ML15355A242
ML15355A242 | |
Person / Time | |
---|---|
Site: | Beaver Valley |
Issue date: | 11/30/2015 |
From: | Peter Presby Operations Branch I |
To: | FirstEnergy Nuclear Operating Co |
Shared Package | |
ML15161A011 | List: |
References | |
U01906 | |
Download: ML15355A242 (32) | |
Text
FENOC FirstEnergy Nuclear Operating Company 4t BEAVER VALLEY POWER STATION TRAINING SECTION September 8, 2015 Mr. Peter Presby USNRC Chief Examiner USNRC Region 1 2100 Renaissance Blvd, Suite 100 King of Prussia, PA 19406-2713 Beaver Valley Training Center Examination Outlines NPD3DOT:3714
Dear Mr. Presby,
Enclosed for your review and approval are the outlines for the Beaver Valley Unit 2 Initial Licensed Operator Examination scheduled to begin December 7, 2015. These outlines are submitted in accordance with NUREG 1021, Operator Licensing Examination Standards for Power Reactors (Revision 10).
The following materials are enclosed:
- Form ES-201-2, Examination Outline Quality Checklist- (Signed)
- Form ES-201-3, Examination Security Agreement (Copy)
- Form ES-301-1, Administrative Topics Outline SRO- Rev. 0
- Form ES-301-2, Control Room/In-Plant Systems Outline RO- Rev. 0
- Form ES-301-2, Control Room/In-Plant Systems Outline SRO-I - Rev. O
- Form ES-301-4, Simulator Scenario Quality Checklist - Rev. 0 (Unsigned)
- Form ES-301-6, Competencies Checklist- Rev. 0
Form ES-401-3, Generic Knowledge and Abilities Outline Tier 3- RO- Rev. 0 (1 page)
Form ES-401-3, Generic Knowledge and Abilities Outline Tier 3- SRO-Rev. 0 (1 page)
- Form ES-401-4, Record of Rejected K/As- Rev. 0
- Form ES-D-1, Scenario Outline - Rev. 0 (4 - All New)
Page 1of2
USN RC Page 2of2 September 4, 2015 The unsigned Form ES-301-4, Simulator Scenario Quality Checklist, is being sent to support Form ES-201-2, Examination Outline Quality Checklist. A signed version of this form will be sent with the exam materials.
The Westinghouse developed PWROG Random Generator software was used to generate both the RO and SRO written examination outlines. This software follows the selection process described in ES-401, Attachment 1, Example Systematic Sampling Methodology and the KIA Elimination Guidance provided in ES-401. Replacement K/As were manually selected utilizing this same guidance. Rejected K/As were documented on Form ES-401-4, Record of Rejected K/As.
The expected additions to the Exam Security Agreement are additional Operations Validation Team members.
We request these materials be withheld from public disclosure until after the completion of the exam. If you have any questions, please feel free to contact Tom Gaydosik at 724-682-1884.
Sincerely, Daniel J. Ronnenberg Superintendent, Nuclear Operations Training Cb~~
David W. Held Unit 2 Shift Manager - Facility Reviewer cc: OPS Letter File Nuclear Records - Site TG for LY - exam outlines - 16 TG/LY
ES-401 PWR Examination Outline Form ES-401-2 Facility: BVPS UNIT 2 RO Date of Exam 12/7 thru 12/18/2015 RO KIA Category Points Tier Group K K K K K K A A A A G TOTAL 1 2 3 4 5 6 1 2 3 4
- 1 3 3 3 3 18 1.
Emergency 2
& 2 1 2 2 9 Abnormal Plant Tier Evolutions Totals 5 4 5 5 27 1
2.
2 2 3 3 3 2 2 3 2 3 3 28 Plant Systems 2 1 1 1 1 1 1 1 0 1 1 1 10 Tier Totals 3 3 4 4 4 3 3 3 3 4 4 38 1 2 3 4 10
- 3. Generic Knowledge and Abilities Category 2 3 2 3 Note:
- 1. Ensure that at least two topics from every applicable KIA category are sampled within each tier of the RO and SRO-only outlines (i.e., except for one category in Tier 3 of the SRO-only outline, the "Tier Totals" in each KIA category shall not be less than two).
(One Tier 3 Radiation Control KIA is allowed if the KIA is replaced by a KIA from another Tier 3 Category).
- 2. The point total for each group and tier in the proposed outline must match that specified in the table. The final point total for each group and tier may deviate by +/-1 from that specified in the table based on NRC revisions. The final RO exam must total 75 points and the SRO-only exam must total 25 points.
- 3. Systems/evolutions within each group are identified on the associated outline; systems or evolutions that do not apply at the facility should be deleted with justification; operationally important, site-specific systems/evolutions that are not included on the outline should be added. Refer to Section D.1.b of ES-401 for guidance regarding the elimination of inappropriate KIA statements.
- 4. Select topics from as many systems and evolutions as possible; sample every system or evolution in the group before selecting a second topic for any system or evolution.
- 5. Absent a plant-specific priority, only those KIAs having an importance rating (IR) of 2.5 or higher shall be selected. Use the RO and SRO ratings for the RO and SRO-only portions, respectively.
- 6. Select SRO topics for Tiers 1 and 2 from the shaded systems and KIA categories.
- 7. The generic (G) KlAs in Tiers 1 and 2 shall be selected from Section 2 of the KIA Catalog, but the topics must be relevant to the applicable evolution or system. Refer to Section D.1.b of ES-401 for the applicable KIAs.
- 8. On the following pages, enter the KIA numbers, a brief description of each topic, the topics' importance ratings (I Rs) for the applicable license level, and the point totals (#)for each system and category. Enter the group and tier totals for each category in the table above; if fuel handling equipment is sampled in a category other than Category A2 or G* on the SRO-only exam, enter it on the left side of Column A2 for Tier 2, Group 2 (Note #1 does not apply). Use duplicate pages for RO and SRO-only exams.
- 9. For Tier 3, select topics from Section 2 of the KIA catalog, and enter the KIA numbers, descriptions, IRs, and point totals(#) on Form ES-401-3. Limit SRO selections to KIAs that are linked to 10 CFR 55.43.
G* Generic KIAs NUREG-1021, Revision 10 RO Page 1 of 13 FENOC Facsimile Rev. 0
ES-401 PWR Examination Outline Form ES-401-2 Emergency and Abnormal Plant Evolutions -Tier 1/Group 1(RO)
E/APE #I Name I Safety Function K K K A *A G KIA Topic(s) IR #
... 1 2 3 1 .2 000007 Reactor Trip I 1 : .
)( .:* .. : EK2 Knowledge of the interrelations between a 3.5 1
- I '1** reactor trip and the following:
[Question 1]
EK2.03 Reactor trip status panel i
(CFR 41.7 I 45.7) h*r: ,.....
000008 Pressurizer (PZR) Vapor Space ) AK1 Knowledge of the operational implications of 3.2 1 Accident (Relief Valve Stuck Open) I 3 the following concepts as they apply to a
- .: Pressurizer Vapor Space Accident:
[Question 2]
AK1 .01 Thermodynamics and flow characteristics of open or leaking Valves (CFR 41.8 I 41.10 I 45.3) 000015/000017 Reactor Coolant Pump (RCP) Malfunctions I 4 x AK2 Knowledge of the interrelations between the Reactor Coolant Pump Malfunctions (Loss of RC 2.9 1 Flow) and the following:
[Question 3] AK2.07 RCP seals
.. (CFR 41.7 / 45.7) 000022 Loss of Reactor Coolant Makeup I )(
1~ AK1 Knowledge of the operational implications of 3.0 1 2 the following concepts as they apply to Loss of Reactor Coolant Makeup:
[Question 4] AK1 .03 Relationship between charging flow and PZR level (CFR 41.8 / 41.10 I 45.3)
CJ,, .~25 Loss of Residual Heat Removal )( ;
AA2 Ability to determine and interpret the following 3.3* 1 System (RHRS) / 4 as they apply to the Loss of Residual Heat Removal System:
I::*
[Question 5] h* .. 1. ~; AA2.04 Location and isolability of leaks l*.:1 d
(CFR: 43.5 / 45.13)
Ii " *.
000026 Loss of Component Cooling Water )( :
AK3 Knowledge of the reasons for the following 4.0 1 (CCW) / 8 responses as they apply to the Loss of Component Cooling Water:
[Question 6] AK3.03 Guidance actions contained in EOP for Loss of CCW (CFR 41.5,41.10 I 45.6 I 45.13) 000027 Pressurizer Pressure Control )( 2.1.28 Knowledge of the purpose and function of 4.1 1 System (PZR PCS) Malfunction I 3 major system components and controls.
I*.
(CFR: 41. 7)1
[Question 7]
000029 Anticipated Transient Without ) :*:'\.I*. EK2 Knowledge of the interrelations between the 2.9* 1 Scram (ATWS) I 1 and the following an ATWS:
EK2.06 Breakers, relays, and disconnects
[Question 8]
(CFR 41.7 / 45.7)
NUREG-1021, Revision 10 RO Page 2 of 13 FENOC Facsimile Rev. 0
ES-401 PWR Examination Outline Form ES-401-2 Emergency and Abnormal Plant Evolutions -Tier 1/Group 1(RO) Continued
= >
,\,
1 i~~ ~~~
E/APE #I Name I Safety Function K K K A KIA Topic(s) IR #
1 2 3
',:< :'.*"j 000038 Steam Generator Tube Rupture )( EK3 Knowledge of the reasons for the following 3.6* 1 1';
(SGTR) / 3 responses as the apply to the SGTR:
. EK3.03 Automatic actions associated with high
[Question 9] .. :*
radioactivity in SIG sample lines (CFR 41.5 / 41.10 / 45.6 / 45.13) 000054 Loss of Main Feedwater (MFW) / 4 .) >>:: AA2 Ability to determine and interpret the following 4.1 1 as they apply to the Loss of Main Feedwater (MFW):
[Question 1O] 1*: ,* .*
1; ... ,.. ;~.,,. AA2.02 Differentiation between loss of all MFW and
,"... trip of one MFW pump
.* ~ 11),i (CFR: 43.5 / 45.13)
.:~ 2.4.18 Knowledge of the specific bases for EOPs.
000055 Loss of Offsite and Onsite Power ':;*: 3.3 1 (Station Blackout) / 6 (CFR: 41.10 / 43.1/45.13)
[Question 11] '
000056 Loss of Offsite Power I 6 )( AK1 Knowledge of the operational implications of 3.7 1 1.~ the following concepts as they apply to Loss of Offsite Power:
[Question 12]
AK1 .01 Principle of cooling by natural convection (CFR 41.8 / 41.10 / 45.3)
-( 57 Loss of Vital AC Electrical ) :1,: AA2 Ability to determine and interpret the following 3.7 1 ln'Su ument Bus / 6 ::*: .
as they apply to the Loss of Vital AC Instrument
') 1:,;,9 Bus:
[Question 13] ' '
AA2.03 RPS panel alarm annunciators and trip indicators (CFR: 43.5 / 45.13) 000062 Loss of Nuclear Service Water I 4 x :,,
AK3. Knowledge of the reasons for the following responses as they apply to the Loss of Nuclear 3.5 1
[Question 14] Service Water:
AK3.04 Effect on the nuclear service water discharge flow header of a loss of CCW I',:; :'c'
1;,:l ;' (CFR 41.4, 41.8 / 45.7) 2.4.4 Ability to recognize abnormal indications for
- ~~
000065 Loss of Instrument Air/ 8 . *. 4.5 1 system operating parameters that are entry-level conditions for emergency and abnormal operating
[Question 15] procedures.
(CFR: 41.10 I 43.2 I 45.6)
.' AA 1 Ability to operate and/or monitor the following 000077 Generator Voltage and Electric Grid )(I 4.1 1 Disturbances / 6 as they apply to Generator Voltage and Electric Grid Disturbances:
[O* 1?.stion 16] AA 1.04 Reactor controls (CFR: 41.5 and 41.10 / 45.5, 45.7, and 45.8)
NUREG-1021, Revision 10 RO Page 3of13 FENOC Facsimile Rev. 0
ES-401 PWR Examination Outline Form ES-401-2 Emergency and Abnormal Plant Evolutions -Tier 1/Group 1(RO) Continued
- =-
E/APE #I Name I Safety Function K K K A,A G KIA Topic(s) IR #
1 2 3 1 2,, f>J' ,'
W/E11 Loss of Emergency Coolant J: LJ,:,' EA 1 Ability to operate and I or monitor the following 3.7 1
~
Recirculation I 4 as they apply to the (Loss of Emergency Coolant
,i , Recirculation)
[Question 17] I ,,i~ , , EA 1.3 Desired operating results during abnormal
',' ,,, ,, and emergency situations
~~f
"; , ,,~ ,,, (CFR: 41. 7 I 45.5 I 45.6)
)( I,,, EA 1 Ability to operate and I or monitor the following iff: +,f,~
W/E12 Uncontrolled Depressurization of all 3.6 1 Steam Generators 14 I as they apply to the (Uncontrolled Depressurization
,," /;~ of all Steam Generators)
[Question 18] EA 1.2 Operating behavior characteristics of the facility.
(CFR: 41. 7 I 45.5 I 45.6) 3 3 3 3 3 3 KIA Category Point Totals: Group Point Total: 18 NUREG-1021, Revision 10 RO Page 4of13 FENOC Facsimile Rev. 0
ES-401 PWR Examination Outline Form ES-401-2 Emergency and Abnormal Plant Evolutions - Tier 1/Group 2(RO)
E/APE #I Name I Safety Function K K K A .A. G KIA Topic(s) IR #
1 2 3 1 .2 .
==000033 Loss of Intermediate Range )( I** AK1 Knowledge of the operational implications of the 2.7 1 1.*.*.
Nuclear Instrumentation I 7 1*.* I!*' following concepts as they apply to Loss of I*
. Intermediate Range Nuclear Instrumentation:
[Question 19] AK1 .01 Effects of voltage changes on performance I* l:J:!!
1 ** ;
(CFR 41.8 I 41.10 I 45.3) 000059 Accidental Liquid Radwaste )
.... AA2 Ability to determine and interpret the following 2.9 1 as they apply to the Accidental Liquid Radwaste Release /9
. .. Release:
(Question 20] AA2.02 The permit for liquid radioactive-waste release (CFR: 43.5 I 45.13) 000067 Plant fire on site I 9 ) AK3 Knowledge of the reasons for the following 3.3 1 responses as they apply to the Plant Fire on Site:
(Question 21] I *. AK3.04 Actions contained in EOP for plant fire on site I***
1**..*! 1.*:. (CFR 41.5,41.10 I 45.6 I 45.13) 000068 Control Room Evacuation I 8 *.... AK2 Knowledge of the interrelations between the
) vI .* 3.7 1 Control Room Evacuation and the following:
[Question 22]
AK2.02 Reactor trip system (CFR 41.7 I 45.7) 000069 Loss of Containment Integrity I 5 ) AK3 Knowledge of the reasons for the following 3.8* 1 responses as they apply to the Loss of Containment (Question 23] Integrity:
"!. 1* .!*
.... AK3.01 Guidance contained in EOP for loss of containment integrity (CFR 41.5,41.10 I 45.6 I 45.13)
W/E02 SI Termination I 3
)( 2.4.21 Knowledge of the parameters and logic used 4.0 1 to assess the status of safety functions, such as
[Question 24] .* reactivity control, core cooling and heat removal, reactor coolant system integrity, containment conditions, radioactivity release control, etc.
.. I * (CFR: 41.7 I 43.5 I 45.12)
W/E03 LOCA Cooldown and )( EK1 Knowledge of the operational implications of the 3.6 1 Depressurization I 4 1*
.! following concepts as they apply to the (LOCA Cooldown and Depressurization)
[Question 25] *.
EK1 .2 Normal, abnormal and emergency operating procedures associated with (LOCA Cooldown and Depressurization).
(CFR: 41.8 I 41.10 I 45.3)
NUREG-1021, Revision 10 RO Page 5of13 FENOC Facsimile Rev. 0
ES-401 PWR Examination Outline Form ES-401-2 Emergency and Abnormal Plant Evolutions -Tier 1/Group 2(RO) Continued E/APE #I Name I Safety Function K K K A A G KIA Topic(s) IR #
1 2 3 1 ;.z, ',,;'
0<1;\
W/E07 Saturated Core Cooling I 4 EA 1 Ability to operate and I or monitor the following
}( .* IJ.{ as they apply to the (Saturated Core Cooling) 3.6 1 Ii
[Question 26]
I* .,. ' ..
EA 1.1 Components, and functions of control and safety systems, including instrumentation, signals, interlocks, failure modes, and automatic and manual I* ...
features.
I*
(CFR: 41. 7 I 45.5 I 45.6)
W/E13 Steam Generator Overpressure I 4 *~ 2.1.23 Ability to perform specific system and 4.3 1 integrated plant procedures during all modes of plant
[Question 27] operation.
(CFR: 41.10 I 43.5 I 45.2 I 45.6)
I .* ..
