LER 88-031-00:on 880902,found That Due to Single Failure Control Room HVAC Sys Could Operate in Recirculation Mode. Motor Operators for Four Remote Air Intake Isolation Valves Replaced W/Manual operators.W/881003 Ltr
ML17284A548
Person / Time
Site: Columbia Energy Northwest icon.png
Issue date: 10/03/1988
From: Powers C, Washington S
WASHINGTON PUBLIC POWER SUPPLY SYSTEM
To:
NRC OFFICE OF ADMINISTRATION & RESOURCES MANAGEMENT (ARM)
References
LER-88-031, LER-88-31, NUDOCS 8810120110
Download: ML17284A548 (11)


Text

+~~~~~~ULA QXRK DIALOG (Rz~~z~

ACCESSION NBR:8810120110 DOC.DATE: 88/10/03 NOTARIZED: NO DOCKET FACIL:50-397 WPPSS Nuclear Project, Unit 2, Washington Public Powe 05000397 AUTH. NAME AUTHOR AFFILIATION WASHINGTON,S.L. Washington Public Power Supply System RECIP.NAME RECIPIENT AFFILIATION

SUBJECT:

LER 88-031-00:on 880902,found that due to single failure control room HVAC sys could operate in recirculation mode.

W/8 ltr.

DISTRIBUTION CODE: IE22D COPIES RECEIVED:LTR I ENCL J SIZE: F TITLE: 50.73 Licensee Event Report (LER), Incident Rpt, etc.

NOTES:

RECIPIENT COPIES RECIPIENT COPIES ID CODE/NAME LTTR ENCL ID CODE/NAME LTTR ENCL PD5 LA 1 1 PD5 PD 1 1 SAMWORTHiR 1 1 INTERNAL: ACRS MICHELSON 1 1 ACRS MOELLER 2 2 ACRS WYLIE 1 1 AEOD/DOA 1 1 AEOD/DSP/NAS 1 1 AEOD/DSP/ROAB 2 2 AEOD/DSP/TPAB 1 1 ARM/DCTS/DAB 1 1 DEDRO 1 1 NRR/DEST/ADS 7E 1 0 NRR/DEST/CEB 8H 1 1 NRR/DEST/ESB'8D 1 1 NRR/DEST/ICSB 7 1 1 NRR/DEST/MEB 9H 1 1 NRR/DEST/MTB 9H 1 1 NRR/DEST/PSB 8D 1 1 NRR/DEST/RSB 8E 1 1 NRR/DEST/SGB 8D 1 1 NRR/DLPQ/HFB 10 1 1 NRR/DLPQ/QAB 10 1 1 NRR/DOEA/EAB 11 1 1 NRR/DREP/RAB 10 1 1 NRR/DREP/RPB 10 2 2 NRPgD SIB 9A 1 1 NUDOCS-ABSTRACT 1 1 REO P'- 02 1 1 RES TELFORDgJ 1 1 RES/DSIR DEPY 1 1 RES/DSIR/EIB 1 1 RGN5 FILE 01 1 1 EXTERNAL EGGG WILLIAMSg S 4 4 FORD BLDG HOYiA 1 1 H ST LOBBY WARD 1 1 LPDR 1 1 NRC PDR .1 1 NSIC HARRISgJ 1 1 NSIC MAYSgG 1 1 D

D S

-46 ;:ENCLI<< -'~45 8

-.wv"~cV'"'TOTAL NUMBER OF COPIES REQUIRED: LTTR

v NRC Form 358 U.S. NUCLEAR AEOULATOAY COMMISSION (9.83 I w APPROVED OMB NO. 315(MIOe EXPIRES: 8/31/88 LICENSEE EVENT REPORT (LER)

FACILITY NAME (II DOCKET NUMBER l2) PAGE 3 Washington Nuclear Plant - Unit 2 0 5 0 0 039 71oF07

')ng e as ure ou ause on ro oom o pera e s n an nana yze Operation Mode Due to Design EVENT DATE (5) LER NUMBER IS) REPORT DATE (7) OTHER FACILI'TIES INVOLVED (8)

