(DRN 05-1013, Am. 103) 3/4 8-1 AMENDMENT NO. 103 (DRN 05-1013, Am. 103)

(DRN 05-1013, Am. 103) 3/4.8 ELECTRICAL POWER SYSTEMS

3/4.8.1 A.C. SOURCES

OPERATING LIMITING CONDITION FOR OPERATION

3.8.1.1 Offsite A.C. circuit voltage, as measured at the Waterford 3 Switchyard, shall be such that predicted post-trip offsite A.C. circuit voltage, as determined by the Grid Operator, will be sufficient to supply post-trip emergency loads.

APPLICABILITY

MODE 1

ACTIONS:

a. When notified by the Grid Operator that predicted post-trip offsite A.C. circuit voltage will be less than 223kV, initiate a Condition Report and complete an

offsite A.C. circuit operability determination within 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />.

SURVEILLANCE REQUIREMENTS

None (DRN 05-1013, Am. 103)

(DRN 07-136, Am. 111) 3/4 8-2AMENDMENT NO. 111 (DRN 07-136, Am. 111)

(DRN 07-136, Am. 111) 3/4.8 ELECTRICAL POWER SYSTEMS

3/4.8.1 A.C. SOURCES

OPERATING/SHUTDOWN

LIMITING CONDITION FOR OPERATION

3.8.1.2 Manufacturers Recommended Inspections of the Emergency Diesel Generator


Note---------------------------------------------------------------

Failure to meet the surveillance requirements do not impact the ability of the emergency diesel generator to perform its safety function.


APPLICABILITY

All MODES

ACTIONS:

a. The provisions of TRM 3.0.3 and 3.0.4 are not applicable.

SURVEILLANCE REQUIREMENTS

4.8.1.2.1 At intervals of 4.5 years or less, subject the diesels to an inspection in accordance with procedures prepared in conjunction with its manufacturers recommendations

for this class of standby service. (DRN 07-136, Am. 111)

(DRN 02-1639; 05-1013,07-136, Am. 111

) 3/4 8-3 AMENDMENT NO. 34, 67, 91

, 103 , 111 (DRN 02-1639; 05-1013,07-136, Am. 111

) (DRN 02-1639)

ELECTRICAL POWER SYSTEMS 3/4.8.3 ONSITE POWER DISTRIBUTION SYSTEMS

OPERATING LIMITING CONDITION FOR OPERATION

3.8.3.1 The rectifiers for the following Static Uninterruptible Power Supplies (SUPS) shall be OPERABLE.

a. SUPS-3MA-S
b. SUPS-3MB-S
c. SUPS-3MC-S
d. SUPS-3MD-S
e. SUPS-3A-S
f. SUPS-3B-S
g. SUPS-3AB-S

APPLICABILITY: MODES 1, 2, 3 and 4.

ACTION: (DRN 04-1191, Am. 91)

a. With any of the above listed SUPS rectifiers inoperable and the associated SUPS is not being supplied from the bypass AC power, restore the rectifier to operable

status or verify the two associated battery chargers are in service within 24

hours; otherwise, enter TRM LCO 3.0.3. (DRN 04-1191, Am. 91)

SURVEILLANCE REQUIREMENTS 4.8.3.1 No additional surveillance requirements other than those required by Technical Specifications 4.8.3.

(DRN 02-1639)

(DRN 05-1013,07-136, Am. 111

) 3/4 8-4 AMENDMENT NO. 13 , 103 , 111 (DRN 05-1013,07-136, Am. 111

) The primary and backup Containment Penetration Conductor Overcurrent Protective Devices listed in Table 3.8-1 are the protective devices that are applicable to Technical Specification 3.8.4.1.

3/4 8-2 AMENDMENT NO. 14 , 95 TABLE 3.8-1 CONTAINMENT PENETRATION CONDUCTOR OVER-CURRENT PROTECTIVE DEVICES OVER-CURRENT PROTECTIVE DEVICES WITHIN EACH VOLTAGE LEVEL (ROMAN) MODES BREAKER IDENTIFYING TIME INTEG. INSP & FOR PROTEC./ NUMBER CURRENT FUNC. CHANNEL FUNC. PREV. WHICH AFFECTED OR CHARAC- TEST CALIB. TEST MAINT. SURV IS COMPONENTS DRAWING DESCRIPTION TYPE TERISTIC 4.8.4.1.a.2 4.8.4.1.a.1.a 4.8.4.1.a.1.b 4.8.4.1.b REQD I 6.9 KV POWER FROM MEDIUM VOLTAGE SWITCHGEAR (NOTE I.3) 1 REACTOR COOLANT PUMP 1A a Primary 289-11A1 Line 15,16,17 Note I.1 Note I.2 NA 10% per R 10% per R every 60 M 1,2,3,4 RC EBKR1A-7A RC EREL1A-7L RC EREL1A-7K RC EREL1A-7M RC EREL1A-7N b Backup (DRN 04-2065, Am. 95) 7KVEBKR1A-1 . RC EREL220-D 424-220 TD Relay 2 adjust to 4 sec NA 10% per R 10% per R every 60 M 1,2,3,4 7KVEREL1A-1E 289-11A1 Line 1 Note I.1 Note II.5 NA 10% per R 10% per R every 60 M 1,2,3,4 7KVEREL1A-1F 289-11A1 Line 1 Note I.1 Note II.5 NA 10% per R 10% per R every 60 M 1,2,3,4 7KVEREL1A-1G 289-11A1 Line 1 Note I.1 Note II.5 NA 10% per R 10% per R every 60 M 1,2,3,4 c Backup 7KVEBKR1A-4 RC EREL220-D 424-220 TD Relay 2 adjust to 4 sec NA 10% per R 10% per R every 60 M 1,2,3,4 7KVEREL1A-4E 289-11A1 Line 10 Note I.1 Note II.5 NA 10% per R 10% per R every 60 M 1,2,3,4 7KVEREL1A-4F 289-11A1 Line 10 Note I.1 Note II.5 NA 10% per R 10% per R every 60 M 1,2,3,4 7KVEREL1A-4G 289-11A1 Line 10 Note I.1 Note II.5 NA 10% per R 10% per R every 60 M 1,2,3,4 (DRN 04-2065, Am. 95) 2 REACTOR COOLANT PUMP 1B a Primary 289-12A1 Line 15,16,17 Note I.1 Note I.2 NA 10% per R 10% per R every 60 M 1,2,3,4 RC EBKR1B-7A RC EREL1B-7A RC EREL1B-7C RC EREL1B-7B RC EREL1B-7D

3/4 8-3 AMENDMENT NO. 14 , 95 TABLE 3. 8-1 (contd)

CONTAINMENT PENETRATION CONDUCTOR OVER-CURRENT PROTECTIVE DEVICES OVER-CURRENT PROTECTIVE DEVICES WITHIN EACH VOLTAGE LEVEL (ROMAN) MODES BREAKER IDENTIFYING TIME INTEG. INSP & FOR PROTEC./ NUMBER CURRENT FUNC. CHANNEL FUNC. PREV. WHICH AFFECTED OR CHARAC- TEST CALIB. TEST MAINT. SURV IS COMPONENTS DRAWING DESCRIPTION TYPE TERISTIC 4.8.4.1.a.2 4.8.4.1.a.1.a 4.8.4.1.a.1.b 4.8.4.1.b REQD b Backup (DRN 04-2065, Am. 95) 7KVEBKR1B-1 RC EREL230-D 424-230 TD Relay 2 adjust to 4 sec NA 10% per R 10% per R every 60 M 1,2,3,4 7KVEREL1B-1E 289-12A1 Line 1 Note I.1 Note II.5 NA 10% per R 10% per R every 60 M 1,2,3,4 7KVEREL1B-1F 289-12A1 Line 1 Note I.1 Note II.5 NA 10% per R 10% per R every 60 M 1,2,3,4 7KVEREL1B-1G 289-12A1 Line 1 Note I.1 Note II.5 NA 10% per R 10% per R every 60 M 1,2,3,4 c Backup

7KVEBKR1B-4 RC EREL230-D 424-230 TD Relay 2 adjust to 4 sec NA 10% per R 10% per R every 60 M 1,2,3,4 7KVEREL1B-4E 289-12A1 Line 10 Note I.1 Note II.5 NA 10% per R 10% per R every 60 M 1,2,3,4 7KVEREL1B-4F 289-12A1 Line 10 Note I.1 Note II.5 NA 10% per R 10% per R every 60 M 1,2,3,4 7KVEREL1B-4G 289-12A1 Line 10 Note I.1 Note II.5 NA 10% per R 10% per R every 60 M 1,2,3,4 (DRN 04-2065, Am. 95) 3 REACTOR COOLANT PUMP 2A a Primary 289-11A1 Line 18,19,20 Note I.1 Note I.2 NA 10% per R 10% per R every 60 M 1,2,3,4 RC EBKR1A-8A RC EREL1A-8A RC EREL1A-8C RC EREL1A-8B RC EREL1A-8D b Backup

(DRN 04-2065, Am. 95) 7KVEBKR1A-1 RC EREL240-D 424-240 TD Relay 2 adjust to 4 sec NA 10% per R 10% per R every 60 M 1,2,3,4 7KVEREL1A-1E 289-11A1 Line 1 Note I.1 Note II.5 NA 10% per R 10% per R every 60 M 1,2,3,4 7KVEREL1A-1F 289-11A1 Line 1 Note I.1 Note II.5 NA 10% per R 10% per R every 60 M 1,2,3,4 7KVEREL1A-1G 289-11A1 Line 1 Note I.1 Note II.5 NA 10% per R 10% per R every 60 M 1,2,3,4 (DRN 04-2065, Am. 95)

3/4 8-4 AMENDMENT NO. 14 , 95 TABLE 3.8-1 CONTAINMENT PENETRATION CONDUCTOR OVER-CURRENT PROTECTIVE DEVICES OVER-CURRENT PROTECTIVE DEVICES WITHIN EACH VOLTAGE LEVEL (ROMAN) MODES BREAKER IDENTIFYING TIME INTEG. INSP & FOR PROTEC./ NUMBER CURRENT FUNC. CHANNEL FUNC. PREV. WHICH AFFECTED OR CHARAC- TEST CALIB. TEST MAINT. SURV IS COMPONENTS DRAWING DESCRIPTION TYPE TERISTIC 4.8.4.1.a.2 4.8.4.1.a.1.a 4.8.4.1.a.1.b 4.8.4.1.b REQD c Backup (DRN 04-2065, Am. 95) 7KVEBKR1A-4 RC EREL240-D 7KVEREL1A-4E 424-240 289-11A1 TD Relay 2 Line 10 Note I.1 Adjust to 4 sec Note II.5 NA NA 10% per R 10% per R 10 % per R 10% per R Every 60 M every 60 M 1,2,3,4 1,2,3,4 7KVEREL1A-4F 289-11A1 Line 10 Note I.1 Note II.5 NA 10% per R 10% per R every 60 M 1,2,3,4 7KVEREL1A-4G 289-11A1 Line 10 Note I.1 Note II.5 NA 10% per R 10% per R every 60 M 1,2,3,4 (DRN 04-2065, Am. 95) 4 REACTOR COOLANT PUMP 2B a Primary 289-12A1 Line 18,19,20 Note I.1 Note I.2 NA 10% per R 10% per R every 60 M 1,2,3,4 RC EBKR1B-8A RC EREL1B-8A RC EREL1B-8C RC EREL1B-8B RC EREL1B-8D b Backup (DRN 04-2065, Am. 95) 7KVEBKR1B-1 RC EREL250-D 424-250 TD Relay 2 adjust to 4 sec NA 10% per R 10% per R every 60 M 1,2,3,4 7KVEREL1B-1E 289-12A1 Line 1 Note I.1 Note II.5 NA 10% per R 10% per R every 60 M 1,2,3,4 7KVEREL1B-1F 289-12A1 Line 1 Note I.1 Note II.5 NA 10% per R 10% per R every 60 M 1,2,3,4 7KVEREL1B-1G 289-12A1 Line 1 Note I.1 Note II.5 NA 10% per R 10% per R every 60 M 1,2,3,4 c Backup 7KVEBKR1B-4 RC EREL250-D 424-250 TD Relay 2 adjust to 4 sec NA 10% per R 10% per R every 60 M 1,2,3,4 7KVEREL1B-4E 289-12A1 Line 10 Note I.1 Note II.5 NA 10% per R 10% per R every 60 M 1,2,3,4 7KVEREL1B-4F 289-12A1 Line 10 Note I.1 Note II.5 NA 10% per R 10% per R every 60 M 1,2,3,4 7KVEREL1B-4G 289-12A1 Line 10 Note I.1 Note II.5 NA 10% per R 10% per R every 60 M 1,2,3,4 (DRN 04-2065, Am. 95)

Items I.1 thru I.4 - Transfer Trip Relays provide backup protection via Startup Transformer and Unit Auxiliary Transformer Breakers Performing the INTEG FUNCT TEST satisfies CHAN CAL.

FSAR Figure 8.3-28 illustrates operation of primary and backup over-current protection.

3/4 8-5 TABLE 3.8-1 (cont'd)

CONTAINMENT PENETRATION CONDUCTOR OVER-CURRENT PROTECTIVE DEVICES OVER-CURRENT PROTECTIVE DEVICES WITHIN EACH VOLTAGE LEVEL (ROMAN) MODES BREAKER IDENTIFYING TIME INTEG. INSP & FOR PROTEC./ NUMBER CURRENT FUNC. CHANNEL FUNC. PREV. WHICH AFFECTED OR CHARAC- TEST CALIB. TEST MAINT. SURV IS COMPONENTS DRAWING DESCRIPTION TYPE TERISTIC 4.8.4.1.a.2 4.8.4.1.a.1.a 4.8.4.1.a.1.b 4.8.4.1.b REQ'D II 480 VOLTS POWER FROM LOW VOLTAGE SWITCHGEAR (NOTE II.6) a Primary 289-20A1 Line 16 Note II.1 Note II.2,II.3 10% of Type NA NA every 60 M 1,2,3,4 per R CRNEBKR31A-8A b Primary 289-20A2 Line 16 Note II.1 Note II.2,II.3 10% of Type NA NA every 60 M 1,2,3,4 per R CRNEREL31A-11C CRNEREL31A-11A CRNEREL31A-11B c Backup 424-2485 TD Relay 2 adjust to 2 sec NA 10% per R 10% per R every 60 M 1,2,3,4 CRNEREL2485 SSDEBKR3A-15

2 CEDM COOLING UNIT E-16 (3A) a Primary* 289-20A1 Line 17 Note II.1 Note II.2,II.3 10% of Type NA NA every 60 M 1,2,3,4 per R CDCEBKR31A-8B b Primary* 289-20A2 Line 17 Note II.1 Note II.2,II.3 10% of Type NA NA every 60 M 1,2,3,4 per R CDCEREL31A-11C CDCEREL31A-11A CDCEREL31A-11B

  • Note II.4 3/4 8-6 TABLE 3.8-1 (cont'd)

CONTAINMENT PENETRATION CONDUCTOR OVER-CURRENT PROTECTIVE DEVICES OVER-CURRENT PROTECTIVE DEVICES WITHIN EACH VOLTAGE LEVEL (ROMAN) MODES BREAKER IDENTIFYING TIME INTEG. INSP & FOR PROTEC./ NUMBER CURRENT FUNC. CHANNEL FUNC. PREV. WHICH AFFECTED OR CHARAC- TEST CALIB. TEST MAINT. SURV IS COMPONENTS DRAWING DESCRIPTION TYPE TERISTIC 4.8.4.1.a.2 4.8.4.1.a.1.a 4.8.4.1.a.1.b 4.8.4.1.b REQ'D 2 CEDM COOLING UNIT E-16 (3A) (Continued) c Backup 424-1139 TD Relay 2 adjust to 1 sec NA 10% per R 10% per R every 60 M 1,2,3,4

CDCEREL1139-3 SSDEBKR3A-15

3 CEDM COOLING UNIT E-16 (3C) a Primary* 289-20A3 Line 23 Note II.1 Note II.2, II.3 10% of Type NA NA every 60 M 1,2,3,4 per R CDCEBKR31A-9B b Primary* 289-20A4 Line 23 Note II.1 Note II.2,II.3 10% of Type NA NA every 60 M 1,2,3,4 per R CDCEREL31A-11H CDCEREL31A-11F CDCEREL31A-11G c Backup 424-1140 TD Relay 2 adjust to 1 sec NA 10% per R 10% per R every 60 M 1,2,3,4 CDCEREL1140-3 SSDEBKR3A-15

4 CEDM COOLING UNIT E-16 (3B) a Primary* 289-21A1 Line 18 Note II.1 Note II.2,II.3 10% of Type NA NA every 60 M 1,2,3,4 per R CDCEBKR31B-8B

  • Note II.4 3/4 8-7 AMENDMENT NO. 105 TABLE 3.8-1 (contd)