2 1 2 1 1 2 KIA Category Point Totals: Group Point Total: 9 NUREG-1021, Revision 10 RO Page 6of13 FENOC Facsimile Rev. 0
ES-401 PWR Examination Outline Form ES-401-2 Plant Systems - Tier 2/Group 1(RO)
System # I Name K K K K K K A A A A ,B~.. *. KIA Topic(s) IR #
- . 1 2 3 4 5 6 1 12 3 4 i:{*11. 1.
003 Reactor Coolant Pump K2 Knowledge of bus power supplies to the
~ '. 3.1 1 System (RCPS) following:
[Question 28] 11i:i:
I**. ' :1 K2.01 RCPS 11, (CFR: 41.7) 004 Chemical and Volume **
Control System x le ,. K5 Knowledge of the operational implications of the following concepts as they apply to the 2.5 1
[Question 29]
I' eves:
I':
1.>1.ii' K5.14 Reduction process of gas concentration in RCS: vent accumulated non-condensable
[i~;~;
l1;1 . , gases from PZR bubble space, depressurized during cooldown or by alternately heating and l;'c* cooling (spray) within allowed pressure band I*
I\~~~ (drive more gas out of solution)
(CFR: 41.5/45.7)
I 005 Residual Heat Removal ) .. K2 Knowledge of bus power supplies to the 2.7* 1 System (RHRS)
I.I
,11 following:
[Question 30] K2.03 RCS pressure boundary motor-operated valves (CFR: 41.7) 006 Emergency Core Cooling A3 Ability to monitor automatic operation of the
) 3.6* 1 System (ECCS) 1. :':
ECCS, including:
[0* --stion 31] l<<\/1 A3.07 RHR pumps I' ;1 (CFR: 41.7 / 45.5) 006 Emergency Core Cooling ) K4 Knowledge of ECCS design feature(s) 1;:1 2.6 1 System (ECCS) I* and/or interlock(s) which provide for the
[Question 32] following:
K4.01 Cooling of centrifugal pump bearings (CFR: 41.7) 007 Pressurizer Relief i,1 K4 Knowledge of PRTS design feature(s)
Tank/Quench Tank System
~ 2.6 1 and/or interlock(s) which provide for the (PRTS) following:
[Question 33]
K4.01 Quench tank cooling
\.,,.1. . (CFR: 41.7) 008 Component Cooling Water lj 2.2.38 Knowledge of conditions and limitations 3.6 1 System (CCWS) in the facility license.
[Question 34]
(CFR: 41.7 / 41.10 / 43.1/45.13) 008 Component Cooling Water ~ K3 Knowledge of the effect that a loss or 4.1 1 System (CCWS) malfunction of the CCWS will have
[Question 35] on the following:
I K3.03 RCP 010 Pressurizer Pressure ) A3 Ability to monitor automatic operation of the
stion 36] ;.:i;j: A3.02 PZR pressure 1**,. (CFR: 41.7 / 45.5)
NUREG-1021, Revision 10 RO Page 7of13 FENOC Facsimile Rev. 0
ES-401 PWR Examination Outline Form ES-401-2 Plant Systems - Tier 2/Group 1(RO) Continued A A A 11~;~
System # I Name K K K K K K A KIA Topic(s) IR #
1 2 3 4 5 6 1 *2 3 4
- .':' :y:.: K6 Knowledge of the effect of a loss or 012 Reactor Protection System ~ 2.9 1 (RPS) malfunction of the following will have on the RPS:
[Question 37]
K6.02 Redundant channels
. (CFR: 41. 7 I 45/7) 013 Engineered Safety Features Actuation System (ESFAS)
}( 'fJ. t KS Knowledge of the operational implications of the following concepts as they apply to the 2.9 1
- *'. .. ESFAS:
[Question 38]
- K5.02 Safety system logic and reliability
).1:;
...... (CFR: 41.5 / 45.7) 022 Containment Cooling }( A2 Ability to (a) predict the impacts of the 2.9* 1 System (CCS) following malfunctions or operations on the CCS; and (b) based on those predictions, use
[Question 39] procedures to correct, control, or mitigate the consequences of those malfunctions or
. operations:
A2.04 Loss of service water
!*l*I::**: (CFR: 41.5 / 43.5 / 45.3 / 45.13)
. A4 Ability to manually operate and/or monitor 1~*~~
022 Containment Cooling }( 3.8 1 System (CCS) in the control room:
[Question 40] i'Jf. A4.05 Containment readings of temperature, pressure, and humidity system.
l:io:
(CFR: 41. 7 I 45.5 to 45.8) 026 Containment Spray System }(
1: A 1 Ability to predict and/or monitor changes in 3.9 1 (CSS) parameters (to prevent exceeding design
[Question 41] limits) associated with operating the CSS controls including:
. A 1.01 Containment pressure
- (CFR
- 41.5 I 45.5) 026 Containment Spray System **~ 2.2.12 Knowledge of surveillance procedures. 3.7 1 (CSS)
. (CFR: 41.10 / 45.13)
[Question 42]
039 Main and Reheat Steam }( K3 Knowledge of the effect that a loss or 3.2* 1 System (MRSS) malfunction of the MRSS will have on the
[Question 43] following:
K3.03 AFW pumps.
(CFR: 41.7 / 45.6) 039 Main and Reheat Steam )( 2.4.1 Knowledge of EOP entry conditions and 4.6 1 System (MRSS) immediate action steps.
[Question 44] (CFR: 41.10 I 43.5 / 45.13)
NUREG-1021, Revision 10 RO Page 8of13 FENOC Facsimile Rev. 0
ES-401 PWR Examination Outline Form ES-401-2 Plant Systems - Tier 2/Group 1(RO) Continued System # I Name K K K K K K A A A A G KIA Topic(s) IR #
1 2 3 4 5 6 1 2 3 4 ..
System 1*
x .1*;. :
A4 Ability to manually operate and monitor in the control room:
3.1* 1
[Question 45) .
A4.01 MFW turbine trip indication 1*: '*\ ** (CFR: 41. 7 I 45.5 to 45.8) 059 Main Feedwater (MFW) *.}(
iH~i?
A2 Ability to (a) predict the impacts of the 3.4* 1 System following malfunctions or operations on the
[~!~*
+'
[Question 46) MFW; and (b) based on those predictions, use procedures to correct, control, or mitigate the
- . consequences of those malfunctions or
.. , operations:
A2.01 Feedwater actuation of AFW system
' (CFR: 41.5 I 43.5 I 45.3 I 45.13) 061 Auxiliary I Emergency x . ..* K5 Knowledge of the operational implications 3.2 1 Feedwater (AFW) System I.* ..
of the following concepts
.... as the apply to the AFW:
[Question 4 7)
K5.02 Decay heat sources and magnitude
.* (CFR: 41.5 I 45.7) 1*=*
062 AC Electrical Distribution A2 Ability to (a) predict the impacts of the D~ 1.;*.*.* 2.7 1 System following malfunctions or operations on the ac
,. distribution system; and (b) based on those
[Question 48) predictions, use procedures to correct, control,
- or mitigate the consequences of those malfunctions or operations:
A2.08 Consequences of exceeding voltage limitations i* : *' (CFR: 41.5 I 43.5 I 45.3 I 45.13)
- /*':'
063 DC Electrical Distribution }( K1 Knowledge of the physical connections 2.7 1 System 2 and/or cause effect relationships between the DC electrical system and the following
[Question 49] 1,,.. ):rj~. systems:
K1 .02 AC electrical system (CFR: 41.2 to 41.9 I 45.7 to 45.8) 064 Emergency Diesel }( K6 Knowledge of the effect of a loss or 2.7 1 Generator (ED/G) System malfunction of the following will have on the
[Question 50] ED/G system:
K6.07 Air receivers
- .; (CFR: 41.7 I 45.7) 073 Process Radiation }( ;:*,*. K3 Knowledge of the effect that a loss or 3.6 1 Monitoring (PRM) System * .... malfunction of the PRM system will have on
[Question 51) . ' the following:
K3.01 Radioactive effluent releases hf (CFR: 41.7 I 45.6)
NUREG-1021, Revision 10 RO Page 9of13 FENOC Facsimile Rev. 0
ES-401 PWR Examination Outline Form ES-401-2 Plant Systems - Tier 2/Group 1(RO) Continued
'11 ,,,'
System # I Name K K K K K K A AA A ,
G KIA Topic(s) IR #
1 2 3 4 5 6 1 '12' 3 4 'I '/'
,I 076 Service Water System )( 1' A 1 Ability to predict and/or monitor changes in 2.6* 1 (SWS) parameters (to prevent exceeding design I~ limits) associated with operating the SWS
[Question 52] ',,
controls including:
,1 1:1i11 A 1.02 Reactor and turbine building closed
', cooling water temperatures.
,,,,,, (CFR: 41.5 / 45.5) 078 Instrument Air System (IAS) )< K1 Knowledge of the physical connections 3,3* 1
[Question 53] and/or cause-effect relationships between the IAS and the following systems:
, 1',
K1 .03 Containment air (CFR: 41.2 to 41.9 / 45.7 to 45.8) 103 Containment System )< 11/'I, K4 Knowledge of containment system design 3.0* 1
~I,'
[Question 54] 1;'.,/c feature(s) and/or interlock(s) which provide for
- ,, the following
I> ,
'i{',"
,'1 K4.01 Vacuum breaker protection (CFR: 41.7) 103 Containment System I,*~,',,, A4 Ability to manually operate and/or monitor
)( ,1, 3.1* 1
[Question 55] in the control room:
cl A4.09 Containment vacuum system (CFR: 41. 7 I 45.5 to 45.8)
=,
2 2 3 3 3 2 2 3 2 3 3 KIA Category Point Totals: Group Point Total: 28 NUREG-1021, Revision 10 RO Page 10of13 FENOC Facsimile Rev. 0
ES-401 PWR Examination Outline Form ES-401-2 Plant Systems - Tier 2/Group 2(RO)
System # I Name K K K K K K A A A A ':.;G KIA Topic(s) 1 2 3 4 5 6 1 1~2 3 4 IR
'1 ',
001 Control Rod Drive System ***i.~1,:* A 1 Ability to predict and/or monitor changes in
}( 3.7 1
[Question 56] l::K parameters (to prevent exceeding design limits) associated with operating the CRDS controls
- . including:
I
- 1; i A 1.04 PZR level and pressures (CFR
- 41.5 / 45.5) 1:
002 Reactor Coolant System }( A3 Ability to monitor automatic operation of the 4.4 1 (RCS) * .... RCS, including:
[Question 57] I 11~,
A3.03 Pressure, temperatures, and flows 1~:
1:1 (CFR: 41. 7 I 45.5) 011 Pressurizer Level Control }( . K6 Knowledge of the effect of a loss or 3.1 1 System (PZR LCS) ,. malfunction on the following will have on the
[Question 58] PZR LCS:
K6.05 Function of PZR level gauges as post
.11 accident monitors
.. (CFR: 41.7 / 45.7) 028 Hydrogen Recombiner and }( K5 Knowledge of the operational implications of 3.4 1 Purge Control System (HRPS) the following concepts as they apply to the
[Question 59] . HRPS:
"111* : .. K5.01 Explosive hydrogen concentration 1*." . (CFR: 41.5 / 45. 7)
(' ~ontainment Purge System K3 Knowledge of the effect that a loss or
}( 2.9 1
(- ,) malfunction of the Containment Purge System
[Question 60] will have on the following:
+~ K3.01 Containment parameters (CFR: 41. 7 I 45.6) 034 Fuel Handling Equipment }( K1 Knowledge of the physical connections 2.6 1 System (FHES) and/or cause effect relationships between the
[Question 61] Fuel Handling System and the following systems:
K1.04 NIS (CFR: 41.2 to 41.9 / 45. 7 to 45.8) x ti
~1 035 Steam Generator System K4 Knowledge of S/GS design feature(s) and/or 2.9 1 (S/GS) .,.: interlock(s) which provide for the following:
~;
[Question 62]
K4.05 Amount of reserve water in SIG 11 ;1~ (CFR:41.7) ii, 045 Main Turbine Generator }( A4 Ability to manually operate and/or monitor in 3.1 1 (MT/G) System the control room:
[Question 63]
A4.01 Turbine valve indicators (throttle, governor, control, stop, intercept), alarms, and annunciators 1* .*. (CFR: 41.7 / 45.5 to 45.8)
NUREG-1021, Revision 10 RO Page 11 of 13 FENOC Facsimile Rev. 0
ES-401 PWR Examination Outline Form ES-401-2 Plant Systems - Tier 2/Group 2(RO) Continued System # I Name K K K K K K A A A A G KIA Topic(s)
IR #
1 2 3 4 5 6 1 2 3 4 .*
072 Area Radiation Monitoring ) 2.4.46 Ability to verify that the alarms are 4.2 1 (ARM) System consistent with the plant conditions.
[Question 64] (CFR: 41.10 I 43.5 I 45.3 I 45.12) 075 Circulating Water System }( K2 Knowledge of bus power supplies to the 2.6* 1
[Question 65] following:
- . *~
K2.03 Emergency/essential SWS pumps (CFR: 41.7)
KIA Category Point Totals: 1 1 1 1 1 1 1 0 1 1 1 Group Point Total: 10 NUREG-1021, Revision 10 RO Page 12of13 FENOC Facsimile Rev. 0
ES 401 Generic Knowledge and Abilities Outline (Tier 3) Form ES-401-3 r'adlity: BVPS UNIT 2 RO Date of Exam 12/7 thru 12/18/2015 RO Category KIA# Topic IR #
- 1. 2.1.29 Knowledge of how to conduct system lineups, such as valves, breakers, 4.1 Conduct switches, etc.
of Operations (CFR: 41.10 I 45.1 I 45.12)
[Question 66]
2.1.45 Ability to identify and interpret diverse indications to validate the 4.3 response of another indication.
(CFR: 41.7 I 43.5 I 45.4)
[Question 67]
Subtotal
- 2. 2.2.6 Knowledge of the process for making changes to procedures.
Equipment (CFR: 41.10 I 43.3 I 45.13)
Control [Question 68]
2.2.15 Ability to determine the expected plant configuration using design and 3.9 configuration control documentation, such as drawings, line-ups, tag-outs, etc.
(CFR: 41.10 I 43.3 I 45.13)
[Question 69]
2.2.39 Knowledge of less than or equal to one hour Technical Specification 3.9 action statements for systems.
(CFR: 41.7 I 41.10 I 43.2 I 45.13)
Question 70 Subtotal
- 3. 2.3.7 Ability to comply with radiation work permit requirements during normal Radiation or abnormal conditions.
Control (CFR: 41.12 I 45.10)
[Question 71]
2.3.13 Knowledge of radiological safety procedures pertaining to licensed 3.4 operator duties, such as response to radiation monitor alarms, containment entry requirements, fuel handling responsibilities, access to locked high-radiation areas, aligning filters, etc.
(CFR: 41.12 I 43.4 I 45.9 I 45.10)
[Question 72]
Subtotal
- 4. 2.4.6 Knowledge of EOP mitigation strategies.
Emergency (CFR: 41.10 I 43.5 I 45.13)
Procedures/ [Question 73]
Plan 2.4.25 Knowledge of fire protection procedures. 3.3 (CFR: 41.10 I 43.5 I 45.13)
[Question 74]
2.4.39 Knowledge of RO responsibilities in emergency plan implementation. 3 _9 (CFR: 41.10/45.11)
Question 75 Subtotal Tier 3 Point Total NUREG-1021, Revision 10 RO Page 13of13 FENOC Facsimile Rev. 0
ES-401 PWR Examination Outline Form ES-401-2 Facility: BVPS UNIT 2 SRO Date of Exam 12/7 thru 12/18/2015 SRO ONLY Points Tier Group A2 G* TOTAL 1
3 3 6 1.
Emergency 2
& 2 2 4 Abnormal Plant Tier Totals 5 5 10 Evolutions 1
- 2. 3 2 5 Plant Systems 2 0 2 1 3 Tier Totals 5 3 8 1 2 3 4 7
- 3. Generic Knowledge and Abilities Category 2 1 2 2 Note:
- 1. Ensure that at least two topics from every applicable KIA category are sampled within each tier of the RO and SRO-only outlines (i.e., except for one category in Tier 3 of the SRO-only outline, the "Tier Totals" in each KIA category shall not be less than two).
(One Tier 3 Radiation Control KIA is allowed if the KIA is replaced by a KIA from another Tier 3 Category).
- 2. The point total for each group and tier in the proposed outline must match that specified in the table. The final point total for each group and tier may deviate by +/-1 from that specified in the table based on NRC revisions. The final RO exam must total 75 points and the SRO-only exam must total 25 points.
- 3. Systems/evolutions within each group are identified on the associated outline; systems or evolutions that do not apply at the facility should be deleted with justification; operationally important, site-specific systems/evolutions that are not included on the outline should be added. Refer to Section D.1.b of ES-401 for guidance regarding the elimination of inappropriate KIA statements.
- 4. Select topics from as many systems and evolutions as possible; sample every system or evolution in the group before selecting a second topic for any system or evolution.
- 5. Absent a plant-specific priority, only those KIAs having an importance rating (JR) of 2.5 or higher shall be selected. Use the RO and SRO ratings for the RO and SRO-only portions, respectively.
