NMP2L2616, Supplemental Response to Request for Additional Information by NRR to Support Review of Relocation of Secondary Containment Bypass Leakage Paths Table from Technical Specifications to the Technical Requirements Manual

From kanterella
(Redirected from ML16081A371)
Jump to navigation Jump to search

Supplemental Response to Request for Additional Information by NRR to Support Review of Relocation of Secondary Containment Bypass Leakage Paths Table from Technical Specifications to the Technical Requirements Manual
ML16081A371
Person / Time
Site: Nine Mile Point Constellation icon.png
Issue date: 03/21/2016
From: Jim Barstow
Exelon Generation Co
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
NMP2L2616
Download: ML16081A371 (21)


Text

Exelon Generation 200 Exelon Way Kennett Square. PA 19348 www exeloncorp.com 10 CFR 5090 NMP2L2616 March 21, 2016 U.S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington. DC 20555-0001 Nine Mile Point Nuclear Station, Unit 2 Renewed Facility Operating License No. NPF-69 NRG Docket No. 50-410

Subject:

Supplemental Response to Request for Additional Information by the Office of Nuclear Reactor Regulation to Support Review of Nine Mile Point Nuclear Station, Unit 2, Relocation of Secondary Containment Bypass Leakage Paths Table from Technical Specifications to the Technical Requirements Manual

References:

1. Letter from J. Barstow (Exelon Generation Company, LLC) to U.S.

Nuclear Regulatory Commission, "License Amendment Request -

Relocation of Secondary Containment Bypass Leakage Paths Table from Technical Specifications to the Technical Requirements Manual," dated March 23, 2015

2. Letter from B. Mozafari (Senior Project Manager, U.S. Nuclear Regulatory Commission) to Mr. Bryan Hanson (Exelon Generation Company, LLC),

"Nine Mile Point Nuclear Station, Unit 2-Request for Additional Information Regarding (CAC MF 5900)," dated December 17, 2015

3. Letter from D. Gudger (Exelon Generation Company, LLC) to U.S. Nuclear Regulatory Commission, "Response to Request for Additional Information by the Office of Nuclear Reactor Regulation to Support Review of Nine Mile Point Nuclear Station, Unit 2, Relocation of Secondary Containment Bypass Leakage Paths Table from Technical Specifications to the Technical Requirements Manual," dated January 8, 2016 By letter dated March 23, 2015 (Reference 1), Exelon Generation Company, LLC (Exelon) requested to change the Nine Mile Point Nuclear Station, Unit 2 (NMP2) Technical Specifications (TS). The proposed amendment request would modify NMP2 TS by relocating the secondary containment bypass leakage paths table from the TS to the Technical Requirements Manual.

U.S. Nuclear Regulatory Commission Supplemental Response to Request for Additional Information Relocation of Secondary Containment Bypass Leakage Paths Docket No. 50-41 O March 21, 2016 Page2 On December 8, 2015, the U.S. Nuclear Regulatory Commission (NRC) emailed a draft Request for Additional Information (RAI). On December 11, 2015, a clarification teleconference was held between NRC and Exelon personnel. The formal RAI (Reference 2) was provided on December 17, 2015.

On January 8, 2016, Exelon submitted to the NRC the RAI response (Reference 3).

Subsequent to this submittal, a second clarification teleconference was performed between the NRC and Exelon on March 1, 2016. to this letter contains the NRC's RAI immediately followed by Exelon's supplemental RAI response. This supplement replaces the RAI response provided on January 8, 2016 (Reference 3), and clarifies the original submittal (Reference 1) as requested during the clarification call on March 1, 2016.

Exelon. has reviewed the information supporting a finding of no significant hazards consideration and the environmental consideration provided to the NRC in Reference 1.

The additional information provided in this response does not affect the bases for concluding that the proposed license amendment does not involve a significant hazards consideration.

Furthermore, the additional information provided in this response does not affect the bases for concluding that neither an environmental impact statement nor an environmental assessment needs to be prepared in connection with the proposed amendment.

With the supplemental information provided in the attached response, Exelon requests approval of the proposed amendment by April 19, 2016. The requested approval date supports the implementation of the hardened containment vent modifications at NMP2 to comply with the schedule required by NRC Order EA-13-109, Order to Modify Licenses with Regard to Reliable Hardened Containment Vents Capable of Operation Under Severe Accident Conditions, dated June 6, 2013. Once approved, the amendment shall be implemented prior to restart from NMP2 2016 refueling outage.

There are no commitments contained in this response.

If you should have any questions regarding this submittal, please contact Ron Reynolds at 610-765-524 7.

I declare under penalty of perjury that the foregoing is true and correct. Executed on the 21 51 day of March 2016.

Respectfully, Jame~a:: ~

Director - Licensing & Regulatory Affairs Exelon Generation Company, LLC

U.S. Nuclear Regulatory Commission Supplemental Response to Request for Additional Information Relocation of Secondary Containment Bypass Leakage Paths Docket No. 50-41 O March 21, 2016 Page 3 : Supplemental Response to Request for Additional Information : Revised Technical Specification Pages and Bases Marked-Up Pages cc: USNRC Region I Regional Administrator w/attachments USN RC Senior Resident Inspector - NMP USNRC Project Manager, NRR - NMP A. L. Peterson, NYSERDA

ATTACHMENT 1 Nine Mile Point Nuclear Station, Unit 2 Relocation of Secondary Containment Bypass Leakage Paths Docket No. 50-41 O Supplemental Response to Request for Additional Information

Supplemental Response to Request for Additional Information Attachment 1 Relocation of Secondary Containment Bypass Leakage Paths Page 1 of 4 RAI STSB-1:

In the existing NMP2 TS, Table 3.6.1.3-1 specifies a numerical value for allowable leakage for each leakage path in standard cubic feet per hour. Surveillance Requirement (SR) 3.6.1.3.11 states:

Verify the leakage rate for the secondary containment bypass leakage paths is within the limits of Table 3.6.1.3-1 when pressurized to;::; 40 psig.

The proposed change is deletion of Table 3.6.1.3-1 and revision of SR 3.6.1.3.11 to state:

Verify the leakage rate for the secondary containment bypass leakage paths is within the limits when pressurized to ;::; 40 psig.

The staff requests additional information to explain why a numerical value limit on the secondary containment bypass leakage is not retained within the proposed SR 3.6.1.3.11 itself. Typically, the safety analysis for a facility assumes a specific amount of bypass leakage when calculating dose consequences. This leakage limit is reflected in the TS to ensure operation within the bounds of the safety analysis.

The regulation at 10 CFR 50.36(c)(3) requires TSs to include items in the category of surveillance requirements, which are requirements relating to test, calibration, or inspection to assure that the necessary quality of systems and components is maintained, that facility operation will be within safety limits, and that the Limiting Conditions for Operations will be met. The leakage limit for the pathways to be considered operable must be specified in the TS.

The staff compared the proposed revision of SR 3.6.1.3.11 with the guidance provided in Generic Letter 91-08. The Generic Letter recommended that the limitation on containment leakage rate be revised to state:

A combined leakage rate of less than or equal to [0.1 O La] for all penetrations that are secondary containment bypass leakage paths when pressurized to Pa.

This requirement has also been retained in the Standard TS.

Provide a technical justification for not retaining a numerical limit on allowable leakage on the secondary containment bypass pathways or propose a change to SR 3.6.1.3.11 to reflect the appropriate limit. If it is proposed to specify the leakage limit in terms of a combined leakage rate, please review LCO 3.6.1.3 Condition D and its associated Required Actions to ensure consistency with the proposed change to SR 3.6.1.3.11.

Exelon Supplemental Response to RAI STSB-1:

Based on a clarification call between the U.S. Nuclear Regulatory Commission (NRC) and Exelon conducted on March 1, 2016, the following supplemental information is provided to the license amendment request submitted on March 23, 2015 (Reference 1), and the above Request for Additional Information.

Supplemental Response to Request for Additional Information Attachment 1 Relocation of Secondary Containment Bypass Leakage Paths Page 2 of 4 In summary, the following changes are requested. Technical Specification (TS) Table 3.6.1.3-1 will be relocated from the TS to the Technical Requirements Manual {TRM) which is a licensee controlled document. Surveillance Requirement (SR) 3.6.1.3.11 will be revised to include three numerical values for the limiting secondary containment leakage rates based on the previously NRC approved Alternative Source Term (AST} licensing basis for Nine Mile Point Unit 2 (NMP2)

(References 2 and 3). Finally, as a result of a plant modification to address the hardened vent as specified in NRC Order EA-13-109 (Reference 4), a secondary containment bypass leakage path is eliminated from the current TS Table 3.6.1.3-1.

The hardened vent modification includes the replacement of Primary Containment Isolation Valve (PCIV) 2CPS* AOV109 and the relocation of this valve from inside primary containment to outside primary containment. Valves 2CPS*SOV133 and 2CPS*V51 provide motive air to the 2CPS*AOV109 air actuator. Therefore, since 2CPS*AOV109 will no longer be located inside primary containment, the motive air lines and valves inside containment will be removed in their entirety and the lines will be cut and isolated by a welded cap on both the inside and outside of primary containment penetration Z92.

