- consumers Power POWERING MICHIGAN'S PROGRESS Palisades Nuclear Plant:
27780 Blue Star Memorial Highway, Covert, Ml 49043 February 25, 1994 Nuclear Regulatory Commission Document Control Desk Washington, DC 20555 David W. Rogers Plant Safety and Licensing Director DOCKET 50-255 - LICENSE DPR PALISADES PLANT - CHANGE IN COMMITMENT -
ELECTRICAL DISTRIBUTION SYSTEM FUNCTIONAL INSPECTION REPORT COMMITMENTS - NRC INSPECTION REPORT No. 91019 The NRC conducted an Electrical Distribution System Functional Inspection (EDSFI) at the Palisades Plant from November 4, 1991 to December 13, 1991 and documented the results in Inspection Report (IR) No. 91019, dated January 31, 1992.
By letter dated March 2, 1992, Consumers Power Company (CPCo) responded to the violations and deviations identified in IR 91019 and provided corrective action necessary to address the violations. Our submittal dated March 31, 1992, responded to the open items contained in IR 91019 and identified corrective action necessary to address the open items.
By letter dated September 27, 1993, we provided the NRC with an EDSFI closeout plan which reflected our understanding of the work scope and the resources
- required to complete the remaining EDSFI commitments.
In that letter we also stated that we would continue to review the remaining EDSFI commitments in conjunction with our known and emergent work loads, and continue to place appropriate emphasis on closure of the remaining EDSFI commitments.
As part of our ongoing review of the remaining EDSFI commitments, we have found it necessary to change two commitment dates. The commitments and the reasons for the changes are discussed in the following paragraphs, as well as new projected compl~tjon dates for these commitments.
NRC Concern No. 3 dealt with the selection basis for the setpoints for the second level undervoltage relays on 2400V buses IC and ID.
Consumers Power Company agreed to review the setpoints for degraded grid voltage conditions and develop a load fl ow model for the system.
The development _oC the_ _
~ __
engineering ~nalysis to-~tudy this fsstie ha~-bi~n ~~g~i~g for the past six months. During review of the analysis it was identified that relay tolerances were not adequately incorporated in the analysis.
Re-work of the engineering 9403080396 940225 PDR ADOCK 05000255 /
Q_
' *i f.
(,
A CMS' ENERGY COMPANY
analysis is necessary and, therefore, we are projecting a completion date of September 1994.
A second commitment, tied to the completion of NRC Concern No. 3, was to use the results of the engineering analysis to determine the effects of potential transformer burden and relay tolerances on the second level undervoltage relay setpoints. This work was to be performed in series with-the engineering analysis and was to be completed approximately two months after completion of the engineering analysis. Since the engineering analysis to select the initial setpoints will be delayed until September 1, 1994 the completion of the determination of the effects of potential transformer burden and relay tolerances will be extended to November 1, 1994.
Also during the EDSFI inspection, the NRC noted a number of deficiencies in our emergency diesel generator system fuel oil supply system documentation.
These deficiencies were documented as NRC Concerns No. 21 and 50.
In our September 27, 1993 letter, we committed to change our technical specifications following the completion of an engineering analyses designed to provide better documentation for fuel oil consumption.
The engineering analyses have been completed; however, the submittal of a Technical Specifications change request (TSCR) implementing the resolution of EDSFI Concerns 21 and 50 will be delayed beyond its initial completion date of March 1, 1994.
The Electrical TSCR has been developed, but its submittal has been delayed because of a potential conflict with a previously submitted TSCR on Shutdown Cooling Requirements.
At the request of the NRR Palisades project manager, the Electrical TSCR will be delayed until after approval of the Shutdown Cooling TSCR, which is expected to occur within about 60 days.
Once the Shutdown Cooling TSCR has been approved, the Electrical TSCR will be submitted, resolving the above EDSFI issues and several other outstanding issues in the electrical *portion of the Palisades Technical Specifications. Current plans call for submittal of the Electrical TSCR by September 1, 1994.
