrical arc flash initiated by intrusion of foreign material
into a switchgear cubicle. The arc flash resulted in a pressure wave that damaged a fire door
serving as part of a 3-hour-rated fire barrier assembly. The NRC expects recipients to review
the information for applicability to their facilities and consider actions, as appropriate, to avoid
similar problems. However, suggestions contained in this IN are not NRC requirements;
therefore, the NRC requires no specific action or written response.
DESCRIPTION OF CIRCUMSTANCES
Turkey Point Nuclear Generating, Unit 3
As part of the transition to the risk-informed fire protection standard outlined in National Fire
Protection Association Standard 805, Performance-Based Standard for Fire Protection for Light
Water Reactor Electric Generating Plants, the licensee for Turkey Point committed to protecting
power cables for Unit 3 equipment required for post-fire safe-shutdown. This involved installing
Thermo-Lag 770-1 mats bound with high-temperature carbon fiber mesh (Thermo-Lag 75) and
matting over Thermo-Lag 330-1 mats. This configuration yields a 3-hour fire rating, an
improvement over the 1-hour rating provided by the Thermo-Lag 330-1 alone. The nuclear
industry has used Thermo-Lag 770-1 since 1995.
Placement of the Thermo-Lag 770-1 requires that the mesh be cut to size to fit the application.
This process creates carbon dust, carbon fibers, threads, and trimmings, which pose foreign
material hazards as they become airborne.
On March 18, 2017, Turkey Point Units 3 and 4 were operating at 100-percent power. The 4A
and 4B trains of high head safety injection (HHSI) were inoperable because of ongoing work to repair a leak on a common line off the minimum flow recirculation lines from the 4A and 4B
HHSI pumps. The HHSI system at Turkey Point consists of four trains3A, 3B, 4A, and
4Bany of which are available for injection to either unit. Despite the inoperability of the two
trains, the licensee determined that sufficient measures were in place to allow them to proceed
with installation of the Thermo-Lag 770-1 insulation material in the 3A switchgear room as part
of a project to upgrade the fire protection barriers in the room. Although bulk cutting of the mats
occurred outside the room, the metal and carbon fiber mesh were trimmed for final fit inside the
3A switchgear room where the installation was occurring.
At 11:07 Eastern Daylight Time, an internal fault on the 3A 4-kilovolt (kV) bus caused a
high-energy arc flash and lockout of the bus. One of the workers involved in the Thermo-Lag
installation was injured as a result of the blast, which also damaged parts of the bus and
associated bus bars. Unit 3 tripped on the resulting undervoltage condition on a vital bus. The
3A reactor coolant pump, which is powered from the 3A bus, tripped when the bus was lost.
The 3B and 3C reactor coolant pumps, powered from the 3B 4-kV bus, tripped on
underfrequency. The force of the pressure wave blew open and destroyed the fire door
between the 3A and 3B 4-kV switchgear rooms, resulting in smoke migration into the 3B
switchgear room.
The licensees evaluation found the most likely cause of the arc flash was conductive material
that entered the reactor coil cabinet,1 a cubicle in the switchgear between the high side of the
switchgear, which provides power to the nonsafety-related reactor coolant pump and main
feedwater pump, and the low side, which provides power to safety-related loads including the
3A HHSI pump. Licensee testing after the event found that the Thermo-Lag 75 used in the
installation of Thermo-Lag 770-1 is composed entirely of an electrically conductive carbon fiber.
Some pieces and several fibers of the mesh material were found inside the reactor coil cabinet
after the event. The foreign material entered either through the unscreened ventilation louvers
or through gaps where the bus bars entered the cabinet and created an electrical bridge from
the bus bars to the wall of the cubicle.
The root cause of the event was that the licensees installation requirements for Thermo-Lag did
not provide adequate guidance to address foreign material exclusion or specific precautions to
control airborne debris during the Thermo-Lag installation process.
Prior to the March 18, 2017, event in the 3A switchgear room, Turkey Point experienced
multiple potential precursor events which rendered the battery charger incapable of performing
its design function. On February 2, 2017, the 3A2 battery charger input breaker and motor
control center (MCC) supply breaker tripped, followed approximately 4 minutes later by a trip of
the spare battery charger input breaker. On February 8, 2017, the 3B2 vital battery charger
input breaker and MCC supply breaker unexpectedly tripped while in service. At the time of
both trips, work related to Thermo-Lag 770-1 installation was in progress in the battery charger
room in the vicinity of the affected chargers.
Subsequent investigation identified a notable level of dust in the battery charger room and also
inside the charger cabinets, which the licensee determined was conductive. The battery
chargers were cleaned and successfully returned to service without incident. The conductive
1 The reactor coil, or current-limiting reactor, is an inductor-type protection device that serves to limit any fault
current seen by the low side of the bus, which is constructed with smaller bus bars and breakers, to a value the
low side is capable of withstanding. properties of the Thermo-Lag 75 carbon fiber used in the Thermo-Lag 770-1 installation were
not discovered until after the arc flash event of March 18, 2018.