CONTAINMENT PENETRATION CONDUCTOR OVER-CURRENT PROTECTIVE DEVICES OVER-CURRENT PROTECTIVE DEVICES WITHIN EACH VOLTAGE LEVEL (ROMAN) MODES BREAKER IDENTIFYING TIME INTEG. INSP & FOR PROTEC./ NUMBER CURRENT FUNC. CHANNEL FUNC. PREV. WHICH AFFECTED OR CHARAC- TEST CALIB. TEST MAINT. SURV IS COMPONENTS DRAWING DESCRIPTION TYPE TERISTIC 4.8.4.1.a.2 4.8.4.1.a.1.a 4.8.4.1.a.1.b 4.8.4.1.b REQD 4 CEDM COOLING UNIT E-16 (3B) (Continued) b Primary* 289-21A2 Line 18 Note II.1 Note II.2,II.3 10% of Type NA NA every 60 M 1,2,3,4 per R CDCEREL31B-11M CDCEREL31B-11K CDCEREL31B-11L (DRN 05-90, Am. 105) c Backup 424-114 1 TD Relay 2 adjust to 1 sec NA 10% per R 10% per R every 60 M 1,2,3,4 (DRN 05-90, Am. 105)

CDCEREL1141-3 SSDEBKR3B-10

5 CEDM COOLING UNIT E-16 (3D) a Primary* 289-21A3 Line 24 Note II.1 Note II.2, II.3 10% of Type NA NA every 60 M 1,2,3,4 per R CDCEBKR31B-9B b Primary* 289-21A4 Line 24 Note II.1 Note II.2, II.3 10% of Type NA NA every 60 M 1,2,3,4 per R CDCEREL31B-11R CDCEREL31B-11P CDCEREL31B-11Q (DRN 05-90, Am. 105) c Backup 424-114 2 TD Relay 2 adjust to 1 sec NA 10% per R 10% per R every 60 M 1,2,3,4 (DRN 05-90, Am. 105)

CDCEREL1142-3 SSDEBKR3B-10 3/4 8-8 TABLE 3.8-1 (cont'd)

CONTAINMENT PENETRATION CONDUCTOR OVER-CURRENT PROTECTIVE DEVICES OVER-CURRENT PROTECTIVE DEVICES WITHIN EACH VOLTAGE LEVEL (ROMAN) MODES BREAKER IDENTIFYING TIME INTEG. INSP & FOR PROTEC./ NUMBER CURRENT FUNC. CHANNEL FUNC. PREV. WHICH AFFECTED OR CHARAC- TEST CALIB. TEST MAINT. SURV IS COMPONENTS DRAWING DESCRIPTION TYPE TERISTIC 4.8.4.1.a.2 4.8.4.1.a.1.a 4.8.4.1.a.1.b 4.8.4.1.b REQ'D6 PRESSURIZER HEATERS BACKUP BANK 1 (B-1) a Primary* 289-23A1 Line 4 Note II.1 Note II.2,II.5 10% of Type NA NA every 60 M 1,2,3,4 per R RC EBKR32A-4C *Note II.4 b Primary* 289-23A2 Line 4 Note II.1 Note II.2,II.5 10% of Type NA NA every 60 M 1,2,3,4 per R RC EREL32A-7S RC EREL32A-7T RC EREL32A-7U c Backup 424-285 TD relay 2 adjust to 0.5 sec NA 10% per R 10% per R every 60 M 1,2,3,4 RC EREL285-E SSDEBKR3A-8 7 PRESSURIZER HEATERS BACKUP BANK 2 (B-2) a Primary* 289-23A1 Line 5 Note II.1 Note II.2,II.5 10% of Type NA NA every 60 M 1,2,3,4 per R RC EBKR32A-4D b Primary* 289-23A2 Line 5 Note II.1 Note II.2, II.5 10% of Type NA NA every 60 M 1,2,3,4 per R RC EREL32A-7A RC EREL32A-7B RC EREL32A-7C c Backup 424-286 TD Relay 2 adjust to 0.5 sec NA 10% per R 10% per R every 60 M 1,2,3,4 RC EREL286-E SSDEBKR3A-8 3/4 8-9 TABLE 3.8-1 (cont'd)

CONTAINMENT PENETRATION CONDUCTOR OVER-CURRENT PROTECTIVE DEVICES OVER-CURRENT PROTECTIVE DEVICES WITHIN EACH VOLTAGE LEVEL (ROMAN) MODES BREAKER IDENTIFYING TIME INTEG. INSP & FOR PROTEC./ NUMBER CURRENT FUNC. CHANNEL FUNC. PREV. WHICH AFFECTED OR CHARAC- TEST CALIB. TEST MAINT. SURV IS COMPONENTS DRAWING DESCRIPTION TYPE TERISTIC 4.8.4.1.a.2 4.8.4.1.a.1.a 4.8.4.1.a.1.b 4.8.4.1.b REQ'D8 PRESSURIZER HEATERS BACKUP BANK 3 (B-3) a Primary* 289-23A1 Line 6 Note II.1 Note II.2,II.5 10% of Type NA NA every 60 M 1,2,3,4 per R RC EBKR32A-5A *Note II.4 b Primary* 289-23A2 Line 6 Note II.1 Note II.2, II.5 10% of Type NA NA every 60 M 1,2,3,4 per R RC EREL32A-7G RC EREL32A-7H RC EREL32A-7I c Backup 424-287 TD Relay 2 adjust to 0.5 sec NA 10% per R 10% per R every 60 M 1,2,3,4

RC EREL287-E SSD EBKR3A-8 9 PRESSURIZER HEATERS BACKUP BANK 4 (B-4) a Primary* 289-24A1 Line 4 Note II.1 Note II.2,II.5 10% of Type NA NA every 60 M 1,2,3,4 per R RC EBKR32B-4C b Primary* 289-24A2 Line 4 Note II.1 Note II.2,II.5 10% of Type NA NA every 60 M 1,2,3,4 per R RC EREL32B-7M RC EREL32B-7N RC EREL32B-7O c Backup 424-288 TD Relay 2 adjust to 0.5 sec NA 10% per R 10% per R every 60 M 1,2,3,4 RC EREL288-E SSDEBKR3B-9 3/4 8-10 TABLE 3.8-1 (cont'd)

CONTAINMENT PENETRATION CONDUCTOR OVER-CURRENT PROTECTIVE DEVICES OVER-CURRENT PROTECTIVE DEVICES WITHIN EACH VOLTAGE LEVEL (ROMAN) MODES BREAKER IDENTIFYING TIME INTEG. INSP & FOR PROTEC./ NUMBER CURRENT FUNC. CHANNEL FUNC. PREV. WHICH AFFECTED OR CHARAC- TEST CALIB. TEST MAINT. SURV IS COMPONENTS DRAWING DESCRIPTION TYPE TERISTIC 4.8.4.1.a.2 4.8.4.1.a.1.a 4.8.4.1.a.1.b 4.8.4.1.b REQ'D10 PRESSURIZER HEATERS BACKUP BANK 5 (B-5) a Primary* 289-24A1 Line 5 Note II.1 Note II.2, II.5 10% of Type NA NA every 60 M 1,2,3,4 per R RC EBKR32B-4D *Note II.4 b Primary* 289-24A2 Line 5 Note II.1 Note II.2,II.5 10% of Type NA NA every 60 M 1,2,3,4 per R RC EREL32B-7S RC EREL32B-7T RC EREL32B-7U c Backup 424-289 TD Relay 2 adjust to 0.5 NA 10% per R 10% per R every 60 M 1,2,3,4

RC EREL289-E SSDEBKR3B-9 11 PRESSURIZER HEATERS BACKUP BANK 6 (B-6) a Primary

  • 289-24A1 Line 6 Note II.1 Note II.2, II.5 10% of Type NA NA every 60 M 1,2,3,4 per R RC EBKR32B-5A b Primary* 289-24A2 Line 6 Note II.1 Note II.2,II.5 10% of Type NA NA every 60 M 1,2,3,4 per R RC EREL32B-7G RC EREL32B-7H RC EREL32B-7I Items II.6 thru II.11 -- The backup protection consists of Transfer Trip Relays activated by any one of the pimary over-current protective relays illutrated on FSAR Figure 8.3-30.

Note II.4 3/4 8-11 AMENDMENT NO. 105 TABLE 3.8-1 (contd)

CONTAINMENT PENETRATION CONDUCTOR OVER-CURRENT PROTECTIVE DEVICES OVER-CURRENT PROTECTIVE DEVICES WITHIN EACH VOLTAGE LEVEL (ROMAN) MODES BREAKER IDENTIFYING TIME INTEG. INSP & FOR PROTEC./ NUMBER CURRENT FUNC. CHANNEL FUNC. PREV. WHICH AFFECTED OR CHARAC- TEST CALIB. TEST MAINT. SURV IS COMPONENTS DRAWING DESCRIPTION TYPE TERISTIC 4.8.4.1.a.2 4.8.4.1.a.1.a 4.8.4.1.a.1.b 4.8.4.1.b REQD 11 PRESSURIZER HEATERS BACKUP BANK 6 (B-6)(Continued) c Backup 424-290 TD Relay 2 adjust to 0.5 sec NA 10% per R 10% per R every 60 M 1,2,3,4 RC EREL290-E SSDEBKR3B-9 12 PRESSURIZER HEATERS PROPORTIONAL BANK 1 (P-1) a Primary 289-23A1 Line 8 Note II.1 Note II.2, II.5 10% of Type NA NA every 60 M 1,2,3,4 per R RC EBKR32A-5C b Primary 289-23A2 Line 8 Note II.1 Note II.2, II.5 10% of Type NA NA every 60 M 1,2,3,4 per R RC EREL32A-7M RC EREL32A-7N RC EREL32A-7O c Backup CHASE- Fuse NA NA NA NA 1,2,3,4 SHAWMUT Fuses A50P200 13 PRESSURIZER HEATERS PROPORTIONAL BANK 2 (P-2) (DRN 05-90, Am. 105) a Primary 289-24A1 Line 8 Note II.1 Note II.2, II.5 10% of Type NA NA every 60 M 1,2,3,4 per R RC EBKR32B-5C b Primary 289-24A2 Line 8 Note II.1 Note II.2, II.5 10% of Type NA NA every 60 M 1,2,3,4 (DRN 05-90, Am. 105) per R RC EREL32B-7A RC EREL32B-7B RC EREL32B-7C

Items II.12 and II.13 -- The protpor tional heater local control pane l houses the backup protection.

3/4 8-12 TABLE 3. 8-1 (cont'd)

CONTAINMENT PENETRATION CONDUCTOR OVER-CURRENT PROTECTIVE DEVICES OVER-CURRENT PROTECTIVE DEVICES WITHIN EACH VOLTAGE LEVEL (ROMAN) MODES BREAKER IDENTIFYING TIME INTEG. INSP & FOR PROTEC./ NUMBER or CURRENT FUNC. CHANNEL FUNC. PREV. WHICH AFFECTED OR CHARAC- TEST CALIB. TEST MAINT. SURV IS COMPONENTS DRAWING DESCRIPTION TYPE TERISTIC 4.8.4.1.a.2 4.8.4.1.a.1.a 4.8.4.1.a.1.b 4.8.4.1.b REQ'D 13 PRESSURIZER HEATERS PROPORTIONAL BANK 2 (P-2)(Continued) c Backup CHASE- Fuse NA NA NA NA 1,2,3,4 SHAWMUT Fuses A50P200

III 240 VOLTS CEDM POWER (NOTES IV.3 & IV.4) 1 CEDM COILS (91 Circuits) a Primary Subgroup Bus Heine- Heinemann Series 10% per R NA NA every 60 M 1,2,3,4 mann 40 AM, Curve 3 CEDEBKR2438 AC2 CEDEBKR2438 BC2 CEDEBKR2438 CC2 CEDEBKR2438 DC2 CEDEBKR2438 EC2 CEDEBKR2438 FC2 CEDEBKR2438 GC2 CEDEBKR2438 HC2 CEDEBKR2438 IC2 CEDEBKR2438 JC2 CEDEBKR2438 AC3 CEDEBKR2438 BC3 CEDEBKR2438 CC3 CEDEBKR2438 DC3 CEDEBKR2438 EC3 CEDEBKR2438 FC3 CEDEBKR2438 GC3 CEDEBKR2438 HC3 CEDEBKR2438 IC3 CEDEBKR2438 JC3 3/4 8-13 AMENDMENT NO.27 TABLE 3.8-1 (cont'd) CONTAINMENT PENETRATION CONDUCTOR OVER-CURRENT PROTECTIVE DEVICES OVER-CURRENT PROTECTIVE DEVICES WITHIN EACH VOLTAGE LEVEL (ROMAN) MODES BREAKER IDENTIFYING TIME INTEG. INSP & FOR PROTEC./ NUMBER CURRENT FUNC. CHANNEL FUNC. PREV. WHICH AFFECTED OR CHARAC- TEST CALIB. TEST MAINT. SURV IS COMPONENTS DRAWING DESCRIPTION TYPE TERISTIC 4.8.4.1.a.2 4.8.4.1.a.1.a 4.8.4.1.a.1.b 4.8.4.1.b REQ'D 1 CEDM COILS (91 Circuits) Continued a Primary Subgroup Bus Heine- Heinemann Series 10% per RNA NA every 60 M 1,2,3,4 mann 40 AM,Curve3 CEDEBKR9218-D CEDEBKR9218-C CEDEBKR9218-A CEDEBKR9218-B b Primary Hold Bus Heine- Heinemann Series 10% per RNA NA every 60 M 1,2,3,4 mann 30 AM,Curve3 CEDEBKR2909-A CEDEBKR2909-B c Backup 60A Fuse Fast Acting NA NA NA NA 1,2,3,4 Semiconductor Fuse Fuses

240 V, 3 phase power feeds from the C-E Reactor Trip Switchgear to the CEDM Cabinets. The 91 circuits separate into subgroups and hold buses. One breaker and three fuses protect each subgroup/hold bus. These cabinets feed power to the CEDM Coils via #4 AWG & #8 AWG penetration conductors.

3/4 8-14 TABLE 3.8-1 (cont'd)

CONTAINMENT PENETRATION CONDUCTOR OVER-CURRENT PROTECTIVE DEVICES OVER-CURRENT PROTECTIVE DEVICES WITHIN EACH VOLTAGE LEVEL (ROMAN) MODES BREAKER IDENTIFYING TIME INTEG. INSP & FOR PROTEC./ NUMBER CURRENT FUNC. CHANNEL FUNC. PREV. WHICH AFFECTED OR CHARAC- TEST CALIB. TEST MAINT. SURV IS COMPONENTS DRAWING DESCRIPTION TYPE TERISTIC 4.8.4.1.a.2 4.8.4.1.a.1.a 4.8.4.1.a.1.b 4.8.4.1.b REQ'D IV 480 VOLTS POWER FROM MCCs

1 SAFETY INJECTION TANK 1A ISOLATION VALVE SI MVAAA331-A (ISI-V1505 TK 1A) a Primary 289-61 Breaker EF Note IV.2, IV.3 10% of Type NA NA every 60 M 1,2,3,4 per R SI EBKR311A-8H Note IV.1 b Backup 289-61 Fuse TRS Note IV.4 NA NA NA NA 1,2,3,4

2 SAFETY INJECTION TANK 2A ISOLATION VALVE SI MVAAA332-A (ISI-V1507 TK 2A) a Primary 289-61 Breaker EF Note IV.2,IV.3 10% of Type NA NA every 60 M 1,2,3,4 per R SI EBKR311A-8M Note IV.1 b Backup 289-61 Fuse TRS Note IV.4 NA NA NA NA 1,2,3,4

3 LP-311 a Primary 289-62 Breaker EF Note IV.2,IV.3 10% of Type NA NA every 60 M 1,2,3,4 per R LTNEBKR311A-12ML Note IV.1 b Backup 289-62 Fuse TRS Note IV.4 NA NA NA NA 1,2,3,4 4 RCS LOOP 2 SDC ISOLATION VALVE SI MVAAA401A (1SI-V1504A) a Primary 289-63 Breaker EF Note IV.2, IV.3 10% of Type NA NA every 60 M 1,2,3,4 per R SI EBKR311A-8D Note IV.1 b Backup 289-63 Fuse TRS Note IV.4 NA NA NA NA 1,2,3,4 3/4 8-15 AMENDMENT 17, 117 TABLE 3.8-1 (cont'd)

CONTAINMENT PENETRATION CONDUCTOR OVER-CURRENT PROTECTIVE DEVICES OVER-CURRENT PROTECTIVE DEVICES WITHIN EACH VOLTAGE LEVEL (ROMAN) MODES BREAKER IDENTIFYING TIME CHANNEL INTEG. INSP & FOR PROTEC./ NUMBER CURRENT FUNC. CALIB. FUNC. PREV. WHICH AFFECTED OR CHARAC- TEST 4.8.4.1 TEST MAINT. SURV IS COMPONENTS DRAWING DESCRIPTION TYPE TERISTIC 4.8.4.1.a.2 a.1.a 4.8.4.1.a.1.b 4.8.4.1.b REQ'D 5 CARS SUCTION VALVE CARMVAAA201-A (2HV-F253A) a Primary 289-64 Breaker EFNote IV.2,IV.3 10% of Type NA NA every 60 M 1,2,3,4 per R CAR EBKR311A-15M Note IV.1 b Backup 289-64 Fuse TRSNote IV.4 NANANANA 1,2,3,4 (EC-935, Am. 117) (EC-935, Am. 117) 7 SAFETY INJECTION TANK 1B ISOLATION VALVE SI MVAAA331-B (1SI-V1506 TK 1B) a Primary 289-65 Breaker EFNote IV.2, IV.3 10% of Type NA NA every 60 M 1,2,3,4 per R SI EBKR311B-8H Note IV.1 b Backup 289-65 Fuse TRSNote IV.4 NANANANA 1,2,3,4 8 SAFETY INJECTION TANK 2B ISOLATION VALVE SI MVAAA332-B (1SI-V1508 TK 2B) a Primary 289-65 Breaker EFNote IV.2,IV.3 10% of Type NA NA every 60 M 1,2,3,4 per R SI EBKR311B-8M Note IV.1 NANANA1,2,3,4 b Backup 289-65 Fuse TRSNote IV.4 NANANANA 1,2,3,4 3/4 8-16 AMENDMENT NO.

