CNL-13-148, Application to Modify Technical Specification 3.4.9, RCS Pressure and Temperature Limits (BFN TS 484)

From kanterella
(Redirected from ML13358A067)
Jump to navigation Jump to search

Application to Modify Technical Specification 3.4.9, RCS Pressure and Temperature Limits (BFN TS 484)
ML13358A067
Person / Time
Site: Browns Ferry 
Issue date: 12/18/2013
From: James Shea
Tennessee Valley Authority
To:
Document Control Desk, Office of Nuclear Reactor Regulation
Shared Package
ML13358A064 List:
References
CNL-13-148
Download: ML13358A067 (38)


Text

Proprietary Information Withhold Under 10 CFR 2.390(d)(1)

This letter is decontrolled when separated from Enclosure 2 Tennessee Valley Authority, 1101 Market Street, Chattanooga, Tennessee 37402 CNL-13-148 December 18, 2013 10 CFR 50.90 ATTN: Document Control Desk U.S. Nuclear Regulatory Commission Washington, D.C. 20555-0001 Browns Ferry Nuclear Plant, Unit 1 Renewed Facility Operating License No. DPR-33 NRC Docket No. 50-259

Subject:

Browns Ferry Nuclear Plant (BFN), Unit I - Application to Modify Technical Specification 3.4.9, "RCS Pressure and Temperature (P/T)

Limits" (BFN TS-484)

In accordance with the provisions of Title 10 of the Code of Federal Regulations (CFR) 50.90, "Application for amendment of license, construction permit, or early site permit," the Tennessee Valley Authority (TVA) is submitting a license amendment request to revise the Browns Ferry Nuclear Plant, Unit 1, Technical Specifications (TS) for Limiting Condition for Operation (LCO) 3.4.9, "RCS Pressure and Temperature (PIT) Limits." This submittal satisfies the commitment to prepare and submit revised BFN, Unit 1, P/T limits prior to the start of the period of extended operation as discussed in Section 4.2.5 provided in "Browns Ferry Nuclear Plant (BFN) - Units 1, 2 and 3 - Application for Renewed Operating Licenses," dated December 31, 2003 (ADAMS Accession No. ML040060359).

This submittal satisfies the requirements of NUREG-1843, "Safety Evaluation Report Related to the License Renewal of the Browns Ferry Nuclear Plant, Units 1, 2, and 3," dated April 2006 (ADAMs Accession No. ML061030032), commitment 39 which required the development and submittal of revised P/T limit curves for NRC approval prior to the period of extended operation. In the "Browns Ferry Nuclear Plant - NRC Post-Approval Site Inspection for License Renewal, Inspection Report," dated October 3, 2013 (Inspection Report 005000259/2013009, 005000260/2013009, 005000296/2013009), with respect to commitment 39, it was stated that new P/T limits will be calculated and approved before the period of extended operation. The current NRC approved P/T limit curves were approved prior to the period of extended operation and are applicable for operation into, but not to the end of the period of extended operation. Therefore, the proposed PIT limit curves were developed based on analyses projected to the end of the period of extended operation as required by 10 CFR 54.21 (c)(1)(ii).

Printed on recycled Paper

U.S. Nuclear Regulatory Commission Page 2 December 18, 2013 to this letter provides a description, technical evaluation, regulatory evaluation and environmental consideration of the proposed changes. Attachments 1 and 2 to provide a markup of the proposed changes to the BFN, Unit 1, TS and TS Bases (information only), respectively. Attachments 3 and 4 to Enclosure 1 provide retyped versions of the BFN, Unit 1, TS and TS Bases (information only), respectively, to show the incorporation of the proposed changes. Attachment 5 to Enclosure 1 provides a conforming markup of the BFN Updated Final Safety Analysis Report (UFSAR) that result from this proposed change. to this letter contains information which General Electric - Hitachi (GEH) and Electric Power Research Institute (EPRI) consider to be proprietary in nature and subsequently, pursuant to 10 CFR 2.930, "Public inspections, exceptions, request for withholding," paragraph (a)(4), it is requested that such information be withheld from public disclosure. Enclosure 4 provides the affidavits supporting the request. Enclosure 3 contains the redacted version of the proprietary attachment with the proprietary material removed, which is suitable for public disclosure.

TVA requests that the NRC approve this amendment by December 22, 2014, with implementation within 60 days of issuance.

TVA has determined that there are no significant hazards considerations associated with the proposed changes and that the changes qualify for a categorical exclusion from environmental review pursuant to the provisions of 10 CFR 51.22(c)(9).

The BFN Plant Operations Review Committee and the BFN Nuclear Safety Review Board have reviewed the proposed changes and determined that operation of BFN in accordance with the proposed changes will not endanger the health and safety of the public.

Additionally, in accordance with 10 CFR 50.91 (b)(1), TVA is sending a copy of this letter and the non-proprietary enclosures to the Alabama State Department of Public Health.

There are no new regulatory commitments associated with this submittal. Please address any questions regarding this request to Edward D. Schrull at 423-751-3850.

I declare under penalty of perjury that the foregoing is true and correct. Executed on this 18th day of December 2013.

Respe ly, J.

.Shea ic resident, Nuclear Licensing n c o0sures:

1.

Evaluation of Proposed Changes

2.

NEDC-33445P - Pressure and Temperature Limits Report (PTLR) Up to 25 and 38 Effective Full-Power Years (Proprietary)

3.

NEDO-33445 - Pressure and Temperature Limits Report (PTLR) Up to 25 and 38 Effective Full-Power Years (Non-Proprietary)

4.

