EOP:

FR-Z.2 TITLE:

RESPONSE

TO CONTAINMENT FLOODING REV 2

PAGE 1 of 4 ROCHESTER GAS AND ELECTRIC CORPORATION GINNA STATION CONTROLLED COPY NUMBER TECHNICAL REVIEW PORC REVIEW DATE SUPERINTEN E

EFFECTIVE DATE QA ~

NON-QA REVIEWED BY:

9OO42O07as 9oo4so PDR-ADOCa OSOOOaey P.

pwu CATEGORY 1.0 8INNASTATIPf4 SIAR!:

DATE TIME.

CG!~IIPLETED:

DATE TIME:

Z

/

EOP:

FR-Z.2

RESPONSE

TO CONTAINMENT FLOODING REV:

2 PAGE 2 of 4 A.

PURPOSE This procedure provides actions to respond to CNMT flooding.

B.

ENTRY CONDITIONS/SYMPTOMS, l.

ENTRY CONDITIONS This procedure is entered from:

a.

F-0.5, CONTAINMENT Critical Safety Function Status

Tree, on an ORANGE condition.

EOP:

FR-Z.2

RESPONSE

TO CONTAINMENT FLOODING REV:

2 PAGE 3 of 4 STEP ACTION/EXPECTED RESPONSE

RESPONSE

NOT OBTAINED NOTE:

Adverse CNMT values should be used whenever CNMT pressure is greater than 4 psig or CNMT radiation is greater than 10-

~ R/hr.

1 Try To Identify Unexpected Source Of Water To Sump:

o Service water indications Isolate suspect flow paths if" possible.

o Annunciator C-10, CONTAINMENT RECIRC CLRS VATER OUTLET LO FLOW 920 GPM o

Both SV header pressures-APPROXIMATELY EQUAL o

Check CNMT fire system isolation valve (AOV-9227) -

CLOSED o

Check CCW surge tank level-STABLE o

Check reactor makeup water tank level - STABLE o

Check AFV pump discharge pressure

- GREATER THAN S/G PRESSURE o

Verify MFV pumps - TRIPPED 2

Direct HP To Sample CNMT Sump For The Following:

~ Activity

~ Boron

~ Chromates

jX

EOP:

FR-Z.2

RESPONSE

TO CONTAINMENT FLOODING REV:

2 PAGE 4 of 4

STEP ACTION/EXPECTED RESPONSE

RESPONSE

NOT OBTAINED 3 Notify Plant Staff Of Sump Level And Activity Level To Obtain Recommended Action 4

Return To Procedure And Step In Effect

-END-