2-1 AMENDMENT NO. 119

(EC-22790, Am. 119) 2.2 LIMITING SAFETY SYSTEM SETTINGS REACTOR TRIP SETPOINTS 2.2.1 The reactor protective instrumentation setpoints shall be set consistent with the Trip Setpoint values shown in Table 2.2-1.

APPLICABILITY:

As shown for each channel in Table 3.3-1.

ACTION:

With a reactor protective instrumentation setpoint less conservative than the value shown in the Allowable Values column of Table 2.2-1, declare the channel inoperable and apply the applicable ACTION statement requirement of Specification 3.3-1 until the channel is restored to OPERABLE status with its trip setpoint adjusted consistent with the Trip Setpoint value.

(EC-22790, Am. 119)

2-2 AMENDMENT NO. 119

(EC-22790, Am. 119)

Table 2.2-1 REACTOR PROTECTIVE INSTRUMENTATION TRIP SETPOINT LIMITS FUNCTIONAL UNIT TRIP SETPOINT ALLOWABLE VALUES

1. Steam Generator Level - High

 87.7% (1)

 88.62% (1)

TABLE NOTATIONS (1)

% of the distance between steam generator upper and low level instrument nozzles.

(EC-22790, Am. 119)