117 TABLE 3.8-1 (cont'd)

CONTAINMENT PENETRATION CONDUCTOR OVER-CURRENT PROTECTIVE DEVICES OVER-CURRENT PROTECTIVE DEVICES WITHIN EACH VOLTAGE LEVEL (ROMAN) MODES BREAKER IDENTIFYING TIME INTEG. INSP & FOR PROTEC./ NUMBER CURRENT FUNC. CHANNEL FUNC. PREV. WHICH AFFECTED OR CHARAC- TEST CALIB. TEST MAINT. SURV IS COMPONENTS DRAWING DESCRIPTION TYPE TERISTIC 4.8.4.1.a.2 4.8.4.1.a.1.a 4.8.4.1.a.1.b 4.8.4.1.b REQ'D

9 LP-310 a Primary 289-66 Breaker EF Note IV.2,IV.3 10% of Type NA NA every 60 M 1,2,3,4 per R LTNEBKR311B-7ML Note IV.1

b Backup 289-66 Fuse TRS Note IV.4 NA NA NA NA 1,2,3,4

10 RCS LOOP 1 SDC ISOLATION VALVE SI MVAAA401-B (1SI-V1502B) a Primary 289-67 Breaker EF Note IV.2,IV.3 10% of Type NA NA every 60 M 1,2,3,4 per R SI EBKR311B-8D Note IV.1

b Backup 289-67 Fuse TRS Note IV.4 NA NA NA NA 1,2,3,4

11 CARS SUCTION VALVE CARMVAAA201-B (2HV-F254B))

a Primary 289-68 Breaker EF Note IV.2,IV.3 10% of Type NA NA every 60 M 1,2,3,4 per R CAR EBKR311B-15M Note IV.1

b Backup 289-68 Fuse TRS Note IV.4 NA NA NA NA 1,2,3,4 (EC-935, Am. 117)

(EC-935, Am. 117)

3/4 8-17 AMENDMENT 17, 39, 126TABLE 3.8-1 (cont'd) CONTAINMENT PENETRATION CONDUCTOR OVER-CURRENT PROTECTIVE DEVICES OVER-CURRENT PROTECTIVE DEVICES WITHIN EACH VOLTAGE LEVEL (ROMAN)

MODES BREAKER IDENTIFYING TIME INTEG. INSP & FOR PROTEC./ NUMBER CURRENT FUNC. CHANNEL FUNC. PREV. WHICH AFFECTED OR CHARAC- TEST CALIB. TEST MAINT. SURV IS COMPONENTS DRAWING DESCRIPTION TYPETERISTIC 4.8.4.1.a.2 4.8.4.1.a.1.a 4.8.4.1.a.1.b 4.8.4.1.b REQ'D (EC-41803, Am. 126) 13 CONT. 30KVA TRANSF. PDP 377A a Primary 289-71 Breaker HFD Note IV.2,IV.3 10% of Type NA NA every 60 M 1,2,3,4 (EC-41803, Am. 126) per R LVD EBKR312A-12MR Note IV.1 b Backup 289-71 Fuse TRS Note IV.4 NA NA NA NA 1,2,3,4 14 RCP 2A OIL LIFT PUMP A a Primary 289-71 Breaker EF Note IV.2,IV.3 10% of Type NA NA every 60 M 1,2,3,4 per R RC EBKR312A-9H Note IV.1 b Backup 289-71 Fuse TRS Note IV.4 NA NA NA NA 1,2,3,4 15 RCP 1A OIL LIFT PUMP A a Primary 289-71 Breaker EF Note IV.2,IV.3 10% of Type NA NA every 60 M 1,2,3,4 per R RC EBKR312A-9E Note IV.1 b Backup 289-71 Fuse TRS Note IV.4 NA NA NA NA 1,2,3,4 16 STEAM GENERATOR 1 VENT VALVE MS MVAAA101-A (2MS-V668) The motor operator is abandoned in place. Breakers/cables are spared.

17 MOVABLE DETECTOR DRIVE MACHINE 1 THE MOVABLE DETECTOR DRIVE MACHINE 1 WAS DISCONNECTED. BOTH THE BREAKER AND FUSE ARE SPARED. (MNI EBKR312A-12ML) 3/4 8-18 AMENDMENT 39, 126TABLE 3. 8-1 (cont'd) CONTAINMENT PENETRATION CONDUCTOR OVER-CURRENT PROTECTIVE DEVICES OVER-CURRENT PROTECTIVE DEVICES WITHIN EACH VOLTAGE LEVEL (ROMAN)

MODES BREAKER IDENTIFYING TIME INTEG. INSP & FOR PROTEC./ NUMBER CURRENT FUNC. CHANNEL FUNC. PREV. WHICH AFFECTED OR CHARAC- TEST CALIB. TEST MAINT. SURV IS COMPONENTS DRAWING DESCRIPTION TYPETERISTIC 4.8.4.1.a.2 4.8.4.1.a.1.a 4.8.4.1.a.1.b 4.8.4.1.b REQ'D 18 STEAM GENERATOR 2 VENT VALVE MS MVAAA101-B (2MS-V667) The motor operator is abandoned in place. Breakers/cables are spared. 19 RCP 1B OIL LIFT PUMP A (EC-15976, Am. 126) a Primary 289-74 Breaker HFD Note IV.2,IV.3 10% of Type NA NA every 60 M 1,2,3,4 (EC-15976, Am. 126) per R RC EBKR312B-9E Note IV.1 b Backup 289-74 Fuse TRS Note IV.4 NA NA NA NA 1,2,3,4 20 RCP 2B OIL LIFT PUMP A a Primary 289-74 Breaker EF Note IV.2,IV.3 10% of Type NA NA every 60 M 1,2,3,4 per R RC EBKR312B-9H Note IV.1 b Backup 289-74 Fuse TRS Note IV.4 NA NA NA NA 1,2,3,4 21 MOVABLE DETECTOR DRIVE MACHINE 2 THE MOVABLE DETECTOR DRIVE MACHINE 2 WAS DISCONNECTED. BOTH THE BREAKER AND FUSE ARE SPARED.(MNI EBKR312B-12ML) 22 CONT. 30KVA TRANSF. PDP 378B a Primary 289-75 Breaker EF Note IV.2, IV.3 10% of Type NA NA every 60 M 1,2,3,4 per R LVD EBKR312B-12MR Note IV.1 b Backup 289-75 Fuse TRS Note IV.4 NA NA NA NA 1,2,3,4 3/4 8-19 TABLE 3.8-1 (cont'd)

CONTAINMENT PENETRATION CONDUCTOR OVER-CURRENT PROTECTIVE DEVICES OVER-CURRENT PROTECTIVE DEVICES WITHIN EACH VOLTAGE LEVEL (ROMAN) MODES BREAKER IDENTIFYING TIME INTEG. INSP & FOR PROTEC./ NUMBER CURRENT FUNC. CHANNEL FUNC. PREV. WHICH AFFECTED OR CHARAC- TEST CALIB. TEST MAINT. SURV IS COMPONENTS DRAWING DESCRIPTION TYPE TERISTIC 4.8.4.1.a.2 4.8.4.1.a.1.a 4.8.4.1.a.1.b 4.8.4.1.b REQ'D 23 H2 RECOMBINER POWER SUPPLY A a Primary 289-77 Breaker FJ Note IV.2, IV.3 10% of Type NA NA every 60 M 1,2,3,4 per R HRAEBKR313A-3M Note IV.1 b Backup 289-77 Fuse TRS NOTE IV.4 NA NA NA NA 1,2,3,4 24 REACTOR CAVITY COOLING SYSTEM FAN S-2 (3A) a Primary 289-78 Breaker EF Note IV.2,IV.3 10% of Type NA NA every 60 M 1,2,3,4 per R RCCEBKR313A-12M Note IV.1 b Backup 289-78 Fuse TRS Note IV.4 NA NA NA NA 1,2,3,4

25 RADIATION REMOVAL UNIT E-13 (3A) a Primary 289-78 Breaker EF Note IV.2,IV.3 10% of Type NA NA every 60 M 1,2,3,4 per R ARREBKR313A-12E Note IV.1 b Backup 289-78 Fuse TRS Note IV.4 NA NA NA NA 1,2,3,4 26 RCP 1A OIL LIFT PUMP B a Primary 289-78 Breaker EF Note IV.2,IV.3 10% of Type NA NA every 60 M 1,2,3,4 per R RC EBKR313A-10J Note IV.1 b Backup 289-78 Fuse TRS Note IV.4 NA NA NA NA 1,2,3,4 3/4 8-20 AMENDMENT NO. 126TABLE 3.8-1 (cont'd) CONTAINMENT PENETRATION CONDUCTOR OVER-CURRENT PROTECTIVE DEVICES OVER-CURRENT PROTECTIVE DEVICES WITHIN EACH VOLTAGE LEVEL (ROMAN)

MODES BREAKER IDENTIFYING TIME INTEG. INSP & FOR PROTEC./ NUMBER CURRENT FUNC. CHANNEL FUNC. PREV. WHICH AFFECTED OR CHARAC- TEST CALIB. TEST MAINT. SURV IS COMPONENTS DRAWING DESCRIPTION TYPETERISTIC 4.8.4.1.a.2 4.8.4.1.a.1.a 4.8.4.1.a.1.b 4.8.4.1.b REQ'D 27 RCP 2A OIL LIFT PUMP B a Primary 289-78 Breaker EFNote IV.2,IV.3 10% of Type NA NA every 60 M 1,2,3,4 per R RC EBKR313A-10M Note IV.1 b Backup 289-78 Fuse TRS Note IV.4 NA NA NA NA 1,2,3,4 28 H2 RECOMBINER POWER SUPPLY B a Primary 289-80 Breaker FJNote IV.2,IV.3 10% of Type NA NA every 60 M 1,2,3,4 per R HRAEBKR313B-3M Note IV.1 b Backup 289-80 Fuse TRS Note IV.4 NA NA NA NA 1,2,3,4 29 REACTOR CAVITY COOLING SYSTEM FAN S-2 (3B) (EC-15976, Am. 126) a Primary 289-81 Breaker HFDNote IV.2, IV.3 10% of Type NA NA every 60 M 1,2,3,4 (EC-15976, Am. 126) per R RCCEBKR313B-12M Note IV.1 b Backup 289-81 Fuse TRS Note IV.4 NA NA NA NA 1,2,3,4 30 RADIATION REMOVAL UNIT E-13 (3B) a Primary 289-81 Breaker EF Note IV.2,IV.3 10% of Type NA NA every 60 M 1,2,3,4 per R ARREBKR313B-12E Note IV.1 b Backup 289-81 Fuse TRS Note IV.4 NA NA NA NA 1,2,3,4 3/4 8-21 AMENDMENT NO. 02, 122TABLE 3.8-1 (cont'd) CONTAINMENT PENETRATION CONDUCTOR OVER-CURRENT PROTECTIVE DEVICES OVER-CURRENT PROTECTIVE DEVICESWITHIN EACH VOLTAGE LEVEL (ROMAN) MODES BREAKER IDENTIFYING TIME INTEG. INSP & FOR PROTEC./ NUMBER CURRENT FUNC. CHANNEL FUNC. PREV. WHICH AFFECTED OR CHARAC- TEST CALIB. TEST MAINT. SURV IS COMPONENTS DRAWING DESCRIPTION TYPE TERISTIC 4.8.4.1.a.2 4.8.4.1.a.1.a 4.8.4.1.a.1.b 4.8.4.1.b.. REQ'D 31 RCP 1B OIL LIFT PUMP B a Primary 289-81 Breaker EF Note IV.2, IV.3 10% of Type NA NA every 60 M 1,2,3,4 per R RC EBKR313B-10J Note IV.1

b Backup 289-81 Fuse TRS Note IV.4 NA NA NA NA 1,2,3,4

32 RCP 2B OIL LIFT PUMP B a Primary 289-81 Breaker EF Note IV.2, IV.3 10% of Type NA NA every 60 M 1,2,3,4 per R RC EBKR313B-10M Note IV.1

b Backup 289-81 Fuse TRS Note IV.4 NA NA NA NA 1,2,3,4

33 MISSILE SHIELD TRUCK RECEPTACLE a Primary*

CRNEBKR316B-3BR

b Backup*

  • ITEM IV.33 - Primary breaker is locked out in the open position during MODES 1,2,3,4. Therefore, non OPERABLE primary or back up protection does not place the plant in an LCO

>(EC-22965, Am. 122)34 CONTAINMENT COOLING UNIT AH-1 (3A-SA) a Primary 289-97 Breaker JDNote IV.2,IV.3 10% of Type NA NA every 60 M 1,2,3,4 <(EC-22965, Am. 122) per R CCSEBKR317A-2M b Backup 289-20A1 Breaker ECS Note IV.6, IV.7,IV.8 10% of Type NA NA every 60 M 1,2,3,4 per R SSDEBKR31A 7A Note IV.5 c Backup 289-20A2 Relay IAC66T Note IV.6,IV.7,IV.8 10% of Type NA NA every 60 M 1,2,3,4 per R 3/4 8-22 TABLE 3.8-1 (cont'd)

CONTAINMENT PENETRATION CONDUCTOR OVER-CURRENT PROTECTIVE DEVICES OVER-CURRENT PROTECTIVE DEVICES WITHIN EACH VOLTAGE LEVEL (ROMAN) MODES BREAKER IDENTIFYING TIME INTEG. INSP & FOR PROTEC./ NUMBER CURRENT FUNC. CHANNEL FUNC. PREV. WHICH AFFECTED OR CHARAC- TEST CALIB. TEST MAINT. SURV IS COMPONENTS DRAWING DESCRIPTION TYPE TERISTIC 4.8.4.1.a.2 4.8.4.1.a.1.a 4.8.4.1.a.1.b 4.8.4.1.b REQ'D 35 CONTAINMENT COOLING UNIT AH-1 (3C-SA) a Primary 289-97 Breaker JL Note IV.2,IV.3 10% of Type NA NA every 60 M 1,2,3,4 CCSEBKR317A-3M per R b Backup 289-20A1 Breaker ECS Note IV.6,IV.7&,IV.8 10% of Type NA NA every 60 M 1,2,3,4 per R SSDEBKR31A 7A Note IV.5 c Backup 289-20A2 Relay IAC66T Note IV.6,IV.7,IV.8 10% of Type NA NA every 60 M 1,2,3,4 per R 36 CONTAINMENT COOLING UNIT AH-1 (3B-SB) a Primary 289-97 Breaker JL Note IV.2,IV.3 10% of Type NA NA every 60 M 1,2,3,4 per R CCSEBKR317B-3M b Backup 289-21A1 Breaker ECS Note IV.6,IV.7,IV.8 10% of Type NA NA every 60 M 1,2,3,4 per R SSDEBKR31B 7A Note IV.5 c Backup 289-21A2 Relay IAC66T Note IV.6,IV.7,IV.8 10% of Type NA NA every 60 M 1,2,3,4 per R 37 CONTAINMENT COOLING UNIT AH-1 (3D-SB) a Primary 289-97 Breaker JL Note IV.2,IV.3 10% of Type NA NA every 60 M 1,2,3,4 per R CCSEBKR317B-2M

b Backup 289-21A1 Breaker ECS Note IV.6,IV.7,IV.8 10% of Type NA NA every 60 M 1,2,3,4 per R SSDEBKR31B 7A Note IV.5 c Backup 289-21A2 Relay IAC66T Note IV.6,IV.7,IV.8 10% of Type NA NA every 60 M 1,2,3,4 per R 3/4 8-23 TABLE 3.8-1 (cont'd)

CONTAINMENT PENETRATION CONDUCTOR OVER-CURRENT PROTECTIVE DEVICES OVER-CURRENT PROTECTIVE DEVICES WITHIN EACH VOLTAGE LEVEL (ROMAN) MODES BREAKER IDENTIFYING TIME INTEG. INSP & FOR PROTEC/. NUMBER CURRENT FUNC. CHANNEL FUNC. PREV. WHICH AFFECTED OR CHARAC- TEST CALIB. TEST MAINT. SURV IS COMPONENTS DRAWING DESCRIPTION TYPE TERISTIC 4.8.4.1.a.2 4.8.4.1.a.1.a 4.8.4.1.a.1.b 4.8.4.1.b. REQ'D 38 CONTAINMENT SUMP PUMP A a Primary 289-45 Breaker EF Note IV.2,IV.3 10% of Type NA NA every 60 M 1,2,3,4 per R SP EBKR213A-4J b Backup 289-45 Fuse TRS Note IV.4 NA NA NA NA 1,2,3,4

39 LP-306 a Primary 289-45 Breaker EF Note IV.2,IV.3 10% of Type NA NA every 60 M 1,2,3,4 per R LTNEBKR213A-11FR b Backup 289-45 Fuse TRS Note IV.4 NA NA NA NA 1,2,3,4

