05000272/LER-1980-027, Forwards LER 80-027/03L-0

From kanterella
(Redirected from ML18082A612)
Jump to navigation Jump to search
Forwards LER 80-027/03L-0
ML18082A612
Person / Time
Site: Salem 
Issue date: 06/18/1980
From: Librizzi F
Public Service Enterprise Group
To: Grier B
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
Shared Package
ML18082A614 List:
References
NUDOCS 8006240486
Download: ML18082A612 (2)


LER-1980-027, Forwards LER 80-027/03L-0
Event date:
Report date:
2721980027R00 - NRC Website

text

....

OPS~G Public Service Electric and Gas Company 80 Park Place Newark, N.J. 07101 Phone 201/430-7000 Mr. Boyce H. Grier Director of USNRC June 18,.1980 Off ice of Inspection and Enforcement Region l 631 Park Avenue King of Prussia, Pennsylvania 19406

Dear Mr. Grier:

LICENSE NO. DPR-70 DOCKET NO. 50-272 REPORTABLE OCCURRENCE 80-27/03L Pursuant to the requirements of Salem Generating Station Unit No. l Technical Specifications, Section 6.9.1, we are submitting Licensee Event Report. for Reportable Occurrence 80-27/03L.

This report is required within thirty (30) days of the occurrence.

Sincerely yours, Ji,

./ / L '-....-._. t--._ - )'\\....

F. P. Librizdi General Manager -

Electric Production CC:

Director, Office of Inspection and Enforcement (30 copies)

Director, Office of Management Information and Program Control (3 copies) 95-2001 (200M) 2-78

Report Number:

80-27/03L Repoft Date:

6/18/80 Occurrence Date:

5/21/80 Facility:

Salem Generating Station Unit 1 Public Service Electric & Gas Company Hancock's Bridge, New Jersey 08038 IDENTIFICATION OF OCCURRENCE:

Missed Surveillance CONDITIONS PRIOR TO OCCURRENCE:

Mode 1 Reactor Power 100%

DESCRIPTION OF OCCURRENCE:

In reviewing the surveillance requirements for Unit 2 fuel load, it was discovered the equivalent surveillance, 4.7.10.l.2(cl), for Unit 1 had not been completed.

The surveillance requires at least once per 18 mopths, during shutdown, the fire pump diesel engine shall be proved operable by subjecting the diesel to an inspection in accordance with procedures prepared in conjunction with its manufacturer's recommendations for the class of service.

DESIGNATION OF APPARENT CAUSE OF OCCURRENCE:

Personnel error *

. ANALYSIS OF OCCURRENCE:

The surveillance requirement had not beep previously identified and when noted, it was determined based on the number of hours of operation, no inspection was necessary.

A tracking mechanism was not utilized to ensure any necessary inspections were completed on time.

. CORRECTIVE ACTION:

Based on discussions with the manufacturer, no inspection was necessary.

The tracking system has been corrected to ensure the surveillance requirements are reviewed periodically.

FAILURE DATA:

Not Applicable Prepared By* ___

. _M_. __

  • J_*. __

M_u_r~p_h_Y.._ __

Manager - Salem Generating Station SORC Meeting No.' ' ' ---------