MONTH DAY YEAR YEAR SEOUENTIAL "??: MONTH OAY YEAR FACILITYNAMES DOCKET NUMBER(SI NUMBER %F4 NUMBER 0 5 0 0 0 09 028 8 8 8 0 31 00 10 0 3 8 8 0 5 0 0 0 THIS AEPORT IS SUBMITTED PURSUANT T0 THE AEOUIREMENTS OF 10 CF R (): (Cheep onr or more of thr followinpi (11 OPERAT INC MODE (8) 20.C02(b) 20.405(c) 50.73(el(2) (lv) 73.7)Br)

POWER = 20.405( ~ )(I ) (I) 50M(v ) (1) 50.73( ~ I (2)(v) 73.71(c)

LEYEL 0 0 0 20.e05(e) II)(ll) 50.38(cl l2) 50.73(e) (2)(viil OTHER ISpeeify in Aplrrret hrlow rodin Trer, IIRC Fohn 20.e05(e)(1)(ilil 50.73(e) l2) (S 50 73( ~ l(2)(viill(A) 366AI 20.e05( ~ )ill(lv) 50.7 3(e l(2)(iil 50.73(e)(2l(vill)ISI 20.e05( ~ )(1)(vl 50.73(el(2)(iii) 50.73( ~ l(2)(rrl v LICENSEE CONTACT FOR THIS LER (12)

NAME TELEPHONE NUMBER AREA CODE S.L. Washin ton, Compliance Engineer 0 9 7 7 - 2 8 0 COMPLFTE ONE LINE FOR EACH COMPONENT FAILURE DESCRIBED IN THIS REPORT (13)

'8vv'c+. ry ."r MANUFAC MANUFAG EPORTABLE:

CAUSE SYSTEM COMPONENT TV RE R PR ~r'.Pg*rmeIrfy CAUSE SYSTEM COMPONENT TVRER TO NPRDS p

?

K>~3'> I'gag,,.r

.ooyrri FAXES%!

SUPPLEMENTAL REPORT EXPECTED IICI MONTH DAY YEAR EXPECTED SUBMISSION DATE (15)

YES Ilfyn, complerr fXpfCyfD SUBhrISSIOIY DAFfi NO 8 0 1 8 9 ABBTRAOT ILimlr to Ir00 rpecer, I 8, epproxlmerrly tifrren einple.r peer ryprwri Nen linn) 118)

On September 2, 1988 a Design Engineer determined that due to a single failure the Control Room Heating and Ventilation (HVAC) System could operate in the recirculation mode during emergency conditions. This unanalyzed condition was found while performing an engineering evaluation of the safety significance of the event reported in LER 88-005-00.

During a Loss of Coolant Accident (LOCA) the normal fresh air intake for the Control Room HVAC is isolated and two remote air intake lines're opened. Each remote air intake line .,

has two isolation valves and one valve is powered from division 1 and the other from division 2. A single failure (not a loss of power failure) in a power division could cause a valve in each remote air intake line to isolate. With the loss of all fresh air input the Control Room HVAC would continue to operate but in the recirculation mode. In the recirculation mode the Control Room would not r'emain pressurized with respect to surrounding areas, and operating post LOCA in this mode is not analyzed (for control room habitability).

Immediate corrective actions were: The motor operators for the four (two per line)-

remote air intake isolation valves were replaced with manual operators. Two of the four ,.

radiation purge line isolation valves motor operators were electrically disconnected.-

Both isolation valves on one remote intake line were locked open to assure that a single failure could not result in recirculation mode operation. The Control Room Emergency Filtration System was started and the Control Room HVAC System is operating in the pressurization mode.