- 6. Select SRO topics for Tiers 1 and 2 from the shaded systems and KIA categories.
- 7. The generic (G) KIAs in Tiers 1 and 2 shall be selected from Section 2 of the KIA Catalog, but the topics must be relevant to the applicable evolution or system. Refer to Section D.1.b of ES-401 for the applicable KIAs.
- 8. On the following pages, enter the KIA numbers, a brief description of each topic, the topics' importance ratings (!Rs) for the applicable license level, and the point totals (#)for each system and category. Enter the group and tier totals for each category in the table above; if fuel handling equipment is sampled in a category other than Category A2 or G* on the SRO-only exam, enter it on the left side of Column A2 for Tier 2, Group 2 (Note #1 does not apply). Use duplicate pages for RO and SRO-only exams.
- 9. For Tier 3, select topics from Section 2 of the KIA catalog, and enter the KIA numbers, descriptions, IRs, and point totals(#) on Form ES-401-3. Limit SRO selections to KIAs that are linked to 10 CFR 55.43.
G* Generic KIAs NUREG-1021, Revision 10 SRO Page 1 of 6 FENOC Facsimile Rev. 0
ES-401 PWR Examination Outline Form ES-401-2 Emergency and Abnormal Plant Evolutions -Tier 1/Group 1(SRO)
E/APE #I Name I Safety Function K K K A A G KIA Topic(s) IR #
1 2 3 1 2 000009 Small Break LOCA I 3 ) EA2 Ability to determine or interpret the following as 3.9 1
[Question 76] they apply to a small break LOCA:
EA2.05 The time available for action before PZR is empty, given the rate of decrease of PZR level (CFR 43.5 / 45.13) 000011 Large Break LOCA I 3 2.4.41 Knowledge of the emergency action level 4.6 1
)~
[Question 77] thresholds and classifications.
(CFR: 41.10 / 43.5 / 45.11) 000040 Steam Line Rupture I 4 M2 Ability to determine and interpret the following 4.5 1
.*~
[Question 78] as they apply to the Steam Line Rupture:
M2.05 When ESFAS systems may be secured (CFR: 43.5 / 45.13) 000058 Loss of DC Power I 6 2.2.25 Knowledge of the bases in Technical 4.2 1
- !,J< Specifications for limiting conditions for operations
[Question 79]
and safety limits.
(CFR: 41.5 / 41.7 / 43.2)
\. 4 LOCA Outside Containment I 3 )< 2.4.11 Knowledge of abnormal condition procedures. 4.2 1
[Question 80] (CFR: 41.10 / 43.5 / 45.13)
W/E05 Loss of Secondary Heat Sink I 4 ) EA2 Ability to determine and interpret the following 4.4 1
[Question 81] as they apply to the (Loss of Secondary Heat Sink)
EA2.1 Facility conditions and selection of appropriate procedures during abnormal and emergency operations.
(CFR: 43.5 I 45.13) 3 3 6 KIA Category Point Totals: Group Point Total:
NUREG-1021, Revision 10 SRO Page 2 of 6 FENOC Facsimile Rev. 0
ES-401 PWR Examination Outline Form ES-401-2 Emergency and Abnormal Plant Evolutions - Tier 1/Group 2(SRO)
, ~r E/APE #I Name I Safety Function K K K A A G KIA Topic(s) IR #
,, 1 2 3 1 2 "
000003 Dropped Control Rod / 1 l( 2.2.36 Ability to analyze the effect of maintenance h'~
,',"" 4.2 1 activities, such as degraded power sources, on the
~~<
[Question 82]
status of limiting conditions for operations.
(CFR: 41.10 / 43.2 / 45.13) 000024 Emergency Boration I 1
"~~ 2.1.23 Ability to perform specific system and 4.4 1
[Question 83] integrated plant procedures during all modes of plant operation.
(CFR: 41.10 I 43.5 I 45.2 I 45.6)
W/E06 Degraded Core Cooling I 4 EA2 Ability to determine and interpret the following
"~ as they apply to the (Degraded Core Cooling) 4.2 1
[Question 84]
EA2.1 Facility conditions and selection of appropriate procedures during abnormal and emergency operations.
(CFR: 43.5 / 45.13)
W/E09 Natural Circulation Operations I 4 EA2 Ability to determine and interpret the following
'~ 3.8 1 as they apply to the (Natural Circulation Operations)
[Question 85]
EA2.2 Adherence to appropriate procedures and
',' ,": operation within the limitations in the facility*s license and amendments.
(CFR: 43.5 I 45.13)
KIA Category Point Totals: 0 0 0 0 2 2 Group Point Total: 4 NUREG-1021, Revision 10 SRO Page 3 of 6 FENOC Facsimile Rev. 0
ES-401 PWR Examination Outline Form ES-401-2 Plant Systems - Tier 2/Group 1(SRO)
System # I Name K 1
K 2
K 3
K 4
K K A 5 6 1 A A 2 3 A
4
,/~ KIA Topic(s) IR #
===--
003 Reactor Coolant Pump "~i:.; A2 Ability to (a) predict the impacts of the I )(
3.9 1 System (RCPS) "* following malfunctions or operations on the 1- *l"'.~{ RCPS; and (b) based on those predictions,
[Question 86]
use procedures to correct, control, or mitigate
' ;?'~- the consequences of those malfunctions or operations:
A2.02 Conditions which exist for an abnormal shutdown of an RCP in comparison to a normal shutdown of an RCP (CFR: 41.5 / 43.5/ 45.3 / 45/13)
.. ..1 004 Chemical and Volume l~t~?: A2 Ability to (a) predict the impacts of the Control System
.)c following malfunctions or operations on the 3.3 1
[Question 87] eves; and (b) based on those predictions, use procedures to correct, control, or mitigate the consequences of those malfunctions or operations:
A2.33 Fact that isolating cation demineralizer
- stops boron dilution and enables restoration of r
normal boron concentration (CFR: 41.5/ 43/5 I 4513 I 45/5) 013 Engineered Safety Features
- p. 1tion System (ESFAS) )( 2.4.1 Knowledge of EOP entry conditions and 4.8 1 Ii immediate action steps.
[to. ~stion 88] (CFR: 41.10 I 43.5 I 45.13)
.* ~,[,
11 076 Service Water System )( A2 Ability to (a) predict the impacts of the 3.1 1 (SWS) 1::. following malfunctions or operations on the SWS; and (b) based on those predictions, use
[Question 89]
procedures to correct, control, or mitigate the consequences of those malfunctions or operations:
A2.02 Service water header pressure (CFR: 41.5 I 43.5 I 4513 I 45/13) u~-'.:
2.4.34 Knowledge of RO tasks performed
'~~
078 Instrument Air System (IAS) 4.1 1
[Question 90] outside the main control room during an emergency and the resultant operational I;-; effects.
(CFR: 41.10 I 43.5 I 45.13) 3 2 5
KIA Category Point Totals: Group Point Total:
NUREG-1021, Revision 10 SRO Page 4 of 6 FENOC Facsimile Rev. 0
ES-401 PWR Examination Outline Form ES-401-2 Plant Systems - Tier 2/Group 2(SRO)
- A,
~~~
System # I Name K K K K K K A A A KIA Topic(s) 1 2 3 4 5 6 1 *2 3 4 IR #
- >11 033 Spent Fuel Pool Cooling .* A2 Ability to (a) predict the impacts of the System (SFPCS)
)( following malfunctions or operations on the 3.5 1
[Question 91] Spent Fuel Pool Cooling System ; and (b)
" based on those predictions, use procedures to
- 1 correct, control, or mitigate the consequences of those malfunctions or operations:
. '*" A2.01 Inadequate SDM 1:1~~
(CFR: 41.5 I 43.5 I 45.31 45.13) 041 Steam Dump System 2.4.50 Ability to verify system alarm setpoints (SDS)/Turbine Bypass Control '~ and operate controls identified in the !alarm 4.0 1
.,, response manual.
[Question 92] 111
- . (CFR: 41.10 I 43.5 I 45.3) 079 Station Air System (SAS) .)( A2 Ability to (a) predict the impacts of the following malfunctions or operations on the 3.2 1
[Question 93]
,.. SAS; and (b) based on those predictions, use
.* procedures to correct, control, or mitigate the
" consequences of those malfunctions or
} operations:
,11 A2.01 Cross-connection with IAS I '.1 *' (CFR: 41.5 / 43.5 I 45.31 45.13) 11 '
=
l<-t... ..;ategory Point Totals: 2 1 Group Point Total: 3 NUREG-1021, Revision 10 SRO Page 5 of 6 FENOC Facsimile Rev. 0
ES 401 Generic Knowledge and Abilities Outline (Tier 3) Form ES-401-3 Facility: BVPS UNIT 2 SRO Date of Exam 12/7 thru 12/18/2015 SRO Only Category Kl A# Topic IR #
- 1. 2.1.4 Knowledge of individual licensed operator responsibilities related to shift 3.8 Conduct staffing, such as medical requirements, "no-solo" operation, maintenance of Operations of active license status, 10CFR55, etc.
(CFR: 41.10 / 43.2)
[Question 94]
2.1.36 Knowledge of procedures and limitations involved in core alterations. 4.1 (CFR: 41.10 / 43.6 / 45.7)
[Question 95]
Subtotal 2
- 2. 2.2.42 Ability to recognize system parameters that are entry-level conditions for Equipment Technical Specifications.
Control (CFR: 41. 7 I 41.10 I 43.2 I 43.3 I 45.3)
[Question 96]
Subtotal 1
- 3. 2 .3 .4 Knowledge of radiation exposure limits under normal or emergency Radiation conditions.
Control (CFR: 41.12 I 43.4 I 45.10)
[Question 97]
2.3.11 Ability to control radiation releases. 4.3 (CFR: 41.11 I 43.4 / 45.10)
[Question 98]
Subtotal 2
- 4. 2.4.29 Knowledge of the emergency plan.
Emergency (CFR: 41.10 / 43.5 / 45.11)
Procedures/
[Question 99]
Plan 2.4.44 Knowledge of emergency plan protective action recommendations. 4.4 (CFR: 41.10 / 41.12 / 43.5 / 45.11)
[Question 100]
Subtotal 2 Tier 3 Point Total 7 NUREG-1021, Revision 10 SRO Page 6 of 6 FENOC Facsimile Rev. 0
ES-401 Record of Rejected K/As Form ES-401-4 Facility: BVPS Unit 2 Date of Exam 12/7 thru 12/18/2015 Operating Test No.: BV2LOT15 NRC Tier I Randomly Reason for Rejection Group Selected KIA 1/1 000025 Question #5; Beaver Valley does not use Residual Heat Removal AA2.05 (RHRS) for Low Pressure Injection (LPI). Randomly selected 025 AA2.04 as a replacement.
1/1 057 AA2.11 Question #13: There is no interface between the MFP running indicator and controller, and the Vital AC busses at Beaver Valley.
Reselect due to lack of applicability. Discussed with Chief Examiner. Randomly selected 057 AA2.03 as a replacement.
2/1 026 A1.02 Question #41; Beaver Valley does not operate the CNMT Spray Sytem based on CNMT temperature. Procedurally the EOPs use CNMT pressure. The procedures do not refer to CNMT Temp for any control functions of CSS. Randomly selected 026A1.01 as a replacement.
2/1 059 A2.07 Question #46; Beaver Valley does not have MFW pump turbines.
Randomly selected 059 A2.01 as a replacement.
2/2 041 G2.4.41 Question #92: 041 Steam Dump System (SDS)/Turbine Bypass Control 2.4.41 Knowledge of the emergency action level thresholds and classifications. Reselected due to oversampling. Similar to Q77 (011 G2.4.41 ). Randomly selected 041 2.4.50 as a replacement.
NUREG-1021, Revision 10 FENOC Facsimile Revision 0
ES-301 Administrative Topics Outline Form ES-301-1 Facility: Beaver Valley Unit 2 Date of Examination: 12/7 thru 12/18 2015 amination Level RO [ID SROD Operating Test Number BV2LOT15 NRC Administrative Type Describe activity to be performed Topic Code*
(See Note)
Conduct of D,R 2.1.43 (4.1)
Operations Ability to use procedures to determine the effects on reactivity of plant (ROA1.1) changes, such as reactor coolant system temperature, secondary plant, fuel depletion, etc.
JPM 2AD-016 Plot and Evaluate 1/M Data Conduct of N,R 2.1.4 (3.3)
Operations Knowledge of individual licensed operator responsibilities related to (RO A 1.2) shift staffing, such as medical requirements, "no-solo" operation, maintenance of active license status, 10CFR55, etc.
JPM 3AD-023 Determine if License Status is Maintained Active (RO)
Equipment N,R 2.2.41 (3.5) 1trol Ability to obtain and interpret station electrical and mechanical (RO A 2) drawings.
JPM 2AD-048 Determine Isolation Boundary Points and Mark on PlantVOND Radiation Control D, R 2.3.11 (3.8)
(RO A 3) Ability to control radiation releases.
JPM 2AD-010 Determine GW Storage Tank Discharge Bleed Flow Rate Emergency Plan NOT EVALUATED (RO A 4)
NOTE: All items (5 total) are required for SROs. RO applicants require only 4 items unless they are retaking only the administrative topics (which would require all 5 items).
- Type Codes & Criteria (C)ontrol Room, (S)imulator, or Class(R)oom (D)irect from bank t:_ 3 for ROs; ~ 4 for SROs & RO retakes)
(N)ew or (M)odified from bank (~ 1)
(P)revious 2 exams t:_ 1; randomly selected)
=--=============================================================================dl NUREG-1021, Revision 10 FENOC Facsimile rO
ES-301 Administrative Topics Outline Form ES-301-1 Facility: Beaver Valley Unit 2 Date of Examination: 12/7 thru 12/18 2015
' "qmination Level RO D SRO !RI Operating Test Number BV2LOT15 NRC
=
Administrative Type Describe activity to be performed Topic (See Note) Code*
Conduct of D,R 2.1.43 (4.3)
Operations Ability to use procedures to determine the effects on reactivity of (SRO A 1.1) plant changes, such as reactor coolant system temperature, secondary plant, fuel depletion, etc.
JPM 2AD-019 Plot and Evaluate 1/M Data and Determine Required Actions Conduct of N,R 2.1.4 (3.8)
Operations Knowledge of individual licensed operator responsibilities related to (SRO A 1.2) shift staffing, such as medical requirements, "no-solo" operation, maintenance of active license status, 10CFR55, etc.
JPM 3AD-024 Evaluate Operators Work History to Determine if License Status is Active (SRO)
Equipment Control N,R 2.2.41 (3.9)
, <0 A 2) Ability to obtain and interpret station electrical and mechanical drawings.
JPM 2AD-049 Identify Isolation Boundary Points and Mark on Plant VOND then Identify Method of Plant Configuration Control Radiation Control M,R 2.3.4 (3.7)
(SRO A 3) Knowledge of radiation exposure limits under normal or emergency conditions.
JPM 2AD-038 Determine Emergency Exposure Authorization Limits Emergency Plan D,R 2.4.44 (4.4)
(SRO A4) Knowledge of emergency plan protective action recommendations.
JPM 2AD-037 Determine Protective Action Recommendations (Part 1)
NOTE: All items (5 total) are required for SROs. RO applicants require only 4 items unless they are retaking only the administrative topics (which would require all 5 items).
- -* 1pe Codes & Criteria (C)ontrol Room, (S)imulator, or Class(R)oom (D)irect from bank ('.:. 3 for ROs; ~ 4 for SROs & RO retakes)
(N)ew or (M)odified from bank ~ 1)
(P)revious 2 exams ('.:. 1; randomly selected)
NUREG-1021, Revision 10 FENOC Facsimile rO
ES 301 C on t ro IRoom /I n- Pl an t Siys tems 0 utrme - -
Form ES 301 2 Facility: BVPS UNIT 2 Date of Examination: 12/7/15 thru 12/18/15 Exam Level: RO [RI SRO(I) D SRO(U) D Operating Test No.: BV2LOT15 NRC Control Room Systems@ (8 for RO); (7 for SRO-I); (2 or 3 for SRO-U)
System I JPM Title Type Code* Safety Function 81 - Transfer to Hot Leg Recirculation (2CR-570) S,D,EN 3 82 - Discharge Steam Generator Slowdown Evaporator Test Tank [2SGC- S, N,A 9 TK23A] to Unit 2 Cooling Tower Slowdown. (2CR-660)
S3 - Rod Control Assembly Partial Movement Test - (Rods continue to S,N,A 1 move during performance of the test) (2CR-747)
S4 - Batch to the Refuel Water Storage Tank (2CR-537) S,D 2 S5 - Perform QPTR Alarm Test (2CR-144) S,D 7 S6 - Respond to Containment Air Recirculation Fan High Vibration Alarm S,N,A 5 (2CR-661)
S7 - Perform a Hot Bus Transfer (2CR-523) S,D,A 6 S8 - Start A Reactor Coolant Pump (2CR-513) S, D,A, L 4P In-Plant Systems@ (3 for RO); (3 for SRO-I); (3 or 2 for SRO-U)
P1 - Uninterruptible Power Supply [UPS*VITBS2-3(4)] Shutdown (2PL-021) D 6 P2 - Reset the Terry Turbine Trip Throttle Valve (2PL-004) D,R 4S P3 - Place the Diesel Air Compressor in Service (2PL-031) D, E 8
@ All RO and SRO control room (and in-plant) systems must be different and serve different safety functions; all 5 SRO-U systems must serve different safety functions; in-plant systems and functions may overlap those tested in the control room.