In addition, we have enclosed updates to the tables originally provided as Attachments 1 and 2 to our September 27, 1993 letter. Attachment 1 of this letter identifies by the assigned NRC inspection report number each EDSFI open item, violation, or deviation.
The corresponding EDSFI concern number, identified during the EDSFI inspection, is provided as a cross reference.
The attachment identifies the previously identified-commitment date and provides the new commitment date where a schedule revision is necessary.
Lastly, the attachment identifies the completion date of previously closed commitments and those commitments that have been closed since our September 27, 1993 letter. of this letter describes the EDSFI concerns that were identified during the EDSFI inspection, but were not included in the EDSFI inspection report.
As with.Attachment 1, Attachment 2 identifies the completion date of previously closed commitments and those commitments that have been closed since our September 27, 1993 letter.
2
As previously mentioned in our September 27, 1993 letter, we will continue to review the remaining EDSFI commitments in conjunction with our known and emergent work loads and will continue to place appropriate emphasis on closure of the remaining EDSFI commitments.
For your information we have provided an updated version of the tables we originally provided in our September 27, 1993 letter which shows activities completed since our last submittal and the new commitment dates discussed above.
(LJw,~-
David W Rogers Plant Safety and Licensing Director CC Administrator, Region III, USNRC NRC Resident Inspector - Palisades Attachments 3
ATTACHMENT I Consumers Power Company Palisades Plant Docket 50-255 Table I Docketed EDSFI Concerns sorted by EDSFI Inspection Report Open Item Number February 25, 1994 5 Pages
2/25/94 NRC NUMBER CONCERN (91-19-XX)
NUMBER 91-19-01 14 91-19-01 14a 91-19-01 19 91-19-01 19b 91-19-01 68 91-19-02 46 91-19-03 37 91-19-04 01 104 91-19-04 01 04a 91-19-05 04:
91-19-06 43 91-19-07 01 oi 91-19-08 91.-19-08 51a Palisades Nuclear Plant - Consumers Power Company Docketed EDSFI Concerns Sorted by Inspection Report Number TABLE COMMITMENT DESCRIPTION For conservatism, correct cable r*esistances in PSS/E Loadflow Model to 90 deg c.
For conservatism, correct cable resistances of the Safeguards cable to 90 degC (Loadflow) and 25 deg C *
(Short Circuit). Correct SafeGuards Reactances based on field tests and analyses.
Determine the effects of circuit breaker and fuse impedances on LF/SC models Review o~ station power load flow calculations. Concerns about assumed cable temperatures, applicability of sources for ass1.J111>tions in the calcs, and up-to-dateness of the calcs (since 1988/89). Also hard to trace the sources for some of the values used in the calcs.
Determine maximum allowable a!11'S and the total allowable time for worst case accident conditions for cables feeding 2400 v busses 1C and 10.
See also A-NL-92-079.
Identify voltages on Class 1E Equipment due to a stuck Tap Changer.
Establish Operating Procedure.
Update the Post-LOCA Analysis on SUT 1-2 and determine maximum allowable amperage and total allowable time for worst case accident conditions for cable feeding 2400v buses 1C and 10 from SUT 1-2.
This is also addressed by A-NL-92-112.
Initiate a change to.the FSAR to make an exception to the 200 Deg C requirement for the two cables feeding switchyard power.
Review the 480V system for similar situations of cables not properly protected.
(Switchyard Station Power Transformer Cable.)
Document maximum voltage ass~tions and update the short circuit analysis with cable resistances at 25 deg C.
Inadequate Operating Procedures relative to 2400 system ground f.ault indication. Concern is lack of emphasis on the need to prompt action, and method.*
(Overvoltage on Ungrounded 2400V System.)
The Plant determined that no corrective action was required on this item.*
Identify minimum required 2400 v voltages prior to transferring diesel generator loads back to an available off-site supply and incorporate voltage limits into appropriate operating procedures.
Retransfer of LOCA loads to the preferred Coffsite) source from the EOG may lead to a voltage drop of
>2%.
This may cause activation of the second level of UV relays.