Valves 2CPS*SOV133 and 2CPS*V51 are currently listed in TS Table 3.6.1.3-1. The TS Table specifies an allowable leakage value applicable to each valve in Standard Cubic Feet per Hour (SCFH). Removal of valves 2CPS*SOV133 and 2CPS*V51 from primary containment eliminates the secondary containment bypass leakage path such that the two valves can be deleted from TS Table 3.6.1.3-1. Removal of this secondary containment bypass leakage path is conservative with respect to dose consequences following a LOCA. Therefore, the LOCA dose consequence analysis was not modified as a result of this change.

The secondary containment bypass leakage paths and limits specified in the current TS Table 3.6.1.3-1 are direct inputs to the approved AST licensing basis for NMP2 for the Loss of Coolant Accident (LOCA) evaluation as submitted in License Amendment Request dated May 31, 2007 (Reference 2), and approved by Amendment 125 (Reference 3). As detailed in Exelon Design Analysis H21C-106 (Reference 5), these pathways release activity across four different release points; each release point having unique atmospheric dispersion coefficients. Additionally, each pathway has unique flow and fission product removal characteristics. As a result of these varying release pathway characteristics, the current approved LOCA AST licensing basis is not configured to transform the multiple leakage limits into a single numerical value. Based on the AST analysis methodology, the secondary containment bypass leakage pathways are divided into the following (4) groups: Main Steam Isolation Valves (open/closed), Bypass (Drywell),

Bypass (Suppression Chamber), and Bypass (Delayed from Drywell). SR 3.6.1 .3.12 requires verification of the leakage rate through each main steam isolation valve; therefore, the remaining three groups are identified as the secondary containment bypass leakage associated with SR 3.6.1.3.11.

The current approved AST LOCA analysis documents the procedure used to convert volumetric flow rate under test conditions to volumetric flow rate under accident conditions {page C3 of Reference 5). This procedure is employed to establish volumetric flow rates under test conditions for the three groups of secondary bypass leakage for the proposed TS SR 3.6.1.3.11 as detailed below.

A brief description of the three groups is as follows:

Supplemental Response to Request for Additional Information Attachment 1 Relocation of Secondary Containment Bypass Leakage Paths Page 3 of 4 a Bypass (Drywell): Includes all bypass pathways with no delays considered originating in the drywell except those listed below in the third group. This leakage group will have a combined effective leakage rate less than or equal to 8.74 SCFH. This value is calculated by dividing the combined actual flowrate of 3.394 CFH by 0.388.

b Bypass (Suppression Chamber): Includes all bypass pathways with no delays considered originating in the suppression chamber. This leakage group will have a combined effective leakage rate less than or equal to 1.67 SCFH. This value is calculated by dividing combined actual flowrate of 0.6483 CFH by 0.388.

c Bypass (Delayed from Drywell): Includes feedwater, 14" containment purge, and reactor water cleanup, delays are considered and conservatively combined. This leakage group will have a combined effective leakage rate less than or equal to 28.17 SCFH. This value is calculated by dividing combined actual flowrate of 10.93 CFH by 0.388.

It is noted that in the above description the combined effective leakage rate corresponds to the combined leakage rate weighted by the X/Q normalization factor as outlined in the AST analysis (page C6 of Reference 5). In addition, the AST analysis uses the term "Wetwell" which is synonymous with Suppression Chamber.

The proposed revision to SR 3.6.1.3.11 as shown in Attachment 2 reflects the limits of the three groups described above. The TS Table 3.6.1.3-1 will be relocated to the TRM as shown in . The elimination of valves 2CPS*SOV133 and 2CPS*V51 as a result of the hardened vent modification will be reflected in the new TRM table. Changes to the TRM are licensee controlled and subject to the provisions of 10 CFR 50.59.

TS Limiting Condition for Operation 3.6.1.3, Condition D, and its associated Required Actions, were reviewed and no changes are necessary as a result of this proposed change. However, changes to the applicable TS Bases section is provided in Attachment 2.

The marked up TS pages and marked up TS Bases pages provided with this supplemental response supersedes the previously submitted marked up pages provided in the license amendment request dated March 23, 2015, and the RAI response submittal dated January 8, 2016, in their entirety.

References:

1. Letter from J. Barstow (Exelon Generation Company, LLC) to U.S. Nuclear Regulatory Commission, "License Amendment Request - Relocation of Secondary Containment Bypass Leakage Paths Table from Technical Specifications to the Technical Requirements Manual," dated March 23, 2015
2. Letter from K. Nietmann (Nine Mile Point Nuclear Station) to Document Control Desk (U.S. NRC), "License Amendment Request Pursuant to 10 CFR 50.90: Application of Alternate Source Term," dated May 31, 2007 (ML071580314)

Supplemental Response to Request for Additional Information Attachment 1 Relocation of Secondary Containment Bypass Leakage Paths Page 4 of 4

3. Letter from R. Guzman (Senior Project Manager, U.S. Nuclear Regulatory Commission) to K. Polson (Nine Mile Point Nuclear Station), "Nine Mile Point Nuclear Station, Unit 2-lssuance of Amendment RE: Implementation of Alternative Radiological Source Term (TAC NO. MD5758)," dated May 29, 2008 (ML081230439)
4. NRG Order EA-13-109, "Issuance of Order to Modify Licenses with Regard to Reliable Hardened Containment Vents Capable of Operation Under Severe Accident Conditions,"

dated June 6, 2013

5. H21C-106, "Unit 2 LOCA w/LOOP AST Methodology," dated May 31, 2007

[Attachment 7 to Reference 2, ML071580354]

ATTACHMENT 2 Nine Mile Point Nuclear Station, Unit 2 Relocation of Secondary Containment Bypass Leakage Paths Docket No. 50-41 O PROPOSED TECHNICAL SPECIFICATION and BASES MARKED-UP PAGES TS Pages 3.6.1.3-1, -12, -14 and -15 Bases Pages B3.6.1.3-1 through -3, -8, -18 and -19 TAM Pages 3.6-23a and -23b

PC IVs Secondary Containment Bypass 3.6.1 .3 Leakage Valve 3.6 CONTAINMENT SYSTEMS DELETE 3.6.1.3 Primary Containment Isolation Vi Ives (PCIVs)

LCO 3.6.1.3 Each PCIV and each AOA PGl\/ listed iA Teele 3.S.1.3 1 shall be OPERABLE.

APPLICABILITY: MODES 1, 2, and 3, When associated instrumentation is required to be OPERABLE per LCO 3.3.6.1, "Primary Containment Isolation Instrumentation."

ACTIONS


N0 TES-----------------------------------------------------------

1. Penetration flow paths may be unisolated intermittently under administrative controls.
2. Separate Condition entry is allowed for each penetration flow path.
3. Enter applicable Conditions and Required Actions for systems made inoperable by PCIVs.
4. Enter applicable Conditions and Required Actions of LCO 3.6.1 .1, "Primary Containment," when PCIV leakage results in exceeding overall containment leakage rate acceptance criteria.

CONDITION REQUIRED ACTION COMPLETION TIME A. -------------NOTE-------------- A.1 Isolate the affected 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> except Only applicable to penetration flow path for main steam penetration flow paths by use of at least line with two or more one closed and PC IVs. de-activated AND


automatic valve, closed manual valve, 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> for main One or more blind flange, or steam line penetration flow paths check valve with flow with one PCIV through the valve inoperable except due secured.

to leakage not within limit. AND (continued)

NMP2 3.6.1.3-1 Amendment 91

PC IVs 3.6.1.3 SURVEILLANCE REQUIREMENTS (continued)

SURVEILLANCE FREQUENCY SR 3.6.1.3.6 Perform leakage rate testing for each 184 days primary containment purge valve with resilient seals. AND Once within 92 days after opening the valve SR 3.6.1.3.7 Verify the isolation time of each MSIV is In accordance

~ 3 seconds and s 5 seconds. with the lnservice Testing Program SR 3.6.1.3.8 Verify each automatic PCIV actuates to 24 months the isolation position on an actual or simulated isolation signal.

SR 3.6.1.3.9 Verify a representative sample of reactor 24 months instrumentation line EFCVs actuates to the isolation position on an actual or simulated instrument line break signal.