40 LP-301 a Primary 289-45 Breaker EF Note IV.2,IV.3 10% of Type NA NA every 60 M 1,2,3,4 per R LTNEBKR213A-11CL b Backup 289-45 Fuse TRS Note IV.4 NA NA NA NA 1,2,3,4 41 LP-302 a Primary 289-45 Breaker EF Note IV.2,IV.3 10% of Type NA NA every 60 M 1,2,3,4 per R LTNEBKR213A-11CR

b Backup 289-45 Fuse TRS Note IV.4 NA NA NA NA 1,2,3,4

3/4 8-24 TABLE 3.8-1 (cont'd)

CONTAINMENT PENETRATION CONDUCTOR OVER-CURRENT PROTECTIVE DEVICES OVER-CURRENT PROTECTIVE DEVICES WITHIN EACH VOLTAGE LEVEL (ROMAN) MODES BREAKER IDENTIFYING TIME INTEG. INSP & FOR PROTEC./ NUMBER CURRENT FUNC. CHANNEL FUNC. PREV. WHICH AFFECTED OR CHARAC- TEST CALIB. TEST MAINT. SURV IS COMPONENTS DRAWING DESCRIPTION TYPE TERISTIC 4.8.4.1.a.2 4.8.4.1.a.1.a 4.8.4.1.a.1.b 4.8.4.1.b REQ'D 42 LP-304 a Primary 289-45 Breaker EF Note IV.2,IV.3 10% of Type NA NA every 60 M 1,2,3,4 per R LTNEBKR213A-11FL b Backup 289-45 Fuse TRS Note IV.4 NA NA NA NA 1,2,3,4

43 CONTAINMENT ELEVATOR D a Primary 289-47 Breaker EF Note IV.2, IV.3 10% of Type NA NA every 60 M 1,2,3,4 per R ELVEBKR213B-12CL b Backup 289-47 Fuse TRS Note IV.4 NA NA NA NA 1,2,3,4

44 REFUELING CAVITY DRAIN PUMP a Primary 289-48 Breaker EF Note IV.2, IV.3 10% of Type NA NA every 60 M 1,2,3,4 per R FS EBKR213B-11J b Backup 289-48 Fuse TRS Note IV.4 NA NA NA NA 1,2,3,4 45 REFUELING EQUIPMENT a Primary 289-50 Breaker EF Note IV.2, IV.3 10% of Type NA NA every 60 M 1,2,3,4 per R FHSEBKR213B-12CR b Backup 289-50 Fuse TRS Note IV.4 NA NA NA NA 1,2,3,4 3/4 8-25 TABLE 3.8-1 (cont'd)

CONTAINMENT PENETRATION CONDUCTOR OVER-CURRENT PROTECTIVE DEVICES OVER-CURRENT PROTECTIVE DEVICES WITHIN EACH VOLTAGE LEVEL (ROMAN) MODES BREAKER IDENTIFYING TIME INTEG. INSP & FOR PROTEC./ NUMBER CURRENT FUNC. CHANNEL FUNC. PREV. WHICH AFFECTED OR CHARAC- TEST CALIB. TEST MAINT. SURV IS COMPONENTS DRAWING DESCRIPTION TYPE TERISTIC 4.8.4.1.a.2 4.8.4.1.a.1.a 4.8.4.1.a.1.b 4.8.4.1.b REQ'D 46 REFUELING EQUIPMENT a Primary 289-48 Breaker EF Note IV.2, IV.3 10% of Type NA NA every 60 M 1,2,3,4 per R FHS EBKR213B-12FL b Backup 289-48 Fuse TRS Note IV.4 NA NA NA NA 1,2,3,4

47 CONTAINMENT SUMP PUMP B a Primary 289-49 Breaker EF Note IV.2,IV.3 10% of Type NA NA every 60 M 1,2,3,4 per R SP EBKR213B-4J b Backup 289-49 Fuse TRS Note IV.4 NA NA NA NA 1,2,3,4

48 LP-303 a Primary 289-49 Breaker EF Note IV.2,IV.3 10% of Type NA NA every 60 M 1,2,3,4 per R LTNEBKR213B-11CR b Backup 289-49 Fuse TRS Note IV.4 NA NA NA NA 1,2,3,4 49 LP-305 a Primary 289-49 Breaker EF Note IV.2,IV.3 10% of Type NA NA every 60 M 1,2,3,4 per R LTNEBKR213B-11FL

b Backup 289-49 Fuse TRS Note IV.4 NA NA NA NA 1,2,3,4 3/4 8-26 TABLE 3.8-1 (cont'd)

CONTAINMENT PENETRATION CONDUCTOR OVER-CURRENT PROTECTIVE DEVICES OVER-CURRENT PROTECTIVE DEVICES WITHIN EACH VOLTAGE LEVEL (ROMAN) MODES BREAKER IDENTIFYING TIME INTEG. INSP & FOR PROTEC./ NUMBER CURRENT FUNC. CHANNEL FUNC. PREV. WHICH AFFECTED OR CHARAC- TEST CALIB. TEST MAINT. SURV IS COMPONENTS DRAWING DESCRIPTION TYPE TERISTIC 4.8.4.1.a.2 4.8.4.1.a.1.a 4.8.4.1.a.1.b 4.8.4.1.b REQ'D 50 LP-300 a Primary 289-49 Breaker EF Note IV.2, IV.3 10% of Type NA NA every 60 M 1,2,3,4 per R LTNEBKR213B-11CL b Backup 289-49 Fuse TRS Note IV.4 NA NA NA NA 1,2,3,4

51 SDC LOOP 2 VACUUM PRIMING PUMP a Primary 289-45 Breaker EF-3 Note IV.2,IV.3 10% of Type NA NA every 60 M 1,2,3,4 per R SI EBKR213A-8H b Backup 289-43 Fuse TRS Note IV.4 NA NA NA NA 1,2,3,4

52 SDC LOOP 1 VACUUM PRIMING PUMP a Primary 289-47 Breaker EF-3 Note IV.2, IV.3 10% of Type NA NA every 60 M 1,2,3,4 per R SI EBKR213B-5J b Backup 289-47 Fuse TRS Note IV.4 NA NA NA NA 1,2,3,4 53 PDP 365A RECEPTACLES a Primary 289-104 Breaker TED Note IV.2,IV.3 10% of Type NA NA every 60 M 1,2,3,4 per R SSDEBKR65A-7 3/4 8-27 TABLE 3.8-1 (cont'd)

CONTAINMENT PENETRATION CONDUCTOR OVER-CURRENT PROTECTIVE DEVICES OVER-CURRENT PROTECTIVE DEVICES WITHIN EACH VOLTAGE LEVEL (ROMAN) MODES BREAKER IDENTIFYING TIME INTEG. INSP & FOR PROTEC./ NUMBER CURRENT FUNC. CHANNEL FUNC. PREV. WHICH AFFECTED OR CHARAC- TEST CALIB. TEST MAINT. SURV IS COMPONENTS DRAWING DESCRIPTION TYPE TERISTIC 4.8.4.1.a.2 4.8.4.1.a.1.a 4.8.4.1.a.1.b 4.8.4.1.b REQ'D 53 PDP 365A RECEPTACLES (Continued) b Backup 289-104 Breaker TED Note IV.2,IV.3 10% of Type NA NA every 60 M 1,2,3,4 per R SSDEBKR65A-7A 54 PDP 366B RECEPTACLES a Primary 289-104 Breaker TED Note IV.2, IV.3 10% of Type NA NA every 60 M 1,2,3,4 per R SSDEBKR66B-7 b Backup 289-104 Breaker TED Note IV.2, IV.3 10% of Type NA NA every 60 M 1,2,3,4 per R SSDEBKR66B-7A

3/4 8-28 TABLE 3.8-1 (cont'd)

CONTAINMENT PENETRATION CONDUCTOR OVER-CURRENT PROTECTIVE DEVICES OVER-CURRENT PROTECTIVE DEVICES WITHIN EACH VOLTAGE LEVEL (ROMAN) MODES BREAKER IDENTIFYING TIME INTEG. INSP & FOR PROTEC./ NUMBER CURRENT FUNC. CHANNEL FUNC. PREV. WHICH AFFECTED OR CHARAC- TEST CALIB. TEST MAINT. SURV IS COMPONENTS DRAWING DESCRIPTION TYPE TERISTIC 4.8.4.1.a.2 4.8.4.1.a.1.a 4.8.4.1.a.1.b 4.8.4.1.b REQ'D V 208 VOLTS CONTROL POWER FROM PDPs OR MCCs 1 RCP 1A HEATER

a Primary 424-2269 Breaker TEB Note V.2 10% of Type NA NA every 60 M 1,2,3,4 per R RC EBKR1A-7B b Backup 424-2269 Breaker TEB Note V.2 10% of Type NA NA every 60 M 1,2,3,4 per R RC EBKR1A-7C 2 RCP 2A HEATER

a Primary 424-2269 Breaker TEB Note V.2 10% of Type NA NA every 60 M 1,2,3,4 per R RC EBKR1A-8B b Backup 424-2269 Breaker TEB Note V.2 10% of Type NA NA every 60 M 1,2,3,4 per R RC EBKR1A-8C 3 RCP 1B HEATER a Primary 424-2270 Breaker TEB Note V.2 10% of Type NA NA every 60 M 1,2,3,4 per R RC EBKR1B-7B b Backup 424-2270 Breaker TEB Note V.2 10% of Type NA NA every 60 M 1,2,3,4 per R RC EBKR1B-7C 3/4 8-29 TABLE 3.8-1 (cont'd)

CONTAINMENT PENETRATION CONDUCTOR OVER-CURRENT PROTECTIVE DEVICES OVER-CURRENT PROTECTIVE DEVICES WITHIN EACH VOLTAGE LEVEL (ROMAN) MODES BREAKER IDENTIFYING TIME INTEG. INSP & FOR PROTEC./ NUMBER CURRENT FUNC. CHANNEL FUNC. PREV. WHICH AFFECTED OR CHARAC- TEST CALIB. TEST MAINT. SURV IS COMPONENTS DRAWING DESCRIPTION TYPE TERISTIC 4.8.4.1.a.2 4.8.4.1.a.1.a 4.8.4.1.a.1.b 4.8.4.1.b REQ'D 4 RCP 2B HEATER a Primary 424-2270 Breaker TEB Note V.2 10% of Type NA NA every 60 M 1,2,3,4 per R RC EBKR1B-8B b Backup 424-2270 Breaker TEB Note V.2 10% of Type NA NA every60 M 1,2,3,4 per R RCEBKR1B-8C VI 120 VOLTS CONTROL POWER FROM PDPs OR MCCs 1 SI TANK 1A LEAKAGE DRAIN SOLENOID VALVE SI ISV0303-A (1SI-F1551TK1A) a Primary 289-186 Circuit 26 Breaker Note VI.2 10% of Type NA NA every 60 M 1,2,3,4 CD per R SI EBKR94A-26 b Backup 289-186A Circuit 26 Fuse NA NA NA NA 1,2,3,4 FRN 2 SI TANK 2A LEAKAGE DRAIN SOLENOID VALVE SI ISV0304-A (1SI-F1553TK2A) a Primary 289-186 Circuit 38 Breaker Note VI.2 10% of Type NA NA every 60 M 1,2,3,4 CD per R SI EBKR94A-38 b Backup 289-186A Circuit 38 Fuse NA NA NA NA 1,2,3,4 FRN 3 COMPONENT COOLING WATER FROM RCP'S ISOL. SOLENOID VALVE CC ISV0710 (2CC-F243A/B)*

a Primary 289-108A Circuit 4 Fuse Note VI.2 10% of Type NA NA every 60 M 1,2,3,4 NO BKR FRN per R b Backup 289-108A Circuit 4 Fuse NA NA NA NA 1,2,3,4 FRN

  • Two fuses in series, one each, + and - poles 3/4 8-30 AMENDMENT NO.02

,37 TABLE 3.8-1 (cont'd)

CONTAINMENT PENETRATION CONDUCTOR OVER-CURRENT PROTECTIVE DEVICES OVER-CURRENT PROTECTIVE DEVICES WITHIN EACH VOLTAGE LEVEL (ROMAN) MODES BREAKER IDENTIFYING TIME INTEG. INSP & FOR PROTEC./ NUMBER CURRENT FUNC. CHANNEL FUNC. PREV. WHICH AFFECTED OR CHARAC- TEST CALIB. TEST MAINT. SURV IS COMPONENTS DRAWING DESCRIPTION TYPE TERISTIC 4.8.4.1.a.2 4.8.4.1.a.1.a 4.8.4.1.a.1.b 4.8.4.1.b REQ'D4 CONT ISOL FROM SI TANK DRAIN TO RWSP SOLENOID VALVE SI ISV0343 (2SI-F1561A/B) a Primary 289-186 Circuit 5 Breaker Note VI.2 10% of Type NA NA every 60 M 1,2,3,4 per R SI EBKR94A-5 b Backup 289-186A Circuit 5 Fuse NA NA NA NA 1,2,3,4 FRN 5 SI TANK 1A NITROGEN SUPPLY SOLENOID VALVE NG ISV0161-A (2SI-F605TK1A) a Primary 289-186 Circuit 16 Breaker Note VI.2 10% of Type NA NA every 60 M 1,2,3,4 CD per R NG EBKR94A-16 b Backup 289-186A Circuit 16 Fuse NA NA NA NA 1,2,3,4 FRN 6 SI TANK 2A NITROGEN SUPPLY SOLENOID VALVE NG ISV0162-A (2SI-F607TK2A) a Primary 289-186 Circuit 25 Breaker Note VI.2 10% of Type NA NA every 60 M 1,2,3,4 CD per R NG EBKR94A-25 b Backup 289-186A Circuit 25 Fuse NA NA NA NA` 1,2,3,4 FRN

7 SI TANK 1A VENT SOLENOID VALVE SI ISV0323-A (2SI-E636) a Primary 289-186 Circuit 30 Breaker Note VI.2 10% of Type NA NA every 60 M 1,2,3,4 CD per R SI EBKR94A-30 b Backup

289-186A 289-186A Circuit 30 Fuse NA NA NA NA 1,2,3,4 FRN 3/4 8-31 TABLE 3.8-1 (cont'd)

CONTAINMENT PENETRATION CONDUCTOR OVER-CURRENT PROTECTIVE DEVICES OVER-CURRENT PROTECTIVE DEVICES WITHIN EACH VOLTAGE LEVEL (ROMAN) MODES BREAKER IDENTIFYING TIME INTEG. INSP & FOR PROTEC./ NUMBER CURRENT FUNC. CHANNEL FUNC. PREV. WHICH AFFECTED OR CHARAC- TEST CALIB. TEST MAINT. SURV IS COMPONENTS DRAWING DESCRIPTION TYPE TERISTIC 4.8.4.1.a.2 4.8.4.1.a.1.a 4.8.4.1.a.1.b 4.8.4.1.b REQ'D 8 SI TANK 2A VENT SOLENOID VALVE SI ISV0324-A (2SI-E638) a Primary 289-186 Circuit 36 Breaker Note VI.2 10% of Type NA NA every 60 M 1,2,3,4 CD per R SI EBKR94A-36 b Backup 289-186A Circuit 36 Fuse NA NA NA NA 1,2,3,4 FRN 9 LETDOWN STOP VALVE SOLENOID VALVE CVCISV0101 (1CH-F1516A/B) a Primary 289-147 Circuit 1 Breaker Note VI.2 10% of Type NA NA every 60 M 1,2,3,4 CD per R CVC EBKR90A-1 b Backup 289-147A Circuit 1 Fuse NA NA NA NA 1,2,3,4 FRN 10 RCS LOOP 1 HOT LEG INJECTION DRAIN SOLENOID VALVE SI ISV0301 (1SI-V2504) a Primary 289-147 Circuit 30 Breaker Note VI.2 10% of Type NA NA every 60 M 1,2,3,4 CD per R SI EBKR90A-30 b Backup 289-147A Circuit 30 Fuse NA NA NA NA 1,2,3,4 FRN

11 SI TANK 1A FILL/DRAIN SOLENOID VALVE SI ISV0307-A (2SI-F1564TK1A) a Primary 289-186 Circuit 28 Breaker Note VI.2 10% of Type NA NA every 60 M 1,2,3,4 CD per R SI EBKR94A-28 b Backup 289-186A Circuit 28 Fuse NA NA NA NA 1,2,3,4 FRN

3/4 8-32 AMENDMENT NO. 02 , 87 , 105 TABLE 3.8-1 (contd)

CONTAINMENT PENETRATION CONDUCTOR OVER-CURRENT PROTECTIVE DEVICES OVER-CURRENT PROTECTIVE DEVICES WITHIN EACH VOLTAGE LEVEL (ROMAN) MODES BREAKER IDENTIFYING TIME INTEG. INSP & FOR PROTEC./ NUMBER CURRENT FUNC. CHANNEL FUNC. PREV. WHICH AFFECTED OR CHARAC- TEST CALIB. TEST MAINT. SURV IS COMPONENTS DRAWING DESCRIPTION TYPE TERISTIC 4.8.4.1.a.2 4.8.4.1.a.1.a 4.8.4.1.a.1.b 4.8.4.1.b REQD 12 CONTAINMENT PURGE ISOLATION SOLENOID VALVES CAPISV0103, CAPISV0103-2, CAPISV0104, & CAPISV0104-2 (2HV-B151A & 2HV-B152A) a Primary 289-120 Circuit 26 Breaker Note VI.2 10% of Type NA NA every 60 M 1,2,3,4 EE per R CAP EBKR60A-26 b Backup 289-120A F1 Fuse NA NA NA NA 1,2,3,4 TRS 13 H2 ANALYZER PANEL SYSTEM A a Primary 289-120 Circuit 32 Breaker Note VI.2 10% of Type NA NA every 60 M 1,2,3,4 (DRN 05-90, Am. 105)