Affidavits cc: See page 3

U.S. Nuclear Regulatory Commission Page 3 December 18, 2013 cc (Enclosures):

NRC Regional Administrator - Region II NRC Senior Resident Inspector - Browns Ferry Nuclear Plant State Health Officer, Alabama State Department of Public Health

ENCLOSURE I EVALUATION OF PROPOSED CHANGES TENNESSEE VALLEY AUTHORITY BROWNS FERRY NUCLEAR PLANT UNIT I BFN 13-484, Browns Ferry Nuclear Plant (BFN), Unit 1, Application to Modify Technical Specification 3.4.9, "RCS Pressure and Temperature (P/T) Limits" 1.0

SUMMARY

DESCRIPTION 2.0 DETAILED DESCRIPTION 2.1 Proposed Changes 2.2 Need for Proposed Changes

3.0 TECHNICAL EVALUATION

4.0 REGULATORY EVALUATION

4.1 Applicable Regulatory Requirements and Criteria 4.2 Precedent 4.3 No Significant Hazards Consideration 4.4 Conclusions

5.0 ENVIRONMENTAL CONSIDERATION

6.0 REFERENCES

ATTACHMENTS

1.

Proposed Technical Specifications Pages Markups

2.

Proposed Technical Specifications Bases Pages Markups (for information only)

3.

Proposed Retyped Technical Specifications Pages

4.

Proposed Retyped Technical Specifications Bases Pages (for Information only)

5.

Proposed Updated Final Safety Analysis Report Page Markups El-1

ENCLOSURE I EVALUATION OF PROPOSED CHANGES 1.0

SUMMARY

DESCRIPTION This evaluation supports a request to amend the Browns Ferry Nuclear Plant (BFN), Unit 1, Renewed Facility Operating License No. DPR-33 (Reference 1). The proposed changes modify the BFN, Unit 1, Technical Specification (TS) requirements related to the Reactor Coolant System (RCS) Pressure and Temperature (P/T) Limits in TS 3.4.9, "RCS Pressure and Temperature (P/T) Limits."

Specifically, the proposed change replaces the current sets of TS Figures 3.4.9-1 and 3.4.9-2.

The figures proposed to be replaced consist of two sets of P/T limit curves, one set valid up to 12 effective full power years (EFPY) of operation and another set valid from 12 EFPY to 16 EFPY of operation. The proposed change replaces the current curves with a set of figures valid for operation up to 25 EFPY and another set valid for operation from >25 EFPY and

-<38 EFPY. This proposed TS change is necessary to satisfy the commitment to develop and submit to the NRC P/T limits that have been projected to the end of the period of extended operation, prior to the start of the period of extended operation.

2.0 DETAILED DESCRIPTION 2.1 Proposed Changes TVA proposes to delete and replace TS Figures 3.4.9-1 and 3.4.9-2 that are applicable for operations up to 12 EFPY and for operations > 12 EFPY and < 16 EFPY, respectively, with new TS Figures 3.4.9-1 and 3.4.9-2 that are applicable for operations up to 25 EFPY and for operations > 25 EFPY and < 38 EFPY, respectively.

In addition, an associated note for each figure is changed to reflect the new operational applicability limit with respect to EFPY.

2.2 Need for Proposed Changes The License Renewal Application for BFN Units 1, 2, and 3 (Reference 2) states in Appendix A -

UFSAR Supplement, Section A.3.1.5, "Because of the relationship between the operating pressure-temperature limits and the fracture toughness transition of the reactor vessel, all three units will require new operating pressure-temperature limit curves to be calculated and approved for the extended period of operation."

License Condition 2.E in the BFN, Unit 1, renewed operating license (Reference 1) states, "The UFSAR supplement, as revised, describes certain future activities to be completed prior to the period of extended operation. TVA shall complete these activities no later than December 20, 2013, and shall notify the NRC in writing when implementation of these activities is complete and can be verified by NRC inspection."

The current Unit 1 PIT limit curves were approved by the NRC through the license amendment process (Reference 3) and are valid to 16 EFPY, well into the period of extended operation.

The proposed PIT limit curves which reflect the analyses projected to the end of the period of extended operation required by 10 CFR 54.21 (c)(1)(ii) use conservative fluence values calculated for a period of 60 years operation. The current approved Unit 1 P/T limit curves are valid up to 16 EFPY which covers entry into the period of extended operation. The proposed Unit 1 PIT limit curves are necessary to replace the current curves and provide operational coverage beyond the current approved limit of 16 EFPY to 38 EFPY.

E1-2

ENCLOSURE I EVALUATION OF PROPOSED CHANGES

3.0 TECHNICAL EVALUATION

10 CFR 50 Appendix G, "Fracture Toughness Requirements," requires the establishment of P/T limits for reactor coolant pressure boundary materials. Appendix G also requires an adequate margin to brittle failure be maintained during normal operation, anticipated operational occurrences, and system hydrostatic tests. The P/T limits are acceptance limits in themselves, because operation in accordance with these limitations precludes operation in an unanalyzed condition. The P/T limits are not derived from Design Basis Accident analyses.

The proposed P/T limit curves are composite curves established by superimposing limits derived from stress analyses of those portions of the reactor vessel and head that are the most restrictive. At any specific pressure, temperature, and temperature rate of change, one location within the reactor vessel will dictate the most restrictive limit. Across the span of the P/T limit curves, different locations are more restrictive, and thus, the curves are composites of the most restrictive regions.

These proposed P/T limit curves are primarily dependent upon the fracture toughness of the vessel ferritic materials. The key parameters which characterize a material's fracture toughness are the reference temperature of nil-ductility transition (RTNDT) and the Upper Shelf Energy (USE). These parameters are defined in 10 CFR 50, Appendix G, and in Appendix G of the ASME Boiler and Pressure Vessel Code,Section XI. These documents also contain the requirements used to establish the P/T operating limits to avoid brittle fracture. The method used to account for irradiation embrittlement is described in Regulatory Guide 1.99, "Radiation Embrittlement of Reactor Vessel Materials," Rev. 2.

Regulatory Guide 1.190, "Calculational and Dosimetry Methods for Determining Pressure Vessel Neutron Fluence," provides an acceptable method for calculating P/T limits that satisfies the requirements of 10 CFR 50 Appendix G.