PDR ADOCK 050003~9~7 l IF(gr NRC Form 388

NRC Form 3SSA US. NUCLEAR REGULATORY COMMISSION (8831 LICENSEE EVENT REPORT {LER) TEXT CONTINUATION APPROVED OMB NO. 3160WI04 EXPIRES: 8/31/BB FACILITY NAME Ill DOCKET NUMBER 12) LER NUMBER Idl ~ AQE (3l YEAR @N'EQUENTIAL @j REVISION NUMS E II NUM S II Washington Nuclear Plant - Unit 2 o s o o o 397 8 3 1 0 0 0 2 QF 7 TEXT //moro Nmco llroSuiorE ow //I/ooo////IC Forrrr 3/FIA'f/(ill Abstract (Cont'd)

The cause of this event was the Plant Architect/Engineer (AE) did not provide a, Control Room HVAC System design which protected the system against all possible single failures. The root cause of this event is a lack of communication between AE design groups.

Further corrective actions include: The Control Room HVAC recirculation mode of operation will be analyzed and inleakage tests conducted, the safety significance of this event. A technical specification change will be if necessary, to determine requested to allow normal Control Room HVAC operation. A letter will be sent to Burns & Roe Inc. requesting a 10CFR Part 21 evaluation.

The safety significance of this event is being evaluated and a supplemental report will be submitted when it is completed.

Plant Conditions a) Power Level - OX b) Plant Mode - 4 (Cold Shutdown)

Event Descri tion On September 2, 1988 a Design Engineer determined that, due to single failures, the Control Room Heating and Ventilation (HVAC) System could operate during emergency conditions in the recirculation mode, which is an unanalyzed condition. This unanalyzed condition was discovered while performing an engineering evaluation committed to in LER 88-005-00 to evaluate the potential effects of minor Control Room HVAC system changes on system bypass flow.

The following brief description of the Control Room HVAC System (before modification) for normal operation and emergency operation during a Loss of Coolant Accident (LOCA) is presented to aid in understanding the event hnd the changes made to the system. Figure 1 is a partial diagram of the Control Room HVAC System prior to the event. The Control Room HVAC System consists of two redundant systems for both normal and emergency operation. During normal operation, 1000cfm of fresh air ~

from the normal roof intake Radwaste Building is mixed with 20,000cfm of recirculated air (through fan 51A or 51B). Seven hundred and fifty (750) cfm is exhausted from the control room through fan 51 and the remaining 250cfm pressurizes the control room and is exfiltrated. Also during normal operation, the remote air ;

intake isolation valves (51A and B and 52A and B) are closed and the radiation monitor purge line valves (51D and E and 52D and E) are open with radiation monitor purge line .fans 53A and B operating. During a LOCA when any of the following trip levels are reached 1) High drywell pressure (RF" signal), 2) Low low reactor water - '=.

level (NAR signal) or 3) Reactor building ventilation exhaust high radiation ("ZN signal) the following actions occur:

a) The normal roof intake Radwaste Building is isolated by closing valves 51C and 52C.

NRC PORM SSSA o U.S.GPO: I 0 BB042+838/add IBMI

NRC fons 3EEA VS. NVCLEAR REGULATORY COMMISSION N43)

LICENSEE EVENT REPORT {LER) TEXT CONTINUATION APPROV EO OMS NO. 3)50M)04 EXPIRES: S/31/88 fACILITYNAME (I) OOCKET NUMSER (2) LER NVMSER (E) PAGE (3)

YEAR m: 5EQVENZIAL NUM ER rPrpl

45 SKVIEION NVM ES Washington Nuclear Plant - Unit 2 0 s 0 0 0 397 8 8 031 0 0 0 3 oF 7 TExT /// moro 5/roco/5 rfr/brorE off /I/or/on/I ///Ic Form 3(E)AS/ (\T) b) The 750cfm control room exhaust fan (51) de-energizes.

c) The remote air intake isolation valves (51A, 51B, 52A, and 52B) open and the radiation monitor purge line isolation valves (51D, 51E, 52D and 52E) close.

The remote air intake isolation valves and the radiation monitor purge line isolation valves are interlocked so when an intake line is opened the-associated purge line is isolated.

d) The control room emergency filtration system is automatically started and draws 1000cfm of fresh air through the remote air intakes. This additional air, when added to the recirculated air, pressurizes the control room.

