MONTHYEARML17313B0991999-10-14014 October 1999 Forwards LER 99-005-00 Reporting Findings & Corrective Actions Taken as Result of Out of Tolerance MSSV Condition in Unit 1 Which Was Discovered During pre-outage Testing ML17313B0881999-10-12012 October 1999 Forwards Response to NRC 990831 RAI Re Several Relief Requests That Accompanied Second ten-yr Interval ISI Program Submitted on 980317.Revised Relief Request 6 Is Provided in Encl 2 ML17300B3501999-09-29029 September 1999 Forwards Revised Bases Pages,Providing Addl Discussion of Options Available to Exit Required Action G of TS 3.8.1 & Revised Page for TS 3.3.7,in Response to NRC RAI Re Proposed Amend to TS 3.8.1 & 3.3.7 ML17300B3551999-09-28028 September 1999 Responds to Aministrative Ltr 99-03, Preparation & Scheduling of Operator Licensing Exams. Proposed Palo Verde Operator Licensing Exam Schedule & Estimated Number of Applicants Planning to Take Exams Encl ML17313B0851999-09-24024 September 1999 Requests Approval of Alternative to Repair Requirements of 10CFR50.55a,authorizing Alternative Use of Mechanical Nozzle Seal Assemblies,As Described in Encl,For RCS Hot Leg Instrumentation & Sampling Nozzles for Two Operating Cycles ML17313B0781999-09-20020 September 1999 Forwards Rev 22 to PVNGS Emergency Plan. Summary Description of Changes,Included ML17300B3331999-09-14014 September 1999 Forwards MOR for August 1999 & Revised MOR for Jul 1999 for Pvngs,Units 1,2 & 3 ML17300B3351999-09-0808 September 1999 Informs That Repairs to Plant EDG 2A Jacket Water Cooling sub-sys Were Completed & EDG Was Declared Operable on 990903 at Approx 21:45 Mst.Noed Was Not Necessary,Since 72 Hour Completion Time Was Met ML17313B0761999-09-0303 September 1999 Requests Enforcement Discretion to TS Section 3.8.1, AC Sources - Operating. Enforcement Discretion Would Allow,On One Time Basis,Extension of Completion Time in Required Action B.4 of TS 3.8.2 from 72 H to 108 H ML17313B0731999-08-31031 August 1999 Informs That RR Bean (License OP-50452-1) Has Been Permanently Reassigned to Position That Does Not Require License & Requests That Individuals License Be Expired Per 10CFR55.55 ML20211A9501999-08-12012 August 1999 Discusses 990720-21 Workshop Conducted in Region IV Ofc,Re Exchange of Info in Area of Use of Risk Insights in Regulatory Activities.List of Attendees,Summary of Topic & Issues,Agenda & Copies of Handouts Encl ML17313B0581999-08-0606 August 1999 Forwards Rev 1 of Changes to TS Bases Implemented Between Aug 1998 & Jul 1999.Insertion Instructions & List of Affected Pages Included ML17313B0311999-08-0303 August 1999 Submits Response to NRC AL 99-02, Operating Reactor Licensing Actions Estimates, for Fys 2000 & 2001 ML20210L1461999-08-0303 August 1999 Informs That NRC Plans to Administer Gfes of Written Operator Licensing Exam on 991006.Requests Submittal of Ltr Identifying Individuals Taking Exam,Personnel Allowed Access to Exams & Mailing Address for Exams ML17313B0431999-07-30030 July 1999 Advises of Listed Senior Mgt Changes That Have Taken Place at Plant ML17313B0441999-07-30030 July 1999 Forwards Comments on Draft NRC Repts Evaluation of AOVs at Us Light-Water Reactors (1999) & Idaho Natl Engineering & Environ Lab Rept (INEEL)EXT-98-00383,Study of AOVs in Npps. ML17313B0151999-07-20020 July 1999 Submits Request to Obtain All Data Previously Sent by PVNGS & Currently in REIRS for OLs NPF-41,NPF-51 & NPF-74.Data Is Requested in Electronic Form (Ascii Format) as It Currently Exists in REIRS Sys ML17313B0091999-07-20020 July 1999 Forwards Requested Calculations Performed to Verify That Increase in Max Radially Averaged Enrichment for Fuel Assemblies from 4.3 Weight Percent to 4.8 Weight Percent Did Not Affect Requirements for TSs 3.7.15,3.7.17 & 4.3.1 ML17313B0171999-07-16016 July 1999 Forwards LER 99-005-00,re Automatic Rt Which Occurred on 990618,following Sensor Failure in Core Protection Calculators.Corrective Actions Described in LER Are Not Necessary to Maintain Compliance with Regulations ML17300B3111999-07-15015 July 1999 Forwards PVNGS Unit 2 ISI Rept for Eighth Refueling Outage. No Commitments Made to NRC by Ltr ML17300B3141999-07-15015 