The P/T limit curves for BFN, Unit 1, have been revised based on methodologies consistent with this regulatory guide using plant-specific material and fluence information. The proposed P/T limit curves reflect changes from those currently licensed. The new P/T limit curves incorporate a revised fluence calculated in accordance with NRC approved GE Licensing Topical Report NEDC-32983P-A, (Reference 4) representing BFN, Unit 1, operating conditions of up to 3952 MWt and incorporate the NRC approved methodologies described in GEH Topical Report NEDC-33178P-A (Reference 5). The operating condition of up to 3952 MWt represents the Extended Power Uprate (EPU) power level; however, the current license power level is 3458 MWt. The latest information from the BWRVIP Integrated Surveillance Program (ISP) applicable to BFN, Unit 1, has been incorporated.

Five separate curves are depicted in the revised TS Figure 3.4.9-1 and Figure 3.4.9-2 to clearly show the P/T limitations for the reactor bottom head area and the vessel beltline and upper vessel areas for all operating conditions.

Curve 1 of Figure 3.4.9-1 specifies minimum temperature for bottom head during mechanical heatup or cooldown following nuclear shutdown (i.e., reactor not critical).

Curve 2 of Figure 3.4.9-1 specifies minimum temperature for upper RPV and beltline during mechanical heatup or cooldown following nuclear shutdown (i.e., reactor not critical).

Curve 3 of Figure 3.4.9-1 specifies minimum temperature for core operation (i.e., reactor critical).

E1-3

ENCLOSURE I EVALUATION OF PROPOSED CHANGES Curve 1 of Figure 3.4.9-2 specifies minimum temperature for bottom head during in-service leak or hydrostatic testing.

Curve 2 of Figure 3.4.9-2 specifies minimum temperature for upper RPV and beltline during in-service leak or hydrostatic testing.

The 1998 Edition of the ASME Section XI Boiler and Pressure Vessel Code including 2000 Addenda was used for the evaluation to generate the P/T curves.

Values of initial RTNDT for the vessel materials were calculated in accordance with the methods described in GEH Topical Report NEDC-33178P-A. The values used to determine the initial RTNDT were obtained from the Certified Material Test Reports (CMTRs) for BFN, Unit 1. Initial RTNDT values for the BFN, Unit 1, weld materials were not calculated; these values were obtained from previous reports (References 6 and 7) and verified for input for this evaluation.

The adjusted reference temperature (ART) for the beltline region was determined using the methods described in Regulatory Guide 1.99, Rev. 2. These values are summarized in Tables B-4 and B-5 of Enclosures 2 and 3.

The limiting adjusted reference temperature value of 1930F for the 38 EFPY calculation remains below the 200°F criterion of Regulatory Guide 1.99, Rev. 2. The Upper Shelf Energy (USE) equivalent margin analyses values calculated for end of life (i.e., 38 EFPY) remain within the limits of Regulatory Guide 1.99, Rev. 2 and 10 CFR 50 Appendix G. A single set of P/T curves for the heatup and cooldown operating condition at a given EFPY that apply for both the 1/4T and 3/4T locations was developed. When combining pressure and thermal stresses, it is usually necessary to evaluate stresses at the 1/4T location (assumed inside surface flaw) and the 3/4T location (assumed outside surface flaw) because the thermal gradient tensile stress of interest is in the inner wall during cooldown and is in the outer wall during heatup. However, as a conservative simplification, the thermal gradient stress at the 1/4T location is assumed to be tensile for both heatup and cooldown. This results in the approach of applying the maximum tensile stress at the 1/4T location. This approach is conservative because irradiation effects cause the allowable toughness, KIR, at 1/4T to be less than that at 3/4T for a given metal temperature. This approach causes no operational difficulties, because BFN, Unit 1, is at steam saturation conditions during normal operation, well above the heatup/cooldown curve limits.

The GEH Pressure-Temperature Limits Report for BFN, Unit 1, provided as Enclosures 2 (proprietary) and 3 (non-proprietary), demonstrates the technical methods and contains the data for producing the composite P/T curves which are proposed to be placed in the TS. Table 1 in the GEH Report for BFN, Unit 1, contains the data for producing the composite 25 EFPY curves. In the same manner, Table 2 of the GEH Report contains the data for producing the composite 38 EFPY curves.

The proposed P/T curves have been developed utilizing the methodology of Regulatory Guide 1.190 and ASME Section XI. The regulatory guidance provides an allowance for margin to be included in the bounding values of the ART. Use of this methodology ensures adequate safety margins are maintained. In addition, the analysis conforms to the requirements of 10 CFR 50, Appendix G, which ensures the most limiting material is considered in the development of the P/T curves. The vessel is in compliance with the regulatory requirements, adequate safety margins are maintained, and, therefore, BFN, Unit 1 operation to 38 EFPY, representing a 60 year license, will not have an adverse effect on reactor vessel fracture toughness.

E1-4

ENCLOSURE I EVALUATION OF PROPOSED CHANGES

4.0 REGULATORY EVALUATION

4.1 Applicable Regulatory Requirements and Criteria Pursuant to 10 CFR 50.90, TVA is submitting a request for a Technical Specifications (TS) change to renewed license DPR-33 for BFN, Unit 1. The proposed change revises the reactor vessel pressure-temperature (P/T) limits depicted in current TS Figure 3.4.9-1 and Figure 3.4.9-2.

10 CFR 50, Appendix G, contains the requirements for the P/T limit curves, and requires that P/T curves for the reactor pressure vessel be at least as conservative as those obtained by applying the methodology of Appendix G to Section Xl of the American Society of Mechanical Engineers (ASME) Code.

The regulatory requirements for fluence calculations are contained in General Design Criteria (GDC) 30 and 31. NRC issued Regulatory Guide 1.190 in March 2001, which provided state-of-the-art calculations and measurement procedures that are acceptable to the NRC staff for determining pressure vessel fluence. NRC has approved vessel fluence calculation methodologies which satisfy the requirements of GDCs 30 and 31 performed with approved methodologies or with methods which are shown to adhere to the guidance in Regulatory Guide 1.190. The analyses supporting this submittal were performed in accordance with Regulatory Guide 1.190 guidance.