Page 1*
PREVIOUS COMMITMENT COMMITMENT DATE DATE DUE DATE CLOSED 12/01/93 12/01/93 4/14/93 12/01/94 12/01/94 6/07/93 6/30/94 1/01/95 12/01/92 12/01/92 8/27/92 9/30/93 7/31/94 6/30/94 7/31/94 6/30/94 7/31/94 6/01/92 6/01/92 6/01/92 9/01/92 9/01/92 8/25/92 12/01/93 12/15/94 3/30/92 3/30/92 3/30/92 3/30/92 3/30/92 12/10/91 9/30/94 12/15/94 6/30/92 6/30/92 5/13/92
2/25/94 NRC NUMBER (91-19-XX) 91-19-09 91-19-09 91-19-10 91-19-11 91-19-11 91-19-11 91-19-12 91-19-12 91-19-14 91-19-14 91-19-14 91-19-15 CONCERN NUMBER 42 52 62 I
11 01 11 UI 11 45:
45a 10 10a 10b 331 Palisades Nuclear Plant - Consumers Power Company Docketed EDSFI Concerns Sorted by Inspection Report Number TABLE COMMITMENT DESCRIPTION Load flow analyses do not include all motor loads per FSAR requirement to start the largest load with all other loads running.
Submit a change to the FSAR 8.3.2 wording and review Chapter 8 to ensure that cur*rent Loadflow Analyses align with FSAR statements and conmitments per D-PAL-91-104B.
Complete additional analyses of Post LOCA Operating Contingencies per EOPs and incorporate o*iesel Generator Loading Limits into the appropriate Operating Procedures as required.
The control scheme for the EOG ~toys several automatic trip mechanisms that do not require two or more independent measurements in the trip logic.
Differences between station battery internal resistance shown in the DBO 4.01 and that used in the referenced calcul~tion (010/SC).
Review and revise TSSP's RT-BC and RT-80 to demonstrate load shedding of the emergency loads.
(Engineered Safeguards Testing.)
Submit a Technical Specification Change Request that contains a more conservative emergency diesel generator testing requirement to address NRC concern.that the Tech Spec wording that allows for the automatic starting of only "selected motors and equipment" (apparently original TS wording) is not consistent with emergency diesel testing as stated in the Combustion Engineering Standard TS.
(Reference Violation #2d from Nov, 91-19-12 from Inspection Report, EDSFI Concern 45.
Violation #2d from Nov, 91-19-12 from Inspection Report, EDSFI Concern 45.
Use results from the walkdowns conducted on all MCCs located outside of containment for the purpose of verifying components to implement actions to ensure plant equipment matches the setting sheet specifications.
For safety-related MCCs, make operability determinations for discrepant information.
Provide walkdown verification of setting sheet specifications for MCCs located inside containment.
Operability determinations will be made for discrepant information relating to safety-related MCCs.
The team found thermal overloads set at different values than the setting sheets.
What program is used to control that the thermal overloads are properly set and sized?
The OBD for the EOG states that there are two independent starting circuits on separate DC sources.
How can we get assurance that without channel B field flashing *ckt, the EOG can meet the 1.0 sec start requirement?
Page 2*
PREVIOUS COMMITMENT COMMITMENT DATE DATE DUE DATE CLOSED 12/01/92 12/01/92 8/25/92 12/01/93 7/20/93 6/30/93 6/01/93 4/24/92 6/01/92 8/01/92 11/30/92 5/15/92 11/30/92 3/27/92 6/01/94 5/15/95 6/30/93 7/20/93 4/24/92 6/01/92 8/01/92 2/16/95 5/15/92 11/30/92 3/27/92 1/06/92 6/18/93 4/24/92 5/12/92 7/30/92 2/25/92 3/25/92 3/26/92
2/25/94 NRC NUMBER CONCERN (91-19-XX)
NUMBER Palisades Nuclear Plant - Consumers Power Company Docketed EDSFI Concerns Sorted by Inspection Report Number TABLE COMMITMENT DESCRIPTION 91-19-16 59 Exceeded.Tech Spec limit of 750 amps on EOG during the monthly testing without reporting this to the NRC.