The event described in LER 88-005 was for leakage around the emergency filters in excess of the technical specification allowable limit. During the engineering evaluation committed to in LER 88-005 to determine the effect of the excess leakage on control room habitability, a design engineer determined that postulated single failures could cause some combination of remote air intake line isolation valves to fail to open or to re-isolate and; thus, isolate both remote air intake lines. If this condition existed during LOCA conditions, the Control Room HVAC would be running in a recirculation mode only since the normal roof intake is also isolated.

In the recirculation mode the 20,000cfm would continue to be drawn from the control room and recirculated back to the control room; however, without the fresh air input the control room would not be pressurized. In a neutral pressure condition the inleakage to the control room would increase and this condition is not analyzed.

Immediate Actions The planned Plant Startup was delayed until the following actions were completed.

1) The motor operators were removed and manual operators were installed on the remote air intake isolation valves (51A and B and 52A and B). The valve operators were changed to manual so the isolation valves on one remote intake line could be opened without an FAZ signal present; thereby, assuring that a single failure could not cause operation in the recirculation mode. With this remote air intake line open, the control room emergency filtration system was started. This put the Control Room HVAC system in the pressurization mode of operation which satisfied the action statement of Technical Specification 3.3.7. 1. The current Plant configuration is the West remote intake line is open (51A and 52A are locked open) and the East remote intake line is closed with 52B locked closed and 51B locked open. Figure 2 shows the post event Control Room HVAC configuration. 2) Two of the radiation purge line isolation valve electro-pneumatic operator motors (52D and 51E) were electrically disconnected which causes the valves to open. This was done so that only one manual action is required to isolate a remote path and cause the associated purge path to open or vice versa. 3) The 750cfm control room exhaust fan (51) was de-energized. 4) Specific directions for Plant. Operators to execute to maintain design bases in the event of a LOCA were provided in (approved) deviated Plant procedures. Each new operations crew was provided training by Operation Managers.

NRC PORM 345A oV S GPO'IOSS.OS24 SSS/Edd (043)

NRC form 3SSA U.S. NUCLEAR REOULATORY COMMISSION 1883 l LICENSEE EVENT REPORT ILER) TEXT CONTINUATION APPROVED OMS NO, 3150&181 EXPIRES: 8/31/88 fACILITYNAME Ill POCKET NUMSER 12I LER NUMSER Id) ~ AOE IS) yEAR 'la SEOVCNT/AL NVM Ell;:.iv,.'lEVISION NVM Ell Washington Nuclear Plant - Unit 2 o s o o o 397 88 31 0 0 4 OF 7 TEXT //frr>>fo N>>of /1 rodule4 Irfo aSR/fr>>/H/IC Form 3838'f/ (ITI Further Evaluation and Corrective Action A. Further Evaluation This event was reported per 10CFR50.72(b)(2)(i) on September 2, 1988 at 1702 hours0.0197 days <br />0.473 hours <br />0.00281 weeks <br />6.47611e-4 months <br />. The event is reported per 10CFR50.73(a)(2)(ii)(A). For this event the condition is unanalyzed but the actual safety significance has not yet been determined; however, based on a review of existing analysis this condition is potentially safety significant.

There were no structures, systems, or components inoperable prior to this event which contributed to the event.

The cause of this event was the failure of the Plant Architect/Engineer (Burns 8 Roe Inc.) to provide a system design for which a single failure could not isolate both remote air intakes and cause the Control Room HVAC System to operate in the recirculation mode, or to analyze the recirculation mode of operation. The root cause of this event is a lack of communication between the Architect/Engineer design groups.

B. Further Corrective Action The Control Room HVAC recirculation mode of operation will be analyzed and, the if necessary, recirculation tests conducted to determine control room inleakage in mode to determine Post LOCA control room habitability.

2) A Plant Technical Specification change will be requested to allow normal (not in the emergency filtration pressurization mode) operation of the control room HVAC system with the present Plant configuration.
3) A letter will be sent to Burns 8 Roe Inc., requesting a 10CFR Part 21 evaluation.

