05000272/LER-1980-060, Forwards LER 80-060/03L-0

From kanterella
(Redirected from ML18085A334)
Jump to navigation Jump to search
Forwards LER 80-060/03L-0
ML18085A334
Person / Time
Site: Salem 
Issue date: 11/28/1980
From: Librizzi F
Public Service Enterprise Group
To: Grier B
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
Shared Package
ML18085A335 List:
References
NUDOCS 8012050382
Download: ML18085A334 (2)


LER-1980-060, Forwards LER 80-060/03L-0
Event date:
Report date:
2721980060R00 - NRC Website

text


s Public Service Electric and Gas Company 80 Park Place Newark, N.J. 07101 Phone 201 /430-7000 Mr. Boyce H. Grier Director of USNRC November 28, 1980 Off ice of Inspection and Enforcement Region 1 631 Park Avenue King of Prussia, Pennsylvania 19406

Dear Mr. Grier:

LICENSE NO. DPR-70 DOCKET NO. 50-272 REPORTABLE OCCURRENCE 80-60/03L c.:J u:;.

~;~~~~

o--o._.

o~:D

~-Ulc;

~m

o

(}

rri

(/)

'-.D Q'_)

c:>

0 rn 0

-~

.:=.k..

\\.l~

0

\\.11 Pursuant to the requirements of Salem Generating Station Unit No. 1 Technical Specifications, Section 6.9.1, we are submitting Licensee Event Report for Reportable Occurrence 80-60/03L.

This report is required within thirty (30) days of the occurrence.

Sincerely yours,

/J-~~~~-

F. P. L1br1zz1 General Manager -

Electric Production CC:

Director, Office of Inspection and Enforcement (30 copies)

Director, Office of Management Information and Program Control

( 3 copies) r*-

.: :_~}

(-)*=*

z;~

c:0

'.:::c:J

- iC:

CJ

z 95-2001 (200M) 2-78

Report Number:

_Report Date:

Occurrence Date:

80.0/03L 11/28/80 10/08/80 Facility:

Salem Generating Station, Unit 1 Public Service Electric & Gas Company Hancock's Bridge, New Jersey 08038 IDENTIFICATION OF OCCURENCE:

Diesel Generators Inoperable CONDITIONS PRIOR TO OCCURRENCE:

Mode 6 DESCRIPTION OF OCCURRENCE:

The llSW nuclear HDR was out of service and cleared and tagged for repairs.

The diesels were found to be overheating.

All the diesels were declared inoperable and Action Statement 3.8.l.2b was entered at 2158 hours0.025 days <br />0.599 hours <br />0.00357 weeks <br />8.21119e-4 months <br /> on October 8, 1980.

It was determined that when the indicator for the 12SW21 valve was in the open position, the valve was actually closed.

The valve was opened and tagged to remain in th open position by the shift supervisor until the indicator was properly aligned.

It was determined that sufficient cooling water was available for the diesels.

The lA Diesel was run for one hour with no overheating problems and subsequently declared operable.

Then the lB and lC Diesels were run at the same time for an hour with no overheating problems and subsequently declared operable.

The Action Statement

.was terminated at 0216 hours0.0025 days <br />0.06 hours <br />3.571429e-4 weeks <br />8.2188e-5 months <br /> on October 9, 1980.

DESIGNATION OF APPARENT CAUSE OF OCCURRENCE:

The apparent cause of the occurrence was that the valve positioner and indicator were aligned incorrectly with the valve.

ANALYSIS OF OCCURRENCE:

Inoperable diesel generators constitute a loss of an emergency power source.

CORRECTIVE ACTION

The 12SW21 valve positioner and indicator were aligned correctly.

FAILURE DATA:,

Not Applicable Prepared by:

J. c; Osuch Manager -

Salem Generating Station SORC Meeting No.

96-80