EE per R HRA EBKR60A-32 b Backup 289-120a F18 Fuse NA NA NA NA 1,2,3,4 (DRN 05-90, Am. 105)

FNM (DRN 04-182, Am. 87) c Primary 289-120 Circuit 7 Breaker Note VI.2 10% of Type NA NA every 60 M 1,2,3,4 (DRN 05-90, Am. 105)

EE per R HRA EBKR60A-7 d Backup 289-120a F17 Fuse NA NA NA NA 1,2,3,4 (DRN 05-90, Am. 105)

FNM (DRN 04-182, Am. 87)

3/4 8-33 TABLE 3.8-1 (cont'd)

CONTAINMENT PENETRATION CONDUCTOR OVER-CURRENT PROTECTIVE DEVICES OVER-CURRENT PROTECTIVE DEVICES WITHIN EACH VOLTAGE LEVEL (ROMAN) MODES BREAKER IDENTIFYING TIME INTEG. INSP & FOR PROTEC./ NUMBER CURRENT FUNC. CHANNEL FUNC. PREV. WHICH AFFECTED OR CHARAC- TEST CALIB. TEST MAINT. SURV IS COMPONENTS DRAWING DESCRIPTION TYPE TERISTIC 4.8.4.1.A.2 4.8.4.1.a.1.a 4.8.4.1.a.1.b 4.8.4.1.b REQ'D 14 CONTAINMENT SPRAY RISER LEVEL PUMP A TEST SOLENOID VALVE CS ISV0129-A (2CS-E608A) a Primary 289-120 Circuit 9 Breaker Note VI.2 10% of Type NA NA every 60 M 1,2,3,4 EE per R CS EBKR60A-9 b Backup 289-120A F3 Fuse NA NA NA NA 1,2,3,4 TRS 15 SI TANK 2A FILL/DRAIN SOLENOID VALVE SI ISV0308-A(2SI-F1566TK2A) a Primary 289-186 Circuit 40 Breaker Note VI.2 10% of Type NA NA every 60 M 1,2,3,4 CD per R SI EBKR94A-40

b Backup 289-186A Circuit 40 Fuse NA NA NA NA 1,2,3,4 FRN 16 SI TANK 1B VENT SOLENOID VALVE SI ISV0323-B (2SI-E633) a Primary 289-186 Circuit 34 Breaker Note VI.2 10% of Type NA NA every 60 M 1,2,3,4 CD per R SI EBKR94A-34 b Backup 289-186A Circuit 34 Fuse NA NA NA NA 1,2,3,4 FRN

17 SI TANK 2B VENT SOLENOID VALVE SI ISV0326-B (2SI-E635) a Primary 289-186 Circuit 27 Breaker Note VI.2 10% of Type NA NA every 60 M 1,2,3,4 CD per R SI EBKR94A-27 b Backup 289-186A Circuit 27 Fuse NA NA NA NA 1,2,3,4 FRN 3/4 8-34 AMENDMENT NO. 02 TABLE 3.8-1 (cont'd)

CONTAINMENT PENETRATION CONDUCTOR OVER-CURRENT PROTECTIVE DEVICES OVER-CURRENT PROTECTIVE DEVICES WITHIN EACH VOLTAGE LEVEL (ROMAN) MODES BREAKER IDENTIFYING TIME INTEG. INSP & FOR PROTEC./ NUMBER CURRENT FUNC. CHANNEL FUNC. PREV. WHICH AFFECTED OR CHARAC- TEST CALIB. TEST MAINT. SURV IS COMPONENTS DRAWING DESCRIPTION TYPE TERISTIC 4.8.4.1.a.2 4.8.4.1.a.1.a 4.8.4.1.a.1.b 4.8.4.1.b REQ'D 18 RCS LOOP 2 SDC ISOLATION VALVE SI MVAAA405-A SOLENOID VALVES (1SI-V1503A)*

a Primary 289-108A Circuit 7 Fuse NA NA NA NA 1,2,3,4 NO BKR FRN b Backup 289-108A Circuit 7 Fuse NA NA NA NA 1,2,3,4 FRN

19 CONTAINMENT VACUUM RELIEF SOLENOID VALVE CVRISV0201 (2HV-B156A) a Primary 289-147 Circuit 14 Breaker Note VI.2 10% of Type NA NA every 60 M 1,2,3,4 CD per R CVR EBKR90A-14 b Backup 289-147A Circuit 14 Fuse NA NA NA NA 1,2,3,4 FRN

20 CONTAINMENT FAN COOLERS SYS A VALVES a Primary 289-120 Circuit 17 Breaker Note VI.2 10% of Type NA NA every 60 M 1,2,3,4 EE per R CCSEBKR60A-17 b Backup 289-120A F6 Fuse NA NA NA NA 1,2,3,4 TRS

  • Two fuses in series, one each, + and - poles 3/4 8-35 TABLE 3.8-1 (cont'd)

CONTAINMENT PENETRATION CONDUCTOR OVER-CURRENT PROTECTIVE DEVICES OVER-CURRENT PROTECTIVE DEVICES WITHIN EACH VOLTAGE LEVEL (ROMAN) MODES BREAKER IDENTIFYING TIME INTEG. INSP & FOR PROTEC./ NUMBER CURRENT FUNC. CHANNEL FUNC. PREV. WHICH AFFECTED OR CHARAC- TEST CALIB. TEST MAINT. SURV IS COMPONENTS DRAWING DESCRIPTION TYPE TERISTIC 4.8.4.1.a.2 4.8.4.1.a.1.a 4.8.4.1.a.1.b 4.8.4.1.b REQ'D 21 CONTAINMENT FAN COOLER AH-1(3A-SA) MOTOR SPACE HEATER a Primary 289-120 Circuit 13 Breaker Note VI.2 10% of Type NA NA every 60 M 1,2,3,4 EE per R CCSEBKR60A-13 b Backup 289-120A F4 Fuse NA NA NA NA 1,2,3,4 TRS 22 CONTAINMENT FAN COOLER AH-1(3C-SA) MOTOR SPACE HEATER a Primary 289-120 Circuit 15 Breaker Note VI.2 10% of Type NA NA every 60 M 1,2,3,4 EE per R CCSEBKR60A-15

b Backup 289-120A F5 Fuse NA NA NA NA 1,2,3,4 TRS

23 CEDM COOLING UNIT E-16(3A) MOTOR SPACE HEATER* a Primary 424-1139 Breaker TED Note VI.2 10% of Type NA NA every 60 M 1,2,3,4 per R CDC EBKR31A-31 b Backup 424-1139 Breaker TED Note VI.2 10% of Type NA NA every 60 M 1,2,3,4 per R CDCEBKR31A-32

  • 120/280V SWGR heater bus, double breaker protection.

3/4 8-36 TABLE 3.8-1 (cont'd)

CONTAINMENT PENETRATION CONDUCTOR OVER-CURRENT PROTECTIVE DEVICES OVER-CURRENT PROTECTIVE DEVICES WITHIN EACH VOLTAGE LEVEL (ROMAN) MODES BREAKER IDENTIFYING TIME INTEG. INSP & FOR PROTEC./ NUMBER CURRENT FUNC. CHANNEL FUNC. PREV. WHICH AFFECTED OR CHARAC- TEST CALIB. TEST MAINT. SURV IS COMPONENTS DRAWING DESCRIPTION TYPE TERISTIC 4.8.4.1.a.2 4.8.4.1.a.1.a 4.8.4.1.a.1.b 4.8.4.1.b REQ'D 24 CEDM COOLING UNIT E-16(3C) MOTOR SPACE HEATER*

a Primary 424-1140 Breaker TED Note VI.2 10% of Type NA NA every 60 M 1,2,3,4 per R CDCEBKR31A-33 b Backup 424-1140 Breaker TED Note VI.2 10% of Type NA NA every 60 M 1,2,3,4 per R CDCEBKR31A-34 25 SI TANK 1B LEAKAGE DRAIN SOLENOID VALVE SI ISV0303-B (2SI-F1552TK1B) a Primary 289-187 Circuit 26 Breaker Note VI.2 10% of Type NA NA every 60 M 1,2,3,4 CD per R SI EBKR95B-26 b Backup 289-187A Circuit 26 Fuse NA NA NA NA 1,2,3,4 FRN 26 SI TANK 2B LEAKAGE DRAIN SOLENOID VALVE SI ISV0304-B (1SI-F1554TK2B) a Primary 289-187 Circuit 38 Breaker Note VI.2 10% of Type NA NA every 60 M 1,2,3,4 CD per R SI EBKR95B-38 b Backup 289-187A Circuit 38 Fuse NA NA NA NA 1,2,3,4 FRN

  • 120/208V SWGR heater bus, double breaker protection.

3/4 8-37 TABLE 3.8-1 (cont'd)

CONTAINMENT PENETRATION CONDUCTOR OVER-CURRENT PROTECTIVE DEVICES OVER-CURRENT PROTECTIVE DEVICES WITHIN EACH VOLTAGE LEVEL (ROMAN) MODES BREAKER IDENTIFYING TIME INTEG. INSP & FOR PROTEC./ NUMBER CURRENT FUNC. CHANNEL FUNC. PREV. WHICH AFFECTED OR CHARAC- TEST CALIB. TEST MAINT. SURV IS COMPONENTS DRAWING DESCRIPTION TYPE TERISTIC 4.8.4.1.a.2 4.8.4.1.a.1.a 4.8.4.1.a.1.b 4.8.4.1.b REQ'D 27 WASTE GAS CONT. ISOLATION VALVE SOLENOID VALVE GWMISV0104 (2WM-F157AB) a Primary 289-187 Circuit 7 Breaker Note VI.2 10% of Type NA NA every 60 M 1,2,3,4 CD per R GWMEBKR95B-7 b Backup 289-187A Circuit 7 Fuse NA NA NA NA 1,2,3,4 FRN 28 SI TANK 1B NITROGEN SUPPLY SOLENOID VALVE NG ISV0161-B (2SI-F606TK1B) a Primary 289-187 Circuit 16 Breaker Note VI.2 10% of Type NA NA every 60 M 1,2,3,4 CD per R NG EBKR95B-16 b Backup 289-187A Circuit 16 Fuse NA NA NA NA 1,2,3,4 FRN 29 SI TANK 2B NITROGEN SUPPLY SOLENOID VALVE NG ISV0162-B (2SI-F608TK2B) a Primary 289-187 Circuit 25 Breaker Note VI.2 10% of Type NA NA every 60 M 1,2,3,4 CD per R NG EBKR95B-25 b Backup 289-187A Circuit 25 Fuse NA NA NA NA 1,2,3,4 FRN 30 SI TANK 1B VENT SOLENOID VALVE SI ISV0325-B (2SI-E637) a Primary 289-187 Circuit 30 Breaker Note VI.2 10% of Type NA NA every 60 M 1,2,3,4 CD per R SI EBKR95B-30

b Backup 289-187A Circuit 30 Fuse NA NA NA NA 1,2,3,4 FRN 3/4 8-38 TABLE 3.8-1 (cont'd)

CONTAINMENT PENETRATION CONDUCTOR OVER-CURRENT PROTECTIVE DEVICES OVER-CURRENT PROTECTIVE DEVICES WITHIN EACH VOLTAGE LEVEL (ROMAN) MODES BREAKER IDENTIFYING TIME INTEG. INSP & FOR PROTEC./ NUMBER CURRENT FUNC. CHANNEL FUNC. PREV. WHICH AFFECTED OR CHARAC- TEST CALIB. TEST MAINT. SURV IS COMPONENTS DRAWING DESCRIPTION TYPE TERISTIC 4.8.4.1.a.2 4.8.4.1.a.1.a 4.8.4.1.a.1.b 4.8.4.1.b REQ'D 31 SI TANK 2B VENT SOLENOID VALVE SI ISV0324-B (2SI-E639) a Primary 289-187 Circuit 27 Breaker Note VI.2 10% of Type NA NA every 60 M 1,2,3,4 CD per R SI EBKR95B-27 b Backup 289-187A Circuit 27 Fuse NA NA NA NA 1,2,3,4 FRN 32 RCP BLEED OFF CONT. ISOL. SOLENOID VALVE RC ISV0606 (2CH-F1513A/B) a Primary 289--187 Circuit 2 Breaker Note VI.2 10% of Type NA NA every 60 M 1,2,3,4 CD per R RC EBKR95B-2

b Backup 289-187A Circuit 2 Fuse NA NA NA NA 1,2,3,4 FRN

33 LETDOWN CONT. ISOL. VALVE SOLENOID VALVE CVCISV0103 (1CH-F2501 A/B) a Primary 289-148 Circuit 1 Breaker Note VI.2 10% of Type NA NA every 60 M 1,2,3,4 CD per R CVC EBKR91B-1 b Backup 289-148A Circuit 1 Fuse NA NA NA NA 1,2,3,4 FRN 3/4 8-39 TABLE 3.8-1 (cont'd)

CONTAINMENT PENETRATION CONDUCTOR OVER-CURRENT PROTECTIVE DEVICES OVER-CURRENT PROTECTIVE DEVICES WITHIN EACH VOLTAGE LEVEL (ROMAN) MODES BREAKER IDENTIFYING TIME INTEG. INSP & FOR PROTEC./ NUMBER CURRENT FUNC. CHANNEL FUNC. PREV. WHICH AFFECTED OR CHARAC- TEST CALIB. TEST MAINT. SURV IS COMPONENTS DRAWING DESCRIPTION TYPE TERISTIC 4.8.4.1.a.2 4.8.4.1.a.1.a 4.8.4.1.a.1.b 4.8.4.1.b REQ'D 34 RCS LOOP 2 HOT LEG INJECTION DRAIN SOLENOID VALVE SI ISV0302 (1SI-V2505) a Primary 289-148 Circuit 28 Breaker Note VI.2 10% of Type NA NA every 60 M 1,2,3,4 CD per R SI EBKR91B-28 b Backup 289-148A Circuit 28 Fuse NA NA NA NA 1,2,3,4 FRN 35 SOLENOID VALVE (BM-109) a Primary 289-187 Circuit 1 Breaker Note VI.2 10% of Type NA NA every 60 M 1,2,3,4 CD per R BM EBKR95B1

b Backup 289-187A Circuit 1 Fuse NA NA NA NA 1,2,3,4 FRN

36 CONTAINMENT PURGE ISOLATION SOLENOID VALVES CAPISV0203, CAPISV0203-2, CAPISV0204, & CAPISV0204-2 (2HV-B153B & 2HV-B154B) a Primary 289-121 Circuit 26 Breaker Note VI.2 10% of Type NA NA every 60 M 1,2,3,4 EE per R CAPEBKR61B-26 b Backup 289-121A F6 Fuse NA NA NA NA 1,2,3,4 TRS 37 CONTAINMENT VACUUM RELIEF SOLENOID VALVE CVRISV0101 (2HV-B157B) a Primary 289-148 Circuit 14 Breaker Note VI.2 10% of Type NA NA every 60 M 1,2,3,4 CD per R CVREBKR91B-14 b Backup 289-148A Circuit 14 Fuse NA NA NA NA 1,2,3,4 FRN 3/4 8-40 AMENDMENT NO. 02 , 86 , 105 TABLE 3.8-1 (contd)

CONTAINMENT PENETRATION CONDUCTOR OVER-CURRENT PROTECTIVE DEVICES OVER-CURRENT PROTECTIVE DEVICES WITHIN EACH VOLTAGE LEVEL (ROMAN) MODES BREAKER IDENTIFYING TIME INTEG. INSP & FOR PROTEC./ NUMBER CURRENT FUNC. CHANNEL FUNC. PREV. WHICH AFFECTED OR CHARAC- TEST CALIB. TEST MAINT. SURV IS COMPONENTS DRAWING DESCRIPTION TYPE TERISTIC 4.8.4.1.a.2 4.8.4.1.a.1.a 4.8.4.1.a.1.b 4.8.4.1.b REQD 38 STEAM GENERATOR NO. 1 BLOWDOWN CONT. ISOL. SOLENOID VALVE BD ISV0102-A (2BD-F603) a Primary 289-187 Circuit 6 Breaker Note VI.2 10% of Type NA NA every 60 M 1,2,3,4 CD per R BD EBKR95B-6 b Backup 289-187A Circuit 6 Fuse NA NA NA NA 1,2,3,4 FRN 39 STEAM GENERATOR NO. 2 BLOWDOWN CONT. ISOL. SOLENOID VALVE BD ISV0102-B (2BD-F605) a Primary 289-187 Circuit 8 Breaker Note VI.2 10% of Type NA NA every 60 M 1,2,3,4 CD per R BD EBKR95B-8

b Backup 289-187A Circuit 8 Fuse NA NA NA NA 1,2,3,4 FRN 40 H2 ANALYZER PANEL SYSTEM B a Primary 289-121 Circuit 32 Breaker Note VI.2 10% of Type NA NA every 60 M 1,2,3,4 EE per R