- Type Codes Criteria for RO I SRO-I / SRO-U (A)lternate Path 4-6 /4-6 /2-3 (C)ontrol room (D)irect from bank S9/S8/S4 (E)mergency or abnormal in-plant ;?:1/;?:1/;?:1 (EN)gineered safety feature ;::: 1 I;::: 1 I~ 1 (control room system)
(L)ow-power I Shutdown ;?:1/;?:1/;?:1 (N)ew or (M)odified from bank including 1(A) ;?:2/;?:2/;?:1 (P)revious 2 exams ::; 3/::; 3 /::; 2 (randomly selected)
- ?
- 1/;?:1/:<!1 II (R)CA (S)imulator NUREG-1021, Revision 10 FENOC Facsimile
ES -301 C on t ro IR oom /I n- Pl an t Siys tems 0 utrme -
Form ES 301 -2 Facility: BVPS UNIT 2 Date of Examination: 12/7/15 th1u 1£/ IV/
Exam Level: ROD SRO(I) [RI SRO(U) D Operating Test No.: BV2LOT15 NRC Control Room Systems@ (8 for RO); (7 for SRO-I); (2 or 3 for SRO-U)
System I JPM Title Type Code* Safety Function S1 - Transfer to Hot Leg Recirculation (2CR-570) S,D,EN 3 S2 - Discharge Steam Generator Slowdown Evaporator Test Tank [2SGC- S,N,A 9 TK23A] to Unit 2 Cooling Tower Slowdown. (2CR-660)
S3 - Rod Control Assembly Partial Movement Test - (Rods continue to S, N,A 1 move during performance of the test) (2CR-747)
S4 - Batch to the Refuel Water Storage Tank (2CR-537) S,D 2 S6 - Respond to Containment Air Recirculation Fan High Vibration Alarm S,N,A 5 (2CR-661)
S7 - Perform a Hot Bus Transfer (2CR-523) S,D,A 6 SB - Start A Reactor Coolant Pump (2CR-513) S, D,A, L 4P In-Plant Systems@ (3 for RO); (3 for SRO-I); (3 or 2 for SRO-U)
P1 - Uninterruptible Power Supply [UPS*VITBS2-3(4)] Shutdown (2PL-021) D 6 P2 - Reset the Terry Turbine Trip Throttle Valve (2PL-004) D,R 4S P3 - Place the Diesel Air Compressor in Service (2PL-031) D, E 8
@ All RO and SRO control room (and in-plant) systems must be different and serve different safety functions; all 5 SRO-U systems must serve different safety functions; in-plant systems and functions may overlap those tested in the control room.
- Type Codes Criteria for RO I SRO-I I SRO-U (A)lternate Path 4-6 /4-6 /2-3 (C)ontrol room (D)irect from bank S9/S8/S4 (E)mergency or abnormal in-plant 2!1/2!1/2!1 (EN)gineered safety feature 2! 1 I 2! 1 I~ 1 (control room system)
(L)ow-power I Shutdown 2!1/2!1/2!1 (N)ew or (M)odified from bank including 1(A) 2!2/2!2/2! 1 (P)revious 2 exams s 3/ s 3 Is 2 (randomly selected)
(R)CA 2!1/2!1/2!1 ii (S)imulator NUREG-1021, Revision 10 FENOC Facsimile
A,ppen d"1x D s cenario Outline 2L1 5 N1 Facility: BVPS Unit2 Scenario No. 1 Op Test No.: BV2LOT15 NRC Examiners: Candidates: SRO ATC BOP Initial IC-142(15): 48% power, MOL, Equ. XE Conditions, CB "D"@ 158 steps, RCS boron -
Conditions: 558 ppm.
Turnover: Maintain 48% power.
Critical Tasks: 1. CT-10 (E-0.M) Crew closes PORV block MOV
- 2. CT-13 (E-0.Q) Crew manually trips turbine
- 3. CT-43 (FR-H.1.A) Crew establishes feedwater flow Event Malf. No. Event Type Event Description No.
1 XMT-RCS019A (I,A) ATC, SRO Pressurizer level transmitter, 2RCS*LT459 drifts low.
(TS) SRO 2 XMT-MSS053A (I,A) BOP, SRO 2MSS*PT496 fails low over 30 sec, requires manual control of (TS) SRO 2FWS*FCV498.
3 RCS02A (C,A) A TC, SRO 30 gpm RCS leak (unisolable)
(TS) SRO t (R) ATC (N) BOP, SRO Ops management directed Emergency Shutdown, AOP 2.51.1.
5 RCS02A (M) ALL 400 gpm loop A LOCA , requires manual Rx trip 6 EHC08A (C) BOP, SRO Auto main Turbine trip failure 7 VLV-RCS034A 2RCS*PCV456 lifts/fails to reseat on Rx trip, requires manual (C) ATC, SRO closure of MOV block valve, 2RCS*MOV536.
8 PMP-AFWOO 1, 2, (M) ALL Loss of all feed, Entry into FR-H.1, success path - main feed LOA-AFW022 9 VLV- 2SSR-AOV117A, B, C, SG BD sample line auto isolation MSC104,105,106 (C) ATC, SRO failure (N)ormal, (R)eactivity, (I)nstrument, (C)omponent, (M)ajor, (A)bnormal E-O-FR-H.1 -E-O- E-1 NUREG-1021, Revision 10 FENOC Facsimile rO
Appendix D Scenario Outline 2L15N1 After taking the shift at 48% power, Pressurizer level transmitter, 2RCS-LT459 will drift low. The crew will diagnose the indications and IA W AOP 2.4.1, Process Control Failure, remove the failed channel from service and ensure the plant is stable, the SRO will transition to the instrument failure procedure for further channel actions and will address Tech Specs for the failed channel.
The channel 3, "C" SG steam pressure transmitter, 2MSS*PT496, will then drift low, the crew will recognize the SG level perturbation and IA W AOP 2.4.1, the BOP will place the controller for 2FWS*FCV498 in manual and will restore SG level, the SRO will transition to the instrument failure procedure for additional channel removal actions and will address Tech Specs for the failed instrument.
A non-isolable 30 gpm leak will then occur on the "A" loop, the crew will enter AOP 2.6.7, Excessive Primary Plant Leakage, to evaluate leak rate and leak location. The crew will determine the leak rate is greater than 10 gpm and is not isolable. The SM will report to the SRO that due to the leakage, management directs an immediate plant shutdown IAW AOP 2.51.1 at 2% per minute.
When reactor power lowers to< 42%, the RCS leak will increase to 400 gpm. The crew will identify degrading plant parameters and the SRO will direct a pre-emptive reactor trip and enter E-0. The turbine will fail to automatically trip due to the reactor trip, the BOP will manually trip the turbine.
Additionally, PORV, 2RCS*PCV456 will fail 20% open on the reactor trip. The ATC will identify the open PORV, attempt to close it, recognize that the PORV did not close and close the block valve, 2RCS*MOV536 to isolate the stuck open PORV.
When "Verifying AFW Status" in E-0, the crew will identify that all auxiliary feedwater pumps have failed, the SRO will transition to FR-H.1. While performing the actions ofFR-H.1, the ATC will identify that the SG blowdown sample valves failed to automatically close and will manually close 2SSR*AOV 117A, B &
C.
IA W FR-H.1 direction the crew will restore feedwater flow by starting a main feedwater pump. After feed flow is verified, the SRO will return to E-0.
The crew will progress thru E-0 and transition to E-1 after diagnosing that containment pressure and sump level are not consistent with pre-event values.
The scenario will be terminated when the crew "Checks if SI Flow Should be Reduced" and determines plant conditions support SI termination and transition to ES-1.1.
Expected procedure flow path is E FR-H.1 - E E-1 NUREG-1021, Revision 10 FENOC Facsimile rO
A.ppen d"1x D s cenario
- outme r 2L15N2 Facility: BVPS Unit 2 Scenario No. 2 Op Test No.: BV2LOT15 NRC Examiners: Candidates: SRO ATC BOP Initial IC-143 (10): 100% power, BOL, Equ. XE Conditions, CB "D" @227 steps, RCS boron -
Conditions: 1100 ppm.
Turnover: Maintain current plant conditions Critical Tasks: 1. CT-6 (E-0.1) Crew establishes SIS Flow
- 2. CT-52 (FR-S.l.C) Crew inserts negative reactivity
- 3. CT-17 (E-2.A) Crew isolates the faulted SG Event Malf. No. Event Type Event Description No.
1 XMT-MSS043A (R) ATC Load rejection - VPL failure, (N) BOP/SRO 20M-26.4.X 2 GEN02 (C,A) BOP/SRO MUG Voltage regulator overexcitation failure.
3 XMT-RCS030A (I,A) ATC/SRO 2RCS*PT444 drifts HIGH, PRZR pressure decreases, manual SROT.S. control of PRZR pressure required.
4 FLX-CFW33 (M)ALL 2800 gpm Feedwater leak inside CNMT on "C" SG. CNMT
.., ' SRO T.S . pressure rises above TS allowable prior to trip.
5 PPLOlA (M) ALL ATWS - Failure of auto/manual Rx trip.
PPLOlB 6 CRFOlA (C) ATC/SRO Control Rods require manual insertion.
7 VLV-SIS069 2SIS*MOV867A and 2SIS*MOV867B auto open failure.
VLV-SIS070 (C) ATC, SRO 8 VLV-MSC021, (C) BOP/SRO "B" Train Hydrogen Analyzer fails to automatically start on 023,024,025 SIS signal.
9 VLV-AFW014 (C) BOP/SRO AFW valve, 2FWE*HCV100B, fails to close from the CR.
(N)ormal, (R)eactivity, (I)nstrument, (C)omponent, (M)ajor, (A)bnormal E-0----+ FR-S.1 ----+ E-0----+ E-2 NUREG-1021, Revision 10 FENOC Facsimile rO
Appendix D Scenario Outline 2L15N2 After taking the shift at 100% power, the valve position limiter will fail to 70% causing a load rejection.
The control rods will initially insert in response to the load rejection but will stop moving at 217 steps. The crew will initially respond with AOP 2.1.3, Unexpected Control Rod Movement, and then transition to AOP 2.35.2, Load Rejection, after the load rejection is diagnosed. The crew will stabilize the plant after which the BOP will be directed to use procedure 20M-26.4.X, Recovering Turbine Governor Valves from the Valve Position Limiter, to remove the turbine from the valve position limiter.
The MUG, main unit generator, voltage regulator will then fail causing an over excitation of the MUG, IAW AOP 2.4.1, Process Control Failure, the BOP will place the voltage regulator to "OFF" and correct the over excitation by manually adjusting the "base adjust".
The controlling PRZR pressure channel, 2RCS*PT444 will drift high causing RCS pressure to lower due to the pressurizer spray valves/PORV's opening. The crew will initially respond IAW AOP 2.4.1, identify the failure and close the spray valves/PORV's, the SRO will then transition to 20M-6.4.IF, attachment 2 to address the failed channel. The ATC controls PRZR pressure by manually operating the PRZR heaters and spray valves, or manual control of the PRZR pressure master controller. The SRO will address applicable TS entered due to the instrument failure.
A ramped 2800 gpm feedwater leak on the "C" SG inside of containment causing containment pressure to rise above TS allowable, the crew will investigate and diagnose a feedwater leak inside containment. The SRO will direct a pre-emptive reactor trip due to the leak. The reactor will fail to trip from the control room. The SRO will direct the ATC and BOP to perform the IOA's ofFR-S.l, "Response to Nuclear Power Generation - ATWS. The control rods will require manual insertion by the ATC. The reactor will be tripped via a local operator after being dispatched and the crew will return to E-0.
SIS will automatically actuate due to high containment pressure. Upon SIS actuation, 2SIS*MOV867A and 2SIS*MOV867B will fail to automatically open, the ATC will manually open valves to initiate SIS injection flow.
Additionally, the "B" train Hydrogen Analyzer will fail to automatically start due to the SI signal, the BOP will manually start the "B" Hydrogen Analyzer.
The crew will progress thru E-0, diagnose a faulted SG and transition to E-2, Faulted Steam Generator Isolation.
When the BOP attempts to isolate Aux feedwater flow to the "C" SG, it will be identified that 2FWE*HCV100B will fail to close from the Control Room. The BOP will take contingency actions using EOP Attachment A-1.24, AFW Throttle Valve Failure, to isolate AFW flow to the faulted "C" SG.
After the crew has completed isolation of the faulted SG, plant conditions will support SI termination, the crew will transition to ES-1.1, SI Termination, at which time the scenario will be terminated.
Expected procedure flow path is E FR-S.1 - E E-2 NUREG-1021, Revision 10 FENOC Facsimile rO
A,ppen d"1x D s cenario Outline 2L15N4 Facility: BVPS Unit2 Scenario No. 4 Op Test No.: BV2LOT15 NRC Examiners: Candidates: SRO ATC BOP Initial IC 145: 4.8% power, MOL, Rx SIU in progress, CB "D"@ 105 steps, RCS boron - 1349 Conditions: ppm.
Turnover: Raise power to 15% to SIU main turbine IAW 20M-52.4.A.
Critical Tasks: 1. CT-11 (E-0.0) Cnmt isolation
- 2. CT-18 (E-3.A) Crew isolates ruptured SG
- 3. CT-19 (E-3.B) Crew establishes/maintains RCS temperature
- 4. CT-20 (E-3.C) Crew depressurizes RCS to meet SI termination criteria Event Malf. No. Event Type Event Description No.
1 (R)ATC Normal power increase to 15% IAW 20M-52.4.A (N) SRO 2 CNH-CFWll (C,A) BOP/SRO 2FWS*FCV479, Bypass Feedwater valve controller fails as is in AUTO, requires manual operation.
3 PMP-CHS002 (C,A) ATC/SRO 2CHS*P21B, Charging/ HHSI pump shaft seizure.
SRO (TS) 4 XMT-MSC038A SRO (TS) 2LMS*PT952, CNMT Pressure transmitter fails high 5 PPL02A (M) ALL Spurious Rx trip 6 RCS04B (M) ALL 21B SG 520 gpm Tube Rupture 7 PPL07B (C) ATC/SRO 2CHS *P21 C, Charging I HHSI auto start failure 8 VLV-SEA015 (C) BOP/SRO Train B CIA failure with 2CHS*MOV378 failing to auto close 9 VLV- (C) ATC/SRO PRZR PORV fails to close when opened for RCS RCS03 2,3 3 ,34 depressurization in E-3, requires isolation.
(N)ormal, (R)eactivity, (I)nstrument, (C)omponent, (M)ajor, (A)bnormal E ES-0.1 - E E-3 NUREG-1021, Revision 10 FENOC Facsimile rO
Appendix D Scenario Outline 2L15N4 The crew will take the shift at 4.8% power with instructions to raise power to 15% IAW the reactivity plan to SIU the main turbine. The following malfunctions will occur as power is raised.
After power is >5% and a dilution has been performed, the "B" Charging/ HHSI pump will experience a shaft seizure. The crew will respond with AOP 2.7.1, Loss of Charging or Letdown, and start the standby charging pump after isolating charging and letdown. The crew will dispatch operators to place the spare charging pump 2CHS*P21C in service on the 2DF bus. The SRO will address the applicable TS.
Also occurring at 5% power, the "A" bypass feedwater regulating valve controller will fail as is. As power rises, the controller problem will become evident requiring the BOP to manually control "A" SG level IA W AOP 2.4.1, Process Control Failure.
At 8% reactor power, Containment Pressure Transmitter, 2LMS*PT952, will fail high. The SRO will enter the instrument failure procedure and address the applicable TS.
When the reactor reaches 10% power, a spurious reactor trip will occur, the crew will enter E-0, Reactor Trip and Safety Injection. The crew will determine SI is not actuated nor required and transition to ES-0.1, Reactor Trip Response.
5 minutes after the reactor trip occurs a 520 gpm SGTR, steam generator tube rupture, will occur on the "B" SG. The crew will note that plant parameters are degrading and IA W ES-0.1, left hand page direction, actuate SI and return to E-0. The crew will diagnose a SGTR has occurred and will transition to E-3, Steam Generator Tube Rupture.
2CHS *P21 C will fail to automatically start from the SIS but will start when the ATC attempts a manual start.
The safety injection actuation will fail to actuate the train "B" CIA signal, and train "A" CIA valve, 2CHS*MOV378 will fail to automatically close. While performing attachment A-0.11, Verification of Automatic Actions, the BOP will recognize the failure and isolate the containment penetration via either manually actuating Train "B" CIA or manually closing 2CHS*MOV378.
The crew will progress thru E-3, when a PORV is opened to depressurize the RCS it will fail to close, the ATC will then close the applicable MOV block valve to isolate the stuck open PORV.
The scenario will be terminated after the crew establishes a normal charging flowpath in E-3.