4.2 Precedent The NRC has previously approved a License Amendment Request (LAR) that included two sets of P/T limit curves for BFN Units 2 and 3 (Amendments 288 and 247), one set for operation up to 23 EFPY (Unit 2) and up to 20 EFPY (Unit 3), and a second set for operations up to 30 EFPY (Unit 2) and up to 28 EFPY (Unit 3) (Reference 8). TVA proposed to the NRC in the February 24, 2004 LAR letter (Reference 9) that both sets of curves be placed in the TS upon approval of the amendments. In the NRC Safety Evaluation for BFN Units 2 and 3, Amendments 288 and 247, dated March 10, 2004 (Reference 8), the NRC stated that because the applicability of each set of curves was clearly defined, the approach proposed by TVA was acceptable.

The NRC has previously approved an LAR that revised facility P/T limit curves based on the application of methodology in GE Hitachi Nuclear Energy (GEH) Licensing Topical Reports NEDC-33178P-A (Reference 5) and NEDC-32983P-A (Reference 4) for the Peach Bottom Atomic Power Station, Units 2 and 3, Amendment Nos. 286 and 289, issued by NRC letter dated April 1, 2013 (ADAMS Accession No. ML13079A219). The Peach Bottom Atomic Power Station LAR used the 1998 edition of the ASME Boiler and Pressure Vessel Code including 2000 Addenda in its evaluation; and, applied calculated fluence values based on uprated conditions that conservatively bounded future operations.

4.3 No Significant Hazards Consideration The proposed change modifies the Browns Ferry Nuclear Plant (BFN), Unit 1, Technical Specification (TS) requirements related to TS 3.4.9, "RCS Pressure and Temperature (P/T)

Limits."

Tennessee Valley Authority (TVA) has concluded that the changes to BFN, Unit 1, TS 3.4.9 do not involve a significant hazards consideration. TVA's conclusion is based on its evaluation in accordance with 10 CFR 50.91 (a)(1) of the three standards set forth in 10 CFR 50.92, "Issuance of Amendment," as discussed below:

E1-5

ENCLOSURE I EVALUATION OF PROPOSED CHANGES

1.

Does the proposed amendment involve a significant increase in the probability or consequences of any accident previously evaluated?

Response: No The proposed changes are to accepted operating parameters that have been approved in previous license amendments. The changes to P/T curves were developed based on NRC approved methodologies. The proposed changes deal exclusively with the reactor vessel P/T curves, which define the permissible regions for operation and testing. Failure of the reactor vessel is not considered as a design basis accident. Through the design conservatisms used to calculate the P/T curves, reactor vessel failure has a low probability of occurrence and is not considered in the safety analyses. The proposed changes adjust the reference temperature for the limiting material to account for irradiation effects and provide the same level of protection as previously evaluated and approved.

The adjusted reference temperature calculations were performed in accordance with the requirements of 10 CFR 50 Appendix G using the guidance contained in Regulatory Guide 1.190, "Calculational and Dosimetry Methods for Determining Pressure Vessel Neutron Fluence," to reflect use of the operating limits to no more than 38 Effective Full Power Years (EFPY). These changes do not alter or prevent the operation of equipment required to mitigate any accident analyzed in the BFN Final Safety Analysis Report.

Therefore, the proposed change does not involve a significant increase in the probability or consequences of an accident previously evaluated.

2.

Does the proposed amendment create the possibility of a new or different kind of accident from any accident previously evaluated?

Response: No The proposed changes are to accepted operating parameters that have been approved in previous license amendments. The changes to P/T curves were developed based on NRC approved methodologies. The proposed changes to the reactor vessel P/T curves do not involve a modification to plant equipment. No new failure modes are introduced. There is no effect on the function of any plant system, and no new system interactions are introduced by this change. Therefore, the proposed change does not create the possibility of a new or different kind of accident from any previously evaluated.

3.

Does the proposed amendment involve a significant reduction in a margin of safety?

Response: No The proposed changes are to accepted operating parameters that have been approved in previous license amendments. The changes to P/T curves were developed based on NRC approved methodologies. The proposed curves conform to the guidance contained in Regulatory Guide 1.190, "Calculational and Dosimetry Methods for Determining Pressure Vessel Neutron Fluence," and maintain the safety margins specified in 10 CFR 50 Appendix G. Therefore, the proposed change does not involve a significant reduction in a margin of safety.

Based on the above, TVA concludes that the proposed amendment(s) present no significant hazards consideration under the standards set forth in 10 CFR 50.92(c), and, accordingly, a finding of "no significant hazards consideration" is justified.

E1-6

ENCLOSURE I EVALUATION OF PROPOSED CHANGES 4.4 Conclusions In conclusion, based on the considerations discussed above, (1) there is reasonable assurance that the health and safety of the public will not be endangered by operation in the proposed manner, (2) such activities will be conducted in compliance with the Commission's regulations, and (3) the issuance of the amendment will not be inimical to the common defense and security or to the health and safety of the public.

5.0 ENVIRONMENTAL CONSIDERATION

A review has determined that the proposed amendment would change a requirement with respect to installation or use of a facility component located within the restricted area, as defined in 10 CFR 20, or would change an inspection or surveillance requirement. However, the proposed amendment does not involve (i) a significant hazards consideration, (ii) a significant change in the types or significant increase in the amounts of any effluents that may be released offsite, or (iii) a significant increase in individual or cumulative occupational radiation exposure.

Accordingly, the proposed amendment meets the eligibility criterion for categorical exclusion set forth in 10 CFR 51.22(c)(9). Therefore, pursuant to 10 CFR 51.22(b), no environmental impact statement or environmental assessment need be prepared in connection with the proposed amendment.

