FR-H.3

RESPONSE

TO STEAM GENERATOR HIGH LEVEL REV 2

PAGE 1 of 5 ROCHESTER GAS AND ELECTRIC CORPORATION GINNA STATION CONTROLLED COPY NUMBER TECHNICAL REVIEW PORC REVIEW DATE T SUPERINTE DE T EFFECTIVE DATE QA NON-QA CATEGORY 1.0 REVIEWED BY:

G INNASTATION START:

9'000200yyh 9004LO-

, p

  • DDCI( 050002yy i l PNu TIME:

EOP:

FR-H.3 TITLE:

RESPONSE

TO STEAM GENERATOR HIGH LEVEL REV:

2 PAGE 2 of 5 A.

PURPOSE This procedure provides actions to respond to a S/G high level condition and to address the S/G overfill concern.

B.

ENTRY CONDITIONS/SYMPTOMS 1.

ENTRY CONDITIONS This procedure is entered from:

a.

F-0.3, HEAT SINK Critical Safety Function Status Tree on a YELLOW condition, and b ~

FR H ~ 2 ~

RESPONSE

TO STEAM GENERATOR OVERPRESSURE g

if the affected S/G narrow range level is high.

EOP:

FR-H.3 TITLE:

RESPONSE

TO STEAM GENERATOR HIGH LEVEL REV 2

PAGE 3 of 5 STEP ACTION/EXPECTED RESPONSE

RESPONSE

NOT OBTAINED CAUTION o

IP S/G NARROW RANGE LEVEL HAS INCREASED TO GREATER THAN 90X [85X ADVERSE CNMT], THEN AN EVALUATION SHOULD BE MADE FOR S/G OVERFILL CONSIDERATIONS.

STEAM SHOULD NOT BE RELEASED FROM ANY S/G WITH LEVEL GREATER THAN 90%

[85%

ADVERSE CNMT] PRIOR TO OVERFILL EVALUATION.

o IF S/G OVERFILL IS EXPECTED AN ATTEMPT SHOULD BE MADE TO DISPATCH PERSONNEL TO PIN MAIN STEAMLINES.

J NOTE:

o Throughout this procedure, "affected" refers to any S/G in which narrow range level is greater than 67X.

o Adverse CNMT values should be used whenever CNMT pressure is greater than 4 psig or CNMT radiation is greater than 10-

~ R/hr.

1 Identify Affected S/G(s):

a.

Narrow range level - GREATER THAN 67X

a. IF less than 67X in all S/Gs, THEN return to procedure and step in effect.

2 Verify FW Isolation To Affected S/G(s):

a.

MFW pumps - TRIPPED b.

MPW flow control valve(s)-

CLOSED

~

MPW regulating valve(s)

~

MFW bypass valve(s) c.

MPW pump discharge valve(s)-

CLOSED

a. Trip MFW pumps.
b. Manually close valves.
c. Manually close valves.
d. Verify both S/G pressures-GREATER THAN CONDENSATE HEADER PRESSURE
d. Stop any running condensate pumps.

EOP:

FR-H.3

RESPONSE

TO STEAM GENERATOR HIGH LEVEL REV:

2 PAGE 4 of 5 STEP ACTION/EXPECTED RESPONSE

RESPONSE

NOT OBTAINED 3

Close AFW And SAFW Flow Control Valves To Affected S/G (s):

o S/G A

~ MOV-4007 and AOV-4480, MDAFW pump

~ AOV-4297, TDAFW pump

~ MOV-9701A, SAFW pump o

S/G B

Stop pumps feeding affected S/G(s).

~ MOV-4008 and AOV-4481, MDAPW pump

~ AOV-4298, TDAFW pump

~ MOV-9701B, SAPW pump 4

Check Affected S/G(s)

Level:

a. Narrow range level - LESS THAN 90X [85X adverse CNMT]
b. Narrow range level - DECREASING
c. Control APW flow to maintain narrow range level between 17X

[25X adverse CNMT] and 39%

d. Return to procedure and step in effect a.

Go to Step 5.

b.

Go to Step 5.

5 Close Affected S/G TDAFW Pump Steam Supply Valve And Place In PULL STOP

~ S/G A, MOV-3505A

~ S/G B, MOV-3504A

EOP:

FR-H.3

RESPONSE

TO STEAM GENERATOR HIGH LEVEL REV:

2 PAGE 5 of 5 STEP ACTION/EXPECTED RESPONSE

RESPONSE

NOT OBTAINED 6

Close Affected S/G(s)

MSIV And Bypass Valves 7

Check Affected S/G(s)

Radiation Levels NORMAL

~ S/G blowdown, R-19

~ S/G A, R-31

~ S/G B, R-32 IF an E-3 or ECA-3 series procedure is in effect, THEN return to procedure and step in effect.

IF

NOT, THEN go to E-3, STEAM GENERATOR TUBE RUPTURE, Step 1.

8 Establish Blowdown From Affected S/G(s):

a. Reset SI and CI
b. Reset XY relays for affected S/G blowdown valves
c. Place blowdown key switch for affected S/G to defeat
d. Verify S/G blowdown valves-OPEN
e. Dispatch AO to establish blowdown to condenser or flash
tank, as desired (Refer to T-14F, STEAM GENERATOR BLOWDOWN SYSTEM STARTUP) 9 Return To Procedure And Step In Effect

-END-

rI I

0, PI e

(