Expected procedure flow path is E-0 ~ ES-0.1 ~ E-0 ~ E-3 NUREG-1021, Revision 10 FENOC Facsimile rO
FENOC FirstEnergy Nuclear Operating Company 4t BEAVER VALLEY POWER STATION TRAINING SECTION September 8, 2015 Mr. Peter Presby USNRC Chief Examiner USNRC Region 1 2100 Renaissance Blvd, Suite 100 King of Prussia, PA 19406-2713 Beaver Valley Training Center Examination Outlines NPD3DOT:3714
Dear Mr. Presby,
Enclosed for your review and approval are the outlines for the Beaver Valley Unit 2 Initial Licensed Operator Examination scheduled to begin December 7, 2015. These outlines are submitted in accordance with NUREG 1021, Operator Licensing Examination Standards for Power Reactors (Revision 10).
The following materials are enclosed:
- Form ES-201-2, Examination Outline Quality Checklist- (Signed)
- Form ES-201-3, Examination Security Agreement (Copy)
- Form ES-301-1, Administrative Topics Outline SRO- Rev. 0
- Form ES-301-2, Control Room/In-Plant Systems Outline RO- Rev. 0
- Form ES-301-2, Control Room/In-Plant Systems Outline SRO-I - Rev. O
- Form ES-301-4, Simulator Scenario Quality Checklist - Rev. 0 (Unsigned)
- Form ES-301-6, Competencies Checklist- Rev. 0
Form ES-401-3, Generic Knowledge and Abilities Outline Tier 3- RO- Rev. 0 (1 page)
Form ES-401-3, Generic Knowledge and Abilities Outline Tier 3- SRO-Rev. 0 (1 page)
- Form ES-401-4, Record of Rejected K/As- Rev. 0
- Form ES-D-1, Scenario Outline - Rev. 0 (4 - All New)
Page 1of2
USN RC Page 2of2 September 4, 2015 The unsigned Form ES-301-4, Simulator Scenario Quality Checklist, is being sent to support Form ES-201-2, Examination Outline Quality Checklist. A signed version of this form will be sent with the exam materials.
The Westinghouse developed PWROG Random Generator software was used to generate both the RO and SRO written examination outlines. This software follows the selection process described in ES-401, Attachment 1, Example Systematic Sampling Methodology and the KIA Elimination Guidance provided in ES-401. Replacement K/As were manually selected utilizing this same guidance. Rejected K/As were documented on Form ES-401-4, Record of Rejected K/As.
The expected additions to the Exam Security Agreement are additional Operations Validation Team members.
We request these materials be withheld from public disclosure until after the completion of the exam. If you have any questions, please feel free to contact Tom Gaydosik at 724-682-1884.
Sincerely, Daniel J. Ronnenberg Superintendent, Nuclear Operations Training Cb~~
David W. Held Unit 2 Shift Manager - Facility Reviewer cc: OPS Letter File Nuclear Records - Site TG for LY - exam outlines - 16 TG/LY
ES-401 PWR Examination Outline Form ES-401-2 Facility: BVPS UNIT 2 RO Date of Exam 12/7 thru 12/18/2015 RO KIA Category Points Tier Group K K K K K K A A A A G TOTAL 1 2 3 4 5 6 1 2 3 4
- 1 3 3 3 3 18 1.
Emergency 2
& 2 1 2 2 9 Abnormal Plant Tier Evolutions Totals 5 4 5 5 27 1
2.
2 2 3 3 3 2 2 3 2 3 3 28 Plant Systems 2 1 1 1 1 1 1 1 0 1 1 1 10 Tier Totals 3 3 4 4 4 3 3 3 3 4 4 38 1 2 3 4 10
- 3. Generic Knowledge and Abilities Category 2 3 2 3 Note:
- 1. Ensure that at least two topics from every applicable KIA category are sampled within each tier of the RO and SRO-only outlines (i.e., except for one category in Tier 3 of the SRO-only outline, the "Tier Totals" in each KIA category shall not be less than two).
(One Tier 3 Radiation Control KIA is allowed if the KIA is replaced by a KIA from another Tier 3 Category).
- 2. The point total for each group and tier in the proposed outline must match that specified in the table. The final point total for each group and tier may deviate by +/-1 from that specified in the table based on NRC revisions. The final RO exam must total 75 points and the SRO-only exam must total 25 points.
- 3. Systems/evolutions within each group are identified on the associated outline; systems or evolutions that do not apply at the facility should be deleted with justification; operationally important, site-specific systems/evolutions that are not included on the outline should be added. Refer to Section D.1.b of ES-401 for guidance regarding the elimination of inappropriate KIA statements.
- 4. Select topics from as many systems and evolutions as possible; sample every system or evolution in the group before selecting a second topic for any system or evolution.
- 5. Absent a plant-specific priority, only those KIAs having an importance rating (IR) of 2.5 or higher shall be selected. Use the RO and SRO ratings for the RO and SRO-only portions, respectively.
- 6. Select SRO topics for Tiers 1 and 2 from the shaded systems and KIA categories.
- 7. The generic (G) KlAs in Tiers 1 and 2 shall be selected from Section 2 of the KIA Catalog, but the topics must be relevant to the applicable evolution or system. Refer to Section D.1.b of ES-401 for the applicable KIAs.
- 8. On the following pages, enter the KIA numbers, a brief description of each topic, the topics' importance ratings (I Rs) for the applicable license level, and the point totals (#)for each system and category. Enter the group and tier totals for each category in the table above; if fuel handling equipment is sampled in a category other than Category A2 or G* on the SRO-only exam, enter it on the left side of Column A2 for Tier 2, Group 2 (Note #1 does not apply). Use duplicate pages for RO and SRO-only exams.
- 9. For Tier 3, select topics from Section 2 of the KIA catalog, and enter the KIA numbers, descriptions, IRs, and point totals(#) on Form ES-401-3. Limit SRO selections to KIAs that are linked to 10 CFR 55.43.
G* Generic KIAs NUREG-1021, Revision 10 RO Page 1 of 13 FENOC Facsimile Rev. 0
ES-401 PWR Examination Outline Form ES-401-2 Emergency and Abnormal Plant Evolutions -Tier 1/Group 1(RO)
E/APE #I Name I Safety Function K K K A *A G KIA Topic(s) IR #
... 1 2 3 1 .2 000007 Reactor Trip I 1 : .
)( .:* .. : EK2 Knowledge of the interrelations between a 3.5 1
- I '1** reactor trip and the following:
[Question 1]
EK2.03 Reactor trip status panel i
(CFR 41.7 I 45.7) h*r: ,.....
000008 Pressurizer (PZR) Vapor Space ) AK1 Knowledge of the operational implications of 3.2 1 Accident (Relief Valve Stuck Open) I 3 the following concepts as they apply to a
- .: Pressurizer Vapor Space Accident:
[Question 2]
AK1 .01 Thermodynamics and flow characteristics of open or leaking Valves (CFR 41.8 I 41.10 I 45.3) 000015/000017 Reactor Coolant Pump (RCP) Malfunctions I 4 x AK2 Knowledge of the interrelations between the Reactor Coolant Pump Malfunctions (Loss of RC 2.9 1 Flow) and the following:
[Question 3] AK2.07 RCP seals
.. (CFR 41.7 / 45.7) 000022 Loss of Reactor Coolant Makeup I )(
1~ AK1 Knowledge of the operational implications of 3.0 1 2 the following concepts as they apply to Loss of Reactor Coolant Makeup:
[Question 4] AK1 .03 Relationship between charging flow and PZR level (CFR 41.8 / 41.10 I 45.3)
CJ,, .~25 Loss of Residual Heat Removal )( ;
AA2 Ability to determine and interpret the following 3.3* 1 System (RHRS) / 4 as they apply to the Loss of Residual Heat Removal System:
I::*
[Question 5] h* .. 1. ~; AA2.04 Location and isolability of leaks l*.:1 d
(CFR: 43.5 / 45.13)
Ii " *.
000026 Loss of Component Cooling Water )( :
AK3 Knowledge of the reasons for the following 4.0 1 (CCW) / 8 responses as they apply to the Loss of Component Cooling Water:
[Question 6] AK3.03 Guidance actions contained in EOP for Loss of CCW (CFR 41.5,41.10 I 45.6 I 45.13) 000027 Pressurizer Pressure Control )( 2.1.28 Knowledge of the purpose and function of 4.1 1 System (PZR PCS) Malfunction I 3 major system components and controls.
I*.
(CFR: 41. 7)1
[Question 7]
000029 Anticipated Transient Without ) :*:'\.I*. EK2 Knowledge of the interrelations between the 2.9* 1 Scram (ATWS) I 1 and the following an ATWS:
EK2.06 Breakers, relays, and disconnects
[Question 8]
(CFR 41.7 / 45.7)
NUREG-1021, Revision 10 RO Page 2 of 13 FENOC Facsimile Rev. 0
ES-401 PWR Examination Outline Form ES-401-2 Emergency and Abnormal Plant Evolutions -Tier 1/Group 1(RO) Continued
= >
,\,
1 i~~ ~~~
E/APE #I Name I Safety Function K K K A KIA Topic(s) IR #
1 2 3
',:< :'.*"j 000038 Steam Generator Tube Rupture )( EK3 Knowledge of the reasons for the following 3.6* 1 1';
(SGTR) / 3 responses as the apply to the SGTR:
. EK3.03 Automatic actions associated with high
[Question 9] .. :*
radioactivity in SIG sample lines (CFR 41.5 / 41.10 / 45.6 / 45.13) 000054 Loss of Main Feedwater (MFW) / 4 .) >>:: AA2 Ability to determine and interpret the following 4.1 1 as they apply to the Loss of Main Feedwater (MFW):
[Question 1O] 1*: ,* .*
1; ... ,.. ;~.,,. AA2.02 Differentiation between loss of all MFW and
,"... trip of one MFW pump
.* ~ 11),i (CFR: 43.5 / 45.13)
.:~ 2.4.18 Knowledge of the specific bases for EOPs.
000055 Loss of Offsite and Onsite Power ':;*: 3.3 1 (Station Blackout) / 6 (CFR: 41.10 / 43.1/45.13)
[Question 11] '
000056 Loss of Offsite Power I 6 )( AK1 Knowledge of the operational implications of 3.7 1 1.~ the following concepts as they apply to Loss of Offsite Power:
[Question 12]
AK1 .01 Principle of cooling by natural convection (CFR 41.8 / 41.10 / 45.3)
-( 57 Loss of Vital AC Electrical ) :1,: AA2 Ability to determine and interpret the following 3.7 1 ln'Su ument Bus / 6 ::*: .
as they apply to the Loss of Vital AC Instrument
') 1:,;,9 Bus:
[Question 13] ' '
AA2.03 RPS panel alarm annunciators and trip indicators (CFR: 43.5 / 45.13) 000062 Loss of Nuclear Service Water I 4 x :,,
AK3. Knowledge of the reasons for the following responses as they apply to the Loss of Nuclear 3.5 1
[Question 14] Service Water:
AK3.04 Effect on the nuclear service water discharge flow header of a loss of CCW I',:; :'c'
1;,:l ;' (CFR 41.4, 41.8 / 45.7) 2.4.4 Ability to recognize abnormal indications for
- ~~
000065 Loss of Instrument Air/ 8 . *. 4.5 1 system operating parameters that are entry-level conditions for emergency and abnormal operating
[Question 15] procedures.
(CFR: 41.10 I 43.2 I 45.6)
.' AA 1 Ability to operate and/or monitor the following 000077 Generator Voltage and Electric Grid )(I 4.1 1 Disturbances / 6 as they apply to Generator Voltage and Electric Grid Disturbances:
[O* 1?.stion 16] AA 1.04 Reactor controls (CFR: 41.5 and 41.10 / 45.5, 45.7, and 45.8)
NUREG-1021, Revision 10 RO Page 3of13 FENOC Facsimile Rev. 0
ES-401 PWR Examination Outline Form ES-401-2 Emergency and Abnormal Plant Evolutions -Tier 1/Group 1(RO) Continued
- =-
E/APE #I Name I Safety Function K K K A,A G KIA Topic(s) IR #
1 2 3 1 2,, f>J' ,'
W/E11 Loss of Emergency Coolant J: LJ,:,' EA 1 Ability to operate and I or monitor the following 3.7 1
~
Recirculation I 4 as they apply to the (Loss of Emergency Coolant
,i , Recirculation)
[Question 17] I ,,i~ , , EA 1.3 Desired operating results during abnormal
',' ,,, ,, and emergency situations
~~f
"; , ,,~ ,,, (CFR: 41. 7 I 45.5 I 45.6)
)( I,,, EA 1 Ability to operate and I or monitor the following iff: +,f,~
W/E12 Uncontrolled Depressurization of all 3.6 1 Steam Generators 14 I as they apply to the (Uncontrolled Depressurization
,," /;~ of all Steam Generators)
[Question 18] EA 1.2 Operating behavior characteristics of the facility.
(CFR: 41. 7 I 45.5 I 45.6) 3 3 3 3 3 3 KIA Category Point Totals: Group Point Total: 18 NUREG-1021, Revision 10 RO Page 4of13 FENOC Facsimile Rev. 0
ES-401 PWR Examination Outline Form ES-401-2 Emergency and Abnormal Plant Evolutions - Tier 1/Group 2(RO)
E/APE #I Name I Safety Function K K K A .A. G KIA Topic(s) IR #
1 2 3 1 .2 .
==000033 Loss of Intermediate Range )( I** AK1 Knowledge of the operational implications of the 2.7 1 1.*.*.
Nuclear Instrumentation I 7 1*.* I!*' following concepts as they apply to Loss of I*
. Intermediate Range Nuclear Instrumentation:
[Question 19] AK1 .01 Effects of voltage changes on performance I* l:J:!!
1 ** ;
(CFR 41.8 I 41.10 I 45.3) 000059 Accidental Liquid Radwaste )
.... AA2 Ability to determine and interpret the following 2.9 1 as they apply to the Accidental Liquid Radwaste Release /9
. .. Release:
(Question 20] AA2.02 The permit for liquid radioactive-waste release (CFR: 43.5 I 45.13) 000067 Plant fire on site I 9 ) AK3 Knowledge of the reasons for the following 3.3 1 responses as they apply to the Plant Fire on Site:
(Question 21] I *. AK3.04 Actions contained in EOP for plant fire on site I***
1**..*! 1.*:. (CFR 41.5,41.10 I 45.6 I 45.13) 000068 Control Room Evacuation I 8 *.... AK2 Knowledge of the interrelations between the
) vI .* 3.7 1 Control Room Evacuation and the following:
[Question 22]
AK2.02 Reactor trip system (CFR 41.7 I 45.7) 000069 Loss of Containment Integrity I 5 ) AK3 Knowledge of the reasons for the following 3.8* 1 responses as they apply to the Loss of Containment (Question 23] Integrity:
"!. 1* .!*
.... AK3.01 Guidance contained in EOP for loss of containment integrity (CFR 41.5,41.10 I 45.6 I 45.13)
W/E02 SI Termination I 3
)( 2.4.21 Knowledge of the parameters and logic used 4.0 1 to assess the status of safety functions, such as
[Question 24] .* reactivity control, core cooling and heat removal, reactor coolant system integrity, containment conditions, radioactivity release control, etc.
.. I * (CFR: 41.7 I 43.5 I 45.12)
W/E03 LOCA Cooldown and )( EK1 Knowledge of the operational implications of the 3.6 1 Depressurization I 4 1*
.! following concepts as they apply to the (LOCA Cooldown and Depressurization)
[Question 25] *.
EK1 .2 Normal, abnormal and emergency operating procedures associated with (LOCA Cooldown and Depressurization).
(CFR: 41.8 I 41.10 I 45.3)
NUREG-1021, Revision 10 RO Page 5of13 FENOC Facsimile Rev. 0
ES-401 PWR Examination Outline Form ES-401-2 Emergency and Abnormal Plant Evolutions -Tier 1/Group 2(RO) Continued E/APE #I Name I Safety Function K K K A A G KIA Topic(s) IR #
1 2 3 1 ;.z, ',,;'
0<1;\
W/E07 Saturated Core Cooling I 4 EA 1 Ability to operate and I or monitor the following
}( .* IJ.{ as they apply to the (Saturated Core Cooling) 3.6 1 Ii
[Question 26]
I* .,. ' ..
EA 1.1 Components, and functions of control and safety systems, including instrumentation, signals, interlocks, failure modes, and automatic and manual I* ...
features.
I*
(CFR: 41. 7 I 45.5 I 45.6)
W/E13 Steam Generator Overpressure I 4 *~ 2.1.23 Ability to perform specific system and 4.3 1 integrated plant procedures during all modes of plant
[Question 27] operation.
(CFR: 41.10 I 43.5 I 45.2 I 45.6)
I .* ..
2 1 2 1 1 2 KIA Category Point Totals: Group Point Total: 9 NUREG-1021, Revision 10 RO Page 6of13 FENOC Facsimile Rev. 0
ES-401 PWR Examination Outline Form ES-401-2 Plant Systems - Tier 2/Group 1(RO)
System # I Name K K K K K K A A A A ,B~.. *. KIA Topic(s) IR #
- . 1 2 3 4 5 6 1 12 3 4 i:{*11. 1.