Additional information appears in Turkey Point Licensee Event Report 05000250/2017-001-00,
dated May 16, 2017 (Agencywide Documents Access and Management System (ADAMS)
Accession No. ML17136A372) and the following reports; NRC Reactive Inspection Report 05000250/2017008, 05000251/2017008, dated May 12, 2017 (ADAMS Accession
No. ML17132A258), NRC Integrated Inspection Report 05000250/2017001, 05000251/2017001 dated May 11, 2017 (ADAMS Accession No. ML17131A318), NRC Integrated Inspection Report 05000250/2017002, 05000251/2017002 dated August 11, 2017 (ADAMS Accession
No. ML17223A012), NRC Integrated Inspection Report 05000250/2017003, 05000251/2017003 dated November 9, 2017 (ADAMS Accession No. ML17313B131), and NRC Design Bases
Assurance Inspection (Team) Report 05000250/2017007, 05000251/2017007 dated October 2,
2017 (ADAMS Accession No. ML17277A837).
DISCUSSION
The importance of foreign material exclusion controls has long been recognized, but such
controls have traditionally focused on the vulnerability of open equipment, particularly during
maintenance periods. This event shows that electrical equipment that is not designed to be
airtight can be vulnerable to airborne dust and debris in its normal operating configuration. Best
practices for avoiding this type of situation include the following:
Work instructions for activities involving cutting or grinding specifically address potential
foreign material hazards created by the work.
The impact of ventilation systems and portable fans for habitability is carefully
considered for work in the vicinity of energized electrical equipment, especially work that
may generate electrically conductive dust or small pieces that may become airborne.
Training and procedures cultivate a mindset that considers the potential for foreign
material intrusion for all activities, not just during outages or when equipment enclosures
are open.
The corrective action program provides for thorough review, identification, and root
cause analysis of potential precursor events related to maintenance activity failures.
The failure of the fire door was unexpected in this situation. NUREG/CR-6850,
EPRI/NRC-RES Fire PRA Methodology for Nuclear Power Facilities, Volume 2, Detailed
Methodology, issued September 2005, provides a method for determining the zone of influence
from an arc flash event. This includes the assumption that components located within 0.91 meters (3 feet) horizontally of either the front or rear panels, at or below the top of the faulting
cabinet section, will suffer physical damage and functional failure from an arc flash event. The
distance from the reactor coil cabinet to the affected door is 4.42 meters (14.5 feet), well outside
the high-energy arc flash impact assessment area. An NRC review confirmed that the 3-hour
rated fire door met the licensing basis and design requirements, which do not require blast
resistance for doors separating the two safety-related switchgear rooms. The NRC is engaged
in testing to assess whether the method for estimating the zone of influence as discussed in
NUREG/CR-6850 is appropriate for all configurations.
CONTACT
This IN requires no specific action or written response. Please direct any questions about this
matter to the technical contacts listed below.
/ra/ (Paul G. Krohn for)
/ra/
Timothy J. McGinty, Director
Mark S. Miller, Acting Director
Division of Construction Inspection
Division of Inspection and Regional Support
and Operational Programs
Office of Nuclear Reactor Regulation
Office of New Reactors
Technical Contacts: Rebecca Sigmon, NRR
301-415-0895 E-mail: Rebecca.Sigmon@nrc.gov
301-415-3972
E-mail: Brian.Metzger@nrc.gov
Note: NRC generic communications may be found on the NRC public Web site, https://www.nrc.gov, under NRC Library. NRC INFORMATION NOTICE 2018-09, ELECTRICAL ARC FLASH CAUSED BY FOREIGN
MATERIAL DAMAGES FIRE DOOR, Date: August 10, 2018
ADAMS Accession Number: ML18150A146 *via email EPID No. L-2018-GEN-0002 OFFICE
NRR/IOEB/DIRS*
NRR/APLB/DRA*
QTE*
NRR/IOEB/DIRS/BC*
NRR/APLB/DRA/BC*
NAME
RSigmon
BMetzger
JDougherty
RElliott
GCasto
DATE
07/12/2018
07/12/2018
06/05/2018
07/16/2018
07/13/2018 OFFICE
NRO/DEI*
NRR/DRA/D*
NRR/DIRS/IRGB/PM*
NRR/DIRS/IRGB/LA*
NRR/DIRS/IRGB/BC*
NAME
IGarcia
MFranovich
ASchwab
ELee
BPham
DATE
07/16/2018
07/26/2018
07/27/2018
07/30/2018
08/02/2018 OFFICE
NRO/DCIP/D
NRR/DIRS/D
NAME
TMcGinty (PKrohn)
MMiller
DATE
08/08/2018
08/10/2018
OFFICIAL RECORD COPY