6.0 REFERENCES

1.

Tennessee Valley Authority Browns Ferry Nuclear Plant, Unit 1, Docket No. 50-259, Renewed Facility Operating License, Renewed License No. DPR-33 (ADAMS Accession No. ML061110094).

2.

Letter from TVA to NRC, "Browns Ferry Nuclear Plant (BFN), Units 1, 2 and 3 - Application for Renewed Operating Licenses," dated December 31, 2003 (ADAMS Accession No. ML040060359).

3.

Letter from NRC to TVA, "Browns Ferry Nuclear Plant, Unit 1 - Issuance of Amendments Regarding Update of Pressure-Temperature Limit Curves (TAC No. MC5373) (TS 428),"

dated July 26, 2006 (ADAMS Accession No. ML061090658).

4.

GE Nuclear Energy, NEDC-32983P-A, "General Electric Methodology for Reactor Pressure Vessel Fast Neutron Flux Evaluations," (TAC No. MC9891).

5.

GEH Nuclear Energy, NEDC-33178P-A, Revision 1, "GE Hitachi Energy Methodology for Development of Reactor Pressure Vessel Pressure-Temperature Curves,"

June 2009 (GEH Proprietary).

6.

Evaluation of RTNDT, USE, and Chemical Composition of Core Region Electroslag Welds for Quad Cities Units 1 and 2, Framatome Technologies, Lynchburg, Virginia, January 1996 (BAW-2259).

7.

Letter, TE Abney (TVA) to US NRC, "Browns Ferry Nuclear Plant (BFN) - Units 1, 2, and 3

- Generic Letter (GL) 92-01, Revision 1, Supplement 1, Reactor Vessel Structural Integrity

- Response to NRC Request for Additional Information (TAC Nos. MAl 179, MA1 180, and MA1181)", September 8, 1998.

E11-7

ENCLOSURE I EVALUATION OF PROPOSED CHANGES

8.

Letter from NRC to TVA, "Browns Ferry Nuclear Plant, Units 2 and 3 - Issuance of Amendments Regarding Pressure-Temperature Limit Curves (TAC Nos. MC0807 and MC0808)," dated March 10, 2004 (ADAMS Accession Nos. ML040480013, ML040750188, and ML040750194).

9.

Letter from TVA to NRC, "Browns Ferry Nuclear Plant (BFN) - TVA Revision to Implementation Plant Described in Units 2 and 3 - Technical Specifications (TS) Change No. 441 Revision 1 - Pressure-Temperature (P-T) Curve Update (MC0807 and MC0808),"

dated February 24, 2004 (ADAMS Accession No. ML040550496).

E1-8

ATTACHMENT I Proposed Technical Specifications Pages Markups

RCS P/T Limits 3.4.9 1400 Curve No.l1

'1 2

3 Minimum temperature for 4

12* ~REs Eii i

mechanical heatup or bottom head during BROWN FR

/cooldown following nuclear shutdown.

11 CURVES 1, 2, AND 3'.1 1200 ARE VALIDiFOR 12 F

0V 0 ERATIOI Curve No.

2 1100 Minimum temperature for upper RPV and beltline during mechanical 1000 heatup or cooldown following nuclear shutdown.

90 S0 x

o lCurve No.

3

a. 80 Minimum temperature for 0 1 0

core operation (criticality).

c~70 ul' 0 0Notes S60 These curves include

.. 0 sufficient margin to U

provide protection S50 against feedwater

____-00 nozzle degradation.

Z"0The curves allow for shifts in RTNDT of the 40 Reactor vessel beltline 30 materials, in accordance with Reg.

30-Guide 1.99 Rev.

2 to n

0 compensate for radiation embrittlement a.L 20

_for

+-; EFPY.

0 BOTTM 25 H

FLANGE The acceptable area for 10 Roperation is to the

-003ureright of the applicable 0

2 5

7 10 12 15 17 20 22 25 2N 30 5

0 5

05 0

50 5

05 0

MINIMUM REACTOR VESSEL METAL TEMPERATURE 0F

  • Replace with Insert 1I Figure 3.4.9-1 Pressure/Temperature Limits for Mechanical Heatup, Cooldown following Shutdown, and Reactor Critical Operations BFN-UNIT 1 3.4-29 Amendment No.-234, 256 July 26, 2006

1400 1300 1200 1100 l100 m

900 IL 0

w 800 Cl) 700 0

600 z

_ 500

-J u) 400 co)

L 300 I

200 100 0

0 25 50 75 100 125 150 175 200 225 250 275 300 MINIMUM REACTOR VESSEL METAL TEMPERATURE (°F)

Ilnsert 11

RCS P/T Limits 3.4.9 1400

-/

Curve No.

1 3.1 2

Minimum temperature for 3400 bottom head during BROMIS FE RY UNIT 1 in-service leak or S

2hydrostatic testing.

120 CURVES 1 AND 2 ARE ALID FOR 32 FPY OF 0 ERATJ ON Curve No.

2 1100 Minimum temperature for upper RPV and beltline during in-service leak 1000 or hydrostatic testing.

(

90 Notes 0

These curves include sufficient margin to 80

_,/_

provide protection 0

against feedwater 0

nozzle degradation.

1-70 The curves allow for W

0 shifts in RTNDT of the Reactor vessel beltline 60 materials, in c

0 accordance with Reg.

0 Guide 1.99 Rev.

2 to I.-

50 compensate for 0U radiation embrittlement 0

~for

+* EFPY.