003 Reactor Coolant Pump K2 Knowledge of bus power supplies to the
~ '. 3.1 1 System (RCPS) following:
[Question 28] 11i:i:
I**. ' :1 K2.01 RCPS 11, (CFR: 41.7) 004 Chemical and Volume **
Control System x le ,. K5 Knowledge of the operational implications of the following concepts as they apply to the 2.5 1
[Question 29]
I' eves:
I':
1.>1.ii' K5.14 Reduction process of gas concentration in RCS: vent accumulated non-condensable
[i~;~;
l1;1 . , gases from PZR bubble space, depressurized during cooldown or by alternately heating and l;'c* cooling (spray) within allowed pressure band I*
I\~~~ (drive more gas out of solution)
(CFR: 41.5/45.7)
I 005 Residual Heat Removal ) .. K2 Knowledge of bus power supplies to the 2.7* 1 System (RHRS)
I.I
,11 following:
[Question 30] K2.03 RCS pressure boundary motor-operated valves (CFR: 41.7) 006 Emergency Core Cooling A3 Ability to monitor automatic operation of the
) 3.6* 1 System (ECCS) 1. :':
ECCS, including:
[0* --stion 31] l<<\/1 A3.07 RHR pumps I' ;1 (CFR: 41.7 / 45.5) 006 Emergency Core Cooling ) K4 Knowledge of ECCS design feature(s) 1;:1 2.6 1 System (ECCS) I* and/or interlock(s) which provide for the
[Question 32] following:
K4.01 Cooling of centrifugal pump bearings (CFR: 41.7) 007 Pressurizer Relief i,1 K4 Knowledge of PRTS design feature(s)
Tank/Quench Tank System
~ 2.6 1 and/or interlock(s) which provide for the (PRTS) following:
[Question 33]
K4.01 Quench tank cooling
\.,,.1. . (CFR: 41.7) 008 Component Cooling Water lj 2.2.38 Knowledge of conditions and limitations 3.6 1 System (CCWS) in the facility license.
[Question 34]
(CFR: 41.7 / 41.10 / 43.1/45.13) 008 Component Cooling Water ~ K3 Knowledge of the effect that a loss or 4.1 1 System (CCWS) malfunction of the CCWS will have
[Question 35] on the following:
I K3.03 RCP 010 Pressurizer Pressure ) A3 Ability to monitor automatic operation of the
stion 36] ;.:i;j: A3.02 PZR pressure 1**,. (CFR: 41.7 / 45.5)
NUREG-1021, Revision 10 RO Page 7of13 FENOC Facsimile Rev. 0
ES-401 PWR Examination Outline Form ES-401-2 Plant Systems - Tier 2/Group 1(RO) Continued A A A 11~;~
System # I Name K K K K K K A KIA Topic(s) IR #
1 2 3 4 5 6 1 *2 3 4
- .':' :y:.: K6 Knowledge of the effect of a loss or 012 Reactor Protection System ~ 2.9 1 (RPS) malfunction of the following will have on the RPS:
[Question 37]
K6.02 Redundant channels
. (CFR: 41. 7 I 45/7) 013 Engineered Safety Features Actuation System (ESFAS)
}( 'fJ. t KS Knowledge of the operational implications of the following concepts as they apply to the 2.9 1
- *'. .. ESFAS:
[Question 38]
- K5.02 Safety system logic and reliability
).1:;
...... (CFR: 41.5 / 45.7) 022 Containment Cooling }( A2 Ability to (a) predict the impacts of the 2.9* 1 System (CCS) following malfunctions or operations on the CCS; and (b) based on those predictions, use
[Question 39] procedures to correct, control, or mitigate the consequences of those malfunctions or
. operations:
A2.04 Loss of service water
!*l*I::**: (CFR: 41.5 / 43.5 / 45.3 / 45.13)
. A4 Ability to manually operate and/or monitor 1~*~~
022 Containment Cooling }( 3.8 1 System (CCS) in the control room:
[Question 40] i'Jf. A4.05 Containment readings of temperature, pressure, and humidity system.
l:io:
(CFR: 41. 7 I 45.5 to 45.8) 026 Containment Spray System }(
1: A 1 Ability to predict and/or monitor changes in 3.9 1 (CSS) parameters (to prevent exceeding design
[Question 41] limits) associated with operating the CSS controls including:
. A 1.01 Containment pressure
- (CFR
- 41.5 I 45.5) 026 Containment Spray System **~ 2.2.12 Knowledge of surveillance procedures. 3.7 1 (CSS)
. (CFR: 41.10 / 45.13)
[Question 42]
039 Main and Reheat Steam }( K3 Knowledge of the effect that a loss or 3.2* 1 System (MRSS) malfunction of the MRSS will have on the
[Question 43] following:
K3.03 AFW pumps.
(CFR: 41.7 / 45.6) 039 Main and Reheat Steam )( 2.4.1 Knowledge of EOP entry conditions and 4.6 1 System (MRSS) immediate action steps.
[Question 44] (CFR: 41.10 I 43.5 / 45.13)
NUREG-1021, Revision 10 RO Page 8of13 FENOC Facsimile Rev. 0
ES-401 PWR Examination Outline Form ES-401-2 Plant Systems - Tier 2/Group 1(RO) Continued System # I Name K K K K K K A A A A G KIA Topic(s) IR #
1 2 3 4 5 6 1 2 3 4 ..
System 1*
x .1*;. :
A4 Ability to manually operate and monitor in the control room:
3.1* 1
[Question 45) .
A4.01 MFW turbine trip indication 1*: '*\ ** (CFR: 41. 7 I 45.5 to 45.8) 059 Main Feedwater (MFW) *.}(
iH~i?
A2 Ability to (a) predict the impacts of the 3.4* 1 System following malfunctions or operations on the
[~!~*
+'
[Question 46) MFW; and (b) based on those predictions, use procedures to correct, control, or mitigate the
- . consequences of those malfunctions or
.. , operations:
A2.01 Feedwater actuation of AFW system
' (CFR: 41.5 I 43.5 I 45.3 I 45.13) 061 Auxiliary I Emergency x . ..* K5 Knowledge of the operational implications 3.2 1 Feedwater (AFW) System I.* ..
of the following concepts
.... as the apply to the AFW:
[Question 4 7)
K5.02 Decay heat sources and magnitude
.* (CFR: 41.5 I 45.7) 1*=*
062 AC Electrical Distribution A2 Ability to (a) predict the impacts of the D~ 1.;*.*.* 2.7 1 System following malfunctions or operations on the ac
,. distribution system; and (b) based on those
[Question 48) predictions, use procedures to correct, control,
- or mitigate the consequences of those malfunctions or operations:
A2.08 Consequences of exceeding voltage limitations i* : *' (CFR: 41.5 I 43.5 I 45.3 I 45.13)
- /*':'
063 DC Electrical Distribution }( K1 Knowledge of the physical connections 2.7 1 System 2 and/or cause effect relationships between the DC electrical system and the following
[Question 49] 1,,.. ):rj~. systems:
K1 .02 AC electrical system (CFR: 41.2 to 41.9 I 45.7 to 45.8) 064 Emergency Diesel }( K6 Knowledge of the effect of a loss or 2.7 1 Generator (ED/G) System malfunction of the following will have on the
[Question 50] ED/G system:
K6.07 Air receivers
- .; (CFR: 41.7 I 45.7) 073 Process Radiation }( ;:*,*. K3 Knowledge of the effect that a loss or 3.6 1 Monitoring (PRM) System * .... malfunction of the PRM system will have on
[Question 51) . ' the following:
K3.01 Radioactive effluent releases hf (CFR: 41.7 I 45.6)
NUREG-1021, Revision 10 RO Page 9of13 FENOC Facsimile Rev. 0
ES-401 PWR Examination Outline Form ES-401-2 Plant Systems - Tier 2/Group 1(RO) Continued
'11 ,,,'
System # I Name K K K K K K A AA A ,
G KIA Topic(s) IR #
1 2 3 4 5 6 1 '12' 3 4 'I '/'
,I 076 Service Water System )( 1' A 1 Ability to predict and/or monitor changes in 2.6* 1 (SWS) parameters (to prevent exceeding design I~ limits) associated with operating the SWS
[Question 52] ',,
controls including:
,1 1:1i11 A 1.02 Reactor and turbine building closed
', cooling water temperatures.
,,,,,, (CFR: 41.5 / 45.5) 078 Instrument Air System (IAS) )< K1 Knowledge of the physical connections 3,3* 1
[Question 53] and/or cause-effect relationships between the IAS and the following systems:
, 1',
K1 .03 Containment air (CFR: 41.2 to 41.9 / 45.7 to 45.8) 103 Containment System )< 11/'I, K4 Knowledge of containment system design 3.0* 1
~I,'
[Question 54] 1;'.,/c feature(s) and/or interlock(s) which provide for
- ,, the following
I> ,
'i{',"
,'1 K4.01 Vacuum breaker protection (CFR: 41.7) 103 Containment System I,*~,',,, A4 Ability to manually operate and/or monitor
)( ,1, 3.1* 1
[Question 55] in the control room:
cl A4.09 Containment vacuum system (CFR: 41. 7 I 45.5 to 45.8)
=,
2 2 3 3 3 2 2 3 2 3 3 KIA Category Point Totals: Group Point Total: 28 NUREG-1021, Revision 10 RO Page 10of13 FENOC Facsimile Rev. 0
ES-401 PWR Examination Outline Form ES-401-2 Plant Systems - Tier 2/Group 2(RO)
System # I Name K K K K K K A A A A ':.;G KIA Topic(s) 1 2 3 4 5 6 1 1~2 3 4 IR
'1 ',
001 Control Rod Drive System ***i.~1,:* A 1 Ability to predict and/or monitor changes in
}( 3.7 1
[Question 56] l::K parameters (to prevent exceeding design limits) associated with operating the CRDS controls
- . including:
I
- 1; i A 1.04 PZR level and pressures (CFR
- 41.5 / 45.5) 1:
002 Reactor Coolant System }( A3 Ability to monitor automatic operation of the 4.4 1 (RCS) * .... RCS, including:
[Question 57] I 11~,
A3.03 Pressure, temperatures, and flows 1~:
1:1 (CFR: 41. 7 I 45.5) 011 Pressurizer Level Control }( . K6 Knowledge of the effect of a loss or 3.1 1 System (PZR LCS) ,. malfunction on the following will have on the
[Question 58] PZR LCS:
K6.05 Function of PZR level gauges as post
.11 accident monitors
.. (CFR: 41.7 / 45.7) 028 Hydrogen Recombiner and }( K5 Knowledge of the operational implications of 3.4 1 Purge Control System (HRPS) the following concepts as they apply to the
[Question 59] . HRPS:
"111* : .. K5.01 Explosive hydrogen concentration 1*." . (CFR: 41.5 / 45. 7)
(' ~ontainment Purge System K3 Knowledge of the effect that a loss or
}( 2.9 1
(- ,) malfunction of the Containment Purge System
[Question 60] will have on the following:
+~ K3.01 Containment parameters (CFR: 41. 7 I 45.6) 034 Fuel Handling Equipment }( K1 Knowledge of the physical connections 2.6 1 System (FHES) and/or cause effect relationships between the
[Question 61] Fuel Handling System and the following systems:
K1.04 NIS (CFR: 41.2 to 41.9 / 45. 7 to 45.8) x ti
~1 035 Steam Generator System K4 Knowledge of S/GS design feature(s) and/or 2.9 1 (S/GS) .,.: interlock(s) which provide for the following:
~;
[Question 62]
K4.05 Amount of reserve water in SIG 11 ;1~ (CFR:41.7) ii, 045 Main Turbine Generator }( A4 Ability to manually operate and/or monitor in 3.1 1 (MT/G) System the control room:
[Question 63]
A4.01 Turbine valve indicators (throttle, governor, control, stop, intercept), alarms, and annunciators 1* .*. (CFR: 41.7 / 45.5 to 45.8)
NUREG-1021, Revision 10 RO Page 11 of 13 FENOC Facsimile Rev. 0
ES-401 PWR Examination Outline Form ES-401-2 Plant Systems - Tier 2/Group 2(RO) Continued System # I Name K K K K K K A A A A G KIA Topic(s)
IR #
1 2 3 4 5 6 1 2 3 4 .*
072 Area Radiation Monitoring ) 2.4.46 Ability to verify that the alarms are 4.2 1 (ARM) System consistent with the plant conditions.
[Question 64] (CFR: 41.10 I 43.5 I 45.3 I 45.12) 075 Circulating Water System }( K2 Knowledge of bus power supplies to the 2.6* 1
[Question 65] following:
- . *~
K2.03 Emergency/essential SWS pumps (CFR: 41.7)
KIA Category Point Totals: 1 1 1 1 1 1 1 0 1 1 1 Group Point Total: 10 NUREG-1021, Revision 10 RO Page 12of13 FENOC Facsimile Rev. 0
ES 401 Generic Knowledge and Abilities Outline (Tier 3) Form ES-401-3 r'adlity: BVPS UNIT 2 RO Date of Exam 12/7 thru 12/18/2015 RO Category KIA# Topic IR #
- 1. 2.1.29 Knowledge of how to conduct system lineups, such as valves, breakers, 4.1 Conduct switches, etc.
of Operations (CFR: 41.10 I 45.1 I 45.12)
[Question 66]
2.1.45 Ability to identify and interpret diverse indications to validate the 4.3 response of another indication.
(CFR: 41.7 I 43.5 I 45.4)
[Question 67]
Subtotal
- 2. 2.2.6 Knowledge of the process for making changes to procedures.
Equipment (CFR: 41.10 I 43.3 I 45.13)
Control [Question 68]
2.2.15 Ability to determine the expected plant configuration using design and 3.9 configuration control documentation, such as drawings, line-ups, tag-outs, etc.
(CFR: 41.10 I 43.3 I 45.13)
[Question 69]
2.2.39 Knowledge of less than or equal to one hour Technical Specification 3.9 action statements for systems.
(CFR: 41.7 I 41.10 I 43.2 I 45.13)
Question 70 Subtotal
- 3. 2.3.7 Ability to comply with radiation work permit requirements during normal Radiation or abnormal conditions.
Control (CFR: 41.12 I 45.10)
[Question 71]
2.3.13 Knowledge of radiological safety procedures pertaining to licensed 3.4 operator duties, such as response to radiation monitor alarms, containment entry requirements, fuel handling responsibilities, access to locked high-radiation areas, aligning filters, etc.
(CFR: 41.12 I 43.4 I 45.9 I 45.10)
[Question 72]
Subtotal
- 4. 2.4.6 Knowledge of EOP mitigation strategies.
Emergency (CFR: 41.10 I 43.5 I 45.13)
Procedures/ [Question 73]
Plan 2.4.25 Knowledge of fire protection procedures. 3.3 (CFR: 41.10 I 43.5 I 45.13)
[Question 74]
2.4.39 Knowledge of RO responsibilities in emergency plan implementation. 3 _9 (CFR: 41.10/45.11)
Question 75 Subtotal Tier 3 Point Total NUREG-1021, Revision 10 RO Page 13of13 FENOC Facsimile Rev. 0
ES-401 PWR Examination Outline Form ES-401-2 Facility: BVPS UNIT 2 SRO Date of Exam 12/7 thru 12/18/2015 SRO ONLY Points Tier Group A2 G* TOTAL 1
3 3 6 1.
Emergency 2
& 2 2 4 Abnormal Plant Tier Totals 5 5 10 Evolutions 1
- 2. 3 2 5 Plant Systems 2 0 2 1 3 Tier Totals 5 3 8 1 2 3 4 7
- 3. Generic Knowledge and Abilities Category 2 1 2 2 Note:
- 1. Ensure that at least two topics from every applicable KIA category are sampled within each tier of the RO and SRO-only outlines (i.e., except for one category in Tier 3 of the SRO-only outline, the "Tier Totals" in each KIA category shall not be less than two).
(One Tier 3 Radiation Control KIA is allowed if the KIA is replaced by a KIA from another Tier 3 Category).
- 2. The point total for each group and tier in the proposed outline must match that specified in the table. The final point total for each group and tier may deviate by +/-1 from that specified in the table based on NRC revisions. The final RO exam must total 75 points and the SRO-only exam must total 25 points.
- 3. Systems/evolutions within each group are identified on the associated outline; systems or evolutions that do not apply at the facility should be deleted with justification; operationally important, site-specific systems/evolutions that are not included on the outline should be added. Refer to Section D.1.b of ES-401 for guidance regarding the elimination of inappropriate KIA statements.
- 4. Select topics from as many systems and evolutions as possible; sample every system or evolution in the group before selecting a second topic for any system or evolution.
- 5. Absent a plant-specific priority, only those KIAs having an importance rating (JR) of 2.5 or higher shall be selected. Use the RO and SRO ratings for the RO and SRO-only portions, respectively.
- 6. Select SRO topics for Tiers 1 and 2 from the shaded systems and KIA categories.