July 1999 Forwards Corrected Electronic Files for Individual Monitoring Repts for 1998.Original Electronic Files Were Found to Have Two Administrative Errors,Which Has Been Corrected.Encl Withheld,Per 10CFR2.790 ML20209G6771999-07-0808 July 1999 Forwards Supplemental Info to Confirm That Decommissioning Funding Plans of Public Service Co of Nm for Interests in PVNGS Have Been Reviewed by Nm Public Regulation Commission. Final Order & Recommended Decisions in Case 2742,also Encl ML17300B2931999-07-0202 July 1999 Submits Withdrawal of Relief 5 for Second ISI Interval for Units 1,2 & 3.Proposed Alternative Is Related to Exam Requirements for Component Supports for Second ISI Interval ML17313A9951999-06-26026 June 1999 Provides Response to NRC GL 98-01,Suppl 1, Y2K Readiness of Computer Sys at Nuclear Power Plants. ML17300B2831999-06-26026 June 1999 Requests NRC Approval of Proposed Alternative IAW Provisions of 10CFR50.55a(a)(3)(i) to 10CFR50.55a(g) & Requirements of ASME Boiler & Pressure Vessel Code Section XI for Repairs & Installation.Description of Proposed Alternative,Encl ML17313A9901999-06-15015 June 1999 Forwards Response to RAI Re GL 96-05, Periodic Verification of Design-Basis Capability of Safety-Related Movs. No Commitments Being Made to NRC by Ltr ML17313A9521999-05-24024 May 1999 Notifies NRC That Ja Proctor,License SOP-50314,has Been Permanently Reassigned to Position That Does Not Require License.License Should Be Expired,Per 10CFR55.55 ML20206Q3111999-05-18018 May 1999 Final Response to FOIA Request for Documents.Forwards App a Records Being Released in Entirety ML17313A9311999-05-13013 May 1999 Notifies NRC That Rev 2 to COLR for Unit 2 Remains Applicable Following Recently Completed Unit 2 Reload ML17313A9481999-05-12012 May 1999 Informs of Change Needed in Order to Update Current Mailing List.Future Mailings for J Horne Should Be Forwarded to Listed Address ML17313A9261999-05-0707 May 1999 Forwards LER 99-004-00,per 10CFR50.73.LER Repts Findings & Corrective Actions Taken as Result of Unit 2 Out of Tolerance Pressurizer Safety Valve (Psv) Condition Which Was Discovered During Outage Testing ML20206H1931999-05-0303 May 1999 Forwards 1998 Annual Rept, for SONGS Units 2 & 3 & PVNGS Units 1,2 & 3.SCEs Form 10K Annual Rept to Securites & Exchange Commission for Fiscal Yr Ending 981231,encl ML17313A9091999-04-30030 April 1999 Forwards Proprietary Proposed Test Outlines for Initial License Exams to Be Administered at PVNGS in Aug/Sept 1999. No Commitments Are Contained in Ltr.Proprietary Info Withheld ML17313A9181999-04-30030 April 1999 Forwards Electronic File of Individual Monitoring Repts for 1998.Encl Withheld Per 10CFR2.790 ML17313A9191999-04-30030 April 1999 Forwards Special Rept 2-SR-99-001 Re SG Tube Plugging in PVNGS Unit 2,per TS Reporting Requirement 5.6.8.Complete Results of SG Tube Inservice Insp Will Be Submitted by 000422 ML17300B3751999-04-23023 April 1999 Forwards LER 99-003-00,reporting Condition Prohibited by TS 3.7.17 Where Spent Fuel Assembly Was Stored in Inappropriate Region in Spent Fuel Pool ML17313A9081999-04-23023 April 1999 Documents 990421 Telcon with E Emeigh,Which Requested Extension for Submitting Next Matl Balance Rept for Pvngs,As Required by 10CFR70.53 & 74.13.Required Info Will Be Submitted by 990531 ML20205T7421999-04-21021 April 1999 Forwards Partially Withheld Insp Repts 50-528/99-05, 50-529/99-05 & 50-530/99-05 on 990322-26.Determined That Security Program Properly Implemented.Insp Repts Details Withheld (Ref 10CFR73.21) ML17313B0271999-04-21021 April 1999 Forwards Proprietary Epec Pro Forma Cashflow Statement for 1999.Proprietary Info Withheld,Per 10CFR2.790.Affidavit Encl ML17313A9031999-04-21021 April 1999 Forwards Rev to Relief Request 12 Submitted 990420 to Second 10-yr ISI Interval.Revised Relief Request Discusses in More Detail Actions APS Will Take When There Is Identified Leakage from Bolted Connection ML17313A8971999-04-20020 April 1999 Requests Use of Alternatives to 10CFR50.55a(g) Inservice Insp Requirements.Proposed Alternatives Are Related to Visual Exam of Bolted Connections 05000529/LER-1999-002, Forwards LER 99-002-00 