SR 3.6.1.3.10 Remove and test the explosive squib from 24 months on a each shear isolation valve of the TIP STAGGERED TEST System. j lDELETE I BASIS SR 3.6.1.3.11 \/-

'..t:,, it..._

'J ** ,_

I ./

_i .t:

In accordance seeeRElary seRtaiRFReRt ey13ass leaka~e with 10 CFR 50 13aths is within the limite ef Teiele- Appendix J d.e. ~ .d ~ when 13Fesst1Fii!:ea te ~ 4G Testing Program

~ Plan

~

I Verify the leakage rate for the secondary containment bypass (continued) leakage when pressurized to ;::40 psig is:

a . Bypass (Drywell) : s 8.74 SCFH; and

b. Bypass (Suppression Chamber):~ 1.67 SCFH; and c . Bypass (Drywell with delays) : ~ 28.17 SCFH NMP2 3.6.1.3-12 Amendment 94-, 96

PC IVs DELETE 3.6.1.3 Table 3.6.1.3-1 (page 1 of 2)

Secondary Containment Bypass Leakage Paths Leakage Rate Limits VALVE NUMBER PER VALVE LEAK RA TE SCFH 2MSS*MOV111 1.875 2MSS*MOV112 2MSS*MOV208 0.625 2CMS*SOV74A, B (d) 0.2344 2CMS*SOV75A, B (d) 2CMS*SOV76A, B (d) 2CMS*SOV77A, B (d) 2DER*MOV119 (a) 2DER*RV344 2DER*MOV120 1.25 2DER*MOV130 0.625 2DER*MOV131 2DFR*MOV120 1.875 2DFR*MOV121 (b) 2DFR*RV228 2DFR*MOV139 0.9375 2DFR*MOV140 2WCS*MOV102 2.5 2WCS*MOV112 2FWS*V23A, B 12.0 2FWS*V12A, B 2CPS*AOV104 4.38 2CPS*AOV106 2CPS*AOV105 3.75 2CPS*AOV107 (a) The combined leakage rate for these two valves shall be ~ 1.25 SCFH.

b The combined leaka e rate for these two valves shall be ~ 1.875 SCFH.

The information from this Technical Specification section has been relocated to the TRM and maintained in accordance with the 10 CFR 50 Appendix J Testing Program Plan.

NMP2 3.6.1.3-14 Amendment Bi, .:tM, 106

DELETE

--~

Table 3.6.1.3-1 (page 2 of 2)

Secondary Containment Bypass Leakage Paths Leakage Rate Limits VALVE NUMBER PER VALVE LEAK RATE SCFH 2CPS*SOV119 0.625 2CPS*SOV120 2CPS*SOV121 2CPS*SOV122 21AS*SOV164 0.9375 21AS*V448 21AS*SOV165 0.9375 21AS*V449 2GSN*SOV166 (c) 2GSN*V170 21AS*SOV166 (c) 21AS*SOV184 21AS*SOV167 (c) 21AS*SOV185 21AS*SOV168 (c) 21AS*SOV180 2CPS*SOV132 (c) 2CPS*V50 2CPS*SOV133 (c) 2CPS*V51 The combined leak rate for these penetrations shall be ~ 3.6 SCFH. The assigned leakage rate through a penetration shall be that of the valve with the highest leakage rate in that penetration. However, if a penetration is isolated by one closed and de-activated automatic valve, closed manual valve, or blind flange , the leakage through the penetration shall be the actual pathway leakage.

(d) The LCO requirements and leakage rate limit shall apply until such time as a modification eliminates the potential secondary containment bypass leakage path .

...._____ IThe information from this Technical Specification section has been relocated to the TRM and maintained in accordance with the 10 CFR 50 Appendix J Testing Program Plan .

NMP2 3.6.1.3-15 Amendment 94, 106

PC IVs B 3.6.1.3 B 3.6 CONTAINMENT SYSTEMS secondary containment bypass leakage valves B 3.6.1.3 Primary Containment Isolation Valves (PCIVs)

DELETE BASES BACKGROUND The function of the PC IVs and the non PG IVs listed in J able 3.6.1.3 1 (2GMS*SOV74A, 748, 75A, 758, 76A, 768, 77A, and 778), in combination with other accident mitigation systems, is to limit fission product release during and following postulated Design Basis Accidents (DBAs) to within DELETE limits. Primary containment isolation within the time limits specified for those PC IVs designed to close automatically ensures that the release of radioactive material to the environment will be consistent with the assumptions used in the analyses for a OBA.

The OPERABILITY requirements for PCIVs help ensure that an adequate primary containment boundary is maintained during and after an accident by minimizing potential paths to the environment. Therefore, the OPERABILITY requirements provide assurance that the primary containment function assumed in the safety analysis will be maintained. These isolation devices consist of either passive devices or active (automatic) devices. Manual valves, de-activated automatic valves secured in their closed position (including check valves with flow through the valve secured}, blind flanges (which include plugs and caps as listed in Reference 1), and closed systems are considered passive devices. Check valves, or other automatic valves designed to close without operator action following an accident, are considered active devices. Two barriers in series are provided for each penetration, except for penetrations isolated by excess flow check valves, so that no single credible failure or malfunction of an active component can result in a loss of isolation or leakage that exceeds limits assumed in the safety analysis. One of these barriers may be a closed system.

The 12 and 14 inch primary containment purge valves are PCIVs that are qualified for use during all operational conditions. The 12 and 14 inch primary containment purge valves are normally maintained closed in MODES 1, 2, and 3 to ensure the primary containment boundary is maintained.

However, the purge valves may be open when being used for pressure control, inerting, de-inerting, ALARA, or air quality considerations since they are fully qualified.

(continued)

NMP2 B 3.6.1.3-1 Revision 0

PC IVs B 3.6.1.3 BASES BACKGROUND A two inch bypass line is provided when the primary (continued) containment full flow line to the Standby Gas Treatment (SGT) System is isolated.

APPLICABLE The PCIVs LCO was derived from the assumptions related SAFETY ANALYSES to minimizing the loss of reactor coolant inventory, and establishing the primary containment boundary during major accidents. As part of the primary containment boundary, secondary containment PCI AOA PGIVs listed iA Table 3.6.1 .3 1 OPERABILITY supports leak tightness of primary containmen . refore, ~-------.

bypass leakage valves the safety analysis of any event requiring isolation of DELETE primary containment is applicable to this LCO.

The DBAs that result in a release of radioactive material for which the consequences are mitigated by PCIVs are a loss of coolant accident (LOCA) and a main steam line break secondary (MSLB) (Refs. 2 and 3) . In the analysis for each of these containment bypass accidents, it is assumed that PCIVs are either closed or leakage valves nction to close within the required isolation time fo wing event initiation. This ensures that potential pat to the environment through PCIVs (including primary contar ment purge valves) are minimized. Of the events DELETE analyze in References 2 and 3, the LOCA is the mos The secondary containment limiting e nt due to radiological consequences.

bypass leakage paths addition, tli non PGIVs listed iA Table 3.6.1.3 1 are also leakage rate limits are assumed to be closed during the LOCA. The closure time of relocated to the Technical the main steam isolation valves (MSIVs) is a significant Requirements Manual variable from a radiological standpoint. The MSIVs are (TRM) Table 3.6.1.3-1 and required to close within 3 to 5 seconds since the 3 second are maintained in re time is assumed in the MSIV closure (the most severe overpr urization transient) analysis (Ref. 4) and 5 second accordance with the 10 closure tim

  • assumed in the MSLB analysis (Ref. 3).

CFR 50 Appendix J Testing Likewise, it is a med that the primary containment Program Plan. isolates such that re se of fission products to the environment is controlle .

The OBA analysis assumes that isolation of the primary containment is complete and leakage terminated, except for the maximum allowable leakage, La. prior to fuel damage.

The single failure criterion required to be imposed in the conduct of unit safety analyses was considered in the original design of the primary containment purge valves.

Two valves in series on each purge line provide assurance that both the supply and exhaust lines could be isolated even if a single failure occurred .

(continued)

NMP2 B 3.6.1.3-2 Revision 0

PC IVs B 3.6.1.3 BASES APPLICABLE PCIVs satisfy Criterion 3 of Reference 5.

SAFETY ANALYSES (continued)

LCO PCIVs form a part of the primary containment boundary. The PCIV safety function is related to minimizing the loss of reactor coolant inventory and establishing the primary containment boundary during a OBA.

The power operated, automatic isolation valves are required to have isolation times within limits and actuate on an automatic isolation signal. The valves covered by this LCO are listed with their associated stroke times in Ref. 1.

The normally closed manual PCIVs are considered OPERABLE when the valves are closed and blind flanges in place, or open under administrative controls. Normally closed automatic PCIVs, which are required by design (e.g., to meet 10 CFR 50 Appendix R requirements) to be de-activated and closed, are considered OPERABLE when the valve is closed and de-activated. These passive isolation valves and devices are those listed in Reference 1. Purge valves with resilient seals, secondary containment bypass valves, MSIVs, and hydrostatically tested valves must meet additional secondary leakage rate requirements. Other PCIV leakage rates are containment bypass dressed by LCO 3.6.1.1, "Primary Containment," as Type B leakage valves is sting.

This LCO p ides assurance that the PCIVs will perform DELETE their designed s ty functions to minimize the loss of reactor coolant inve ry and establish the primary containment boundary *n accidents. In addition, DELETE ensures leakage through tnefleA-t"bf:VS-ttsfelHR--+-Eteff~

--~i:;;...:i44 are within the limits assumed in the accident analysis.

APPLICABILITY In MO ES 1, 2, and 3, a OBA could cause a release of The secondary containment radi ctive material to primary containment. In MODES 4 bypass leakage paths an 5, the probability and consequences of these events are re uced due to the pressure and temperature limitations of leakage rate limits are t ese MODES. Therefore, most PCIVs are not required to be relocated to the TRM Table PERABLE and the primary containment purge valves are not 3.6.1.3-1 and are maintained required to be normally closed in MODES 4 and 5. Certain in accordance with the 10 valves are required to be OPERABLE, however, to prevent CFR 50 Appendix J Testing inadvertent reactor vessel draindown. These valves are Program Plan.