91-19-16 59a Exceeded. Tech Spec limit of -750 amps on EOG during the monthly testing, without reporting this to the NRC.
91-19-17 91-19-17 91-19-18 12 1Zb 01; 18 91-19-19 u
91-19-20 09 I
91-19-20 26 91-19-21 64 I
91-19-21 None f 91-19-22 20 91-19-22 91-19-22 91-19-22 91-19-22 20a i
20c !
20d.
Various discrepancies betwee*n the E-8 single line drawings and other design or as-built information.
Various discrepancies between the E-8 single line drawings and other design or as-built information.
Update the DC voltage drop and short circuit calculations with cable resistances at rated cable ternperat~re (voltage drop) and at 25 Deg C (short circuit).
Concern about coordination between battery charger breaker and the charger current limit value of 220 amps.
Develop ~nd implement a test: program that periodically verifies that the battery chargers will provide rated output current for an appropriate period of time.
Procurement of test equipment and development of a test procedure is required.
(Work Orders 24203489, 24203490, 24203491, 24203493).
Develop and implement a test program that periodically verifies that the battery chargers will provide rated output cur.rent for an appropriate period of time.
Procurement of test equipment and development of a test procedure is required, ewes 24203489, 90, 91, & 93.)
.It appears that the Control Room alarm "Control Switch Not in Auto" referenced in Section 8.4.1.3 is not installed. EOG Respond t.o Open Items and Unresolved Items in Inspection Report 91-19.
Failure to meet FSAR/TS or seismic criteria for 28 hour3.240741e-4 days <br />0.00778 hours <br />4.62963e-5 weeks <br />1.0654e-5 months <br /> run time, 2500 gallons available, tank level switches :non-seismic, no visual day tank level scale.
Failure to meet FSAR/TS or seismic criteria for 28 hour3.240741e-4 days <br />0.00778 hours <br />4.62963e-5 weeks <br />1.0654e-5 months <br /> run time, 2500 gallons available, tank level switches non-seismic, no visual day tank level scale. Revise TS run times, determine consumption rate, evaluate new alarm levels and control settings.
Failure to meet FSAR/TS or seismic criteria for 28 hour3.240741e-4 days <br />0.00778 hours <br />4.62963e-5 weeks <br />1.0654e-5 months <br /> run time, 2500 gallons available, tank level switches non-seismic, no visual day tank level scale. Evaluate adequacy of day tank.
- 1) Day tank capacity, alarm and level detector set.ting concerns.
- 2) Some were known since 1983.
What has been done on these items* since then?
(Supplement submitted 12/6/91) ~DG DFO
- 1) Day tank capacity, alarm.and level detector sett'ing concerns.
- 2) Some were known since 1983.
What has been done on these items since.then?
Revise the FSAR to identify changes.
PREVIOUS COMMITMENT DATE 5/31/92 8/01/92 12/01/93 4/30/92 6/30/94 12/01/93 7/20/93 7/20/93 12/01/92 3/31/92 12/01/92 12/01/92 12/01/92 12/15/92 12/16/93 COMMITMENT DUE DATE 5/31/92 8/06/92 12/01/93 4/30/92 12/15/94 Page DATE CLOSED 5/26/92 8/03/92 6/07/93 4/22/92 12/15/93 11/23/93 7/20/93 7/14/93 7/20/93 7/14/93 12/01/92 11/17/92 3/31/92 3/31/92 4/30/93 4/28/93 9/01/94 11/30/93 9/21/93 12/15/92 12/15/92 2/01/94 2/22/94 3'
2/2S/94 NRC NUMBER CONCERN (91-19-XX)
NUMBER 91-19-22 z'oe I
91-19-22 21 91-19-22 21a 91-19-22 2~b 91-19-22 21c 91-19-22 2~d 91-19-22 21e 91-19-22 22 91-19-22 24 91-19-22 24a 91-19-22 so 91-19-22 SOa 91-19-22 SOb I
91-19-22 soc 91-19-22 SOd I
I 91-19-22 SOe 91-19-22 SOf 91-19-22 69 91-19-22 None a Palisades Nuclear Plant - Consumers Power Company Docketed EDSFI Concerns Sorted by Inspection Report Number TABLE COMMITMENT DESCRIPTION
- 1) Day tank capacity, alarm and level detector setting concerns.