Re Findings & Corrective Actions Taken as Result of Plant Out of Tolerance MSSV Condition Which Was Discovered During pre-outage Testing1999-04-19019 April 1999 Forwards LER 99-002-00 Re Findings & Corrective Actions Taken as Result of Plant Out of Tolerance MSSV Condition Which Was Discovered During pre-outage Testing ML17313A8931999-04-14014 April 1999 Forwards LER 99-003,reporting Condition Prohibited by TSs That Existed When Surveillance Requirement to Verify Essential Chilled Water Sys Valve Positions Was Not Met ML20205Q0821999-04-13013 April 1999 Forwards Second ISI Interval Relief Request 10 from ASME Section XI & Applicable Addenda Re Visual Exams Performed Subsequent to Repair or Replacement of Component or Alteration of Item ML17313A8901999-04-13013 April 1999 Forwards LER 98-003-01 Re MSSV as-found Lift Pressures out- Side of TS Limits.Ler Suppl Provides Evaluation Findings from Unit 3 out-of-tolerance MSSVs Conditions Which Were Discovered During pre-outage Testing ML17313A8831999-04-0808 April 1999 Forwards 1998 Annual Radioactive Effluent Release Rept for Pvngs,Units 1,2 & 3 & Rev 13 to ODCM, for Pvngs,Units 1,2 & 3 IAW TS 5.6.3 ML20205F3491999-03-30030 March 1999 Forwards Proprietary & non-proprietary Info Re Status of Decommissioning Funding for Pvngs,Units 1,2 & 3,per 10CFR50.75(f)(1).Proprietary Info Withheld,Per Requirements of 10CFR2.790(b)(1) ML17313A8671999-03-24024 March 1999 Submits Info Re Present Levels & Sources of Property Insurance Maintained for Pvngs,Per 10CFR50.54(w)(3) ML17313A8601999-03-16016 March 1999 Forwards Revised Relief Requests PRR-05,PRR-06 & PRR-11 to Clarify That Proposed Design Flow Testing for Lpsi,Hpsi & Containment Spray Pumps Will Be Performed Using Instruments That Comply with Code Requirements,Per 990226 Telcon ML17313A8551999-03-0505 March 1999 Requests Proposed Code Alternative IAW 10CFR50.55a(e)(3),as Acceptable Alternative to Requirements of 10CFR50.55a(e)(1), for Installation of in-line safety-related Flow Measurement Instrument in ASME Class 3 Pipe 1999-09-08
[Table view] Category:INCOMING CORRESPONDENCE
MONTHYEARML17313B0991999-10-14014 October 1999 Forwards LER 99-005-00 Reporting Findings & Corrective Actions Taken as Result of Out of Tolerance MSSV Condition in Unit 1 Which Was Discovered During pre-outage Testing ML17313B0881999-10-12012 October 1999 Forwards Response to NRC 990831 RAI Re Several Relief Requests That Accompanied Second ten-yr Interval ISI Program Submitted on 980317.Revised Relief Request 6 Is Provided in Encl 2 ML17300B3501999-09-29029 September 1999 Forwards Revised Bases Pages,Providing Addl Discussion of Options Available to Exit Required Action G of TS 3.8.1 & Revised Page for TS 3.3.7,in Response to NRC RAI Re Proposed Amend to TS 3.8.1 & 3.3.7 ML17300B3551999-09-28028 September 1999 Responds to Aministrative Ltr 99-03, Preparation & Scheduling of Operator Licensing Exams. Proposed Palo Verde Operator Licensing Exam Schedule & Estimated Number of Applicants Planning to Take Exams Encl ML17313B0851999-09-24024 September 1999 Requests Approval of Alternative to Repair Requirements of 10CFR50.55a,authorizing Alternative Use of Mechanical Nozzle Seal Assemblies,As Described in Encl,For RCS Hot Leg Instrumentation & Sampling Nozzles for Two Operating Cycles ML17313B0781999-09-20020 September 1999 Forwards Rev 22 to PVNGS Emergency Plan. Summary Description of Changes,Included ML17300B3331999-09-14014 September 1999 Forwards MOR for August 1999 & Revised MOR for Jul 1999 for Pvngs,Units 1,2 & 3 ML17300B3351999-09-0808 September 1999 Informs That Repairs to Plant EDG 2A Jacket Water Cooling sub-sys Were Completed & EDG Was Declared Operable on 990903 at Approx 21:45 Mst.Noed Was Not Necessary,Since 72 Hour Completion Time Was Met ML17313B0761999-09-0303 September 1999 Requests Enforcement Discretion to TS Section 3.8.1, AC Sources - Operating. Enforcement Discretion Would Allow,On One Time Basis,Extension of Completion Time in Required Action B.4 of TS 3.8.2 from 72 H to 108 H ML17313B0731999-08-31031 August 1999 Informs That RR Bean (License OP-50452-1) Has Been Permanently Reassigned to Position That Does