Safet Si nificance safety significance of thi s event wi1 1 be determined by compl eting the The engineering - evaluation (committed to 'n LER 88-005) and performing tests to determine the actual inleakage to the Control'oom when the Control Room HVAC System is operated in the recirculation mode. The change from automatic to manual operation of the remote air intake isolations valves has been analyzed as required and does not increase the possibility of an accident, nor does it. create the possibility of a new or different kind of accident. A supplemental report will be submitted when the engineering evaluation of the safety significance of this event is completed.

Similar Events None .

NRCPORM 34SA *U8 GPO 18880824 838/4dd 18831

NRC Pnrln 3SSA UA NUCLEAR RECULATORY COMMISSION 1883 I LICENSEE EVENT REPORT ILER) TEXT CONTINUATION APPROVEO OMS NO 3150&104 EXPIRES'/31/88 I'ACILITYNAME Ill OOCKET NUMSER 131 LER NUMSER ISI PACE 13) lj SCOVCNTIAL NVM CR

@>~ REVISION NVM CR Washington Nuclear Plant - Unit 2 o s o o o 397 88 3 1 000 5 OF TEXT /8'rncrp Necn /c rpCNPSIE vcp sc/elena/H/1C Arne 3/C/AS/ lITI EI IS Information Text Reference EIIS Reference System Component Control Room Heating and Ventilation (HVAC) System VH Normal Fresh Air Intake (Normal Roof Intake Radwaste Building) VH Remote Air Intake Line, (East or West) VH Remote Air Intake Isolation Valves ( 51A and B and 52A and B) VH ISV Remote Air Intake Isolation Valve Motor Operator (Electro-Pneumatic Motor Operator) VH 84 Radiation Purge Line Isolation Valves (51D and E and 52D and E) VH ISV Radiation Purge Line Isolation Valve Motor Operator (Electro-Pneumatic Motor Operators) VH 84 Control Room Emergency Filtration System Fan 51A or 51B VH FAN 750cfm Control Room Exhaust Fan (51) VH FAN Radiation Purge Line Exhaust Fans (53A and B) VH FAN NRC CORM SCCA n U.S.GPO:1 08@0424 838/4dd 18431

NRC Form 3ddA U.S. NUCLEAR REGULATORY COMMISSION I0431 LICENSEE EVENT REPORT (LER) TEXT CONTINUATION APPROVED OMS NO. 3050W104 EXPIRES: 8/3I/88 FACILITY NAME (11 OOCKET NUMBER 131 LER NUMBER Idl PAGE IS)

VEA/I pi( SEQUENTIAL NUMSER:. v.

REVISION NUMSER washington Nuc1ear Plant,- Unit 2 o 5 o o o 9 7 8 0 1 0 0 6o" 0 7 TEXT //1 more SO000/I redvkeIE I/00 ~hrRC Forrrr &54'0/ Illl VALVES CLOSE NORMAL RQQF ON HIGH-HlGH INTAKE I "I I RADIATIQN ALARM RADVASTE VALVES I <TYPICAL> BLDG ' I VALVES ROIQTE OPEN QN I OPEN ow I REMOTE INTAKE FAZ 0 FAZ M/TAKE dl OO 5IC DIV I l2 IVEST) I I (EAS TI I

EHO CI.OSE QM FAZ ISI FC RE J OIQ 52C DIV Il 0 IV Il II I DIV I NC slh 52A DIV I 54A"I DIV II 54S-I 51B NC DIV II ( FQDFV Ir DIV II I I DIV IFQ I I I I " ENERG raTER EHERG FILTER I RR TYPICAL I I I I TYPICAL. I I I I 'AM