- 2)
Some were known since 1983.
What has been* done on these items since then?
(Supplement submitted 12/6/91).
EOG DFO.
No evidence exists showing actual EOG fuel consumption rates to support 28-hour day tank capacity.
Calculate consumption rate.for fir.st 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> of OBA *.
No evidence exists showing actual EOG fuel consumption rates to support 28-hour day tank capacity.
Revise FSAR/TS for existing.fuel oil system capabilities.
No evidence exists showing actual EOG fuel consumption rates to support 28-hour day tank capacity.
Determine minimum run time for belly and day tank capacity.
No evidence exists showing actual EOG fuel consumption *rates to determine required day tank capacity.
Evaluate. required vs available fuel oil inventories.
No evidence exists showing t'he actual EOG fuel consumption rates to determine required day tank capacity.
Perform a diesel fuel consumption for.both EDGs.
No evidence exists showing a'ctual EOG fuel consumption rates to determine required day tank capacity.
P-18A & B not*tested to ensure automatic operation.
No acceptance criteria available for pump discharge pressure, motor current or voltages to compare with test results.
DFO.
EOG external day tank fill coruiections: no evidence of testing or maintenance; no guarantee of timely delivery of delivery truck.
Perform test to verify ability to fil.l t.he Day Tank from an external source.
Evaluate need to obtain guarantee for timely delivery of fuel oil.
The TS EOG fuel minimum of 16,000 gal must be revised to incorporate SSDC considerations and recognition of the other demands of T-10.
The TS EOG fuel minimum of 16,000 gal must be revised to incorporate SSDC considerations and recognition of the other demands on T-10.
Determine T-10, T-2S, belly tank unuseable fuel quantity.
The TS EOG fuel minimum of 16,000 gal must be revised to incorporate SSDC consideration and recognition of the other demands on T-10 *.
Confirm FSAR/TS changes have been implemented in mother document.
The TS EOG fuel minimum-of 16,000 gal must be revised to incor~orate SSDG considerations and recognition
.of the other demands on T-10.
The TS EOG fuel minimum of 16,000 gal must be revised to incorporate SSDC considerations and recogn1t1on of the other demands on T-10~ Determine quantity of fuel oil required with and without energy conservation controls.
The TS EOG fuel minimum of 16,000 gal must be revised to incorporate SSDC considerations and recognition of the other demands on T-10.
Revise FSAR/TS fuel oil consumption, available volumes, and run time.
The TS EOG fuel minimum of 16,000 gal must be revised to incorporate SSDC considerations and recognition of the other demands on T-10.
(Supplemented on 12/11/91.)
.storage tank T-10 and its appurtenances are not seismically or tornado qualified (loading and missiles).
Determine T-10, T-2S, belly tank available inventories.
Page
'+
PREVIOUS COMMITMENT COMMITMENT DATE DATE DUE DAT 1E CLOSED 12/01/92 12/22/92 1/04/93 12/01/92 11/30/93 9/21/93 12/01/92 9/01/94 12/01/92 12/31/93 9/21/93 9/30/93 12/31/93 9/29/93 S/31/93 9/30/93 6/11/93 3/31/93 3/31/93 4/14/93 6/30/92 6/30/92 6/29/92 12/1S/92 12/1S/92 12/1S/92 11/30/93 7/01/9~
12/01/92 12/01/93 11/30/93 12/01i92 12/01/93 11/11/93 12/01/93 1/16/94 12/20/93 12/01/92 11/30/93 11/30/93 12/01/92 11/30/93 11/29/93 12/01/93 9/01/94, 6/01/92 6/01/92 4/13/92 12/01/92 11/30/93 11/30/93 3/31/93 3/31/93 3/31/93
2/25/94 NRC NUMBER CONCERN (91-19-XX)
NUMBER 91-19-22 None b 91-19-22 None c 91-19-23 35b 91-19-24 16 91-19-24 16a 91-19-24 16b 91-19-25 55 91-19-25 55a 91-19-25 5Sb 91-19-26 40 91-19-27 70 0/G 7-day Electric Load Study.