HRAEBKR61B-32 (DRN 05-90, Am. 105) b Backup 289-121a F18 Fuse NA NA NA NA 1,2,3,4 (DRN 05-90, Am. 105)

FNM (DRN 04-192, Am. 86) c Primary 289-121 Circuit 7 Breaker Note VI.2 10% of Type NA NA every 60 M 1,2,3,4 (DRN 05-90, Am. 105)

EE per R HRAEBKR61B-7 d Backup 289-121a F17 Fuse NA NA NA NA 1,2,3,4 (DRN 05-90, Am. 105)

FNM (DRN 04-192, Am. 86)

3/4 8-41 AMENDMENT NO. 02 TABLE 3.8-1 (cont'd)

CONTAINMENT PENETRATION CONDUCTOR OVER-CURRENT PROTECTIVE DEVICES OVER-CURRENT PROTECTIVE DEVICES WITHIN EACH VOLTAGE LEVEL (ROMAN) MODES BREAKER IDENTIFYING TIME INTEG. INSP & FOR PROTEC./ NUMBER CURRENT FUNC. CHANNEL FUNC. PREV. WHICH AFFECTED OR CHARAC- TEST CALIB. TEST MAINT. SURV IS COMPONENTS DRAWING DESCRIPTION TYPE TERISTIC 4.8.4.1.a.2 4.8.4.1.a.1.a 4.8.4.1.a.1.b 4.8.4.1.b REQ'D 41 CONTAINMENT SPRAY RISER LEVEL PUMP B TEST SOLENOID VALVE CS ISV0129-B (2CS-E609B) a Primary 289-121 Circuit 9 Breaker Note VI.2 10% of Type NA NA every 60 M 1,2,3,4 EE per R CS EBKR61B-9 b Backup 289-121A F2 Fuse NA NA NA NA 1,2,3,4 TRS 42 CONTAINMENT SUMP PUMPS ISOLATION VALVE SOLENOID VALVE SP ISV0105 (2WM-F104A/B) a Primary 289-187 Circuit 9 Breaker Note VI.2 10% of Type NA NA every 60 M 1,2,3,4 CD per R SP EBKR95B-9 b Backup 289-187A Circuit 9 Fuse NA NA NA NA 1,2,3,4 FRN

43 SI TANK 1B FILL/DRAIN SOLENOID VALVE SI ISV0307-B (2SI-F1565TK1B) a Primary 289-187 Circuit 28 Breaker Note VI.2 10% of Type NA NA every 60 M 1,2,3,4 CD per R SI EBKR95B-28 b Backup 289-187A Circuit 28 Fuse NA NA NA NA 1,2,3,4 FRN 44 SI TANK 2B FILL/DRAIN SOLENOID VALVE SI ISV0308-B (2SI-F1567TK2B) a Primary 289-187 Circuit 40 Breaker Note VI.2 10% of Type NA NA every 60 M 1,2,3,4 CD per R SI EBKR95B-40 b Backup 289-187A Circuit 40 Fuse NA NA NA NA 1,2,3,4 FRN 3/4 8-42 TABLE 3.8-1 (cont'd)

CONTAINMENT PENETRATION CONDUCTOR OVER-CURRENT PROTECTIVE DEVICES OVER-CURRENT PROTECTIVE DEVICES WITHIN EACH VOLTAGE LEVEL (ROMAN) MODES BREAKER IDENTIFYING TIME INTEG. INSP & FOR PROTEC./ NUMBER CURRENT FUNC. CHANNEL FUNC. PREV. WHICH AFFECTED OR CHARAC- TEST CALIB. TEST MAINT. SURV IS COMPONENTS DRAWING DESCRIPTION TYPE TERISTIC 4.8.4.1.a.2 4.8.4.1.a.1.a 4.8.4.1.a.1.b 4.8.4.1.b REQ'D 45 SI TANK 1A VENT SOLENOID VALVE SI ISV0325-A (2SI-E632) a Primary 289-187 Circuit 36 Breaker Note VI.2 10% of Type NA NA every 60 M 1,2,3,4 CD per R SI EBKR95B- 36 b Backup 289-187A Circuit 36 Fuse NA NA NA NA 1,2,3,4 FRN 46 SI TANK 2A VENT SOLENOID VALVE SI ISV0326-A (2SI-E634) a Primary 289-187 Circuit 34 Breaker Note VI.2 10% of Type NA NA every 60 M 1,2,3,4 CD per R SI EBKR95B-34

b Backup 289-187A Circuit 34 Fuse NA NA NA NA 1,2,3,4 FRN 47 COOLANT SAMPLING ISOLATION VALVE SOLENOID VALVE PSLISV0105 (2SL-F1501A/B) a Primary 289-187 Circuit 29 Breaker Note VI.2 10% of Type NA NA every 60 M 1,2,3,4 CD per R PSL EBKR95B- 29 b Breaker 289-187A Circuit 29 Fuse NA NA NA NA 1,2,3,4 FRN 3/4 8-43 TABLE 3.8-1 (cont'd)

CONTAINMENT PENETRATION CONDUCTOR OVER-CURRENT PROTECTIVE DEVICES OVER-CURRENT PROTECTIVE DEVICES WITHIN EACH VOLTAGE LEVEL (ROMAN) MODES BREAKER IDENTIFYING TIME INTEG. INSP & FOR PROTEC./ NUMBER CURRENT FUNC. CHANNEL FUNC. PREV. WHICH AFFECTED OR CHARAC- TEST CALIB. TEST MAINT. SURV IS COMPONENTS DRAWING DESCRIPTION TYPE TERISTIC 4.8.4.1.a.2 4.8.4.1.a.1.a 4.8.4.1.a.1.b 4.8.4.1.b REQ'D48 PRESSURIZER SURGE LINE SAMPLING ISOLATION VALVE SOLENOID VALVE PSLISV0203 (2SL-F1502A/B) a Primary 289-187 Circuit 31 Breaker Note VI.2 10% of Type NA NA every 60 M 1,2,3,4 CD per R PSL EBKR95B-31 b Backup 289-187A Circuit 31 Fuse NA NA NA NA 1,2,3,4 FRN 49 PRESSURIZER STEAM SPACE SAMPLING ISOLATION VALVE SOLENOID VALVE PSLISV0303 (2SL-F1503A/B) a Primary 289-187 Circuit 33 Breaker Note VI.2 10% of Type NA NA every 60 M 1,2,3,4 CD per R PSLEBKR95B-33

b Backup 289-187A Circuit 33 Fuse NA NA NA NA 1,2,3,4 FRN

50 RCS LOOP 1 SDC ISOLATION VALVE SI MVAAA405-B SOLENOID VALVES (1SI-V1501B)* a Primary 289-109A Circuit 9 Fuse NA NA NA NA 1,2,3,4 NO BKR FRN b Backup 289-109A Circuit 9 Fuse NA NA NA NA 1,2,3,4 FRN

  • Two fuses in series, one each, + and - poles 3/4 8-44 TABLE 3.8-1 (cont'd)

CONTAINMENT PENETRATION CONDUCTOR OVER-CURRENT PROTECTIVE DEVICES OVER-CURRENT PROTECTIVE DEVICES WITHIN EACH VOLTAGE LEVEL (ROMAN) MODES BREAKER IDENTIFYING TIME INTEG. INSP & FOR PROTEC./ NUMBER CURRENT FUNC. CHANNEL FUNC. PREV. WHICH AFFECTED OR CHARAC- TEST CALIB. TEST MAINT. SURV IS COMPONENTS DRAWING DESCRIPTION TYPE TERISTIC 4.8.4.1.a.2 4.8.4.1.a.1.a 4.8.4.1.a.1.b 4.8.4.1.b REQ'D 51 CONTAINMENT FAN COOLER AH-1(3B-SB) MOTOR SPACE HEATER a Primary 289-121 Circuit 13 Breaker Note VI.2 10% of Type NA NA every 60 M 1,2,3,4 EE per R CCSEBKR61B-13 b Backup 289-121A F3 Fuse NA NA NA NA 1,2,3,4 TRS 52 CONTAINMENT FAN COOLER AH-1(3D-SB) MOTOR SPACE HEATER a Primary 289-121 Circuit 15 Breaker NOTE VI.2 10% of Type NA NA every 60 M 1,2,3,4 EE per R CCSEBKR61B-15

b Backup 289-121A F4 Fuse NA NA NA NA 1,2,3,4 TRS

53 CEDM COOLING UNIT E-16(3B) MOTOR SPACE HEATER* a Primary 424-1141 Breaker TED Note VI.2 10% of Type NA NA every 60 M 1,2,3,4 per R CDCEBKR31B-31 b Backup 424-1141 Breaker TED Note VI.2 10% of Type NA NA every 60 M 1,2,3,4 per R CDCEBKR31B-32

  • 120/208V SWGR heater bus, double breaker protection.

3/4 8-45 TABLE 3.8-1 (cont'd)

CONTAINMENT PENETRATION CONDUCTOR OVER-CURRENT PROTECTIVE DEVICES OVER-CURRENT PROTECTIVE DEVICES WITHIN EACH VOLTAGE LEVEL (ROMAN) MODES BREAKER IDENTIFYING TIME INTEG. INSP & FOR PROTEC./ NUMBER CURRENT FUNC. CHANNEL FUNC. PREV. WHICH AFFECTED OR CHARAC- TEST CALIB. TEST MAINT. SURV IS COMPONENTS DRAWING DESCRIPTION TYPE TERISTIC 4.8.4.1.a.2 4.8.4.1.a.1.a 4.8.4.1.a.1.b 4.8.4.1.b REQ'D 54 CEDM COOLING UNIT E-16(3D) MOTOR SPACE HEATER* a Primary 424-1142 Breaker TED Note VI.2 10% of Type NA NA every 60 M 1,2,3,4 per R CDCEBKR31B-33 b Backup 424-1142 Breaker TED Note VI.2 10% of Type NA NA every 60 M 1,2,3,4 per R CDCEBKR31B-34 55 CONTAINMENT FAN COOLERS SYS B VALVES a Primary 289-121 Circuit 17 Breaker Note VI.2 10% of Type NA NA every 60 M 1,2,3,4 EE per R CCSEBKR61B-17 b Backup 289-121A F5 Fuse NA NA NA NA 1,2,3,4 TRS 56 STEAM GENERATOR NO. 1 SAMPLING ISOL. SOLENOID VALVE SSLISV8004-A (2SL F601) a Primary 289-148A Circuit 49 Breaker Note VI.2 10% of Type NA NA every 60 M 1,2,3,4 CD per R SSLEBKR91B-49 b Backup 289-148A Circuit 49 Fuse NA NA NA NA 1,2,3,4 FRN

  • 120/208V SWGR heater bus, double breaker protection.

3/4 8-46 AMENDMENT 37

, 84 TABLE 3.8-1 (cont'd)

CONTAINMENT PENETRATION CONDUCTOR OVER-CURRENT PROTECTIVE DEVICES OVER-CURRENT PROTECTIVE DEVICES WITHIN EACH VOLTAGE LEVEL (ROMAN) MODES BREAKER IDENTIFYING TIME INTEG. INSP & FOR PROTEC./ NUMBER CURRENT FUNC. CHANNEL FUNC. PREV. WHICH AFFECTED OR CHARAC- TEST CALIB. TEST MAINT. SURV IS COMPONENTS DRAWING DESCRIPTION TYPE TERISTIC 4.8.4.1.a.2 4.8.4.1.a.1.a 4.8.4.1.a.1.b 4.8.4.1.b REQ'D57 STEAM GENERATOR NO. 2 SAMPLING ISOL. SOLENOID VALVE SSLISV8004-2 (2SL F603)

a. Primary 289-148A Circuit 45 Breaker Note VI.2 10% of Type NA NA every 60 M 1,2,3,4 CD per R SSLEBKR91B-45 b. Backup 289-148A Circuit 45 Fuse NA NA NA NA 1,2,3,4 (DRN 03-1762, Am. 84) FRN 58 SAMPLE SYSTEM RECORDER PANEL SAMPLE VALVES RX COOLANT HOT LEG 1 SMPL ISOL SOLENOID VALVE, RC-0104 (SV-RC-1151A/B) PRESSURIZER SURGE LINE SMPL SOLENOID VALVE, RC-0316 (SV-RC-2503A/B)

PRESSURIZER STEAM SPACE SMPL ISOL SOLENOID VLV, RC-0319 (SV-RC-2502A/B) VALVES SSL-ISV-8001A(B) ARE GAGGED CLOSED AND SSL-ISV80002A(B) GAGGED OPEN. a. Primary B289-133 Circuit 35 Breaker Note VI.2 10% of Type NA NA Every 60M 1,2,3,4 SSLEBKR 84A-35 EE Per R

b. Backup B289-133A F12 Fuse NA NA NA NA 1,2,3,4 TRS (DRN 03-1762, Am. 84) 59 CONTAINMENT PURGE SYSTEM DAMPERS SOLENOID VALVES CAP SV0201 & CAPISV0202 (SV-D23 & SV-D22)
a. Primary 289-133 Circuit 1 Breaker Note VI.2 10% of Type NA NA every 60 M 1,2,3,4 EE per R HVREBKR84A-1
b. Backup 289-133A F5 Fuse NA NA NA NA 1,2,3,4 TRS
c. Primary 289-134 Circuit 1 Breaker Note VI.2 10% of Type NA NA every 60 M 1,2,3,4 EE per R HVREBKR85B-1
d. Backup 289-134A F2 Fuse NA NA NA NA 1,2,3,4 ATM 3/4 8-47 TABLE 3.8-1 (cont'd)

CONTAINMENT PENETRATION CONDUCTOR OVER-CURRENT PROTECTIVE DEVICES OVER-CURRENT PROTECTIVE DEVICES WITHIN EACH VOLTAGE LEVEL (ROMAN) MODES BREAKER IDENTIFYING TIME INTEG. INSP & FOR PROTEC./ NUMBER CURRENT FUNC. CHANNEL FUNC. PREV. WHICH AFFECTED OR CHARAC- TEST CALIB. TEST MAINT. SURV IS COMPONENTS DRAWING DESCRIPTION TYPE TERISTIC 4.8.4.1.a.2 4.8.4.1.a.1.a 4.8.4.1.a.1.b 4.8.4.1.b REQ'D 60 QUENCH TANK VENT VALVE SOLENOID VALVE RC ISV0323 (7RC-F604) a Primary 289-133 Circuit 8 Breaker Note VI.2 10% of Type NA NA every 60 M 1,2,3,4 EE per R

RC EBKR84A-8 b Backup 289-133A F3 Fuse NA NA NA NA 1,2,3,4 TRS 61 QUENCH TANK DRAIN VALVE SOLENOID VALVE RC ISV0325 (7RC-F605) a Primary 289-133 Circuit 10 Breaker Note VI.2 10% of Type NA NA every 60 M 1,2,3,4 EE RC EBKR84A-10 per R b Backup 289-133A F4 Fuse NA NA NA NA 1,2,3,4 TRS

62 CHARGING LLINE TO LOOP 2A SHUT OFF VALVE SOLENOID VALVE CVCISV0218-B (1CH-E2504B) a Primary 289-148 Circuit 29 Breaker Note VI.2 10% of Type NA NA every 60 M 1,2,3,4 CD CVCEBKR91B-29 per R b Backup 289-148A Circuit 29 Fuse NA NA NA NA 1,2,3,4 FRN 3/4 8-48 TABLE 3.8-1 (cont'd)

CONTAINMENT PENETRATION CONDUCTOR OVER-CURRENT PROTECTIVE DEVICES OVER-CURRENT PROTECTIVE DEVICES WITHIN EACH VOLTAGE LEVEL (ROMAN) MODES BREAKER IDENTIFYING TIME INTEG. INSP & FOR PROTEC./ NUMBER CURRENT FUNC. CHANNEL FUNC. PREV. WHICH AFFECTED OR CHARAC- TEST CALIB. TEST MAINT. SURV IS COMPONENTS DRAWING DESCRIPTION TYPE TERISTIC 4.8.4.1.a.2 4.8.4.1.a.1.a 4.8.4.1.a.1.b 4.8.4.1.b REQ'D63 CHARGING LINE TO LOOP 1A SHUT OFF VALVE SOLENOID VALVE CVCISV0218-A (1CH-E2503A) a Primary 289-147 Circuit 27 Breaker Note VI.2 10% of Type NA NA every 60 M 1,2,3,4 CD per R

CVCEBKR90A-27 b Backup 289-147A Circuit 27 Fuse NA NA NA NA 1,2,3,4 FRN 64 RCP 1A COOLING COIL CCW INLET & OUTLET SOLENOID VALVES CC ISV0665-A & CC ISV0679-A (3CC-P1501A1 & 3CC-P1505A1) a Primary 289-150 Circuit 25 Breaker Note VI.2 10% of Type NA NA every 60 M 1,2,3,4 TEB per R CC EBKR96AB-25

b Backup 424-280 F1 Fuse NA NA NA NA 1,2,3,4 ATM 65 RCP 2A COOLING COIL CCW INLET & OUTLET SOLENOID VALVES CC ISV0666-A & CC ISV0680-A (3CC-P1503A2 & 3CC-P1507A2) a Primary 289-150 Circuit 27 Breaker Note VI.2 10% of Type NA NA every 60 M 1,2,3,4 TEB per R

