3/4 1-1 AMENDMENT 15, 47 REACTIVITY CONTROL SYSTEMS 3/4.1.2 BORATION SYSTEMS CHARGING PUMPS - APPENDIX R LIMITING CONDITION FOR OPERATION 3.1.2.4 Charging pumps A and B shall be OPERABLE.
APPLICABILITY:
MODES 1, 2, 3, and 4 ACTION:
With charging pump A and/or B inoperable, restore the inoperable charging pump(s) to OPERABLE status within 7 days or within the next hour establish an hourly fire watch patrol in accordance with Table 3.1-1.
SURVEILLANCE REQUIREMENTS 4.1.2.4 No additional surveillance requirements other than those required by Technical Specifications 4.1.2.4.
3/4 1-2 AMENDMENT 47, 128 Table 3.1-1 Impacted Fire Areas with Charging Pump(s) Inoperable (LBDCR 14-005)
Out Of Service Component Fire Areas Impacted (Fire Watch Required)
Charging Pump A RAB1A RAB1E RAB3 RAB5 RAB7A RAB7B RAB7C RAB7D RAB8B RAB8C RAB15 RAB23 RAB27 RAB30 RAB31 RAB33 RAB37 RAB39 Charging Pump B RAB1A RAB1E RAB7A RAB7C RAB8A RAB23 RAB27 RAB30 RAB31 RAB34 RAB36 RAB37 RAB39 (LBDCR 14-005)