Palisades Nuclear Plant - Consumers Power Company Docketed EDSFI Concerns Sorted by Inspection Report Number TABLE COMMITMENT DESCRIPTION Document reconmended corrective actions for fuel oil system.
- 1.
Room steam header:
a) not *seismically mounted; b) steam and condensate lines not seismically supported.
- 2.
EOG room HVAC a) ducting not seismic supported; b) more than one fan required to cool room; c) 'SWS flow to jacket and lube oil at max to maintain control room HVAC needs.
The EOG mufflers are not bolted in place. Concern that it could be dislodged and choke the exhaust.
Even if bolted in place, concern exists about seismic qualification.
(Supplemented 12/4/91 and 12/10/91).
The EOG ri..Jfflers are not bolted in place.
Concern that it could be dislodged and choke the exhaust.
Even if bolted in place, concern exists about seismic qualification.
(Supplemented 12/4/91 and 12/10/91).
The EOG mufflers are not bolted in place~ Concern that it could be dislodged and choke the exhaust.
Even if bolted in place, concern exists about seismic qualification.
(Supplemented 12/4/91 and 12/10/91.)
The EDGs*have never been tested to demonstrate the ability to start at the minimum temperature conditions specified by the manufacturer (eg, 90 Deg F lube oil temp and 65 Deg F room temperature). Monthly test does not verify these parameters prior to startup. Perform test of minimum temperature.
The EOGs have never been tested to demonstrate the ability to start at the minimum temperature conditions specified by the manufacturer (eg, 90 Deg F lube oil temperature and 65 Deg F room temperature).
Monthly test does not verify these parameters prior.to startup. Evaluate need to alarm parameters.
The ED Gs *have never been.tested to demonstrate the abi l i ty to start at the mini mum teperature conditions
- specified by the manufacturer (eg, 90 Deg F lube oil temperature and 65 Deg F room temperature). Monthly test does not verify these parameters prior to startup.
Concern that the requirements of JLH 91*084 (8/27/91) have not been proceduralized.
Concerns restriction on maintenance in the switchyard during EOG testing.
(Supplement issued 12/11/91).
FC-839 requires that the low suction pressure and low lube oil pressure trips are to be blocked when charging pump B is fed from the alt pump C bus. However, neither of these trips were verified during Post Mod Testing.
In light of the two ORs.on this mod's wiring, how do we know that the trips are blocked?
Page 5'
PREVIOUS COMMITMENT COMMITMENT DATE DATE DUE DATE CLOSED 7/31/93 12/31/93 11/30/93 I
9/30/93 12/31/93 9/21/93 I
6/30/92 6/30/92 6/30/92 7/01/94 6/18/95 3/31/92 6/15/92 4/28/92 3/20/93 3/20/93 4/08/92 9/30/93 9/30/93 9/27/93 9/30/93 9/30/93 6/09/93 5/01/92 5/01/92 4/30/92 9/30/93 9/30/93 3/04/93 11/30/92 11/30/92 11/30/92
ATTACHMENT 2 Consumers Power Company Pali sades Pl ant Docket 50-255 Table 2 Non-Docketed EDSFI Concerns sorted by Concern Number February 25, 1994 3 Pages
2/25/94 CONCERN Palisades Nuclear Plant - Consumers Power Company Nondocketed EDSFI Concerns TABLE 2 NUMBER COMMITMENT DESCRIPTION 03 Document Second level UV relay setpo.ints with Load Flow model.
Include the effects of AC contactor control circuit voltage drops.
Coordinate results with System Protection Engineering.
03a Review the UnderVoltage relay setpoints using the results of the latest Load Flow model from NECO.