Not Require License & Requests That Individuals License Be Expired Per 10CFR55.55 ML17313B0581999-08-0606 August 1999 Forwards Rev 1 of Changes to TS Bases Implemented Between Aug 1998 & Jul 1999.Insertion Instructions & List of Affected Pages Included ML17313B0311999-08-0303 August 1999 Submits Response to NRC AL 99-02, Operating Reactor Licensing Actions Estimates, for Fys 2000 & 2001 ML17313B0441999-07-30030 July 1999 Forwards Comments on Draft NRC Repts Evaluation of AOVs at Us Light-Water Reactors (1999) & Idaho Natl Engineering & Environ Lab Rept (INEEL)EXT-98-00383,Study of AOVs in Npps. ML17313B0431999-07-30030 July 1999 Advises of Listed Senior Mgt Changes That Have Taken Place at Plant ML17313B0151999-07-20020 July 1999 Submits Request to Obtain All Data Previously Sent by PVNGS & Currently in REIRS for OLs NPF-41,NPF-51 & NPF-74.Data Is Requested in Electronic Form (Ascii Format) as It Currently Exists in REIRS Sys ML17313B0091999-07-20020 July 1999 Forwards Requested Calculations Performed to Verify That Increase in Max Radially Averaged Enrichment for Fuel Assemblies from 4.3 Weight Percent to 4.8 Weight Percent Did Not Affect Requirements for TSs 3.7.15,3.7.17 & 4.3.1 ML17313B0171999-07-16016 July 1999 Forwards LER 99-005-00,re Automatic Rt Which Occurred on 990618,following Sensor Failure in Core Protection Calculators.Corrective Actions Described in LER Are Not Necessary to Maintain Compliance with Regulations ML17300B3111999-07-15015 July 1999 Forwards PVNGS Unit 2 ISI Rept for Eighth Refueling Outage. No Commitments Made to NRC by Ltr ML17300B3141999-07-15015 July 1999 Forwards Corrected Electronic Files for Individual Monitoring Repts for 1998.Original Electronic Files Were Found to Have Two Administrative Errors,Which Has Been Corrected.Encl Withheld,Per 10CFR2.790 ML20209G6771999-07-0808 July 1999 Forwards Supplemental Info to Confirm That Decommissioning Funding Plans of Public Service Co of Nm for Interests in PVNGS Have Been Reviewed by Nm Public Regulation Commission. Final Order & Recommended Decisions in Case 2742,also Encl ML17300B2931999-07-0202 July 1999 Submits Withdrawal of Relief 5 for Second ISI Interval for Units 1,2 & 3.Proposed Alternative Is Related to Exam Requirements for Component Supports for Second ISI Interval ML17313A9951999-06-26026 June 1999 Provides Response to NRC GL 98-01,Suppl 1, Y2K Readiness of Computer Sys at Nuclear Power Plants. ML17300B2831999-06-26026 June 1999 Requests NRC Approval of Proposed Alternative IAW Provisions of 10CFR50.55a(a)(3)(i) to 10CFR50.55a(g) & Requirements of ASME Boiler & Pressure Vessel Code Section XI for Repairs & Installation.Description of Proposed Alternative,Encl ML17313A9901999-06-15015 June 1999 Forwards Response to RAI Re GL 96-05, Periodic Verification of Design-Basis Capability of Safety-Related Movs. No Commitments Being Made to NRC by Ltr ML17313A9521999-05-24024 May 1999 Notifies NRC That Ja Proctor,License SOP-50314,has Been Permanently Reassigned to Position That Does Not Require License.License Should Be Expired,Per 10CFR55.55 ML17313A9311999-05-13013 May 1999 Notifies NRC That Rev 2 to COLR for Unit 2 Remains Applicable Following Recently Completed Unit 2 Reload ML17313A9481999-05-12012 May 1999 Informs of Change Needed in Order to Update Current Mailing List.Future Mailings for J Horne Should Be Forwarded to Listed Address ML17313A9261999-05-0707 May 1999 Forwards LER 99-004-00,per 10CFR50.73.LER Repts Findings & Corrective Actions Taken as Result of Unit 2 Out of Tolerance Pressurizer Safety Valve (Psv) Condition Which Was Discovered During Outage Testing ML20206H1931999-05-0303 May 1999 Forwards 1998 Annual Rept, for SONGS Units 2 & 3 & PVNGS Units 1,2 & 3.SCEs Form 10K Annual Rept to Securites & Exchange Commission for Fiscal Yr Ending 981231,encl ML17313A9191999-04-30030 April 1999 Forwards Special Rept 2-SR-99-001 Re SG Tube Plugging in PVNGS Unit 2,per TS Reporting Requirement 5.6.8.Complete Results of SG Tube Inservice Insp Will Be Submitted by 000422 ML17313A9181999-04-30030 April 1999 Forwards Electronic File of Individual Monitoring Repts for 1998.Encl Withheld Per 10CFR2.790 