(continued)

NMP2 B 3.6.1.3-3 Revision 0

PC IVs B 3.6.1.3 BASES ACTIONS C.1 and C.2 (continued)

Condition C is modified by a Note indicating this Condition is applicable only to those penetration flow paths with only one PCIV. For penetration flow paths with two or more PCIVs, Conditions A and B provide the appropriate Required Actions. This Note is necessary since this Condition is written specifically to address those penetrations with a single PCIV.

Required Action C.2 is modified by two Notes. Note 1 applies to isolation devices located in high radiation areas and allows them to be verified by use of administrative means. Allowing verification by administrative means is considered acceptable, since access to these areas is typically restricted. Note 2 applies to isolation devices that are locked, sealed, or otherwise secured in position and allows these devices to be verified closed by use of administrative means. Allowing verification by administrative means is considered acceptable, since the function of locking, sealing, or securing components is to ensure that these devices are not inadvertently repositioned. Therefore, the probability of misalignment, once they have been verified to be in the proper position, is low.

The secondary containment bypass leakage paths leakage rate limits are relocated to the D.1, D.2, and D.3 TRM Table 3.6.1.3-1 and are ~

maintained in accordance with With the secondary containment bypass leakage rate th 10 CFR A d' J (SR 3.6.1.3.11 ), MSIV leakage rate (SR 3.6.1.3.12), or 50 e . ppen ix hydrostatically tested line leakage rate (SR 3.6.1.3.13) not Testing Program Plan. within limit, the assumptions of the safety analysis may not be met. Therefore, the leakage rate must be restored to within limit or the affected penetration flow path must be isolated within the Completion Times appropriate for each type of valve leakage: a) hydrostatically tested line leakage not on a closed system and secondary containment bypass leakage are required to be restored within 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br />; b) MSIV leakage is required to be restored within 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br />; and c) hydrostatically tested line leakage on a closed system is required to be restored within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br />. The method of isolation must include the use of at least one isolation barrier that cannot be adversely affected by a single active failure. Isolation barriers that meet this criterion are a closed and de-activated automatic valve, a closed manual valve, and a blind flange. Required (continued)

NMP2 B 3.6.1.3-8 Revision 0

PC IVs B 3.6.1.3 BASES SURVEILLANCE SR 3.6.1.3.10 REQUIREMENTS (continued) The TIP shear isolation valves are actuated by explosive charges. An in place functional test is not possible with this design. The explosive squib is removed and tested to provide assurance that the valves will actuate when required. The replacement charge for the explosive squib shall be from the same manufactured batch as the one fired or from another batch that has been certified by having one of the batch successfully fired, and shall be installed in accordance with the manufacturer's recommendations. Other administrative controls, such as those that limit the shelf life and operating life, as applicable, of the explosive

.-T-h_e_s_e-co_n_d_a_ry_c_o_nt-a-in_m_e_n_t---. charges, must be followed. The Surveillance Frequency is bypass leakage paths leakage controlled under the Surveillance Frequency Control Program.

rate limits are relocated to the in TRM Table 3.6.1 .3-1 individual TRM Table 3.6.1.3-1 and are SR 3.6.1.3.11 maintained in accordance with the 10 CFR 50 Appendix J This SR ensures that the leakage te of econdary Testing Program Plan. containment bypass leakage paths (with the exception of the MSIVs, which are tested per SR 3.6.1.3.12) is less than or

~----------~ equal to th *

  • leaka hile the MSIVs are als sifted as seco containmen ss leakage analyzed pathway valves y are evaluated according to SR 3.6.1 . , and if not within limits, actions are in the safety re
  • ed to be taken in accordance with ACTION D. This analysis provides assurance that the assumptions in the radiological (Appendix C of DELETE evaluations that form the basis of the USAA (Ref. 2) are met. The leakage rate of each bypass leakage path is Reference 8) assumed to be the maximum pathway leakage (leakage through the worse of the two isolation valves) unless the penetration is isolated by use of one closed and de-activated automatic valve, closed manual valve, or blind flange. In this case, the leakage rate of the isolated bypass leakage path is assumed to be the actual pathway leakage through the isolation device. If both isolation valves in the penetration are closed, the actual leakage rate is the lesser leakage rate of the two valves. The Frequency is required by the 10 CFR 50 Appendix J Testing Program Plan.

Bypass leakage is considered part of La.

(continued)

NMP2 B 3.6.1.3-18 Revision G, 44 (A 152)

PCIVs B 3.6.1.3 BASES SURVEILLANCE SR 3.6.1.3.12 REQUIREMENTS (continued) The analyses in Reference 1 are based on leakage that is less than the specified leakage rate. Leakage through each MSIV must bes 24 scfh when tested at 40 psig. This ensures that MSIV leakage is properly accounted for in determining the overall primary containment leakage rate. The Frequency is required by the 10 CFR 50 Appendix J Testing Program Plan.

MSIV leakage is considered part of La.

SR 3.6.1.3.13 Surveillance of hydrostatically tested lines provides assurance that the calculation assumptions of Reference 1 are met. The acceptance criteria for the combined leakage of all hydrostatically tested lines is 1 gpm times the total number of hydrostatically tested PCIVs when tested at

1.10 Pa (43.73 psig). The combined leakage rates must be demonstrated in accordance with the leakage test Frequency required by the 10 CFR 50 Appendix J Testing Program Plan.

REFERENCES 1. Technical Requirements Manual.

2. USAA, Section 15.6.5.
3. USAA, Section 15.6.4.
4. USAA, Section 15.2.4.
5. 10 CFR 50.36(c)(2)(ii).
6. USAA, Section 6.2.4.3.2.
7. 10 CFA 50, Appendix J Option B.
8. H21C-106, "Unit 2 LOCA w/LOOP AST Methodology."

NMP2 8 3.6.1.3-19 Revision 0, 3 (AQe), 44 (A 152)

INSERT r----..!;P:!:r~ im~a~C ~o~ntainment Isolation Valves

_ _ _ _ _, _ __ __ _ J TRM 3.6.1 TRM Table 3.6.1.3-1 (page 1 of 2)

Secondary Containment Bypass Leakage Paths Leakage Rate Limits VALVE NUMBER VALVE DESCRIPTION PER VALVE LEAK RATE (SCFH)

Main steam drain line 2MSS*MOV111 (inboard) 1.875 2MSS*MOV112 Main steam drain line 2MSS*MOV208 (outboard) 0.625 2CMS*SOV74A, B (d) 0.2344 2CMS*SOV75A, B (d) 4 Post-accident sampling 2CMS*SOV76A, B (d) lines 2CMS*SOV77A, B (d) 2DER*MOV119 Drywell equipment drain (a) 2DER*RV344 lines 2DER*MOV120 1.25 2DER*MOV130 Drywell equipment vent line 0.625 2DER*MOV131 2DFR*MOV120 1.875 Drywell floor drain line 2DFR*MOV121 (b) 2DFR*RV228 2DFR*MOV139 Drywell floor vent line 0.9375 2DFR*MOV140 2WCS*MOV102 RWCU line 2.5 2WCS*MOV112 2FWS*V23A, B Feedwater line 12.0 2FWS*V12A, B 2CPS*AOV104 CPS supply line to drywell 4.38 2CPS*AOV106 2CPS*AOV105 CPS supply line to supp. 3.75 2CPS*AOV107 chamber (continued)

(a) The combined leakage rate for these two valves shall be ::; 1.25 SCFH.

The combined leakage rate for these two valves shall be ::; 1.875 SCFH .

NMP2 TRM TRM Markup provided for information only.

INSERT rimary Containment Isolation Valves TRM 3.6.1 TRM Table 3.6.1 .3-1 (page 2 of 2)

Secondary Containment Bypass Leakage Paths Leakage Rate Limits VALVE NUMBER VALVE DESCRIPTION PER VALVE LEAK RATE SCFH) 2CPS*SOV119 CPS supply line to supp. chamber 0.625 2CPS*SOV120 2CPS*SOV121 2CPS*SOV122 Inst. air to ADS accumulators 21AS*SOV164 0.9375 21AS*V448 Inst. air to ADS accumulators 21AS*SOV165 0.9375 21AS*V449 N2 purge to TIP index mechanism 2GSN*SOV166 (c) 2GSN*V170 Inst. air to SRV accumulators 21AS*SOV166 (c) 21AS*SOV184 Inst. air to drywell 21AS*SOV167 (c) 21AS*SOV185 Inst. air to CPS valve in supp.

21AS*SOV168 chamber (c) 21AS*SOV180 Inst. air to CPS valve in supp. DELETE 2CPS*SOV132 chamber (c) 2CPS*V50 Inst. air to CPS valve in supp.

2CPS*SOV133 chamber 2CPS*V51 DELETE

================iDELETE (c) The combined leak rate for these penetrations shall be ~ 3.6 SCFH. The assigned leakage rate through a penetration shall be that of the valve with the highest leakage rate in that penetration. However, if a penetration is isolated by one closed and de-activated automatic valve, closed manual valve, or blind flange, the leakage through the penetration shall be the actual pathway leakage.

