05000272/LER-1980-046, Forwards LER 80-046/03L-0

From kanterella
(Redirected from ML18082B144)
Jump to navigation Jump to search
Forwards LER 80-046/03L-0
ML18082B144
Person / Time
Site: Salem 
Issue date: 09/04/1980
From: Librizzi F
Public Service Enterprise Group
To: Grier B
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
Shared Package
ML18082B145 List:
References
NUDOCS 8009120424
Download: ML18082B144 (2)


LER-1980-046, Forwards LER 80-046/03L-0
Event date:
Report date:
2721980046R00 - NRC Website

text

-r* ~**

\\.__

e PS~G Public Service Electric and Gas Company 80 Park Place Newark. N.J. 07101 Phone 2011430-7000 Mr. Boyce H. Grier Director of USNRC.

September 4, 1980 Off ice of Inspection and Enforcement Region 1 631 Park Avenue King of Prussia, Pennsylvania 194d6

Dear Mr. Grier:

LICENSE NO. DPR-70 DOCKET NO. 50-272 REPORTABLE OCCURRENCE 80-46/03L Pursuant to the requirements of Salem Generating Station Unit No. 1 Technical Specifications, Section 6.9.1, we are submitting Licensee Event Report for Reportable Occurrence 80-46/03L.

This report is required within thirty (30)* days of the occurrence.

Sincerely yours, F.~~

General Manager -

Electric Production CC:

Director, Office of Inspection and Enforcement (30 copies)

Director, Office of Management Information and Program Control (3 copies)

~tlO O 9 1 2 o t2 'f s

95-2001 i200MI 2-78

Report Number:

80-46/03L Report Date:

9/4/80 Occurrence Date:

8/10/80 Facility:

Salem Generating Station, Unit l Public Service Electric & Gas Company Hancock's Bridge, New Jersey 08038 IDENTIFICATION OF OCCURRENCE:

Reactor Trip Instrumentation CONDITIONS PRIOR TO OCCURRENCE:

Mode l Reactor Power 81%

DESCRIPTION OF OCCURRENCE:

During routine operation, it was determined that 12 Steam Generator Level - Feed Flow-Steam Flow Mismatch Circuit had failed.

Action Statement 3.3.l.l was entered at 2319 hours0.0268 days <br />0.644 hours <br />0.00383 weeks <br />8.823795e-4 months <br /> and requires that with the number of operable channels one less thdn the total number of channels1 startup and/or power operation may proceed until perfor-mance of the next required channel functional test provided the inoperable channel is placed in the tripped condition within one hour.

DESIGNATION OF APPARENT CAUSE OF OCCURRENCE:

Equipment Failure

CORRECTIVE ACTION

During troubleshooting, it was determined that the feed flow-steam flow mismatch comparator had failed.

The comparator was replaced from stock and tested satisfactorily.

The Action Statement was terminated at 0201 hours0.00233 days <br />0.0558 hours <br />3.323413e-4 weeks <br />7.64805e-5 months <br /> on August 12, 1980.

FAILURE DATA:

Hagan Module Part Number 411082-001 Prepared By M. J. Murphy Manager -

Salem Generating Station SORC Meeting No.

68-80