EOP:

ECA-1.2 TITLE:

LOCA OUTSIDE CONTAINMENT REV 2

PAGE 1 of 9 ROCHESTER GAS AND ELECTRIC CORPORAT N

GINNA STATION NTROLLED COPY NUMBER CHNICAL REV1E PORC REVIEW DA 4 el l~

P l NT UPERIN EN NT, v(~le EFFECTIVE DATE QA NON-Q CATEGORY 1.0 GINNASTATION START:

DATE REVIEWED BY COMPLETED.

9004200671 800410 l~

PDR',

- ADOCN,/05000244 J

P'NU

EOP:

ECA-1.2 LOCA OUTSIDE CONTAINMENT REV:

2 PAGE 2 of 9 A.

PURPOSE This procedure provides actions to identify and isolate a

LOCA outside containment.

B.

ENTRY CONDITIONS/SYMPTOMS 1.

ENTRY CONDITIONS This procedure is entered from:

a.

E-O, REACTOR TRIP OR SAFETY INJECTION, and E-l, LOSS OF REACTOR OR SECONDARY COOLANT, on abnormal r'adiation in the auxiliary building due to a loss of RCS inventory outside containment.

r

EOP:

ECA-1.2 LOCA OUTSIDE CONTAINMENT REV 2

PAGE 3 of 9 STEP ACTION/EXPECTED RESPONSE

RESPONSE

NOT OBTAINED NOTE:

Adverse CNMT values should be used whenever CNMT pressure is greater than 4 psig or CNMT radiation is greater than 10

~ R/hr.

1 Verify Proper RHR Normal Cooling Valve Alignment:

o MOV-700 and MOV-701, RHR suction valves from A hot leg - CLOSED o

MOV-720 and MOV-721, RHR discharge valves to B cold leg-CLOSED Manually close valves.

IF neither MOV-700 nor MOV-701 can be closed, THEN perform the following:

a.

Stop any running RHR pumps.

b. Close the following valves:

~ MOV-856, RHR suction from RWST

~ MOV-704A and MOV-704B, RHR pump suction cross tie valves IF neither MOV-720 nor MOV-721 can be closed, THEN:

a.

Stop any running RHR pump.

'. Close the following valves:

~ HCV-624 and HCV-625, RHR Hx outlet valves

~ HCV-626, RHR Hx bypass valve, if open

EOP:

ECA-1.2 TITLE:

LOCA OUTSIDE CONTAINMENT REV:

2 PAGE 4 of 9 STEP ACTION/EXPECTED RESPONSE

RESPONSE

NOT OBTAINED 2

Check CVCS Valve Alignment:

a. Verify the following valves-CLOSED

~, AOV-310, Excess letdown isolation valve

~ AOV-296, Auxiliary spray valve

~ AOV-392A, Charging line isolation valve to loop B hot leg

a. Manually close valves.

IF AOV-310 can NOT be closed, THEN ensure seal return isolation valve, MOV-313, closed.

IF AOV-296 or AOV-392A"can NOT be closed, THEN perform the following:

1) Manually close HCV-142 charging line flow control valve.
b. Verify the following CI valves-CLOSED

~ MOV-313, seal return isolation valve

~ AOV-371, letdown isolation valve

2) Dispatch AO with RVST area key to locally close V-384A.
b. Manually close valves.

IF either valve can NOT be

closed, THEN dispatch AO to locally isolate flowpath as necessary.

o Close V-315A, seal return filter inlet, to isolate MOV-313 (reach rod outside SURF room).

o Close V-204A, NRHX inlet, to isolate AOV-371 (inside NRHX room).

EOP:

ECA-1.2 LOCA OUTSIDE CONTAINMENT 0

REV:

2 PAGE 5 of 9 STEP ACTION/EXPECTED RESPONSE

RESPONSE

NOT OBTAINED 3

Check Charging Valves For Backflow:

a.

Check charging pumps - ALL PUMPS ORR

b. Close charging line isolation valve to loop B cold, AOV-294 c.

Check RCS pressure.-

INCREASING d.

Go to Step 7

a.

Go to Step 4.

b. Perform the following:
1) Manually close HCV-142, charging line flow control valve.
2) Dispatch AO with RWST area key to locally close V-384A.
c. Restore charging line as necessary and go to Step 4.

EOP ECA-1.2 TITLE:

LOCA OUTSIDE CONTAINMENT REV:

2 PAGE 6 of 9 STEP ACTION/EXPECTED RESPONSE

RESPONSE

NOT OBTAINED 4

RCP Seal Injection Flow To Each RCP GREATER THAN 6 GPM IR CCW is being supplied to either RCP thermal barrier, THEN perform the following:

a.

Ensure at least one charging pump running.

b. Increase charging pump speed and adjust charging line flow control valve (HCV-142) as necessary to establish required seal in)ection flow.

c.

Go to Step 5.

IP neither CCW pump is running, THEN perform the following:

a.

Close RCP CCW return valves.

~ MOV-759A

~ MOV-759B b.

Go to Step 6.

\\

I

~

~

EOP:

ECA-1.2 LOCA"OUTSIDE CONTAINMENT REV:

2 PAGE 7 of 9 STEP ACTION/EXPECTED RESPONSE

RESPONSE

NOT OBTAINED 5

Check RCP Thermal Barrier For Leakage:

a. Close RCP A thermal barrier return valve, AOV-754A
b. Check RCS pressure

- INCREASING c.

Go to Step 7

d. Close RCP B thermal barrier return valve, AOV-754B e.

Check RCS pressure

- INCREASING

f. Go to Step 7
a. Close RCP A CCW return valve, MOV-759A.
b. Restore RCP A thermal barrier cooling, if desired, and go to Step 5d.
d. Close RCP B

CCW return valve, MOV-759B.

e. Restore RCP B thermal barrier cooling, if desired and go to Step 6.

EOP:

ECA-1.2 LOCA OUTSIDE CONTAINMENT REV 2

PAGE 8 of 9 STEP ACTION/EXPECTED RESPONSE

RESPONSE

NOT OBTAINED 6

Check Safeguards Valves For Backflow:

a. Close RHR pump discharge to Rx vessel deluge (MOU-852A) and check for RCS pressure increase b.

Go to Step 7.

c. Dispatch AO with locked valve key to locally close breakers for SI pump discharge to cold leg isolation valves

~ MOV-878B, MCC D position SC

~ MOV-878D, MCC D position SF

d. Close SI pump discharge to cold leg B (MOV-878B) and check for pressure increase e.

Open breakers for MOV-878B and MOV-878D

a. Perform the following:
1) Open MOV-852A.
2) Close RHR pump discharge to Rx vessel deluge (MOV-852B).
3) Check for RCS pressure increase.

IF NOT, THEN open MOV-852B and go to Step 6c.

d. Perform the following:
1) Open MOV-878B.
2) Close SI pump discharge to cold leg A (MOV-878D).
3) Check for RCS pressure increase.

IF NOT, THEN open MOV-878D.

l

I EOP:

ECA-1.2 TlTLE:

LOCA OUTSIDE CONTAINMENT REV:

2 PAGE 9 of 9 STEP ACTION/EXPECTED RESPONSE

RESPONSE

NOT OBTAINED 7

Check If Break Is Isolated:

a.

RCS pressure

- INCREASING b.

Go to E-l, LOSS OP REACTOR OR SECONDARY COOLANT, Step 1

a.

Go to ECA-1.1, LOSS OF EMERGENCY COOLANT RECIRCULATION, Step l.

-END-