_z 25 40 The acceptable area for 0

operation is to the right of the applicable 30M curves.

t 0

20 TTOM--FLNG 0

H E D R E G ION8 o

10

/

68 °F 0\\

0 2 50 5

10 12 15 17 0

0 25 50 75 0

5 0

5 MINIMUM REACTOR VESSEL METAL TEMPERATURE F IN--fReplace

-With Insert 2 Figure 3.4.9-2 Pressure/Temperature Limits for Reactor In-Service Leak and Hydrostatic Testing BFN-UNIT 1 3.4-29a Amendment No. 256 July 26, 2006

1400 1300 1200 1100 s*1000 X

900

(.0 mu 800 mu 700 0

600 500 Lu 400 IL 300 200 100 0

I 0

25 50 75 100 125 150 175 200 225 250 MINIMUM REACTOR VESSEL METAL TEMPERATURE (°F)

Ilnsert 21

RCS P/T Limits 3.4.9 1

2 3

Curve No.

1 BROWNS FERRY UNI 13 Minimum temperature for 1300CUES, 2, AND 3 bottom head during 10 RE VALID FOR 16 mechanical heatup or S0 EROTIC RA 2

cooldown following 1200

-nuclear shutdown.

Curve No.

2 1100 Minimum temperature for upper RPV and beltline during mechanical 1000 heatup or cooldown afollowing nuclear shutdown.

900 Curve No.

3 IL 8Minimum temperature for core operation (criticality).

700 Notes 60_

These curves include o

60 sufficient margin to 13 provide protection against feedwater

___500 nozzle degradation.

2

/The curves allow for shifts in RlDT of the 2

400 Reactor vessel beltline materials, in UJ accordance with Reg.

300 Guide 1.99 Rev.

2 to compensate for cc radiation embrittlement I

200 for i-r EFPY.

BOT ON 38 FLANGE The acceptable area for 68RO operation is to the 100 right of the applicable 0

curves.

0 25 50 75 100 125 150 175 200 225 250 27 300 MINIMUM REACTOR VESSEL METAL TEM PERATURE OF Replace with Insert 3I Figure 3.4.9-1 Pressure/Temperature Limits for Mechanical Heatup, Cooldown following Shutdown, and Reactor Critical Operations BFN-UNIT 1 3.4-29b Amendment No. 2-,

284 September 13, 2013

1400 I

I Browns Ferry Unit 1 1300 Curves 1,2, and 3 Are Valid For 38 1200 EFPY of Operation A

1200 1100

".1000 900 0.

w 800 w

W 700


+

0 n 600 T

_500 43 si 10pi 420 psig U) 400 300 200 20 BOTTOMT 100

=F 100

-HEAD BOLTFUP 0

83*F 0

0 25 50 75 100 125 150 175 200 225 250 275 300 MINIMUM REACTOR VESSEL METAL TEMPERATURE (-F)

Insert 3

RCS P/T Limits 3.4.9 1400

_Curve No. 1 Minimum temperature for 1300 bottom head during 10 RWNFR/UI/_

in-service leak or BROWNS FERRY1,N2 hydrostatic testing.

- CURVES 1, 2, AND 3 ARE VALID FOR 16 C

10l0o

-EFPY OF OPERATION u

Minimum temperature for 5

  • upper RPV and beltline 100NA during in-service leak or hydrostatic testing.

S900 Notes__

.. ]

These curves include sufficient margin to 800 --

provide protection 8

against feedwater nozzle degradation.

o 700

/

The curves allow for shifts in RTNDT of the 600 Reactor vessel beltline materials, in accordance with Reg.

compensate for

_40 radiation embrittlement for+6 EFPY.

38 300 The acceptable area for operation is to the 200 right of the applicable

/BOTTOM FLANGE curves.

HEAD REGION 10 68F 830F Replace with Insert 4 0

25 50 75 100 125 150 175 200 MINIMUM REACTOR VESSEL METAL TEMPERATURE Figure 3.4.9-2 Pressure/Temperature Limits for Reactor In-Service Leak and Hydrostatic Testing BFN-UNIT 1 3.4-29c Amendment No. 2K6, 284 September 13, 2013

1400 Browns Ferry Unit 1 1300 Curves 1 and 2 Are Valid for 38 J

1200 EFPY of Operation 1100 1000 0

800

/

ca IX 700 I-60pi 600.',

50050pi IU c

400 BOTTOM wU 68*F 300 100 0L 0

25 50 75 100 125 150 175 200 225 250 MINIMUM REACTOR VESSEL METAL TEMPERATURE (OF)

In-seRt 47

ATTACHMENT 2 Proposed Technical Specifications Bases Pages Markups (for information only)

RCS P/T Limits B 3.4.9 B 3.4 REACTOR COOLANT SYSTEM (RCS)

B 3.4.9 RCS Pressure and Temperature (P/T) Limits BASES BACKGROUND All components of the RCS are designed to withstand effects of cyclic loads due to system pressure and temperature changes.

These loads are introduced by startup (heatup) and shutdown (cooldown) operations, power transients, and reactor trips. This LCO limits the pressure and temperature changes during RCS heatup and cooldown, within the design assumptions and the stress limits for cyclic operation.

The pressure-temperature (P-T) curves included in the Technical Specifications have been developed to present steam-dome pressure versus minimum vessel metal temperature, incorporating appropriate non-beltline limits and irradiation embrittlement effects in the beltline. There are two sets of curves provided for Unit 1. The first set applies to operation up to 254-2 effective full power years (EFPY), and the second set applies to operation greater than 254-2 EFPY and less than or equal to 3846 EFPY, where 3846 EFPY represents the end of the renewed4 yeae license and 254-2 EFPY is provided as a midpoint between the current EFPY and 384-6 EFPY. The P-T curves are provided in Figure 3.4.9-1 and Figure 3.4.9-2, respectively. Figure 3.4.9-1 contains P-T limit curves for mechanical heatup or cooldown following nuclear shutdown (bottom head and upper RPV/beltline) and for core operation (criticality). Figure 3.4.9-2 contains P-T limit curves for inservice leakage and hydrostatic testing (bottom head and upper RPV/beltline). The maximum rate of change of reactor coolant temperature is contained in SR 3.4.9.5, SR 3.4.9.6, and SR 3.4.9.7.