CC EBKR96AB-27 b Backup 424-282 F1 Fuse NA NA NA NA 1,2,3,4 ATM 3/4 8-49 TABLE 3.8-1 (cont'd)

CONTAINMENT PENETRATION CONDUCTOR OVER-CURRENT PROTECTIVE DEVICES OVER-CURRENT PROTECTIVE DEVICES WITHIN EACH VOLTAGE LEVEL (ROMAN) MODES BREAKER IDENTIFYING TIME INTEG. INSP & FOR PROTEC./ NUMBER CURRENT FUNC. CHANNEL FUNC. PREV. WHICH AFFECTED OR CHARAC- TEST CALIB. TEST MAINT. SURV IS COMPONENTS DRAWING DESCRIPTION TYPE TERISTIC 4.8.4.1.a.2 4.8.4.1.a.1.a 4.8.4.1.a.1.b 4.8.4.1.b REQ'D 66 RCP 1A INSTRUMENTATION AND ACCESSORIES*

a Primary 424-220 Fuse OTS NA NA NA NA 1,2,3,4 NO BKR b Backup 424-220 Fuse OTS NA NA NA NA 1,2,3,4

67 RCP 2A INSTRUMENTATION AND ACCESSORIES* a Primary 424-240 Fuse OTS NA NA NA NA 1,2,3,4 NO BKR b Backup 424-240 Fuse OTS NA NA NA NA 1,2,3,4

68 CEDM COOLING UNITS INLET DAMPERS a Primary 289-149 Circuit 14 Breaker Note VI.2 10% of Type NA NA every 60 M 1,2,3,4 TEB per R CDCEBKR45AB-14 b Backup 424-1145 F2 Fuse NA NA NA NA 1,2,3,4 ATM

  • Two fuses in series, one each, + and - poles 69 CEDM COOLER UNITS INLET DAMPERS a Primary 289-150 Circuit 20 Breaker Note VI.2 10% of Type NA NA every 60 M 1,2,3,4 TEB per R CDCEBKR96AB-20

b Backup 424-1145 F1 Fuse NA NA NA NA 1,2,3,4 ATM 3/4 8-50 AMENDMENT NO. 02 TABLE 3.8-1 (cont'd)

CONTAINMENT PENETRATION CONDUCTOR OVER-CURRENT PROTECTIVE DEVICES OVER-CURRENT PROTECTIVE DEVICES WITHIN EACH VOLTAGE LEVEL (ROMAN) MODES BREAKER IDENTIFYING TIME INTEG. INSP & FOR PROTEC./ NUMBER CURRENT FUNC. CHANNEL FUNC. PREV. WHICH AFFECTED OR CHARAC- TEST CALIB. TEST MAINT. SURV IS COMPONENTS DRAWING DESCRIPTION TYPE TERISTIC 4.8.4.1.a.2 4.8.4.1.a.1.a 4.8.4.1.a.1.b 4.8.4.1.b REQ'D 70 RCP CONTROL BLEEDOFF RELIEF ISOLATION (RC-602) RC ISV0602 (2CH-F1514A/B) a Primary 289-150 Circuit 5 Breaker Note VI.2 10% of Type NA NA every 60 M 1,2,3,4 TEB per R RC EBKR96AB-5

b Backup 424-326 F2 Fuse NA NA NA NA 1,2,3,4 ATM

71 REACTOR DRAIN TANK VENT VALVE SOLENOID GWMISV0101 (7BM-F237) a Primary 289-135 Circuit 11 Breaker Note VI.2 10% of Type NA NA every 60 M 1,2,3,4 EE per R GWM EBKR64AB-11 b Backup 424-401 F1 Fuse NA NA NA NA 1,2,3,4 ATM

72 RECIRC RETURN LINE DRAIN TO CONTAINMENT SUMP SOLENOID VALVE SI ISV0342 (5SI-F1563) a Primary 289-150 Circuit 1 Breaker Note VI.2 10% of Type NA NA every 60 M 1,2,3,4 SI EBKR96AB-1 TEB per R b Backup 424-499 F3 Fuse NA NA NA NA 1,2,3,4 ATM 73 RCP 1B COOLING COIL CCW INLET & OUTLET SOLENOID VALVES CC ISV0665-B & CC ISV0679-B (3CC-P1502B1 & 3CC-P1506B1) a Primary 289-150 Circuit 26 Breaker Note VI.2 10% of Type NA NA every 60 M 1,2,3,4 TEB per R CC EBKR96AB- 26 b Backup 424-281 F2 Fuse NA NA NA NA 1,2,3,4, ATM 3/4 8-51 TABLE 3.8-1 (cont'd)

CONTAINMENT PENETRATION CONDUCTOR OVER-CURRENT PROTECTIVE DEVICES OVER-CURRENT PROTECTIVE DEVICES WITHIN EACH VOLTAGE LEVEL (ROMAN) MODES BREAKER IDENTIFYING TIME INTEG. INSP & FOR PROTEC./ NUMBER CURRENT FUNC. CHANNEL FUNC. PREV. WHICH AFFECTED OR CHARAC- TEST CALIB. TEST MAINT. SURV IS COMPONENTS DRAWING DESCRIPTION TYPE TERISTIC 4.8.4.1.a.2 4.8.4.1.a.1.2 4.8.4.1.a.1.b 4.8.4.1.b REQ'D74 RCP 2B COOLING COIL CCW INLET & OUTLET SOLENOID VALVES CC ISV0666 B & CC ISV0680-B (3CC-P1504B2 & 3CC-P1508B2) a Primary 289-150 Circuit 28 Breaker Note VI.2 10% of Type NA NA every 60 M 1,2,3,4 CC EBKR96AB-28 TEB per R b Backup 424-283 F2 Fuse NA NA NA NA 1,2,3,4 ATM 75 RCP 1B INSTRUMENTATION AND ACCESSORIES* a Primary 424-230 Fuse OTS NA NA NA NA 1,2,3,4 NO BKR b Backup 424-230 Fuse OTS NA NA NA NA 1,2,3,4

76 RCP 2B INSTRUMENTATION AND ACCESSORIES* a Primary 424-250 Fuse OTS NA NA NA NA 1,2,3,4 NO BKR b Backup 424-250 Fuse OTS NA NA NA NA 1,2,3,4

77 CONTAINMENT ATMOSPHERE RADIATION MONITOR ISOLATION SOLENOID VALVE ARMISV0109 (2CA-E604B) a Primary 289-148 Circuit 26 Breaker Note VI.2 10% of Type NA NA every 60 M 1,2,3,4 CD per R ARMEBKR91B-26 b Backup 289-148A Circuit 26 Fuse NA NA NA NA 1,2,3,4 FRN

  • Two fuses in series, one each, + and - poles 3/4 8-52AMENDMENT 17 TABLE 3.8-1 (cont'd)

CONTAINMENT PENETRATION CONDUCTOR OVER-CURRENT PROTECTIVE DEVICES OVER-CURRENT PROTECTIVE DEVICES WITHIN EACH VOLTAGE LEVEL (ROMAN) MODES BREAKER IDENTIFYING TIME INTEG. INSP & FOR PROTEC./ NUMBER CURRENT FUNC. CHANNEL FUNC. PREV. WHICH AFFECTED OR CHARAC- TEST CALIB. TEST MAINT. SURV IS COMPONENTS DRAWING DESCRIPTION TYPE TERISTIC 4.8.4.1.a.2 4.8.4.1.a.1.a 4.8.4.1.a.1.b 4.8.4.1.b REQ'D78 PRESSURIZER AUX SPRAY VALVE SOLENOID VALVE CVCISV0216-A (1CH-E2505A) a Primary 289-147 Circuit 31 Breaker Note VI.2 10% of Type NA NA every 60 M 1,2,3,4 CD per R CVCEBKR90A-31 b Backup 289-147A Circuit 31 Fuse NA NA NA NA 1,2,3,4 FRN 79 PRESSURIZER AUX SPRAY VALVE SOLENOID VALVE CVCISV0216-B (1CH-E2505B) a Primary 289-148 Circuit 31 Breaker Note VI.2 10% of Type NA NA every 60 M 1,2,3,4 CD per R CVCEBKR91B-31

b Backup 289-148A Circuit 31 Fuse NA NA NA NA 1,2,3,4 FRN

80 CONTAINMENT SUMP PUMP RECIRC ISOLATION SOLENOID VALVE SP ISV0102-A a Primary C-1402 CB-1 Breaker Note VI.2 10% of Type NA NA every 60 M 1,2,3,4 Sh 35 CH per R PASEBKR6368-3 b Backup C-1402 Sh 35 CB-1 Breaker CHNote VI.2 10% of Type per R NA NA every 60 M 1,2,3,4 PASEBKR6368-4 3/4 8-53 TABLE 3.8-1 (cont'd)

CONTAINMENT PENETRATION CONDUCTOR OVER-CURRENT PROTECTIVE DEVICES OVER-CURRENT PROTECTIVE DEVICES WITHIN EACH VOLTAGE LEVEL (ROMAN) MODES BREAKER IDENTIFYING TIME INTEG. INSP & FOR PROTEC./ NUMBER CURRENT FUNC. CHANNEL FUNC. PREV. WHICH AFFECTED OR CHARAC- TEST CALIB. TEST MAINT. SURV IS COMPONENTS DRAWING DESCRIPTION TYPE TERISTIC 4.8.4.1.a.2 4.8.4.1.a.1.a 4.8.4.1.a.1.b 4.8.4.1.b REQ'D81 REACTOR COOLANT SYSTEM VENT VALVES SOLENOID VALVES RC ISV3184, RC ISV1015, & RC ISV3186 (2RC-2557A, 2RC-2559A, & 2RC-2561A) a Primary 289-212 Circuit 2 Breaker Note VI.2 10% of Type NA NA every 60 M 1,2,3,4 EE per R RC EBKR004A-2 b Backup 289-120A F2 Fuse NA NA NA NA 1,2,3,4 TRS 82 REACTOR COOLANT SYSTEM VENT VALVES SOLENOID VALVES SOLENOID VALVES RC ISV3183, RC ISV1014, & RC ISV1017 (2RC-2558B, 2RC-2560 B, & 2RC-2562B) a Primary 289-213 Circuit 2 Breaker Note VI.2 10% of Type NA NA every 60 M 1,2,3,4 EE per R RC EBKR005B-2

b Backup 289-121A F1 Fuse NA NA NA NA 1,2,3,4 TRS 83 SI TANK 1A ISOL. VALVE SI MVAAA331-A (1SI-V1505TK1A) SPACE HEATER ) THE SPACE HEATER WAS DISCONNECTED AT THE MCC AND PDP. BOTH THE BREAKER AND FUSE ARE SPARED. (SI EBKR94A-13) 84 SI TANK 1A ISOL. VALVE SI MVAAA331-A (1SI-V1505TK1A) LIMIT SWITCH & INDICATING LIGHTS a Primary 289-147 Circuit 6 Breaker Note VI.2 10% of Type NA NA every 60 M 1,2,3,4 CD per R SI EBKR90A-6 b Backup 289-147A Circuit 6 Fuse NA NA NA NA 1,2,3,4 FRN 3/4 8-54 TABLE 3.8-1 (cont'd)

CONTAINMENT PENETRATION CONDUCTOR OVER-CURRENT PROTECTIVE DEVICES OVER-CURRENT PROTECTIVE DEVICES WITHIN EACH VOLTAGE LEVEL (ROMAN) MODES BREAKER IDENTIFYING TIME INTEG. INSP & FOR PROTEC./ NUMBER CURRENT FUNC. CHANNEL FUNC. PREV. WHICH AFFECTED OR CHARAC- TEST CALIB. TEST MAINT. SURV IS COMPONENTS DRAWING DESCRIPTION TYPE TERISTIC 4.8.4.1.a.2 4.8.4.1.a.1.a. 4.8.4.1.a.1.b 4.8.4.1.b REQ'D 85 SI TANK 2A ISOL. VALVE SI MVAAA332-A (1SI-V1507TK2A) SPACE HEATER THE SPACE HEATER WAS DISCONNECTED AT THE MCC AND PDP. BOTH THE BREAKER AND FUSE ARE SPARED (SI EBKR94A-15)

86 SI TANK 2A ISOL. VALVE SI MVAAA332-A (1SI-V1507TK2A) LIMIT SWITCH & INDICATING LIGHTS a Primary 289-147 Circuit 8 Breaker Note VI.2 10% of T ype NA NA every 60 M 1,2,3,4 CD per R SI EBKR90A-8 b Backup 289-147A Circuit 8 Fuse NA NA NA NA 1,2,3,4 FRN 87 RCP 1A SPEED SENSOR THE RCP 1A SPEED SENSOR HAS BEEN DISCONNECTED. BOTH THE BREAKER AND FUSE ARE SPARED. (RC EBKR77A-5) 88 RCP 2A SPEED SENSOR THE RCP 2A SPEED SENSOR HAS BEEN DISCONNECTED. BOTH THE BREAKER AND FUSE ARE SPARED. (RC EBKR77A-7)

3/4 8-55 TABLE 3.8-1 (cont'd)

CONTAINMENT PENETRATION CONDUCTOR OVER-CURRENT PROTECTIVE DEVICES OVER-CURRENT PROTECTIVE DEVICES WITHIN EACH VOLTAGE LEVEL (ROMAN) MODES BREAKER IDENTIFYING TIME INTEG. INSP & FOR PROTEC./ NUMBER CURRENT FUNC. CHANNEL FUNC. PREV. WHICH AFFECTED OR CHARAC- TEST CALIB. TEST MAINT. SURV IS COMPONENTS DRAWING DESCRIPTION TYPE TERISTIC 4.8.4.1.a.2 4.8.4.1.a.1.a 4.8.4.1.a.1.b 4.8.4.1.b REQ'D 89 RADIATION REMOVAL UNIT E-13 (3A) THEMISTOR

a Primary 289-133 Circuit 24 Breaker Note VI.2 10% of Type NA NA every 60 M 1,2,3,4 EE per R ARREBKR84A-24 b Backup 289-133A F6 Fuse NA NA NA NA 1,2,3,4 TRS 90 CONTAINMENT COOLING UNIT CONDENSING POT FLOW DETECTOR a Primary 289-149 Circuit 3 Breaker Note VI.2 10% of Type NA NA every 60 M 1,2,3,4 TEB per R CCSEBKR45AB- 3 b Backup 424-829 F1 Fuse NA NA NA NA 1,2,3,4 ATM 91 PRESSURIZER NORM. SPRAY VALVES RC MVAAA301-A & RC MVAAA301B (1RC-F1501A & 1RC-F1502B) a Primary 289-150 Circuit 4 Breaker Note VI.2 10% of Type NA NA every 60 M 1,2,3,4 TEB per R RC EBKR96AB- 4 b Backup 424-296 F1 Fuse NA NA NA NA 1,2,3,4 ATM

92 MOVABLE INCORE DETECTOR DRIVE MACHINE #1 CONTROL THE MOVABLE INCORE DETECTOR DRIVE MACHINE #1 CONTROL HAS BEEN DISCONNECTED. BOTH THE BREAKER AND FUSE ARE SPARED.