- 7. The generic (G) KIAs in Tiers 1 and 2 shall be selected from Section 2 of the KIA Catalog, but the topics must be relevant to the applicable evolution or system. Refer to Section D.1.b of ES-401 for the applicable KIAs.
- 8. On the following pages, enter the KIA numbers, a brief description of each topic, the topics' importance ratings (!Rs) for the applicable license level, and the point totals (#)for each system and category. Enter the group and tier totals for each category in the table above; if fuel handling equipment is sampled in a category other than Category A2 or G* on the SRO-only exam, enter it on the left side of Column A2 for Tier 2, Group 2 (Note #1 does not apply). Use duplicate pages for RO and SRO-only exams.
- 9. For Tier 3, select topics from Section 2 of the KIA catalog, and enter the KIA numbers, descriptions, IRs, and point totals(#) on Form ES-401-3. Limit SRO selections to KIAs that are linked to 10 CFR 55.43.
G* Generic KIAs NUREG-1021, Revision 10 SRO Page 1 of 6 FENOC Facsimile Rev. 0
ES-401 PWR Examination Outline Form ES-401-2 Emergency and Abnormal Plant Evolutions -Tier 1/Group 1(SRO)
E/APE #I Name I Safety Function K K K A A G KIA Topic(s) IR #
1 2 3 1 2 000009 Small Break LOCA I 3 ) EA2 Ability to determine or interpret the following as 3.9 1
[Question 76] they apply to a small break LOCA:
EA2.05 The time available for action before PZR is empty, given the rate of decrease of PZR level (CFR 43.5 / 45.13) 000011 Large Break LOCA I 3 2.4.41 Knowledge of the emergency action level 4.6 1
)~
[Question 77] thresholds and classifications.
(CFR: 41.10 / 43.5 / 45.11) 000040 Steam Line Rupture I 4 M2 Ability to determine and interpret the following 4.5 1
.*~
[Question 78] as they apply to the Steam Line Rupture:
M2.05 When ESFAS systems may be secured (CFR: 43.5 / 45.13) 000058 Loss of DC Power I 6 2.2.25 Knowledge of the bases in Technical 4.2 1
- !,J< Specifications for limiting conditions for operations
[Question 79]
and safety limits.
(CFR: 41.5 / 41.7 / 43.2)
\. 4 LOCA Outside Containment I 3 )< 2.4.11 Knowledge of abnormal condition procedures. 4.2 1
[Question 80] (CFR: 41.10 / 43.5 / 45.13)
W/E05 Loss of Secondary Heat Sink I 4 ) EA2 Ability to determine and interpret the following 4.4 1
[Question 81] as they apply to the (Loss of Secondary Heat Sink)
EA2.1 Facility conditions and selection of appropriate procedures during abnormal and emergency operations.
(CFR: 43.5 I 45.13) 3 3 6 KIA Category Point Totals: Group Point Total:
NUREG-1021, Revision 10 SRO Page 2 of 6 FENOC Facsimile Rev. 0
ES-401 PWR Examination Outline Form ES-401-2 Emergency and Abnormal Plant Evolutions - Tier 1/Group 2(SRO)
, ~r E/APE #I Name I Safety Function K K K A A G KIA Topic(s) IR #
,, 1 2 3 1 2 "
000003 Dropped Control Rod / 1 l( 2.2.36 Ability to analyze the effect of maintenance h'~
,',"" 4.2 1 activities, such as degraded power sources, on the
~~<
[Question 82]
status of limiting conditions for operations.
(CFR: 41.10 / 43.2 / 45.13) 000024 Emergency Boration I 1
"~~ 2.1.23 Ability to perform specific system and 4.4 1
[Question 83] integrated plant procedures during all modes of plant operation.
(CFR: 41.10 I 43.5 I 45.2 I 45.6)
W/E06 Degraded Core Cooling I 4 EA2 Ability to determine and interpret the following
"~ as they apply to the (Degraded Core Cooling) 4.2 1
[Question 84]
EA2.1 Facility conditions and selection of appropriate procedures during abnormal and emergency operations.
(CFR: 43.5 / 45.13)
W/E09 Natural Circulation Operations I 4 EA2 Ability to determine and interpret the following
'~ 3.8 1 as they apply to the (Natural Circulation Operations)
[Question 85]
EA2.2 Adherence to appropriate procedures and
',' ,": operation within the limitations in the facility*s license and amendments.
(CFR: 43.5 I 45.13)
KIA Category Point Totals: 0 0 0 0 2 2 Group Point Total: 4 NUREG-1021, Revision 10 SRO Page 3 of 6 FENOC Facsimile Rev. 0
ES-401 PWR Examination Outline Form ES-401-2 Plant Systems - Tier 2/Group 1(SRO)
System # I Name K 1
K 2
K 3
K 4
K K A 5 6 1 A A 2 3 A
4
,/~ KIA Topic(s) IR #
===--
003 Reactor Coolant Pump "~i:.; A2 Ability to (a) predict the impacts of the I )(
3.9 1 System (RCPS) "* following malfunctions or operations on the 1- *l"'.~{ RCPS; and (b) based on those predictions,
[Question 86]
use procedures to correct, control, or mitigate
' ;?'~- the consequences of those malfunctions or operations:
A2.02 Conditions which exist for an abnormal shutdown of an RCP in comparison to a normal shutdown of an RCP (CFR: 41.5 / 43.5/ 45.3 / 45/13)
.. ..1 004 Chemical and Volume l~t~?: A2 Ability to (a) predict the impacts of the Control System
.)c following malfunctions or operations on the 3.3 1
[Question 87] eves; and (b) based on those predictions, use procedures to correct, control, or mitigate the consequences of those malfunctions or operations:
A2.33 Fact that isolating cation demineralizer
- stops boron dilution and enables restoration of r
normal boron concentration (CFR: 41.5/ 43/5 I 4513 I 45/5) 013 Engineered Safety Features
- p. 1tion System (ESFAS) )( 2.4.1 Knowledge of EOP entry conditions and 4.8 1 Ii immediate action steps.
[to. ~stion 88] (CFR: 41.10 I 43.5 I 45.13)
.* ~,[,
11 076 Service Water System )( A2 Ability to (a) predict the impacts of the 3.1 1 (SWS) 1::. following malfunctions or operations on the SWS; and (b) based on those predictions, use
[Question 89]
procedures to correct, control, or mitigate the consequences of those malfunctions or operations:
A2.02 Service water header pressure (CFR: 41.5 I 43.5 I 4513 I 45/13) u~-'.:
2.4.34 Knowledge of RO tasks performed
'~~
078 Instrument Air System (IAS) 4.1 1
[Question 90] outside the main control room during an emergency and the resultant operational I;-; effects.
(CFR: 41.10 I 43.5 I 45.13) 3 2 5
KIA Category Point Totals: Group Point Total:
NUREG-1021, Revision 10 SRO Page 4 of 6 FENOC Facsimile Rev. 0
ES-401 PWR Examination Outline Form ES-401-2 Plant Systems - Tier 2/Group 2(SRO)
- A,
~~~
System # I Name K K K K K K A A A KIA Topic(s) 1 2 3 4 5 6 1 *2 3 4 IR #
- >11 033 Spent Fuel Pool Cooling .* A2 Ability to (a) predict the impacts of the System (SFPCS)
)( following malfunctions or operations on the 3.5 1
[Question 91] Spent Fuel Pool Cooling System ; and (b)
" based on those predictions, use procedures to
- 1 correct, control, or mitigate the consequences of those malfunctions or operations:
. '*" A2.01 Inadequate SDM 1:1~~
(CFR: 41.5 I 43.5 I 45.31 45.13) 041 Steam Dump System 2.4.50 Ability to verify system alarm setpoints (SDS)/Turbine Bypass Control '~ and operate controls identified in the !alarm 4.0 1
.,, response manual.
[Question 92] 111
- . (CFR: 41.10 I 43.5 I 45.3) 079 Station Air System (SAS) .)( A2 Ability to (a) predict the impacts of the following malfunctions or operations on the 3.2 1
[Question 93]
,.. SAS; and (b) based on those predictions, use
.* procedures to correct, control, or mitigate the
" consequences of those malfunctions or
} operations:
,11 A2.01 Cross-connection with IAS I '.1 *' (CFR: 41.5 / 43.5 I 45.31 45.13) 11 '
=
l<-t... ..;ategory Point Totals: 2 1 Group Point Total: 3 NUREG-1021, Revision 10 SRO Page 5 of 6 FENOC Facsimile Rev. 0
ES 401 Generic Knowledge and Abilities Outline (Tier 3) Form ES-401-3 Facility: BVPS UNIT 2 SRO Date of Exam 12/7 thru 12/18/2015 SRO Only Category Kl A# Topic IR #
- 1. 2.1.4 Knowledge of individual licensed operator responsibilities related to shift 3.8 Conduct staffing, such as medical requirements, "no-solo" operation, maintenance of Operations of active license status, 10CFR55, etc.
(CFR: 41.10 / 43.2)
[Question 94]
2.1.36 Knowledge of procedures and limitations involved in core alterations. 4.1 (CFR: 41.10 / 43.6 / 45.7)
[Question 95]
Subtotal 2
- 2. 2.2.42 Ability to recognize system parameters that are entry-level conditions for Equipment Technical Specifications.
Control (CFR: 41. 7 I 41.10 I 43.2 I 43.3 I 45.3)
[Question 96]
Subtotal 1
- 3. 2 .3 .4 Knowledge of radiation exposure limits under normal or emergency Radiation conditions.
Control (CFR: 41.12 I 43.4 I 45.10)
[Question 97]
2.3.11 Ability to control radiation releases. 4.3 (CFR: 41.11 I 43.4 / 45.10)
[Question 98]
Subtotal 2
- 4. 2.4.29 Knowledge of the emergency plan.
Emergency (CFR: 41.10 / 43.5 / 45.11)
Procedures/
[Question 99]
Plan 2.4.44 Knowledge of emergency plan protective action recommendations. 4.4 (CFR: 41.10 / 41.12 / 43.5 / 45.11)
[Question 100]
Subtotal 2 Tier 3 Point Total 7 NUREG-1021, Revision 10 SRO Page 6 of 6 FENOC Facsimile Rev. 0
ES-401 Record of Rejected K/As Form ES-401-4 Facility: BVPS Unit 2 Date of Exam 12/7 thru 12/18/2015 Operating Test No.: BV2LOT15 NRC Tier I Randomly Reason for Rejection Group Selected KIA 1/1 000025 Question #5; Beaver Valley does not use Residual Heat Removal AA2.05 (RHRS) for Low Pressure Injection (LPI). Randomly selected 025 AA2.04 as a replacement.
1/1 057 AA2.11 Question #13: There is no interface between the MFP running indicator and controller, and the Vital AC busses at Beaver Valley.
Reselect due to lack of applicability. Discussed with Chief Examiner. Randomly selected 057 AA2.03 as a replacement.
2/1 026 A1.02 Question #41; Beaver Valley does not operate the CNMT Spray Sytem based on CNMT temperature. Procedurally the EOPs use CNMT pressure. The procedures do not refer to CNMT Temp for any control functions of CSS. Randomly selected 026A1.01 as a replacement.
2/1 059 A2.07 Question #46; Beaver Valley does not have MFW pump turbines.
Randomly selected 059 A2.01 as a replacement.
2/2 041 G2.4.41 Question #92: 041 Steam Dump System (SDS)/Turbine Bypass Control 2.4.41 Knowledge of the emergency action level thresholds and classifications. Reselected due to oversampling. Similar to Q77 (011 G2.4.41 ). Randomly selected 041 2.4.50 as a replacement.
NUREG-1021, Revision 10 FENOC Facsimile Revision 0
ES-301 Administrative Topics Outline Form ES-301-1 Facility: Beaver Valley Unit 2 Date of Examination: 12/7 thru 12/18 2015 amination Level RO [ID SROD Operating Test Number BV2LOT15 NRC Administrative Type Describe activity to be performed Topic Code*
(See Note)
Conduct of D,R 2.1.43 (4.1)
Operations Ability to use procedures to determine the effects on reactivity of plant (ROA1.1) changes, such as reactor coolant system temperature, secondary plant, fuel depletion, etc.
JPM 2AD-016 Plot and Evaluate 1/M Data Conduct of N,R 2.1.4 (3.3)
Operations Knowledge of individual licensed operator responsibilities related to (RO A 1.2) shift staffing, such as medical requirements, "no-solo" operation, maintenance of active license status, 10CFR55, etc.
JPM 3AD-023 Determine if License Status is Maintained Active (RO)
Equipment N,R 2.2.41 (3.5) 1trol Ability to obtain and interpret station electrical and mechanical (RO A 2) drawings.
JPM 2AD-048 Determine Isolation Boundary Points and Mark on PlantVOND Radiation Control D, R 2.3.11 (3.8)
(RO A 3) Ability to control radiation releases.
JPM 2AD-010 Determine GW Storage Tank Discharge Bleed Flow Rate Emergency Plan NOT EVALUATED (RO A 4)
NOTE: All items (5 total) are required for SROs. RO applicants require only 4 items unless they are retaking only the administrative topics (which would require all 5 items).
- Type Codes & Criteria (C)ontrol Room, (S)imulator, or Class(R)oom (D)irect from bank t:_ 3 for ROs; ~ 4 for SROs & RO retakes)
(N)ew or (M)odified from bank (~ 1)
(P)revious 2 exams t:_ 1; randomly selected)
=--=============================================================================dl NUREG-1021, Revision 10 FENOC Facsimile rO
ES-301 Administrative Topics Outline Form ES-301-1 Facility: Beaver Valley Unit 2 Date of Examination: 12/7 thru 12/18 2015
' "qmination Level RO D SRO !RI Operating Test Number BV2LOT15 NRC
=
Administrative Type Describe activity to be performed Topic (See Note) Code*
Conduct of D,R 2.1.43 (4.3)
Operations Ability to use procedures to determine the effects on reactivity of (SRO A 1.1) plant changes, such as reactor coolant system temperature, secondary plant, fuel depletion, etc.
JPM 2AD-019 Plot and Evaluate 1/M Data and Determine Required Actions Conduct of N,R 2.1.4 (3.8)
Operations Knowledge of individual licensed operator responsibilities related to (SRO A 1.2) shift staffing, such as medical requirements, "no-solo" operation, maintenance of active license status, 10CFR55, etc.
JPM 3AD-024 Evaluate Operators Work History to Determine if License Status is Active (SRO)
Equipment Control N,R 2.2.41 (3.9)
, <0 A 2) Ability to obtain and interpret station electrical and mechanical drawings.
JPM 2AD-049 Identify Isolation Boundary Points and Mark on Plant VOND then Identify Method of Plant Configuration Control Radiation Control M,R 2.3.4 (3.7)
(SRO A 3) Knowledge of radiation exposure limits under normal or emergency conditions.
JPM 2AD-038 Determine Emergency Exposure Authorization Limits Emergency Plan D,R 2.4.44 (4.4)
(SRO A4) Knowledge of emergency plan protective action recommendations.
JPM 2AD-037 Determine Protective Action Recommendations (Part 1)
NOTE: All items (5 total) are required for SROs. RO applicants require only 4 items unless they are retaking only the administrative topics (which would require all 5 items).
- -* 1pe Codes & Criteria (C)ontrol Room, (S)imulator, or Class(R)oom (D)irect from bank ('.:. 3 for ROs; ~ 4 for SROs & RO retakes)
(N)ew or (M)odified from bank ~ 1)
(P)revious 2 exams ('.:. 1; randomly selected)
NUREG-1021, Revision 10 FENOC Facsimile rO
ES 301 C on t ro IRoom /I n- Pl an t Siys tems 0 utrme - -
Form ES 301 2 Facility: BVPS UNIT 2 Date of Examination: 12/7/15 thru 12/18/15 Exam Level: RO [RI SRO(I) D SRO(U) D Operating Test No.: BV2LOT15 NRC Control Room Systems@ (8 for RO); (7 for SRO-I); (2 or 3 for SRO-U)
System I JPM Title Type Code* Safety Function 81 - Transfer to Hot Leg Recirculation (2CR-570) S,D,EN 3 82 - Discharge Steam Generator Slowdown Evaporator Test Tank [2SGC- S, N,A 9 TK23A] to Unit 2 Cooling Tower Slowdown. (2CR-660)
S3 - Rod Control Assembly Partial Movement Test - (Rods continue to S,N,A 1 move during performance of the test) (2CR-747)
S4 - Batch to the Refuel Water Storage Tank (2CR-537) S,D 2 S5 - Perform QPTR Alarm Test (2CR-144) S,D 7 S6 - Respond to Containment Air Recirculation Fan High Vibration Alarm S,N,A 5 (2CR-661)
S7 - Perform a Hot Bus Transfer (2CR-523) S,D,A 6 S8 - Start A Reactor Coolant Pump (2CR-513) S, D,A, L 4P In-Plant Systems@ (3 for RO); (3 for SRO-I); (3 or 2 for SRO-U)
P1 - Uninterruptible Power Supply [UPS*VITBS2-3(4)] Shutdown (2PL-021) D 6 P2 - Reset the Terry Turbine Trip Throttle Valve (2PL-004) D,R 4S P3 - Place the Diesel Air Compressor in Service (2PL-031) D, E 8
@ All RO and SRO control room (and in-plant) systems must be different and serve different safety functions; all 5 SRO-U systems must serve different safety functions; in-plant systems and functions may overlap those tested in the control room.