(continued)

BFN-UNIT 1 B 3.4-55 Revision 0, 38,

RCS P/T Limits B 3.4.9 BASES BACKGROUND (continued)

The P-T curves incorporate a fluence calculated in accordance with GE Licensing Topical Report NEDC-32983P (Ref. 10),

which has been approved by the NRC and is in compliance with Regulatory Guide 1.190 (Ref. 11). The fluence represents an Extended Power Uprate (EPU) for the rated power of 3952 MWt, and is conservatively applied for the rated power of 3458 MWt.

The 19984199 Edition of the ASME Section Xl Boiler and Pressure Vessel Code including 20001-996 Addenda was used in accordance with 10 CFR 50.55a.

Each P/T limit curve defines an acceptable region for normal operation. The usual use of the curves is operational guidance during heatup or cooldown maneuvering, when pressure and temperature indications are monitored and compared to the applicable curve to determine that operation is within the allowable region.

The LCO establishes operating limits that provide a margin to brittle failure of the reactor vessel and piping of the reactor coolant pressure boundary (RCPB). The vessel is the component most subject to brittle failure. Therefore, the LCO limits apply mainly to the vessel.

(continued)

BFN-UNIT 1 B 3.4-55a Revision 38, 50,

ATTACHMENT 3 Proposed Retyped Technical Specifications Pages

RCS P/T Limits 3.4.9 1400 Curve No. 1 BroAns Ferry 3

Mnimumte erakrefor

-1300 Unit 1 bdmha n

130 Itxttan head duirin Curves 1, 2, and 3 a etpo are Valid for 25 mechanical heatnu or 12o0 EFPY of Operation shtdowun.

1100 CurveNo. 2

-1000 Ilinirrrtfor

'W Loo ppe RP\\/and berdine during mechcal hea"or ooldmn following nulear

-r 900 shudxmn.

0 0

LU 8oo CurveNo. 3 LU M ninmum e p rn t~

ef or core

=l=700 op'eration(cr iti y).

~Notes:

W 600 Ths CLiVes include t7-suffident margin to provide 2

500 500 psig 5oo psig protection aganst feedater r--:*-*.nozzle degradation. The 430 ps curvesallow for shifts in 40 0 RTNuT d the Reactor vessel M

beitline materials, in 0.

30 odacewith Reg. Gdide 1.99 Rev. 2 to cpensate for raciation embrittlement for 25 200 EFFY.

100 HEAD Theaccetearea for opercon is to t right the applicable curves 0

0 25 50 75 100 125 '150 175 200 225 250 275 300 MINIMUM REACTOR VESSEL METAL TEMPERATURE (°F)

Figure 3.4.9-1 Pressure/Temperature Limits for Mechanical Heatup, Cooldown following Shutdown, and Reactor Critical Operations BFN-UNIT 1 3.4-29 Amendment No. 2-56,

RCS P/T Limits 3.4.9 1400 B4ns Ferry Curve No. 1 BrowUnit 1

/

-2 Minimum temperature for Curves 1 and 2 bottom head during in-service are Valid for 25 leak or hydrostatic testing.

1200 EFPY ofOperation I

-Curve No. 2 1100 Minimum temperature for upper RPV and beitlineduring 10 in-service leak or hydrostatic 0ooo

-testing.

Z 900go Notes:

0 These curves include I-

-w-8 sufficient margin to provide protection against feedwater W

nozzle degradation. The

> 700 curves allow for shifts in 0I--

fiRTN of the Reactor vessel 600 beltline materials, in 9

accordance with Reg. Guide 1.99 Rev. 2 to compensate for s 500 radiation embrittlement for 25 EFPY.

W 400 BOTTOM HA s

The acceptable area for IL 300 operation is to the right of the 2300

-AG applicable curves.

200

-I LI3 I

RLEGION I

~83Tp 100 0

25 50 75 100 125 150 175 200 225 250 MINIMUM REACTOR VESSEL METAL TEMPERATURE (°F)

Figure 3.4.9-2 Pressure/Temperature Limits for Reactor In-Service Leak and Hydrostatic Testing BFN-UNIT 1 3.4-29a Amendment No. 2=5,

RCS P/T Limits 3.4.9 1400 Curve No. 1 Brawms Ferry 1

2 Minimum temperature for Unit 1 bottom head during 1300 Curves 1, 2, and3 cdh a h or are Valid for 38 m

o ln owic Mng nidear cooldonfollo nuclwear 1200 EFPYof Operationshut n.

1100 Curve No. 2 I

Minimum temperature for Z 1000 upp RPV and beltine during mechanical heatup or cooldenfollowng nudear x

900 Shutdown.

0.

0,, 80o0...

Curve No.3 0

Minimum temperature for core S700 operation (criticality).

4 1

60 I

Notes:

'" 600

_Z These curves include sufficient margin to provide

_*500 protection against feedwater

-x430 Ps 410sig 420 psig nozzle degradation. The E

(-

curves allow for shifts in 400 W

-iDRT of the Reactor vessel

!beitline materals, in 300 1

accordance with Reg. Guide 1.99 Rev. 2 to compensate for 200 radiation embrittlement for 38 BOTTOM EFY E001 HAD

__E___Y" 10 68F The acceptable area for 0

1 1

applicable curves.

0 25 50 75 100 125 150 175 200 225 250 275 300 MINIMUM REACTOR VESSEL METAL TEMPERATURE ('F)

Figure 3.4.9-1 Pressure/Temperature Limits for Mechanical Heatup, Cooldown following Shutdown, and Reactor Critical Operations BFN-UNIT I 3.4-29b Amendment No. 2-%, 2-84,

RCS P/T Limits 3.4.9 1400 Browns Ferry 1

2 Curve No. 1 1300 Unit 1

/_11 Minimum temperature for Curves 1 and 2 bottom head during in-service are Valid for 38 leak or hydrostatic testing.