The effects of PT burden, relay tolerance and AC contactor control circuit voltage drop should be clearly documented.
15 17 29 34 34a 35 35a Develop a design basis document related to plant HVAC systems to address NRC concern that the HVAC for 1C and 10 switchgear room has not been tested, is not qualified, and the calculation proving adequacy of the design is not available.
The CTs for breakers 152-105 and 106 are connected to Class 1E overcurrent relays and non-1E anmeter and wattmeter in the Control Room.
There is no elec isolation.
Complete system Protection Engineering's review and redocumentation of all original Bechtel protective d~vice settings.
Improve the Diesel. Engine Air Start Control Circuit Logic.
Clarify statements in the FSAR to reflect actual plant configuration. Transferred to #62.
TS testing *of the EOG alternates the use of the A and B starting circuits. 1) Since TS do not address the use of two starting motors, what is the design basis to meet the 10 second time? 2) Does the use of two air motors constitute independence?
- 1.
Room steam heater: a) not seismically mounted; b) steam and condensate lines not seismically supported.
- 2.
EOG room HVAC ductin.g not seismically supported.
- 1.
Room steam heater: a) not seismically mounted; b) steam and coOdensate lines not seismically supported.
- 2.
EOG room HVAC: a) ducting not seismic supported; b) more than one fan required to cool room; c) SWS
36 Expressed concern that critical components of the Electric Distribution System had seismic support problems.
Suggested that CPCo accelerate the planned SQUG program for these components and later merge this with the Seismic Inspection Program verifications.
39 HVAC system and components for 1C & 1D switchgear rooms, cable spreading room, battery rooms, and electric equipment room is not safety-related,* seismically supported, or tornado-proof.
Concerned about HVAC supporting systems (chilled water) also.
49 The temp of the switchyard battery is not monitored.
(Ref TS 3.7.1) 54 cdmplete System Protection Engineering's calculations for the power penetration's protective device settings which illustrate the lit thermal withstand capability for faults.
57 Electrical calculations/modification packages indicate that there are still design control deficiencies.
58 It is possible that the EOG room and jacket temperature will drop below minimum between the 8 hour9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> walkdowns.
61 Autoclosure of the EOG breaker (152-106) is blocked to avoid connection to a faulted bus.
However, there is no provision to prevent autoclosure to EOG breaker 152-107 on a faulted bus.
Page
- 1 PREVIOUS COMMITMENT COMMITMENT DATE DATE DUE DATE CLOSED 9/30/93 9/01/94 9/30/93 11/01/94 12/01/93 12/01/93 10/15/93 12/01/93 12/01/93 5/14/93
. 12/01/94 12/31/94 7/20/93 5/15/95 9/30/92 9/30/92 2/24/92 5/18/95 6/18/95 10/05/91 10/05/91 10/16/91 12/31/92 6/18/95 12/01/93 12/01/93 7/26/93 11/16/92 11/16/92 11/05/92 12/01/94 12/31/94 12/01/92 12/01/92 11/30/92 11/30/93 11/30/93 6/09/93 7/20/93 5/15/95
Palisades Nuclear Plant -
surners Power Company 2/25/94 Nondocketed EDSFI Concerns TABLE 2 CONCERN NUMBER COMMITMENT DESCRIPTION 65 There is no panel alarm if the crankcase exhaust evacuation motors fail when they should be operating.
Concern is explosive vapors in the EOG rooms.
66 Current drawings and documents do not contain manufacturer size and model information for fuses.
What is fuse control program?
67 Butyl rubber electrical cable is variously shown as having an 85 or 90 Deg C temperature rating.
IR 020 IR 027 IR 031 IR 032 IR 035 IR 052 IR 087 IR 131 IR 131A IR 199 IR 201 IR 206 IR 214 IR 269 IR 284 IR 300 IR 307 Calculations to establish sizing and life use both values.
Manufacturer has revised certification from 90 to 85 degrees since installed.
Are there any tray sections that are overfilled with cables?