The LCO requirements and leakage rate limit shall apply until such time as a modification eliminates the potential secondary containment bypass leakage path.

TRM Markup provided for NMP2 TRM 3.6-23b information only.

Exelon Generation 200 Exelon Way Kennett Square. PA 19348 www exeloncorp.com 10 CFR 5090 NMP2L2616 March 21, 2016 U.S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington. DC 20555-0001 Nine Mile Point Nuclear Station, Unit 2 Renewed Facility Operating License No. NPF-69 NRG Docket No. 50-410

Subject:

Supplemental Response to Request for Additional Information by the Office of Nuclear Reactor Regulation to Support Review of Nine Mile Point Nuclear Station, Unit 2, Relocation of Secondary Containment Bypass Leakage Paths Table from Technical Specifications to the Technical Requirements Manual

References:

1. Letter from J. Barstow (Exelon Generation Company, LLC) to U.S.

Nuclear Regulatory Commission, "License Amendment Request -

Relocation of Secondary Containment Bypass Leakage Paths Table from Technical Specifications to the Technical Requirements Manual," dated March 23, 2015

2. Letter from B. Mozafari (Senior Project Manager, U.S. Nuclear Regulatory Commission) to Mr. Bryan Hanson (Exelon Generation Company, LLC),

"Nine Mile Point Nuclear Station, Unit 2-Request for Additional Information Regarding (CAC MF 5900)," dated December 17, 2015

3. Letter from D. Gudger (Exelon Generation Company, LLC) to U.S. Nuclear Regulatory Commission, "Response to Request for Additional Information by the Office of Nuclear Reactor Regulation to Support Review of Nine Mile Point Nuclear Station, Unit 2, Relocation of Secondary Containment Bypass Leakage Paths Table from Technical Specifications to the Technical Requirements Manual," dated January 8, 2016 By letter dated March 23, 2015 (Reference 1), Exelon Generation Company, LLC (Exelon) requested to change the Nine Mile Point Nuclear Station, Unit 2 (NMP2) Technical Specifications (TS). The proposed amendment request would modify NMP2 TS by relocating the secondary containment bypass leakage paths table from the TS to the Technical Requirements Manual.

U.S. Nuclear Regulatory Commission Supplemental Response to Request for Additional Information Relocation of Secondary Containment Bypass Leakage Paths Docket No. 50-41 O March 21, 2016 Page2 On December 8, 2015, the U.S. Nuclear Regulatory Commission (NRC) emailed a draft Request for Additional Information (RAI). On December 11, 2015, a clarification teleconference was held between NRC and Exelon personnel. The formal RAI (Reference 2) was provided on December 17, 2015.

On January 8, 2016, Exelon submitted to the NRC the RAI response (Reference 3).

Subsequent to this submittal, a second clarification teleconference was performed between the NRC and Exelon on March 1, 2016. to this letter contains the NRC's RAI immediately followed by Exelon's supplemental RAI response. This supplement replaces the RAI response provided on January 8, 2016 (Reference 3), and clarifies the original submittal (Reference 1) as requested during the clarification call on March 1, 2016.

Exelon. has reviewed the information supporting a finding of no significant hazards consideration and the environmental consideration provided to the NRC in Reference 1.

The additional information provided in this response does not affect the bases for concluding that the proposed license amendment does not involve a significant hazards consideration.

Furthermore, the additional information provided in this response does not affect the bases for concluding that neither an environmental impact statement nor an environmental assessment needs to be prepared in connection with the proposed amendment.

With the supplemental information provided in the attached response, Exelon requests approval of the proposed amendment by April 19, 2016. The requested approval date supports the implementation of the hardened containment vent modifications at NMP2 to comply with the schedule required by NRC Order EA-13-109, Order to Modify Licenses with Regard to Reliable Hardened Containment Vents Capable of Operation Under Severe Accident Conditions, dated June 6, 2013. Once approved, the amendment shall be implemented prior to restart from NMP2 2016 refueling outage.

There are no commitments contained in this response.

If you should have any questions regarding this submittal, please contact Ron Reynolds at 610-765-524 7.

I declare under penalty of perjury that the foregoing is true and correct. Executed on the 21 51 day of March 2016.

Respectfully, Jame~a:: ~

Director - Licensing & Regulatory Affairs Exelon Generation Company, LLC

U.S. Nuclear Regulatory Commission Supplemental Response to Request for Additional Information Relocation of Secondary Containment Bypass Leakage Paths Docket No. 50-41 O March 21, 2016 Page 3 : Supplemental Response to Request for Additional Information : Revised Technical Specification Pages and Bases Marked-Up Pages cc: USNRC Region I Regional Administrator w/attachments USN RC Senior Resident Inspector - NMP USNRC Project Manager, NRR - NMP A. L. Peterson, NYSERDA

ATTACHMENT 1 Nine Mile Point Nuclear Station, Unit 2 Relocation of Secondary Containment Bypass Leakage Paths Docket No. 50-41 O Supplemental Response to Request for Additional Information

Supplemental Response to Request for Additional Information Attachment 1 Relocation of Secondary Containment Bypass Leakage Paths Page 1 of 4 RAI STSB-1:

In the existing NMP2 TS, Table 3.6.1.3-1 specifies a numerical value for allowable leakage for each leakage path in standard cubic feet per hour. Surveillance Requirement (SR) 3.6.1.3.11 states:

Verify the leakage rate for the secondary containment bypass leakage paths is within the limits of Table 3.6.1.3-1 when pressurized to;::; 40 psig.

The proposed change is deletion of Table 3.6.1.3-1 and revision of SR 3.6.1.3.11 to state:

Verify the leakage rate for the secondary containment bypass leakage paths is within the limits when pressurized to ;::; 40 psig.

The staff requests additional information to explain why a numerical value limit on the secondary containment bypass leakage is not retained within the proposed SR 3.6.1.3.11 itself. Typically, the safety analysis for a facility assumes a specific amount of bypass leakage when calculating dose consequences. This leakage limit is reflected in the TS to ensure operation within the bounds of the safety analysis.

The regulation at 10 CFR 50.36(c)(3) requires TSs to include items in the category of surveillance requirements, which are requirements relating to test, calibration, or inspection to assure that the necessary quality of systems and components is maintained, that facility operation will be within safety limits, and that the Limiting Conditions for Operations will be met. The leakage limit for the pathways to be considered operable must be specified in the TS.

The staff compared the proposed revision of SR 3.6.1.3.11 with the guidance provided in Generic Letter 91-08. The Generic Letter recommended that the limitation on containment leakage rate be revised to state:

A combined leakage rate of less than or equal to [0.1 O La] for all penetrations that are secondary containment bypass leakage paths when pressurized to Pa.

This requirement has also been retained in the Standard TS.

Provide a technical justification for not retaining a numerical limit on allowable leakage on the secondary containment bypass pathways or propose a change to SR 3.6.1.3.11 to reflect the appropriate limit. If it is proposed to specify the leakage limit in terms of a combined leakage rate, please review LCO 3.6.1.3 Condition D and its associated Required Actions to ensure consistency with the proposed change to SR 3.6.1.3.11.

Exelon Supplemental Response to RAI STSB-1:

Based on a clarification call between the U.S. Nuclear Regulatory Commission (NRC) and Exelon conducted on March 1, 2016, the following supplemental information is provided to the license amendment request submitted on March 23, 2015 (Reference 1), and the above Request for Additional Information.

Supplemental Response to Request for Additional Information Attachment 1 Relocation of Secondary Containment Bypass Leakage Paths Page 2 of 4 In summary, the following changes are requested. Technical Specification (TS) Table 3.6.1.3-1 will be relocated from the TS to the Technical Requirements Manual {TRM) which is a licensee controlled document. Surveillance Requirement (SR) 3.6.1.3.11 will be revised to include three numerical values for the limiting secondary containment leakage rates based on the previously NRC approved Alternative Source Term (AST} licensing basis for Nine Mile Point Unit 2 (NMP2)

(References 2 and 3). Finally, as a result of a plant modification to address the hardened vent as specified in NRC Order EA-13-109 (Reference 4), a secondary containment bypass leakage path is eliminated from the current TS Table 3.6.1.3-1.

The hardened vent modification includes the replacement of Primary Containment Isolation Valve (PCIV) 2CPS* AOV109 and the relocation of this valve from inside primary containment to outside primary containment. Valves 2CPS*SOV133 and 2CPS*V51 provide motive air to the 2CPS*AOV109 air actuator. Therefore, since 2CPS*AOV109 will no longer be located inside primary containment, the motive air lines and valves inside containment will be removed in their entirety and the lines will be cut and isolated by a welded cap on both the inside and outside of primary containment penetration Z92.

Valves 2CPS*SOV133 and 2CPS*V51 are currently listed in TS Table 3.6.1.3-1. The TS Table specifies an allowable leakage value applicable to each valve in Standard Cubic Feet per Hour (SCFH). Removal of valves 2CPS*SOV133 and 2CPS*V51 from primary containment eliminates the secondary containment bypass leakage path such that the two valves can be deleted from TS Table 3.6.1.3-1. Removal of this secondary containment bypass leakage path is conservative with respect to dose consequences following a LOCA. Therefore, the LOCA dose consequence analysis was not modified as a result of this change.