ML17313A9091999-04-30030 April 1999 Forwards Proprietary Proposed Test Outlines for Initial License Exams to Be Administered at PVNGS in Aug/Sept 1999. No Commitments Are Contained in Ltr.Proprietary Info Withheld ML17313A9081999-04-23023 April 1999 Documents 990421 Telcon with E Emeigh,Which Requested Extension for Submitting Next Matl Balance Rept for Pvngs,As Required by 10CFR70.53 & 74.13.Required Info Will Be Submitted by 990531 ML17300B3751999-04-23023 April 1999 Forwards LER 99-003-00,reporting Condition Prohibited by TS 3.7.17 Where Spent Fuel Assembly Was Stored in Inappropriate Region in Spent Fuel Pool ML17313B0271999-04-21021 April 1999 Forwards Proprietary Epec Pro Forma Cashflow Statement for 1999.Proprietary Info Withheld,Per 10CFR2.790.Affidavit Encl ML17313A9031999-04-21021 April 1999 Forwards Rev to Relief Request 12 Submitted 990420 to Second 10-yr ISI Interval.Revised Relief Request Discusses in More Detail Actions APS Will Take When There Is Identified Leakage from Bolted Connection ML17313A8971999-04-20020 April 1999 Requests Use of Alternatives to 10CFR50.55a(g) Inservice Insp Requirements.Proposed Alternatives Are Related to Visual Exam of Bolted Connections 05000529/LER-1999-002, Forwards LER 99-002-00 Re Findings & Corrective Actions Taken as Result of Plant Out of Tolerance MSSV Condition Which Was Discovered During pre-outage Testing1999-04-19019 April 1999 Forwards LER 99-002-00 Re Findings & Corrective Actions Taken as Result of Plant Out of Tolerance MSSV Condition Which Was Discovered During pre-outage Testing ML17313A8931999-04-14014 April 1999 Forwards LER 99-003,reporting Condition Prohibited by TSs That Existed When Surveillance Requirement to Verify Essential Chilled Water Sys Valve Positions Was Not Met ML20205Q0821999-04-13013 April 1999 Forwards Second ISI Interval Relief Request 10 from ASME Section XI & Applicable Addenda Re Visual Exams Performed Subsequent to Repair or Replacement of Component or Alteration of Item ML17313A8901999-04-13013 April 1999 Forwards LER 98-003-01 Re MSSV as-found Lift Pressures out- Side of TS Limits.Ler Suppl Provides Evaluation Findings from Unit 3 out-of-tolerance MSSVs Conditions Which Were Discovered During pre-outage Testing ML17313A8831999-04-0808 April 1999 Forwards 1998 Annual Radioactive Effluent Release Rept for Pvngs,Units 1,2 & 3 & Rev 13 to ODCM, for Pvngs,Units 1,2 & 3 IAW TS 5.6.3 ML20205F3491999-03-30030 March 1999 Forwards Proprietary & non-proprietary Info Re Status of Decommissioning Funding for Pvngs,Units 1,2 & 3,per 10CFR50.75(f)(1).Proprietary Info Withheld,Per Requirements of 10CFR2.790(b)(1) ML17313A8671999-03-24024 March 1999 Submits Info Re Present Levels & Sources of Property Insurance Maintained for Pvngs,Per 10CFR50.54(w)(3) ML17313A8601999-03-16016 March 1999 Forwards Revised Relief Requests PRR-05,PRR-06 & PRR-11 to Clarify That Proposed Design Flow Testing for Lpsi,Hpsi & Containment Spray Pumps Will Be Performed Using Instruments That Comply with Code Requirements,Per 990226 Telcon ML17313A8551999-03-0505 March 1999 Requests Proposed Code Alternative IAW 10CFR50.55a(e)(3),as Acceptable Alternative to Requirements of 10CFR50.55a(e)(1), for Installation of in-line safety-related Flow Measurement Instrument in ASME Class 3 Pipe ML17313A8241999-02-23023 February 1999 Advises That Kp Jarvis,License OP-50287-1,no Longer Needs to Maintain License as Permanently Assigned to Position Requiring No License ML17313A8111999-02-18018 February 1999 Forwards PVNGS Unit 3 7th Refueling Outage, Which Provides Complete Results of SG Tube Inservice Insp Performed,Per TS 5.6.8 ML17313A8721999-02-16016 February 1999 Discusses Resolution of Generic Safety Issue 171, ESF Failures from Loss-of-Offsite Power Subsequent to Loca. Util Has Low Vulnerability to Loca/Grid Collapse/Loop Scenario ML17313A7611999-01-22022 January 1999 Forwards PVNGS Unit 3 Inservice Insp Rept Seventh Refueling Outage, Per 10CFR50.55a.Ltr Contains No New Commitments 1999-09-08
[Table view] |
Text
REGULATORY INFORMATION DISTRIBUTION SYSTEM (RIDS)