- Type Codes Criteria for RO I SRO-I / SRO-U (A)lternate Path 4-6 /4-6 /2-3 (C)ontrol room (D)irect from bank S9/S8/S4 (E)mergency or abnormal in-plant ;?:1/;?:1/;?:1 (EN)gineered safety feature ;::: 1 I;::: 1 I~ 1 (control room system)
(L)ow-power I Shutdown ;?:1/;?:1/;?:1 (N)ew or (M)odified from bank including 1(A) ;?:2/;?:2/;?:1 (P)revious 2 exams ::; 3/::; 3 /::; 2 (randomly selected)
- ?
- 1/;?:1/:<!1 II (R)CA (S)imulator NUREG-1021, Revision 10 FENOC Facsimile
ES -301 C on t ro IR oom /I n- Pl an t Siys tems 0 utrme -
Form ES 301 -2 Facility: BVPS UNIT 2 Date of Examination: 12/7/15 th1u 1£/ IV/
Exam Level: ROD SRO(I) [RI SRO(U) D Operating Test No.: BV2LOT15 NRC Control Room Systems@ (8 for RO); (7 for SRO-I); (2 or 3 for SRO-U)
System I JPM Title Type Code* Safety Function S1 - Transfer to Hot Leg Recirculation (2CR-570) S,D,EN 3 S2 - Discharge Steam Generator Slowdown Evaporator Test Tank [2SGC- S,N,A 9 TK23A] to Unit 2 Cooling Tower Slowdown. (2CR-660)
S3 - Rod Control Assembly Partial Movement Test - (Rods continue to S, N,A 1 move during performance of the test) (2CR-747)
S4 - Batch to the Refuel Water Storage Tank (2CR-537) S,D 2 S6 - Respond to Containment Air Recirculation Fan High Vibration Alarm S,N,A 5 (2CR-661)
S7 - Perform a Hot Bus Transfer (2CR-523) S,D,A 6 SB - Start A Reactor Coolant Pump (2CR-513) S, D,A, L 4P In-Plant Systems@ (3 for RO); (3 for SRO-I); (3 or 2 for SRO-U)
P1 - Uninterruptible Power Supply [UPS*VITBS2-3(4)] Shutdown (2PL-021) D 6 P2 - Reset the Terry Turbine Trip Throttle Valve (2PL-004) D,R 4S P3 - Place the Diesel Air Compressor in Service (2PL-031) D, E 8
@ All RO and SRO control room (and in-plant) systems must be different and serve different safety functions; all 5 SRO-U systems must serve different safety functions; in-plant systems and functions may overlap those tested in the control room.
- Type Codes Criteria for RO I SRO-I I SRO-U (A)lternate Path 4-6 /4-6 /2-3 (C)ontrol room (D)irect from bank S9/S8/S4 (E)mergency or abnormal in-plant 2!1/2!1/2!1 (EN)gineered safety feature 2! 1 I 2! 1 I~ 1 (control room system)
(L)ow-power I Shutdown 2!1/2!1/2!1 (N)ew or (M)odified from bank including 1(A) 2!2/2!2/2! 1 (P)revious 2 exams s 3/ s 3 Is 2 (randomly selected)
(R)CA 2!1/2!1/2!1 ii (S)imulator NUREG-1021, Revision 10 FENOC Facsimile
A,ppen d"1x D s cenario Outline 2L1 5 N1 Facility: BVPS Unit2 Scenario No. 1 Op Test No.: BV2LOT15 NRC Examiners: Candidates: SRO ATC BOP Initial IC-142(15): 48% power, MOL, Equ. XE Conditions, CB "D"@ 158 steps, RCS boron -
Conditions: 558 ppm.
Turnover: Maintain 48% power.
Critical Tasks: 1. CT-10 (E-0.M) Crew closes PORV block MOV
- 2. CT-13 (E-0.Q) Crew manually trips turbine
- 3. CT-43 (FR-H.1.A) Crew establishes feedwater flow Event Malf. No. Event Type Event Description No.
1 XMT-RCS019A (I,A) ATC, SRO Pressurizer level transmitter, 2RCS*LT459 drifts low.
(TS) SRO 2 XMT-MSS053A (I,A) BOP, SRO 2MSS*PT496 fails low over 30 sec, requires manual control of (TS) SRO 2FWS*FCV498.
3 RCS02A (C,A) A TC, SRO 30 gpm RCS leak (unisolable)
(TS) SRO t (R) ATC (N) BOP, SRO Ops management directed Emergency Shutdown, AOP 2.51.1.
5 RCS02A (M) ALL 400 gpm loop A LOCA , requires manual Rx trip 6 EHC08A (C) BOP, SRO Auto main Turbine trip failure 7 VLV-RCS034A 2RCS*PCV456 lifts/fails to reseat on Rx trip, requires manual (C) ATC, SRO closure of MOV block valve, 2RCS*MOV536.
8 PMP-AFWOO 1, 2, (M) ALL Loss of all feed, Entry into FR-H.1, success path - main feed LOA-AFW022 9 VLV- 2SSR-AOV117A, B, C, SG BD sample line auto isolation MSC104,105,106 (C) ATC, SRO failure (N)ormal, (R)eactivity, (I)nstrument, (C)omponent, (M)ajor, (A)bnormal E-O-FR-H.1 -E-O- E-1 NUREG-1021, Revision 10 FENOC Facsimile rO
Appendix D Scenario Outline 2L15N1 After taking the shift at 48% power, Pressurizer level transmitter, 2RCS-LT459 will drift low. The crew will diagnose the indications and IA W AOP 2.4.1, Process Control Failure, remove the failed channel from service and ensure the plant is stable, the SRO will transition to the instrument failure procedure for further channel actions and will address Tech Specs for the failed channel.
The channel 3, "C" SG steam pressure transmitter, 2MSS*PT496, will then drift low, the crew will recognize the SG level perturbation and IA W AOP 2.4.1, the BOP will place the controller for 2FWS*FCV498 in manual and will restore SG level, the SRO will transition to the instrument failure procedure for additional channel removal actions and will address Tech Specs for the failed instrument.
A non-isolable 30 gpm leak will then occur on the "A" loop, the crew will enter AOP 2.6.7, Excessive Primary Plant Leakage, to evaluate leak rate and leak location. The crew will determine the leak rate is greater than 10 gpm and is not isolable. The SM will report to the SRO that due to the leakage, management directs an immediate plant shutdown IAW AOP 2.51.1 at 2% per minute.
When reactor power lowers to< 42%, the RCS leak will increase to 400 gpm. The crew will identify degrading plant parameters and the SRO will direct a pre-emptive reactor trip and enter E-0. The turbine will fail to automatically trip due to the reactor trip, the BOP will manually trip the turbine.
Additionally, PORV, 2RCS*PCV456 will fail 20% open on the reactor trip. The ATC will identify the open PORV, attempt to close it, recognize that the PORV did not close and close the block valve, 2RCS*MOV536 to isolate the stuck open PORV.
When "Verifying AFW Status" in E-0, the crew will identify that all auxiliary feedwater pumps have failed, the SRO will transition to FR-H.1. While performing the actions ofFR-H.1, the ATC will identify that the SG blowdown sample valves failed to automatically close and will manually close 2SSR*AOV 117A, B &
C.
IA W FR-H.1 direction the crew will restore feedwater flow by starting a main feedwater pump. After feed flow is verified, the SRO will return to E-0.
The crew will progress thru E-0 and transition to E-1 after diagnosing that containment pressure and sump level are not consistent with pre-event values.
The scenario will be terminated when the crew "Checks if SI Flow Should be Reduced" and determines plant conditions support SI termination and transition to ES-1.1.
Expected procedure flow path is E FR-H.1 - E E-1 NUREG-1021, Revision 10 FENOC Facsimile rO
A.ppen d"1x D s cenario
- outme r 2L15N2 Facility: BVPS Unit 2 Scenario No. 2 Op Test No.: BV2LOT15 NRC Examiners: Candidates: SRO ATC BOP Initial IC-143 (10): 100% power, BOL, Equ. XE Conditions, CB "D" @227 steps, RCS boron -
Conditions: 1100 ppm.
Turnover: Maintain current plant conditions Critical Tasks: 1. CT-6 (E-0.1) Crew establishes SIS Flow
- 2. CT-52 (FR-S.l.C) Crew inserts negative reactivity
- 3. CT-17 (E-2.A) Crew isolates the faulted SG Event Malf. No. Event Type Event Description No.
1 XMT-MSS043A (R) ATC Load rejection - VPL failure, (N) BOP/SRO 20M-26.4.X 2 GEN02 (C,A) BOP/SRO MUG Voltage regulator overexcitation failure.
3 XMT-RCS030A (I,A) ATC/SRO 2RCS*PT444 drifts HIGH, PRZR pressure decreases, manual SROT.S. control of PRZR pressure required.
4 FLX-CFW33 (M)ALL 2800 gpm Feedwater leak inside CNMT on "C" SG. CNMT
.., ' SRO T.S . pressure rises above TS allowable prior to trip.
5 PPLOlA (M) ALL ATWS - Failure of auto/manual Rx trip.
PPLOlB 6 CRFOlA (C) ATC/SRO Control Rods require manual insertion.
7 VLV-SIS069 2SIS*MOV867A and 2SIS*MOV867B auto open failure.
VLV-SIS070 (C) ATC, SRO 8 VLV-MSC021, (C) BOP/SRO "B" Train Hydrogen Analyzer fails to automatically start on 023,024,025 SIS signal.
9 VLV-AFW014 (C) BOP/SRO AFW valve, 2FWE*HCV100B, fails to close from the CR.
(N)ormal, (R)eactivity, (I)nstrument, (C)omponent, (M)ajor, (A)bnormal E-0----+ FR-S.1 ----+ E-0----+ E-2 NUREG-1021, Revision 10 FENOC Facsimile rO
Appendix D Scenario Outline 2L15N2 After taking the shift at 100% power, the valve position limiter will fail to 70% causing a load rejection.
The control rods will initially insert in response to the load rejection but will stop moving at 217 steps. The crew will initially respond with AOP 2.1.3, Unexpected Control Rod Movement, and then transition to AOP 2.35.2, Load Rejection, after the load rejection is diagnosed. The crew will stabilize the plant after which the BOP will be directed to use procedure 20M-26.4.X, Recovering Turbine Governor Valves from the Valve Position Limiter, to remove the turbine from the valve position limiter.
The MUG, main unit generator, voltage regulator will then fail causing an over excitation of the MUG, IAW AOP 2.4.1, Process Control Failure, the BOP will place the voltage regulator to "OFF" and correct the over excitation by manually adjusting the "base adjust".
The controlling PRZR pressure channel, 2RCS*PT444 will drift high causing RCS pressure to lower due to the pressurizer spray valves/PORV's opening. The crew will initially respond IAW AOP 2.4.1, identify the failure and close the spray valves/PORV's, the SRO will then transition to 20M-6.4.IF, attachment 2 to address the failed channel. The ATC controls PRZR pressure by manually operating the PRZR heaters and spray valves, or manual control of the PRZR pressure master controller. The SRO will address applicable TS entered due to the instrument failure.
A ramped 2800 gpm feedwater leak on the "C" SG inside of containment causing containment pressure to rise above TS allowable, the crew will investigate and diagnose a feedwater leak inside containment. The SRO will direct a pre-emptive reactor trip due to the leak. The reactor will fail to trip from the control room. The SRO will direct the ATC and BOP to perform the IOA's ofFR-S.l, "Response to Nuclear Power Generation - ATWS. The control rods will require manual insertion by the ATC. The reactor will be tripped via a local operator after being dispatched and the crew will return to E-0.
SIS will automatically actuate due to high containment pressure. Upon SIS actuation, 2SIS*MOV867A and 2SIS*MOV867B will fail to automatically open, the ATC will manually open valves to initiate SIS injection flow.
Additionally, the "B" train Hydrogen Analyzer will fail to automatically start due to the SI signal, the BOP will manually start the "B" Hydrogen Analyzer.
The crew will progress thru E-0, diagnose a faulted SG and transition to E-2, Faulted Steam Generator Isolation.
When the BOP attempts to isolate Aux feedwater flow to the "C" SG, it will be identified that 2FWE*HCV100B will fail to close from the Control Room. The BOP will take contingency actions using EOP Attachment A-1.24, AFW Throttle Valve Failure, to isolate AFW flow to the faulted "C" SG.
After the crew has completed isolation of the faulted SG, plant conditions will support SI termination, the crew will transition to ES-1.1, SI Termination, at which time the scenario will be terminated.
Expected procedure flow path is E FR-S.1 - E E-2 NUREG-1021, Revision 10 FENOC Facsimile rO
A,ppen d"1x D s cenario Outline 2L15N4 Facility: BVPS Unit2 Scenario No. 4 Op Test No.: BV2LOT15 NRC Examiners: Candidates: SRO ATC BOP Initial IC 145: 4.8% power, MOL, Rx SIU in progress, CB "D"@ 105 steps, RCS boron - 1349 Conditions: ppm.
Turnover: Raise power to 15% to SIU main turbine IAW 20M-52.4.A.
Critical Tasks: 1. CT-11 (E-0.0) Cnmt isolation
- 2. CT-18 (E-3.A) Crew isolates ruptured SG
- 3. CT-19 (E-3.B) Crew establishes/maintains RCS temperature
- 4. CT-20 (E-3.C) Crew depressurizes RCS to meet SI termination criteria Event Malf. No. Event Type Event Description No.
1 (R)ATC Normal power increase to 15% IAW 20M-52.4.A (N) SRO 2 CNH-CFWll (C,A) BOP/SRO 2FWS*FCV479, Bypass Feedwater valve controller fails as is in AUTO, requires manual operation.
3 PMP-CHS002 (C,A) ATC/SRO 2CHS*P21B, Charging/ HHSI pump shaft seizure.
SRO (TS) 4 XMT-MSC038A SRO (TS) 2LMS*PT952, CNMT Pressure transmitter fails high 5 PPL02A (M) ALL Spurious Rx trip 6 RCS04B (M) ALL 21B SG 520 gpm Tube Rupture 7 PPL07B (C) ATC/SRO 2CHS *P21 C, Charging I HHSI auto start failure 8 VLV-SEA015 (C) BOP/SRO Train B CIA failure with 2CHS*MOV378 failing to auto close 9 VLV- (C) ATC/SRO PRZR PORV fails to close when opened for RCS RCS03 2,3 3 ,34 depressurization in E-3, requires isolation.
(N)ormal, (R)eactivity, (I)nstrument, (C)omponent, (M)ajor, (A)bnormal E ES-0.1 - E E-3 NUREG-1021, Revision 10 FENOC Facsimile rO
Appendix D Scenario Outline 2L15N4 The crew will take the shift at 4.8% power with instructions to raise power to 15% IAW the reactivity plan to SIU the main turbine. The following malfunctions will occur as power is raised.
After power is >5% and a dilution has been performed, the "B" Charging/ HHSI pump will experience a shaft seizure. The crew will respond with AOP 2.7.1, Loss of Charging or Letdown, and start the standby charging pump after isolating charging and letdown. The crew will dispatch operators to place the spare charging pump 2CHS*P21C in service on the 2DF bus. The SRO will address the applicable TS.
Also occurring at 5% power, the "A" bypass feedwater regulating valve controller will fail as is. As power rises, the controller problem will become evident requiring the BOP to manually control "A" SG level IA W AOP 2.4.1, Process Control Failure.
At 8% reactor power, Containment Pressure Transmitter, 2LMS*PT952, will fail high. The SRO will enter the instrument failure procedure and address the applicable TS.
When the reactor reaches 10% power, a spurious reactor trip will occur, the crew will enter E-0, Reactor Trip and Safety Injection. The crew will determine SI is not actuated nor required and transition to ES-0.1, Reactor Trip Response.
5 minutes after the reactor trip occurs a 520 gpm SGTR, steam generator tube rupture, will occur on the "B" SG. The crew will note that plant parameters are degrading and IA W ES-0.1, left hand page direction, actuate SI and return to E-0. The crew will diagnose a SGTR has occurred and will transition to E-3, Steam Generator Tube Rupture.
2CHS *P21 C will fail to automatically start from the SIS but will start when the ATC attempts a manual start.
The safety injection actuation will fail to actuate the train "B" CIA signal, and train "A" CIA valve, 2CHS*MOV378 will fail to automatically close. While performing attachment A-0.11, Verification of Automatic Actions, the BOP will recognize the failure and isolate the containment penetration via either manually actuating Train "B" CIA or manually closing 2CHS*MOV378.
The crew will progress thru E-3, when a PORV is opened to depressurize the RCS it will fail to close, the ATC will then close the applicable MOV block valve to isolate the stuck open PORV.
The scenario will be terminated after the crew establishes a normal charging flowpath in E-3.
Expected procedure flow path is E-0 ~ ES-0.1 ~ E-0 ~ E-3 NUREG-1021, Revision 10 FENOC Facsimile rO