What is the low voltage shutdown point for the inverters?
Evaluate the EOG trip circuitry for bypassing noncoincident logic trips i'n the emergency code.
Update E-46 Normal Battery Loads What are the criteria for cable tray fill/conduit loading?
- Provide the 18 month overload protection surveillances for the essential MOVs.
Provide detail desi'gn of lube oil piping including flange connections.
Provide schematic for all EOG trip circuits and relay setpoints.
Provide schematic for all EOG trip circuits and relay setpoints. Perform closeout review of A-NL-92-147.
(Continuation of Question 67).
Identify all of T-10 supply responsibilities and how it affects Question 67; 'provide calcs showing setpoint establishment for day tank and belly tank; include in Question 67 strategy (prog) to assure adequate (7 days) fuel storage.
I How, is the FSAR requirement for a mini~ day tank fuel oil availability of 2500 gal satisfied?
Provide: 1) Coord. *plots for MCCs 22, 24, 26, and 2 (feed breaker vs largest load breaker); 2) Plot showing prot. of LC transfer protection using through fault protection curve (ANSI C37-91); 3) Protection device setting she7ts and calcs (if av~ilable for typ motors on Bus 10, LC No12, and MC No2.
Is the overspeed trip of the EDGs checked periodically? Provide pertinent data sheets.
Are' there any procedural or physical constraints which would prevent operators from transferring to the offsite source when less than adequate voltage is available?
V-33, V-43, and V-47 switchgear room coolers aren't normally fed from 1E power supplies.
- 1)
What provisions are made to transfer to 1E supplies?
- 2)
Do temp sensors in rooms alarm in Control Room?
- 3)
Is max room temp 104 degrees F.
- 4) If so why is setpoint/action level 104?
Provide information on the fuel filters and lube oil strainers in regard to ability to shift clean and inspect.
(Verbal question from Joubert to Kupka - inspector has already received the information -
que,stion issued for tracking purposes.)
Data sheets provided under Question 245 indicated that breaker 72-302 and 72-401 were last tested in 1980.
Are these breakers in a regular PM program?
Is breaker 72-18 in a PM program?
If not, why aren't these breakers in a testing program.
PREVIOUS COMMITMENT DATE 12/01/92 12/01/93 6/30/92 9/30/92 9/30/92 12/01/92 12/01/93 12/01/93 9/30/92 12/01/93 7/01/93 12/31/92 12/31/92 12/15/92 6/30/92 7/01/93 12/31/91 12/01/92 8/30/92 9/30/92 Page 2
tr COMMITMENT DATE DUE DATE CLOSED 11/30/93 4/29/93 1/15/94 1/12/94 6/30/92 6/24/92 2/22/93 2/18/93 9/30/92 10/02/92 12/01/92 12/08/92 7/01/94 12/15/93 10/14/93 9/30/92 5/11/92 12/01/93 9/13/93 7/01/93 6/07/93 7/01/93 6/07/93 12/31/92 5/24/93 12/15/92 12/21/92 6/30/92 5/11/92 7/01/92 6/07/93 12/31/91 5/24/93 4/01/93 3/19/93 8/30/92 9/03/92 5/01/93 5/04/93
2/25/94 CONCERN Palisades Nuclear Plant -
nsumers Power Company Nondocketed EDSFI Concerns TABLE 2 NUMBER COMMITMENT DESCRIPTION None Complete the USI A-46 review of the Plant Emergency Power System *(EPS), as an integral part of the total SQUG program. Duplicate of Concern 36; closed 6/10/93.
None e Prepare an emergency power system equipment list and perform preliminary screening, walkdown, evaluations, and to prioritize, under the SQUG Program, any* resulting.modifications.
Weak Resolve weaknesses identified in second level undervoltage scheme due to inadvertant Diesel starts during routine plant ?perations and testing.
PREVIOUS COMMITMENT DATE 5/18/95 12/01/92 12/01/93 Page 3,
COMMITMENT DATE DUE DATE CLOSED 5/18/95 6/10/93 12/01/92 11/04/92 7/01/94