ACCESSION NBR:9107120005 DOC.DATE: 91/07/01 NOTARIZED: NO 'OCKET FACIL:STN-50-528 Palo Verde Nuclear Station, Unit 1, Arizona Publi 05000528 STN-50-529 Palo Verde Nuclear Station, Unit 2, Arizona Publi 05000529 STN-50-530 Palo Verde Nuclear Station, Unit. 3, Arizona Publi 05000530 AUTH. NAME AUTHOR'FFXLIATION CONWAY,W.F. Arizona Public Service Co. (formerly Arizona Nuclear Power RECIP.NAME RECIPIENT AFFILIATION Document Control Branch (Document Control Desk)
SUBJECT:
Suppls 880921 response to Action Item 3 of NRC Bulletin D 88-004,consisting of methodology for determining mechanical seal life. Analysis of condensate transfer pump test data does not indicate trend-toward pump degradation. S DISTRIBUTION CODE: IE37D TITLE: Bulletin 88-004 re COPIES RECEIVED:LTR Potential Safety-Related J ENCL Q Loss Pump SIZE:
A NOTES:STANDARDIZED PLANT 05000528 Standardized plant. 05000529 D Standardized plant. 05000530 D
RECIPIENT "COPIES RECIPIENT COPIES ID CODE/NAME LTTR ENCL XD CODE/NAME LTTR ENCL PD5 LA 1 0 PD5 PD 1 1 TRAMMELL,C 1 1 THOMPSON,M 1 1 INTERNAL: AEOD/DOA 1 1 AEOD/DS P/TPAB 1 1 ALEXXON,T 13E21 1 1 MCCOY, M 8E23 1 1 NRR/DET/EMEB 7E 1 1 NRR/DOEA/OEABll 1 1 NRR/DOEA/OGCB11 1 1 NRR/DREP/PEPB9D 1 1 NRR/DS 8E2 " 1 1 NRR/PMAS/ILRB12 1 1 Rgg~F1Ti 2 1 1 RES/DSIR/EIB 1 1 1 1 EXTERNAL NRC PDR 1 1 NSIC 1 1 NOTES: 1 1 D
D D
NOTE TO ALL "RIDS" RECIPIENTS:
PLEASE HELP US TO REDUCE iVASTE! CONTACT THE DOCUMENT CONTROL DESK, ROOihl Pl-37 (EXT. 20079) TO ELIiVl!NATEYOUR NAME FROM DISTRIBUTION LISTS FOR DOCUMENTS YOU DON'T NEED!
TOTAL NUMBER OF COPIES REQUIRED: LTTR 20 ENCL 19
~ I Arizona Public Service Company P.O. BOX 53999 ~ PHOENIX, ARIZONA85072-3999 WILLIAMF. CONWAY 161-04032-WFC/MEP/JMQ EXECUTIVEVICE PRESIDENT NUCLEAR July 1, 1991 Docket Nos. STN 50-528/529/530 U. S. Nuclear Regulatory Commission Attn: Document Control Desk Hail Station Pl-37 Washington, D. C. 20555
References:
A) Letter from E. E. Van Brunt, Jr., APS, to NRC, 161-01159, dated July 8, 1988.
Subject:
Response to NRC Bulletin No.
88-04.
B) Letter from D. B. Karner, APS, to NRC, 161-01270, dated August 29, 1988.
Subject:
Additional Response to NRC Bulletin No.
88-04.
C) Letter from W. F. Conway, APS, to NRC, 161-02345, dated September 21, 1989.
Subject:
Supplemental Response to NRC Bulletin No. 88-04.
D) NRC Bulletin 88-04 from C. E. Rossi, NRC to All holders of operating licenses or construction permits for nuclear power reactors, dated Hay 05, 1988.
Subject:
Potential Safety-Related Pump Loss.
Dear Sirs:
Subj ect: Follow up to the Letter from W. F. Conway, APS, to NRC, 161-02345, dated September 21, 1988 - Reference C and Response to Action P3 of NRC Bulletin 88-04.
File: 91-056-026 References A, B, and C submitted partial responses to the subject bulletin.
Attachment 1 explains the change in methodology for determining mechanical seal life and is a follow up response to Reference C. Attachment, 2 includes a detailed response to Action P3 of NRC Bulletin 88-04. Action 43, of the Bulletin requested an evaluation of the adequacy of the minimum flow bypass lines for safety-related centrifugal pumps with respect to damage resulting from operation and testing in the'inimum flow mode.
This completes our response to the subject Bulletin.
9."L07l20LIO~ 5'l0701 F'DR AGGCf; 0 I.IOI.I 28 I.J PDR
161-04032-'k'PC/NEP/JllQ uly 1 , 1991 U. S . Nuclear Regulatory Commission Attn: Document Control Desk NRC Bulletin 8 8 - 04 Page Two If you should have any ques tions , please contact Michael E. Powell of my staff at ( 602 ) 340 - 49 8 1 .
S incerely ,
WFC/MEP/JMQ Attachment CC: J. B. Martin D. H. Coe D. Corporandy A. C. Gehr A. H. Gutterman
161-04032-WFC/HEP/JMQ uly 1, 1991 ATTACHMENT 1 Follow up to the Letter from W. F. Conway, APS, to NRC, 161-02345, dated September 21, 1988 Reference C Ingersoll-Rand verified the specified mini-flow rates for the PVNGS Safety Injection pumps,'n their evaluation of the potential damages resulting from extended run time on minimum-flow. The vendor's evaluation of the Safety Injection pumps, indicated that the specified miniflow rates are below the minimum continuous stable flow point; however, the vendor never intended and recommends against running the pumps on miniflow for exten'ded periods of time.