DIV s4A I

51A-I IB-I DIVI VH FAN 542 DIV 11 I I I I I I I I I I I I I I I I

.r~ L I

FAN 5lh FAM 5IB

r~ L~

I DIV I DIV 11 I I CONTROL RQQN 51D DIV I FO 52DFO DIV 11 150 CFH

~ roS ll rQ DIV'I 5'IV LEKHR FAH DIV 53A'AH I

53B Dlv II 750 CFH EXHAUST DEOKRGIZE OM FAZ FCR FAll. CLOSED PURGE CGIAUST FAN 51 FOR FAIL OPEN IK:~ NRHALLY CLOSED N7 IS/SMALLY OPEN LO LOCKED OP EH FAZR HIGH ORWELL PRESSURO LOV REACTOR LCR UXXED CLOSED VESSEL VATER LEVEL/ REACTOR BUILDING ANR AISESCIATOR Id VENTILATION EXHAUST HIGH RADIATION, 'PE YASISKOTSM PUSUQ TOYXS RER RAD ELEMENT RRR RAD RECORDER 43 SUPPLY SYSTBM'IOul+

VASHMIOM 9935&868 EHQ~ELECTRO HYDRAILIC OPERATOR TIrLE

=

HAN MANUAL OPERATOR INFORMATION DRAVIMG ON T SEPT 22, 1988 ORIGINAL VNL 2 PARTIAL COMTROL ROIM VENTILATION SYS Figure 1 Pre-Event Control Room HVAC NIIC FOIIM SddA *U.S.QPO:10884424 838/45$

18431

NRC Forr>> 344A V.S. NUCLEAR REGULATORY COMMISSION (0431 LICENSEE EVENT REPORT (LER) TEXT CONTINUATION APPROVf 0 OMS NO. 3I SOWI04 EXPIRES: 8/3I/88 FACILITY NAME lll DOCKS'I NUMBER III LER NUMBER 141 ~ ACE ISI YEAR SEQVSNT IAL 1IW~ IIEvlsloN NVMSSII r%: NVMSS N Washington Nuc1ear P1ant - Unit 2 o 5 o o o 397 0 31 000 7oP 0 7 TEXT ////NSrf fpfcf Ir /44>>inc/, INS SUE//cM/I //RC Fsrrrr 3RIABJ IIII CEASING HORHAL ROOf'NTAKE RADVASTE BLDG RENOTE REHOTE Hn INTAKE INTAKE Sl ENO 5IC DIV I 42 IVEST>

CI.OSC Ok FAZ I/O RE HAH Hhk HAN NAN ENO 52C DIV 11 I I

"I DIV IV 11 Il 548 NO 51A 52A DIV I 34A I DIV 1 28 51'8 LODIV II DIV ll DIV'lILC I DIV I LO EHERG EHERG FILTER FILTER RR TYPICAL AH FAN 5fh 51A-I IB-I FAN 5> FAIL CLOSED FAH 51 FO>> FAIL OPEN HCA ISXUIALLY CLOSED NO>> NORHALLY OPOI LO>> LOCKED CPEH FAZ>> HIGH DRYVELL PRESSURO LOV REACTOR LC>> LOCKED CLOSED VESSEL VATER LEVELS REACTOR BINLDIHG 'mm/SIST PI/SIX: PO XXX VEHTILATOBI EXHAUST HIGH RADIATI AN>> ANABICIATOR IE Ri: RAD anion RR>> RAD RECORDER 43 SUPPLY SYSTEM RKRAIGL VATHD510I 9995'~

OEI>>ELECTRO HYDRAILIC OPERATOR HAN>>HANUAL OPERATOR DBTBIHATIOH DRAVIHG IBE.Y SEPT 22, 1988 CURROIT VIS>>2 PARTIAL CONTROL ROOH VOITILATIOH SYS'igure 2 Post-Event Control Room HVAC N/IC FORM 344A + U.S.GPO:10854 524 535/45$

f043 I

WASHINGTON PUBLIC POWER SUPPLY SYSTEM P.O. Box 968 ~ 3000 George Washington Way ~ Richland, Washington 99352 Docket No. 50-397 October 3, 1988 Document Control'Desk U.S. Nuclear Regulatory Commission Washington, D.C. 20555

Subject:

NUCLEAR PLANT NO. 2 LICENSEE EVENT REPORT NO.88-031

Dear Sir:

Transmitted herewith is Licensee Event Report No.88-031 for the WNP-2 Plant.

This report is submitted in response to the report requirements of 10CFR50.73 and discusses the items of reportability, corrective action taken, and action taken to preclude recurrence.