The secondary containment bypass leakage paths and limits specified in the current TS Table 3.6.1.3-1 are direct inputs to the approved AST licensing basis for NMP2 for the Loss of Coolant Accident (LOCA) evaluation as submitted in License Amendment Request dated May 31, 2007 (Reference 2), and approved by Amendment 125 (Reference 3). As detailed in Exelon Design Analysis H21C-106 (Reference 5), these pathways release activity across four different release points; each release point having unique atmospheric dispersion coefficients. Additionally, each pathway has unique flow and fission product removal characteristics. As a result of these varying release pathway characteristics, the current approved LOCA AST licensing basis is not configured to transform the multiple leakage limits into a single numerical value. Based on the AST analysis methodology, the secondary containment bypass leakage pathways are divided into the following (4) groups: Main Steam Isolation Valves (open/closed), Bypass (Drywell),

Bypass (Suppression Chamber), and Bypass (Delayed from Drywell). SR 3.6.1 .3.12 requires verification of the leakage rate through each main steam isolation valve; therefore, the remaining three groups are identified as the secondary containment bypass leakage associated with SR 3.6.1.3.11.

The current approved AST LOCA analysis documents the procedure used to convert volumetric flow rate under test conditions to volumetric flow rate under accident conditions {page C3 of Reference 5). This procedure is employed to establish volumetric flow rates under test conditions for the three groups of secondary bypass leakage for the proposed TS SR 3.6.1.3.11 as detailed below.

A brief description of the three groups is as follows:

Supplemental Response to Request for Additional Information Attachment 1 Relocation of Secondary Containment Bypass Leakage Paths Page 3 of 4 a Bypass (Drywell): Includes all bypass pathways with no delays considered originating in the drywell except those listed below in the third group. This leakage group will have a combined effective leakage rate less than or equal to 8.74 SCFH. This value is calculated by dividing the combined actual flowrate of 3.394 CFH by 0.388.

b Bypass (Suppression Chamber): Includes all bypass pathways with no delays considered originating in the suppression chamber. This leakage group will have a combined effective leakage rate less than or equal to 1.67 SCFH. This value is calculated by dividing combined actual flowrate of 0.6483 CFH by 0.388.

c Bypass (Delayed from Drywell): Includes feedwater, 14" containment purge, and reactor water cleanup, delays are considered and conservatively combined. This leakage group will have a combined effective leakage rate less than or equal to 28.17 SCFH. This value is calculated by dividing combined actual flowrate of 10.93 CFH by 0.388.

It is noted that in the above description the combined effective leakage rate corresponds to the combined leakage rate weighted by the X/Q normalization factor as outlined in the AST analysis (page C6 of Reference 5). In addition, the AST analysis uses the term "Wetwell" which is synonymous with Suppression Chamber.

The proposed revision to SR 3.6.1.3.11 as shown in Attachment 2 reflects the limits of the three groups described above. The TS Table 3.6.1.3-1 will be relocated to the TRM as shown in . The elimination of valves 2CPS*SOV133 and 2CPS*V51 as a result of the hardened vent modification will be reflected in the new TRM table. Changes to the TRM are licensee controlled and subject to the provisions of 10 CFR 50.59.

TS Limiting Condition for Operation 3.6.1.3, Condition D, and its associated Required Actions, were reviewed and no changes are necessary as a result of this proposed change. However, changes to the applicable TS Bases section is provided in Attachment 2.

The marked up TS pages and marked up TS Bases pages provided with this supplemental response supersedes the previously submitted marked up pages provided in the license amendment request dated March 23, 2015, and the RAI response submittal dated January 8, 2016, in their entirety.

References:

1. Letter from J. Barstow (Exelon Generation Company, LLC) to U.S. Nuclear Regulatory Commission, "License Amendment Request - Relocation of Secondary Containment Bypass Leakage Paths Table from Technical Specifications to the Technical Requirements Manual," dated March 23, 2015
2. Letter from K. Nietmann (Nine Mile Point Nuclear Station) to Document Control Desk (U.S. NRC), "License Amendment Request Pursuant to 10 CFR 50.90: Application of Alternate Source Term," dated May 31, 2007 (ML071580314)

Supplemental Response to Request for Additional Information Attachment 1 Relocation of Secondary Containment Bypass Leakage Paths Page 4 of 4

3. Letter from R. Guzman (Senior Project Manager, U.S. Nuclear Regulatory Commission) to K. Polson (Nine Mile Point Nuclear Station), "Nine Mile Point Nuclear Station, Unit 2-lssuance of Amendment RE: Implementation of Alternative Radiological Source Term (TAC NO. MD5758)," dated May 29, 2008 (ML081230439)
4. NRG Order EA-13-109, "Issuance of Order to Modify Licenses with Regard to Reliable Hardened Containment Vents Capable of Operation Under Severe Accident Conditions,"

dated June 6, 2013

5. H21C-106, "Unit 2 LOCA w/LOOP AST Methodology," dated May 31, 2007

[Attachment 7 to Reference 2, ML071580354]

ATTACHMENT 2 Nine Mile Point Nuclear Station, Unit 2 Relocation of Secondary Containment Bypass Leakage Paths Docket No. 50-41 O PROPOSED TECHNICAL SPECIFICATION and BASES MARKED-UP PAGES TS Pages 3.6.1.3-1, -12, -14 and -15 Bases Pages B3.6.1.3-1 through -3, -8, -18 and -19 TAM Pages 3.6-23a and -23b

PC IVs Secondary Containment Bypass 3.6.1 .3 Leakage Valve 3.6 CONTAINMENT SYSTEMS DELETE 3.6.1.3 Primary Containment Isolation Vi Ives (PCIVs)

LCO 3.6.1.3 Each PCIV and each AOA PGl\/ listed iA Teele 3.S.1.3 1 shall be OPERABLE.

APPLICABILITY: MODES 1, 2, and 3, When associated instrumentation is required to be OPERABLE per LCO 3.3.6.1, "Primary Containment Isolation Instrumentation."

ACTIONS


N0 TES-----------------------------------------------------------

1. Penetration flow paths may be unisolated intermittently under administrative controls.
2. Separate Condition entry is allowed for each penetration flow path.
3. Enter applicable Conditions and Required Actions for systems made inoperable by PCIVs.
4. Enter applicable Conditions and Required Actions of LCO 3.6.1 .1, "Primary Containment," when PCIV leakage results in exceeding overall containment leakage rate acceptance criteria.

CONDITION REQUIRED ACTION COMPLETION TIME A. -------------NOTE-------------- A.1 Isolate the affected 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> except Only applicable to penetration flow path for main steam penetration flow paths by use of at least line with two or more one closed and PC IVs. de-activated AND


automatic valve, closed manual valve, 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> for main One or more blind flange, or steam line penetration flow paths check valve with flow with one PCIV through the valve inoperable except due secured.

to leakage not within limit. AND (continued)

NMP2 3.6.1.3-1 Amendment 91

PC IVs 3.6.1.3 SURVEILLANCE REQUIREMENTS (continued)

SURVEILLANCE FREQUENCY SR 3.6.1.3.6 Perform leakage rate testing for each 184 days primary containment purge valve with resilient seals. AND Once within 92 days after opening the valve SR 3.6.1.3.7 Verify the isolation time of each MSIV is In accordance

~ 3 seconds and s 5 seconds. with the lnservice Testing Program SR 3.6.1.3.8 Verify each automatic PCIV actuates to 24 months the isolation position on an actual or simulated isolation signal.

SR 3.6.1.3.9 Verify a representative sample of reactor 24 months instrumentation line EFCVs actuates to the isolation position on an actual or simulated instrument line break signal.

SR 3.6.1.3.10 Remove and test the explosive squib from 24 months on a each shear isolation valve of the TIP STAGGERED TEST System. j lDELETE I BASIS SR 3.6.1.3.11 \/-

'..t:,, it..._

'J ** ,_

I ./

_i .t:

In accordance seeeRElary seRtaiRFReRt ey13ass leaka~e with 10 CFR 50 13aths is within the limite ef Teiele- Appendix J d.e. ~ .d ~ when 13Fesst1Fii!:ea te ~ 4G Testing Program

~ Plan

~

I Verify the leakage rate for the secondary containment bypass (continued) leakage when pressurized to ;::40 psig is:

a . Bypass (Drywell) : s 8.74 SCFH; and

b. Bypass (Suppression Chamber):~ 1.67 SCFH; and c . Bypass (Drywell with delays) : ~ 28.17 SCFH NMP2 3.6.1.3-12 Amendment 94-, 96

PC IVs DELETE 3.6.1.3 Table 3.6.1.3-1 (page 1 of 2)

Secondary Containment Bypass Leakage Paths Leakage Rate Limits VALVE NUMBER PER VALVE LEAK RA TE SCFH 2MSS*MOV111 1.875 2MSS*MOV112 2MSS*MOV208 0.625 2CMS*SOV74A, B (d) 0.2344 2CMS*SOV75A, B (d) 2CMS*SOV76A, B (d) 2CMS*SOV77A, B (d) 2DER*MOV119 (a) 2DER*RV344 2DER*MOV120 1.25 2DER*MOV130 0.625 2DER*MOV131 2DFR*MOV120 1.875 2DFR*MOV121 (b) 2DFR*RV228 2DFR*MOV139 0.9375 2DFR*MOV140 2WCS*MOV102 2.5 2WCS*MOV112 2FWS*V23A, B 12.0 2FWS*V12A, B 2CPS*AOV104 4.38 2CPS*AOV106 2CPS*AOV105 3.75 2CPS*AOV107 (a) The combined leakage rate for these two valves shall be ~ 1.25 SCFH.

b The combined leaka e rate for these two valves shall be ~ 1.875 SCFH.