At PVNGS, administrative controls and operating procedures are such that the Safety Injection pumps are not operated for extended periods of time at miniflow in accordance with the vendor technical manual recommendations. The vendor further stated that the potentially adverse effects of running a pump on minimum flow for extended periods of time would primarily affect the mechanical seals.
Their resulting equation for calculating seal life was conservatively based on empirical data of vibration at low flow with the effects of starts and stops factored in by assuming a maximum of 500 starts and stops for useful life. The implication of their evaluation is that ensuring adequate mechanical seal life will minimize the effects of extended run time on miniflow.
As stated in Reference C, Ingersoll-Rand provided an equation by which the effect of pump operation on miniflow can be accounted for in determining when seals should be replaced. This equation was intended for the Safety Injection pumps and not the Condensate Transfer pumps, because the Condensate Transfer pumps do not have mechanical seals. Also, PVNGS intended to use the Emergency Response Facility Data Acquisition and Display System (ERFDADS) to log run time hours for input into the Ingersoll-Rand equation to compute seal life.'pon careful evaluation, the Ingersoll-Rand equation appeared to be overly conservative and not specifically applicable to PVNGS. APS also consulted'he mechanical seal vendor, Durametallic to develop an applicable seal life equation. Both the Durametallic and Ingersoll-Rand equations were used to develop a PVNGS specific mechanical seal preventative maintenance task frequency. The periodic seal replacement schedule is based on a) the vendor's equation (Ingersoll-Rand and Durametallic) as guidance, b) the review of operating experience c). the surveillance test data, d) maintenance histories, and e) design basis considerations.
Therefore, APS did not utilize a component evaluation system that would take the necessary data from the plant computer and ERFDADS data acquisition system to compute seal life.
161-04032-I}PC/I IEP/JN(}
uly 1, 1991 ATTACHMENT 1 CONT. ,
Preventative maintenance tasks are being developed which replace Low Pressure Safety Injection mechanical seals every other scheduled refueling outage, and replace High Pressure Safety Injection and Containment Spray mechanical seals every third scheduled refueling outage. This schedule will ensure that adequate seal liEe is available for both normal and post accident operating conditions.
The preventative maintenance frequencies are considered conservative with regard to seal life therefore, surveillance of actual run hours is not necessary, and the ERFDADS system would not be required.
Reference C also stated that until a trending system 'could be developed, a periodic routine taintenance task-would be instituted at the required frequency (based on -Ingersoll-Rand data) to ensure seal lifetimes are not exceeded.
Based on the new methodology for determining seal liEe, a trending system was determined not to be necessary. The preventative maintenance tasks program will replace seals in a proactive manner.
In addition, APS stated in Reference C, that the Engineering Evaluation Department would review each oE the affected pumps'aintenance history to determine when the seals were last replaced, and would issue work requests, as appropriate, to replace seals prior to exceeding their useEul liEetime.
Surveillance test vibration data would also be reviewed for each pump to ensure that no increase in vibration has occurred.
The initial review Eor the purpose of meeting the above commitment was completed on September 18, 1989. Subsequent reviews of maintenance histories, surveillance tests, and control room logs have been performed to ensure adequate mechanical seal life has been maintained. Work reouests have been written for those mechanical seals requiring replacement. Work requests will be written to replace the remaining seals as required,'ntil the Preventative Maintenance Program is in place.
I I
1 i
161-04032-WEC/MEP/JMQ uly. 1 , 199 1 ATTACHMENT 2 Response To Requested Action ¹3 Of NRC Bulletin 88-04 Action ¹3 of NRC 'Bulletin 88-'04 requested an evaluation of the adequacy of the minimum flow bypass lines for safety-related centrifugal pumps (i. the Safety Injection pumps and ii. the Condensate Transfer pumps) with respect to damage resulting from operation and testing in the minimum flow mode. The following items were included in the evaluation:
Consideration of the effects of cumulative operating hours in the minimum flow mode a) over the life of the plant b) during postulated accident scenario involving the largest time spent in that mode.
- i. a) At PVNGS, during a typical 18 month cycle of. full power operation, the High Pressure Safety Injection Pump, Low Pressure Safety Injection Pump, and Containment Spray are run on miniflow for surveillance testing, once per quarter.
Typically the duration is for less than one hour of continuous operation as recommended in the vendor technical manual.