(MNI EBKR77A-32) 3/4 8-56 TABLE 3.8-1 (cont'd)

CONTAINMENT PENETRATION CONDUCTOR OVER-CURRENT PROTECTIVE DEVICES OVER-CURRENT PROTECTIVE DEVICES WITHIN EACH VOLTAGE LEVEL (ROMAN) MODES BREAKER IDENTIFYING TIME INTEG. INSP & FOR PROTEC./ NUMBER CURRENT FUNC. CHANNEL FUNC. PREV. WHICH AFFECTED OR CHARAC- TEST CALIB. TEST MAINT. SURV IS COMPONENTS DRAWING DESCRIPTION TYPE TERISTIC 4.8.4.1.a.2 4.8.4.1.a.1.a 4.8.4.1.a.1.b 4.8.4.1.b REQ'D 93 MOVABLE INCORE DETECTOR SWITCHING DEVICE THE MOVABLE INCORE DETECTOR SWITCHING DEVICE HAS BEEN DISCONNECTED. BOTH THE BREAKER AND FUSE ARE SPARED. (PMCEBKR87A-7) 94 REFUELING MACHINE CONTROL a Primary 5817-4241 Fuse TRS NA NA NA NA 1,2,3,4 NO BKR b Backup 5817-4241 Fuse KTN/ NA NA NA NA 1,2,3,4 KTNR 95 SI TANK 1B ISOL. VALVE SI MVAAA331-B (1SI-V1506TK1B) SPACE HEATER THE SPACE HEATER WAS DISCONNECTED AT THE MCC AND PDP. BOTH THE BREAKER AND FUSE ARE SPARED. (SI EBKR95B-13) 96 SI TANK 1B ISOL. VALVE SI MVAAA331-B (1SI-V1506TK1B) LIMIT SWITCH & INDICATING LIGHTS a Primary 289-148 Circuit 6 Breaker Note VI.2 10% of Type NA NA every 60 M 1,2,3,4 CD per R SI EBKR91B-6 b Backup 289-148A Circuit 6 Fuse NA NA NA NA 1,2,3,4 FRN

97 SI TANK 2B ISOL. VALVE SI MVAAA332-B (1SI-1508TK2B) SPACE HEATER THE SPACE HEATER WAS DISCONNECTED AT THE MCC AND PDP. BOTH THE BREAKER AND FUSE ARE SPARED. (SI EBKR95B-15) 3/4 8-57 TABLE 3.8-1 (cont'd)

CONTAINMENT PENETRATION CONDUCTOR OVER-CURRENT PROTECTIVE DEVICES OVER-CURRENT PROTECTIVE DEVICES WITHIN EACH VOLTAGE LEVEL (ROMAN) MODES BREAKER IDENTIFYING TIME INTEG. INSP & FOR PROTEC./ NUMBER CURRENT FUNC. CHANNEL FUNC. PREV. WHICH AFFECTED OR CHARAC- TEST CALIB. TEST MAINT. SURV IS COMPONENTS DRAWING DESCRIPTION TYPE TERISTIC 4.8.4.1.a.2 4.8.4.1.a.1.a 4.8.4.1.a.1.b 4.8.4.1.b REQ'D98 SI TANK 2B ISOL. VALVE SI MVAAA332-B (1SI-V1508TK2B) LIMIT SWITCH & INDICATING LIGHTS a Primary 289-148 Circuit 8 Breaker Note VI.2 10% of Type NA NA every 60 M 1,2,3,4 CD per R SI BKR91B-8E b Backup 289-148A Circuit 8 Fuse NA NA NA NA 1,2,3,4 FRN 99 RCP 1B SPEED SENSOR THE RCP 1B SPEED SENSOR HAS BEEN DISCONNECTED. BOTH THE BREAKER AND FUSE ARE SPARED. (RC EBKR78B-5) 100 RCP 2B SPEED SENSOR THE RCP 2B SPEED SENSOR HAS BEEN DISCONNECTED. BOTH THE BREAKER AND FUSE ARE SPARED. (RC EBKR78B-7) 101 RADIATION REMOVAL UNIT E-13 (3B) THERMISTOR a Primary 289-134 Circuit 24 Breaker Note VI.2 10% of Type NA NA every 60 M 1,2,3,4 EE per R ARREBKR85B-24 b Backup 289-134A F1 Fuse NA NA NA NA 1,2,3,4 ATM

102 CONTAINMENT AIR LOCKS DOOR POSITION INDICATOR a Primary 289-147 Circuit 33 Breaker Note VI.2 10% of Type NA NA every 60 M 1,2,3,4 CD per R CB EBKR90A-33 b Backup 289-147A Circuit 33 Fuse NA NA NA NA 1,2,3,4 FRN 3/4 8-58 AMENDMENT NO. 106 TABLE 3.8-1 (contd)

CONTAINMENT PENETRATION CONDUCTOR OVER-CURRENT PROTECTIVE DEVICES OVER-CURRENT PROTECTIVE DEVICES WITHIN EACH VOLTAGE LEVEL (ROMAN) MODES BREAKER IDENTIFYING TIME INTEG. INSP & FOR PROTEC./ NUMBER or CURRENT FUNC. CHANNEL FUNC. PREV. WHICH AFFECTED OR CHARAC- TEST CALIB. TEST MAINT. SURV IS COMPONENTS DRAWING DESCRIPTION TYPE TERISTIC 4.8.4.1.a.2 4.8.4.1.a.1.a 4.8.4.1.a.1.b 4.8.4.1.b REQD 103 CONTAINMENT AIR LOCKS DOOR POSITION INDICATOR a Primary 289-148 Circuit 33 Breaker Note VI.2 10% of Type NA NA every 60 M 1,2,3,4 CD per R CB EBKR91B-33 b Backup 289-148A Circuit 33 Fuse NA NA NA NA 1,2,3,4 FRN (DRN 04-1357, Am. 106) 104 REACTOR DRAIN TANK CONT. ISOL. VALVE BM MVAAA109 (2BM-F108AB) POSITION INDICATION a Primary 424-400 &

Circuit 2 Fuse NA NA NA NA 1,2,3,4 405 NON BM EBKR84A-34 b Backup 424-400 & Circuit 30 Fuse NA NA NA NA 1,2,3,4 405 NON

105 WASTE GAS CONT. ISOL. VALVE GWMMVAAA104 (2WM-F157AB) POSITION INDICATION a Primary 424-650 &

Circuit 19 Fuse Note VI.2 NA NA NA NA 1,2,3,4 680 NON LWMEBKR84A-33 b Backup 424-650 & Circuit 22 Fuse NA NA NA NA 1,2,3,4 680 NON (DRN 04-1357, Am. 106) 106 MOVABLE INCORE DETECTOR DRIVE MACHINE #2 CONTROL THE MOVABLE INCORE DETECTOR DRIVE MACHINE #2 CONTROL HAS BEEN DISCONNECTED. BOTH THE BREAKER AND FUSE ARE SPARED. (MNI EBKR78B-32)

3/4 8-59 AMENDMENT 17

,37 , 93 TABLE 3.8-1 (contd)

CONTAINMENT PENETRATION CONDUCTOR OVER-CURRENT PROTECTIVE DEVICES OVER-CURRENT PROTECTIVE DEVICES WITHIN EACH VOLTAGE LEVEL (ROMAN) MODES BREAKER IDENTIFYING TIME INTEG. INSP & FOR PROTEC./ NUMBER CURRENT FUNC. CHANNEL FUNC. PREV. WHICH AFFECTED OR CHARAC- TEST CALIB. TEST MAINT. SURV IS COMPONENTS DRAWING DESCRIPTION TYPE TERISTIC 4.8.4.1.a.2 4.8.4.1.a.1.a 4.8.4.1.a.1.b 4.8.4.1.b REQD 107 CEDM COOLING UNITS VIBRATION SWITCHES* a Primary 289-110A Fuse FB NA NA NA NA 1,2,3,4 NO BKR 424-771 &

2028 b Backup 289-110A Fuse FB NA NA NA NA 1,2,3,4 424-771 & 2028

108 CONTAINMENT PRESSURE EXHAUST SOLENOID VALVE CAR-ISV-200B (2HV-228A) a Primary 289-147 Circuit 18 Breaker Note VI.2 10% of Type NA NA every 60 M 1,2,3,4 CD Per R CAREBKR90A-18 b Backup 289-147A Circuit 18 Fuse NA NA NA NA NA 1,2,3,4 FRN (DRN 04-475, Am. 93

) 109 RADIATION REMOVAL UNIT E-13 (3A) DRAIN SOLENOID VALVE ARR-ISV-0103A a Primary 5817- F3 Fuse NA NA NA NA 1,2,3,4 10186 313002 b Backup 5817- F2 Fuse NA NA NA NA 1,2,3,4 10186 313002 110 RADIATION REMOVAL UNIT E-13 (3B) DRAIN SOLENOID VALVE ARR-ISV-0103B a Primary 5817- F3 Fuse NA NA NA NA 1,2,3,4 10186 313002 b Backup 5817- F2 Fuse NA NA NA NA 1,2,3,4 10186 313002 (DRN 04-475, Am. 93)

  • This circuit has a Westinghouse Trip ac two pole breaker which contains fuses in each pole (positive and negative) of the breaker.

Since this circuit is a DC ungrounded circuit, the fuses are in series and provide primary/

backup protection.

3/4 8-60 AMENDMENT NO. 54,95, 122, 126 TABLE 3.8-1 NOTES CONTAINMENT PENETRATION CONDUCTOR OVER-CURRENT PROTECTIVE DEVICES I. 6.9 KV POWER FROM MEDIUM VOLTAGE SWITCHGEAR I.1) Refer to drawing LOU-1564-B-289 sheet and line numbers as indicated. (DRN 02-194) I.2) Refer to G.E. curve in GEI-19959 instruction book for IAC57 relay and G.E. curve 888B0273-0 in instruction book for IAC66M relay. (DRN 02-194) I.3) Relay testing to be performed in accordance with manufacturer's recommendation. II. 480 VOLTS POWER FROM LOW VOLTAGE SWITCHGEAR II.1) Refer to drawing LOU-1564-B-289 sheet and line numbers as indicated. II.2) Refer to G.E. curve GES-6032A for ECS programmer.

II.3) Refer to G.E. curve in GEI-19959 instruction book for IAC57 relays.

II.4) Primary breaker is equipped with two sets of protective devices. (DRN 04-2065, Am. 95) II.5) Refer to G.E. curve GEK-34055 for IAC77 relays. (DRN 04-2065, Am. 95) II.6) Relay and programmer testing to be performed in accordance with manufacturer's recommendation. IV. 480 VOLTS POWER FROM MCCs IV.1) Refer to drawing LOU-1564-B-289 sheet numbers as indicated. Circuit breakers with adjustable instantaneous mag netic trip element are set on the basis of two times the motor locked rotor current. For static loads the setpoint is the minimum available. IV.2) Refer to the appropriate curves as follows:

EF, EH - ITE/Gould TD8087 EF3 - ITE/Gould Instantaneous Trip FJ Breaker - ITE/Gould TD4948 JL Breaker - ITE/Gould TD4950 TED Breaker - GE GES-6114A (EC-22965, Am. 122) JD Breaker - Eaton SC-4247 - 87D (EC-22965, Am. 122) (EC-15976, Am. 126) HFD Breaker - Westinghouse, SC-4100 Series ( EC-15976, Am. 126) IV.3) Circuit breaker testing to be performed in accordance with manufacturer's recommendation. IV.4) Fuse testing to be performed in accordance with vendor's nondestructive resistance test procedures. IV.5) Backup breaker is equipped with two sets of protective devices. IV.6) Refer to G.E. curve GES-6032A for ECS programmer.

3/4 8-61 TABLE 3.8-1 NOTES (Continued)

CONTAINMENT PENETRATION CONDUCTOR OVER-CURRENT PROTECTIVE DEVICES IV.7) Refer to G.E. curve GES-7004A for IAC66T relays. IV.8) Relay and programmer testing to be performed in accordance with manufacturer's recommendation. IV.9) Equivalent breakers and fuses may be substituted for the types specified. V. 208 VOLTS AND 120 VOLTS CONTROL POWER FROM PDPs or MCCs V.1) For trip setpoint, refer to drawing LOU-1564-B-289 sheet numbers as indicated. V.2) Below is a listing of molded case breakers by type giving the curve number for time-cu rrent characteristic: TYPE/MANUFACTURER CURVE NO. EE, EF ITE TD 4947 CD Heineman CD, CE, CF TEB GE GES-6122B, 6122 TED GE GES-6119C AM Heineman AM QO Square D 630-2 CH Cutler Hammer Safety Breaker Curve V.3) Equivalent breakers and fuses may be substituted for the types specified. VI. 120 VOLTS CONTROL POWER FROM PDPs or MCCs VI.1) For trip setpoint, refer to drawing LOU-1564-B-289 sheet numbers as indicated. VI.2) Below is a listing of molded case breakers by type giving the curve number for time-current characteristic: TYPE/MANUFACTURER CURVE NO. EE, EF ITE TD 4947 CD Heineman CD, CE, CF TEB GE GES-6122B, 6122 TED GE GES-6119C AM Heineman AM QO Square D 630-2 CH Cutler Hammer Safety Breaker Curve VI.3) Equivalent breakers and fuses may be substituted for the types specified.

3/4 8-62 AMENDMENT NO. 58(DRN 02-912)

TABLE 3.8-2 MOTOR-OPERATED VALVES THERMAL OVERLOAD PROTECTION AND/OR BYPPASS DEVICE TABLE(DRN 02-912)

The Valves listed on Table 3.8-2 are the valves that are applicable to Technical Specification 3.8.4.2.

3/4 8-63 Ammendment 10 TABLE 3.8-2 MOTOR-OPERATED VALVES THERMAL OVERLOAD PROTECTION AND/OR BYPASS DEVICES TABLES BYPASS DEVICE VALVE NUMBER FUNCTION (YES/NO)ACCMVAAA110A ACCW Pump A Discharge Line Isolation YES ACCMVAAA110B ACCW Pump B Discharge Line Isolation YES BAMMVAAA113A Boric Acid Gravity Feed YES BAMMVAAA113B Boric Acid Gravity Feed YES BAMMVAAA133 Reactor Makeup Bypass YES CARMVAAA201A CARS Suction YES CARMVAAA201B CARS Suction YES CARMVAAA204A CARS Discharge YES CARMVAAA204B CARS Discharge YES CVCMVAAA183 Volume Control Tank Discharge YES HVCMVAAA201A Control Room Em. Filter Unit North YES HVCMVAAA201B Control Room Em. Filter Unit North YES HVCMVAAA202A Control Room Em. Filter Unit North YES HVCMVAAA202B Control Room Em. Filter Unit North YES HVCMVAAA203A Control Room Em. Filter Unit South YES HVCMVAAA203B Control Room Em Filter Unit South YES HVCMVAAA204A Control Room Em. Filter Unit South YES HVCMVAAA204B Control Room Em. Filter Unit South YES HVRMVAAA304A CVAS A Train Inlet YES HVRMVAAA304B CVAS B Train Inlet YES HVRMVAAA313A CVAS A Train Outlet YES HVRMVAAA313B CVAS B Train Outlet YES MS MVAAA119A Steam Line 1 Upstream Emergency Drain NO MS MVAAA119B Steam Line 2 Upstream Emergency Drain NO MS MVAAA120A Steam Line 1 Upstream Normal Drain NO MS MVAAA120B Steam Line 2 Upstream Normal Drain NO 3/4 8-64 TABLE 3.8-2 (Continued)

MOTOR-OPERATED VALVES THERMAL OVERLOAD PROTECTION AND/OR BYPASS DEVICES TABLE (continued) BYPASS DEVICE VALVE NUMBER FUNCTION (YES/NO)MS MVAAA416 Emergency Feed Water Pump Turbine Stop NO SBVMVAAA101A SBVS A Train Inlet YES SBVMVAAA101B SBVS B Train Inlet YES SBVMVAAA110A SBVS A Train Outlet YES SBVMVAAA110B SBVS B Train Outlet YES SBVMVAAA113A SBVS A Train Recirc YES SBVMVAAA113B SBVS B Train Recirc YES SBVMVAAA114A SBVS A Exhaust YES SBVMVAAA114B SBVS B Exhaust YES SI MVAAA120A SI Pumps A Min. Flow Isolation YES SI MVAAA120B SI Pumps B Min. Flow Isolation YES SI MVAAA121A SI Pumps A Min. Flow Isolation YES SI MVAAA121B SI Pumps B Min. Flow Isolation YES SI MVAAA138A LPSI Flow Control YES SI MVAAA138B LPSI Flow Control YES SI MVAAA139A LPSI Flow Control YES SI MVAAA139B LPSI Flow Control YES SI MVAAA219A HPSI Hdr. A Orifice Bypass NO SI MVAAA219B HPSI Hdr. B Orifice Bypass NO SI MVAAA225A HPSI Flow Control YES SI MVAAA225B HPSI Flow Control YES SI MVAAA226A HPSI Flow Control YES SI MVAAA226B HPSI Flow Control YES 3/4 8-65 AMENDMENT NO.

117 TABLE 3.8-2 (CONT)

MOTOR-OPERATED VALVES THERMAL OVERLOAD PROTECTION AND/OR BYPASS DEVICES TABLE (continued) BYPASS DEVICE VALVE NUMBER FUNCTION (YES/NO)SI MVAAA227A HPSI Flow Control YESSI MVAAA227B HPSI Flow Control YESSI MVAAA228A HPSI Flow Control YES SI MVAAA228B HPSI Flow Control YESSI MVAAA331A Safety Inj. Tank 1A Isolation YES SI MVAAA331B Safety Inj. Tank 1B Isolation YES SI MVAAA332A Safety Inj. Tank 2A Isolation YES SI MVAAA332B Safety Inj. Tank 2B Isolation YES SI MVAAA401A RCS Loop 2 Shutdown Cooling Isolation NO SI MVAAA401B RCS Loop 1 Shutdown Cooling Isolation NO(EC-935, Am. 117) (EC-935, Am. 117) SI MVAAA407A RCS Loop 2 Shutdown Cooling Isolation NOSI MVAAA407B RCS Loop 1 Shutdown Cooling Isolation NO SI MVAAA415A Shutdown Cooling Flow Control NO SI MVAAA415B Shutdown Cooling Flow Control NOSI MVAAA502A Hot Leg Injection NO SI MVAAA502B Hot Leg Injection NO SI MVAAA506A Hot Leg Injection NO SI MVAAA506B Hot Leg Injection NO SI MVAAA602A SIS Sump Outlet Isolation YES SI MVAAA602B SIS Sump Outlet Isolation YES 3/4 8-66 Amendment 19 TABLE 3.8-2 (CONT)

MOTOR-OPERATED VALVES THERMAL OVERLOAD PROTECTION AND/OR BYPASS DEVICES TABLE (continued) BYPASS DEVICE VALVE NUMBER FUNCTION (YES/NO)SI MVAAA135A Shutdown Line A Warm Up Line NO SI MVAAA135B Shutdown Line B Warm Up Line NO SI MVAAA125A Shutdown Heat Exchanger A Inlet Valve NO SI MVAAA125B Shutdown Heat Exchanger B Inlet Valve NO SI MVAAA412A Shutdown Heat Exchanger A Outlet Valve NO SI MVAAA412B Shutdown Heat Exchanger B Outlet Valve NO MS MVAAA401A EFW Pump Turbine Steam Shut-Off Valve YES MS MVAAA401B EFW Pump Turbine Steam Shut-Off Valve YES