The information from this Technical Specification section has been relocated to the TRM and maintained in accordance with the 10 CFR 50 Appendix J Testing Program Plan.

NMP2 3.6.1.3-14 Amendment Bi, .:tM, 106

DELETE

--~

Table 3.6.1.3-1 (page 2 of 2)

Secondary Containment Bypass Leakage Paths Leakage Rate Limits VALVE NUMBER PER VALVE LEAK RATE SCFH 2CPS*SOV119 0.625 2CPS*SOV120 2CPS*SOV121 2CPS*SOV122 21AS*SOV164 0.9375 21AS*V448 21AS*SOV165 0.9375 21AS*V449 2GSN*SOV166 (c) 2GSN*V170 21AS*SOV166 (c) 21AS*SOV184 21AS*SOV167 (c) 21AS*SOV185 21AS*SOV168 (c) 21AS*SOV180 2CPS*SOV132 (c) 2CPS*V50 2CPS*SOV133 (c) 2CPS*V51 The combined leak rate for these penetrations shall be ~ 3.6 SCFH. The assigned leakage rate through a penetration shall be that of the valve with the highest leakage rate in that penetration. However, if a penetration is isolated by one closed and de-activated automatic valve, closed manual valve, or blind flange , the leakage through the penetration shall be the actual pathway leakage.

(d) The LCO requirements and leakage rate limit shall apply until such time as a modification eliminates the potential secondary containment bypass leakage path .

...._____ IThe information from this Technical Specification section has been relocated to the TRM and maintained in accordance with the 10 CFR 50 Appendix J Testing Program Plan .

NMP2 3.6.1.3-15 Amendment 94, 106

PC IVs B 3.6.1.3 B 3.6 CONTAINMENT SYSTEMS secondary containment bypass leakage valves B 3.6.1.3 Primary Containment Isolation Valves (PCIVs)

DELETE BASES BACKGROUND The function of the PC IVs and the non PG IVs listed in J able 3.6.1.3 1 (2GMS*SOV74A, 748, 75A, 758, 76A, 768, 77A, and 778), in combination with other accident mitigation systems, is to limit fission product release during and following postulated Design Basis Accidents (DBAs) to within DELETE limits. Primary containment isolation within the time limits specified for those PC IVs designed to close automatically ensures that the release of radioactive material to the environment will be consistent with the assumptions used in the analyses for a OBA.

The OPERABILITY requirements for PCIVs help ensure that an adequate primary containment boundary is maintained during and after an accident by minimizing potential paths to the environment. Therefore, the OPERABILITY requirements provide assurance that the primary containment function assumed in the safety analysis will be maintained. These isolation devices consist of either passive devices or active (automatic) devices. Manual valves, de-activated automatic valves secured in their closed position (including check valves with flow through the valve secured}, blind flanges (which include plugs and caps as listed in Reference 1), and closed systems are considered passive devices. Check valves, or other automatic valves designed to close without operator action following an accident, are considered active devices. Two barriers in series are provided for each penetration, except for penetrations isolated by excess flow check valves, so that no single credible failure or malfunction of an active component can result in a loss of isolation or leakage that exceeds limits assumed in the safety analysis. One of these barriers may be a closed system.

The 12 and 14 inch primary containment purge valves are PCIVs that are qualified for use during all operational conditions. The 12 and 14 inch primary containment purge valves are normally maintained closed in MODES 1, 2, and 3 to ensure the primary containment boundary is maintained.

However, the purge valves may be open when being used for pressure control, inerting, de-inerting, ALARA, or air quality considerations since they are fully qualified.

(continued)

NMP2 B 3.6.1.3-1 Revision 0

PC IVs B 3.6.1.3 BASES BACKGROUND A two inch bypass line is provided when the primary (continued) containment full flow line to the Standby Gas Treatment (SGT) System is isolated.

APPLICABLE The PCIVs LCO was derived from the assumptions related SAFETY ANALYSES to minimizing the loss of reactor coolant inventory, and establishing the primary containment boundary during major accidents. As part of the primary containment boundary, secondary containment PCI AOA PGIVs listed iA Table 3.6.1 .3 1 OPERABILITY supports leak tightness of primary containmen . refore, ~-------.

bypass leakage valves the safety analysis of any event requiring isolation of DELETE primary containment is applicable to this LCO.

The DBAs that result in a release of radioactive material for which the consequences are mitigated by PCIVs are a loss of coolant accident (LOCA) and a main steam line break secondary (MSLB) (Refs. 2 and 3) . In the analysis for each of these containment bypass accidents, it is assumed that PCIVs are either closed or leakage valves nction to close within the required isolation time fo wing event initiation. This ensures that potential pat to the environment through PCIVs (including primary contar ment purge valves) are minimized. Of the events DELETE analyze in References 2 and 3, the LOCA is the mos The secondary containment limiting e nt due to radiological consequences.

bypass leakage paths addition, tli non PGIVs listed iA Table 3.6.1.3 1 are also leakage rate limits are assumed to be closed during the LOCA. The closure time of relocated to the Technical the main steam isolation valves (MSIVs) is a significant Requirements Manual variable from a radiological standpoint. The MSIVs are (TRM) Table 3.6.1.3-1 and required to close within 3 to 5 seconds since the 3 second are maintained in re time is assumed in the MSIV closure (the most severe overpr urization transient) analysis (Ref. 4) and 5 second accordance with the 10 closure tim

  • assumed in the MSLB analysis (Ref. 3).

CFR 50 Appendix J Testing Likewise, it is a med that the primary containment Program Plan. isolates such that re se of fission products to the environment is controlle .

The OBA analysis assumes that isolation of the primary containment is complete and leakage terminated, except for the maximum allowable leakage, La. prior to fuel damage.

The single failure criterion required to be imposed in the conduct of unit safety analyses was considered in the original design of the primary containment purge valves.

Two valves in series on each purge line provide assurance that both the supply and exhaust lines could be isolated even if a single failure occurred .

(continued)

NMP2 B 3.6.1.3-2 Revision 0

PC IVs B 3.6.1.3 BASES APPLICABLE PCIVs satisfy Criterion 3 of Reference 5.

SAFETY ANALYSES (continued)

LCO PCIVs form a part of the primary containment boundary. The PCIV safety function is related to minimizing the loss of reactor coolant inventory and establishing the primary containment boundary during a OBA.

The power operated, automatic isolation valves are required to have isolation times within limits and actuate on an automatic isolation signal. The valves covered by this LCO are listed with their associated stroke times in Ref. 1.

The normally closed manual PCIVs are considered OPERABLE when the valves are closed and blind flanges in place, or open under administrative controls. Normally closed automatic PCIVs, which are required by design (e.g., to meet 10 CFR 50 Appendix R requirements) to be de-activated and closed, are considered OPERABLE when the valve is closed and de-activated. These passive isolation valves and devices are those listed in Reference 1. Purge valves with resilient seals, secondary containment bypass valves, MSIVs, and hydrostatically tested valves must meet additional secondary leakage rate requirements. Other PCIV leakage rates are containment bypass dressed by LCO 3.6.1.1, "Primary Containment," as Type B leakage valves is sting.

This LCO p ides assurance that the PCIVs will perform DELETE their designed s ty functions to minimize the loss of reactor coolant inve ry and establish the primary containment boundary *n accidents. In addition, DELETE ensures leakage through tnefleA-t"bf:VS-ttsfelHR--+-Eteff~

--~i:;;...:i44 are within the limits assumed in the accident analysis.

APPLICABILITY In MO ES 1, 2, and 3, a OBA could cause a release of The secondary containment radi ctive material to primary containment. In MODES 4 bypass leakage paths an 5, the probability and consequences of these events are re uced due to the pressure and temperature limitations of leakage rate limits are t ese MODES. Therefore, most PCIVs are not required to be relocated to the TRM Table PERABLE and the primary containment purge valves are not 3.6.1.3-1 and are maintained required to be normally closed in MODES 4 and 5. Certain in accordance with the 10 valves are required to be OPERABLE, however, to prevent CFR 50 Appendix J Testing inadvertent reactor vessel draindown. These valves are Program Plan.