- i. b) In post Loss of Coolant Accident (LOCA) procedures the Safety Injection Actuation Signal (SIAS) actuated equipment is reset when the reset criteria is met, shutting off the non-injecting Safety Injection pumps, thus limiting operating time under minimum flow conditions.
ii.a) At PVNGS during a typical 18 month cycle of full power operation, the Condensate Transfer pump is run on miniflow for surveillance testing on a quarterly basis. Typically the duration is one to two hours, and the 100 gpm flowrate during testing is, sufficient to preclude any damage from low flow operations. The Condensate Transfer pumps are also required to provide make-up water to class cooling water systems and the spent fuel pool, when normal make-up water sources are not available. However, these instances are so rare as to make this mode of operation negligible. Note that during make-up operation, the passive miniflow recirculation line is in service.
ii.b) The Condensate Transfer pumps are normally in the standby mode with both pumps starting, automatically with the receipt of a SIAS,. Loss of Offsite Power (LOP), Control Room Essential Filtration Actuation Signal (CREFAS), and a Control Room Ventilation Isolation Actuation Signal (CRVIAS).
I 161-04032-WPC/HEP/JW(}
ul y 1 , 1 99 1 ATTACHMENT 2 CONT ~
The Condensate Transfer pumps provide makeup water to the Diesel Generator (DG) cooling water surge tank, Essential Chilled (EC) water expansion tank and the Essential Cooling Water (EVi') surge tank during postulated accident scenarios.
The makeup water is provided to the DG, EC, and EW systems when the normal makeup to these systems is not available. The Condensate Transfer pumps can operate simultaneously with the Auxiliary Feedwater pumps during accident scenarios. The junction of the common minimum flow recirculation header for the Auxiliary Feedwater and Condensate Transfer pumps is close to the condensate storage tank. Consequently, the backpressure imposed by the Auxiliary Feedwater pump on the Condensate Transfer pump is negligible (less than 1 psi.).
The evaluation should be based on best current estimates of potential pump damage of pumps involved - from test data and field experience.
A review of Safety Injection pump surveillance test data did not indicate any trends toward degrading Safety Injection pump performance. The surveillance test data showed that vibrations on miniflow are well below the acceptable maximum vibration limit set by the vendor. The PVNGS Surveillance tests performed on the Safety Injection pumps monitor the performance of the pumps such that any trends toward a degraded performance are immediately identified.
The mechanical seal vendor's evaluation showed that operating the pumps at high temperatures and high pressures accelerates seal face wear. A review of control room logs determined that during full power operation, the Safety Injection pumps are operated at low temperatures and low pressures under normal operating conditions. The Low Pressure Safety Injection pumps are the only Safety Injection pumps that experience high temperatures and pressures under normal operating conditions, when shutdown cooling is placed in service in mode 4 and prior to mode 3 entry during heatup. However, the amount of time they are exposed to those conditions is administratively limited.
Analysis of Condensate Transfer pump surveillance test data does not indicate any trend toward degrading pump performance.
The Surveillance test data shows vibration levels are well below acceptable vibration limits. The surveillance tests performed on the Condensate Transfer pumps monitor the performance of the pumps so that any trends toward degraded performance at design operating conditions are immediately identified.
t 161-04032-VFC/MEP/ JMg uly 1, 1991 ATTACHMENT 2 CONT.
The Condensate Transfer "A" pump in Unit 1 has been disassembled. There are no signs of impeller low flow damage and the wear ring clearances are within tolerances. The Condensate Transfer "B" pump will be disassembled prior to the next scheduled Unit 1 refueling outage. The frequency of this inspection will be established after the "B" train disassembly.
It should also include verification from the pump suppliers that current miniflow rates are sufficient to ensure no pump damage from low flow operation for short periods of time.
- i. Ingersoll-Rand verified the Safety Injection mini flow rates are sufficient to ensure no pump damage from low flow operation for short periods of time.
Ingersoll-Rand provided an equation to determine mechanical seal life for the Condensate Transfer pump. Because the Condensate Transfer pump does not have mechanical seals, APS has confirmed with the vendor that the Ingersoll-Rand equation does not apply. Ingersoll-Rand has concurred that the specified minimum flow of 30 gpm is not an absolute value and that operation for sh'ort periods of time at lower flow rates would not lead to immediate pump damage.
APS has considered the following information in'the evaluation of the minimum flowrates for the Condensate Transfer pumps:
vendor supplied information calculated estimates for minimum flows low energy size of the pumps seal features of the pumps (packing as opposed to mechanical seals) low maintenance history low run time of the pumps surveillance testing of the pumps pump inspection All of these factors considered together have led APS to conclude that the theoretical analyses alone are not sufficient to determine if low flow damage has occurred to the pumps. Ingersoll-Rand has concurred that the only effective detection of low flow damage to the internals of the pump is from pump disassembly and inspection.
The inspection was performed on the Unit 1 Condensate Transfer "A" pump, as stated in 2.ii., with no signs of impeller 'low flow damage and the wear ring clearances are within tolerances. The frequency of this inspection will be
I I
161-0!i032-'i<PC/HEP/JNQ uly 1, 1991 ATTACHMENT 2 CONT.
established after the "B" train pump disassembly. The "B" train pump wi11 be disassembled prior to the next scheduled Unit 1 refueling outage.
l}}