(continued)

NMP2 B 3.6.1.3-3 Revision 0

PC IVs B 3.6.1.3 BASES ACTIONS C.1 and C.2 (continued)

Condition C is modified by a Note indicating this Condition is applicable only to those penetration flow paths with only one PCIV. For penetration flow paths with two or more PCIVs, Conditions A and B provide the appropriate Required Actions. This Note is necessary since this Condition is written specifically to address those penetrations with a single PCIV.

Required Action C.2 is modified by two Notes. Note 1 applies to isolation devices located in high radiation areas and allows them to be verified by use of administrative means. Allowing verification by administrative means is considered acceptable, since access to these areas is typically restricted. Note 2 applies to isolation devices that are locked, sealed, or otherwise secured in position and allows these devices to be verified closed by use of administrative means. Allowing verification by administrative means is considered acceptable, since the function of locking, sealing, or securing components is to ensure that these devices are not inadvertently repositioned. Therefore, the probability of misalignment, once they have been verified to be in the proper position, is low.

The secondary containment bypass leakage paths leakage rate limits are relocated to the D.1, D.2, and D.3 TRM Table 3.6.1.3-1 and are ~

maintained in accordance with With the secondary containment bypass leakage rate th 10 CFR A d' J (SR 3.6.1.3.11 ), MSIV leakage rate (SR 3.6.1.3.12), or 50 e . ppen ix hydrostatically tested line leakage rate (SR 3.6.1.3.13) not Testing Program Plan. within limit, the assumptions of the safety analysis may not be met. Therefore, the leakage rate must be restored to within limit or the affected penetration flow path must be isolated within the Completion Times appropriate for each type of valve leakage: a) hydrostatically tested line leakage not on a closed system and secondary containment bypass leakage are required to be restored within 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br />; b) MSIV leakage is required to be restored within 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br />; and c) hydrostatically tested line leakage on a closed system is required to be restored within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br />. The method of isolation must include the use of at least one isolation barrier that cannot be adversely affected by a single active failure. Isolation barriers that meet this criterion are a closed and de-activated automatic valve, a closed manual valve, and a blind flange. Required (continued)

NMP2 B 3.6.1.3-8 Revision 0

PC IVs B 3.6.1.3 BASES SURVEILLANCE SR 3.6.1.3.10 REQUIREMENTS (continued) The TIP shear isolation valves are actuated by explosive charges. An in place functional test is not possible with this design. The explosive squib is removed and tested to provide assurance that the valves will actuate when required. The replacement charge for the explosive squib shall be from the same manufactured batch as the one fired or from another batch that has been certified by having one of the batch successfully fired, and shall be installed in accordance with the manufacturer's recommendations. Other administrative controls, such as those that limit the shelf life and operating life, as applicable, of the explosive

.-T-h_e_s_e-co_n_d_a_ry_c_o_nt-a-in_m_e_n_t---. charges, must be followed. The Surveillance Frequency is bypass leakage paths leakage controlled under the Surveillance Frequency Control Program.

rate limits are relocated to the in TRM Table 3.6.1 .3-1 individual TRM Table 3.6.1.3-1 and are SR 3.6.1.3.11 maintained in accordance with the 10 CFR 50 Appendix J This SR ensures that the leakage te of econdary Testing Program Plan. containment bypass leakage paths (with the exception of the MSIVs, which are tested per SR 3.6.1.3.12) is less than or

~----------~ equal to th *

  • leaka hile the MSIVs are als sifted as seco containmen ss leakage analyzed pathway valves y are evaluated according to SR 3.6.1 . , and if not within limits, actions are in the safety re
  • ed to be taken in accordance with ACTION D. This analysis provides assurance that the assumptions in the radiological (Appendix C of DELETE evaluations that form the basis of the USAA (Ref. 2) are met. The leakage rate of each bypass leakage path is Reference 8) assumed to be the maximum pathway leakage (leakage through the worse of the two isolation valves) unless the penetration is isolated by use of one closed and de-activated automatic valve, closed manual valve, or blind flange. In this case, the leakage rate of the isolated bypass leakage path is assumed to be the actual pathway leakage through the isolation device. If both isolation valves in the penetration are closed, the actual leakage rate is the lesser leakage rate of the two valves. The Frequency is required by the 10 CFR 50 Appendix J Testing Program Plan.

Bypass leakage is considered part of La.

(continued)

NMP2 B 3.6.1.3-18 Revision G, 44 (A 152)

PCIVs B 3.6.1.3 BASES SURVEILLANCE SR 3.6.1.3.12 REQUIREMENTS (continued) The analyses in Reference 1 are based on leakage that is less than the specified leakage rate. Leakage through each MSIV must bes 24 scfh when tested at 40 psig. This ensures that MSIV leakage is properly accounted for in determining the overall primary containment leakage rate. The Frequency is required by the 10 CFR 50 Appendix J Testing Program Plan.

MSIV leakage is considered part of La.

SR 3.6.1.3.13 Surveillance of hydrostatically tested lines provides assurance that the calculation assumptions of Reference 1 are met. The acceptance criteria for the combined leakage of all hydrostatically tested lines is 1 gpm times the total number of hydrostatically tested PCIVs when tested at

1.10 Pa (43.73 psig). The combined leakage rates must be demonstrated in accordance with the leakage test Frequency required by the 10 CFR 50 Appendix J Testing Program Plan.

REFERENCES 1. Technical Requirements Manual.

2. USAA, Section 15.6.5.
3. USAA, Section 15.6.4.
4. USAA, Section 15.2.4.
5. 10 CFR 50.36(c)(2)(ii).
6. USAA, Section 6.2.4.3.2.
7. 10 CFA 50, Appendix J Option B.
8. H21C-106, "Unit 2 LOCA w/LOOP AST Methodology."

NMP2 8 3.6.1.3-19 Revision 0, 3 (AQe), 44 (A 152)

INSERT r----..!;P:!:r~ im~a~C ~o~ntainment Isolation Valves

_ _ _ _ _, _ __ __ _ J TRM 3.6.1 TRM Table 3.6.1.3-1 (page 1 of 2)

Secondary Containment Bypass Leakage Paths Leakage Rate Limits VALVE NUMBER VALVE DESCRIPTION PER VALVE LEAK RATE (SCFH)

Main steam drain line 2MSS*MOV111 (inboard) 1.875 2MSS*MOV112 Main steam drain line 2MSS*MOV208 (outboard) 0.625 2CMS*SOV74A, B (d) 0.2344 2CMS*SOV75A, B (d) 4 Post-accident sampling 2CMS*SOV76A, B (d) lines 2CMS*SOV77A, B (d) 2DER*MOV119 Drywell equipment drain (a) 2DER*RV344 lines 2DER*MOV120 1.25 2DER*MOV130 Drywell equipment vent line 0.625 2DER*MOV131 2DFR*MOV120 1.875 Drywell floor drain line 2DFR*MOV121 (b) 2DFR*RV228 2DFR*MOV139 Drywell floor vent line 0.9375 2DFR*MOV140 2WCS*MOV102 RWCU line 2.5 2WCS*MOV112 2FWS*V23A, B Feedwater line 12.0 2FWS*V12A, B 2CPS*AOV104 CPS supply line to drywell 4.38 2CPS*AOV106 2CPS*AOV105 CPS supply line to supp. 3.75 2CPS*AOV107 chamber (continued)

(a) The combined leakage rate for these two valves shall be ::; 1.25 SCFH.

The combined leakage rate for these two valves shall be ::; 1.875 SCFH .

NMP2 TRM TRM Markup provided for information only.

INSERT rimary Containment Isolation Valves TRM 3.6.1 TRM Table 3.6.1 .3-1 (page 2 of 2)

Secondary Containment Bypass Leakage Paths Leakage Rate Limits VALVE NUMBER VALVE DESCRIPTION PER VALVE LEAK RATE SCFH) 2CPS*SOV119 CPS supply line to supp. chamber 0.625 2CPS*SOV120 2CPS*SOV121 2CPS*SOV122 Inst. air to ADS accumulators 21AS*SOV164 0.9375 21AS*V448 Inst. air to ADS accumulators 21AS*SOV165 0.9375 21AS*V449 N2 purge to TIP index mechanism 2GSN*SOV166 (c) 2GSN*V170 Inst. air to SRV accumulators 21AS*SOV166 (c) 21AS*SOV184 Inst. air to drywell 21AS*SOV167 (c) 21AS*SOV185 Inst. air to CPS valve in supp.

21AS*SOV168 chamber (c) 21AS*SOV180 Inst. air to CPS valve in supp. DELETE 2CPS*SOV132 chamber (c) 2CPS*V50 Inst. air to CPS valve in supp.

2CPS*SOV133 chamber 2CPS*V51 DELETE

================iDELETE (c) The combined leak rate for these penetrations shall be ~ 3.6 SCFH. The assigned leakage rate through a penetration shall be that of the valve with the highest leakage rate in that penetration. However, if a penetration is isolated by one closed and de-activated automatic valve, closed manual valve, or blind flange, the leakage through the penetration shall be the actual pathway leakage.

The LCO requirements and leakage rate limit shall apply until such time as a modification eliminates the potential secondary containment bypass leakage path.

TRM Markup provided for NMP2 TRM 3.6-23b information only.