1200 EFPY of Operation Curve No. 2 1100 1100Minimum temperature for upper RPV and beltline during

'B1000

/

in-service leak or hydrostatic Lu

/

testing.

900 1

(L Notes:

8-These curves include 0

sufficient margin to provide

,protection against feedwater

-nozzle degradation. The 64 7p0ig curves allow for shifts in U

__RTNDTof the Reactor vessel

"' 600 beltline materials, in

-z_

[ig accordance with Reg. Guide 500

-1.99 Rev. 2 to compensate for

,*500 Sradiation embrittlement for 38 EFPY.

400 BOTOM 68F I

The acceptable area for

(. 300 operation is to the right of the applicable curves.

200

-- FLANGE REGION 100 0

0 25 50 75 100 125 150 175 200 225 250 MINIMUM REACTOR VESSEL METAL TEMPERATURE (°F)

Figure 3.4.9-2 Pressure/Temperature Limits for Reactor In-Service Leak and Hydrostatic Testing BFN-UNIT 1 3.4-29c Amendment No. 2-,W 284,

ATTACHMENT 4 Proposed Retyped Technical Specifications Bases Pages (for information only)

RCS P/T Limits B 3.4.9 B 3.4 REACTOR COOLANT SYSTEM (RCS)

B 3.4.9 RCS Pressure and Temperature (P/T) Limits BASES BACKGROUND All components of the RCS are designed to withstand effects of cyclic loads due to system pressure and temperature changes.

These loads are introduced by startup (heatup) and shutdown (cooldown) operations, power transients, and reactor trips. This LCO limits the pressure and temperature changes during RCS heatup and cooldown, within the design assumptions and the stress limits for cyclic operation.

The pressure-temperature (P-T) curves included in the Technical Specifications have been developed to present steam-dome pressure versus minimum vessel metal temperature, incorporating appropriate non-beltline limits and irradiation embrittlement effects in the beltline. There are two sets of curves provided for Unit 1. The first set applies to operation up to 25 effective full power years (EFPY), and the second set applies to operation greater than 25 EFPY and less than or equal to 38 EFPY, where 38 EFPY represents the end of the renewed license and 25 EFPY is provided as a midpoint between the current EFPY and 38 EFPY. The P-T curves are provided in Figure 3.4.9-1 and Figure 3.4.9-2, respectively.

Figure 3.4.9-1 contains P-T limit curves for mechanical heatup or cooldown following nuclear shutdown (bottom head and upper RPV/beltline) and for core operation (criticality). Figure 3.4.9-2 contains P-T limit curves for inservice leakage and hydrostatic testing (bottom head and upper RPV/beltline). The maximum rate of change of reactor coolant temperature is contained in SR 3.4.9.5, SR 3.4.9.6, and SR 3.4.9.7.

(continued)

BFN-UNIT 1 B 3.4-55 Revision G, 38,

RCS P/T Limits B 3.4.9 BASES BACKGROUND (continued)

The P-T curves incorporate a fluence calculated in accordance with GE Licensing Topical Report NEDC-32983P (Ref. 10),

which has been approved by the NRC and is in compliance with Regulatory Guide 1.190 (Ref. 11). The fluence represents an Extended Power Uprate (EPU) for the rated power of 3952 MWt, and is conservatively applied for the rated power of 3458 MWt.

The 1998 Edition of the ASME Section Xl Boiler and Pressure Vessel Code including 2000 Addenda was used in accordance with 10 CFR 50.55a.

Each P/T limit curve defines an acceptable region for normal operation. The usual use of the curves is operational guidance during heatup or cooldown maneuvering, when pressure and temperature indications are monitored and compared to the applicable curve to determine that operation is within the allowable region.

The LCO establishes operating limits that provide a margin to brittle failure of the reactor vessel and piping of the reactor coolant pressure boundary (RCPB). The vessel is the component most subject to brittle failure. Therefore, the LCO limits apply mainly to the vessel.

(continued)

BFN-UNIT 1 B 3.4-55a Revision 38, 50,

ATTACHMENT 5 Proposed Updated Final Safety Analysis Report Page Markups

BFN-25.2 Although little corrosion of plain carbon or low-alloy steels occurs at temperatures of 500OF to 6000F, higher corrosion rates occur at temperatures around 1400F. The 0.125-inch minimum-thickness cladding provides the necessary corrosion resistance during reactor shutdown and also helps maintain water clarity during refueling operations. Since the vessel head is exposed to a saturated steam environment throughout its operating lifetime, stainless steel cladding is not required over its interior surfaces. Exterior, exposed ferritic surfaces of pressure-containing parts have a minimum corrosion allowance of 1/16 inch. The interior surfaces of the top head and all carbon and low-alloy steel nozzles exposed to the reactor coolant have a corrosion allowance of 1/16 inch. The vessel shape is designed to limit coolant retention pockets and crevices.

The nil-ductility transition (NDT) temperature is defined as the temperature below which ferritic steel breaks in a brittle, rather than ductile, manner. The NDT temperature increases as a function of neutron exposure at integrated neutron exposures greater than about 1 x 1017 nvt with neutrons of energies in excess of 1 MeV. Since the material NDT temperature dictates the minimum operating temperature at which the reactor vessel can be pressurized, it is desirable to keep the NDT temperature as low as possible. One way that this is accomplished is by selecting fine-grained steels and by using advanced fabrication techniques to minimize radiation effects. The as-fabricated initial NDT temperature for all carbon and low-alloy steel used in the main closure flanges, closure bolting material, and the shell and head materials connecting to these flanges, including the connecting circumferential weld material, is limited to a maximum of 10OF as determined by ASTM E208. For each main closure flange forging, a minimum of 1 tensile, 3 Charpy V-notch, and 2 drop weight test specimens have been tested from each of two locations about 1800 apart on the flange. For all other carbon and low-alloy steel pressure-containing materials, including weld materials and the vessel slo ort 5

skirt material, the es-fbroeeted initial NDT temperature is no higher than 40F. A grain size of 5 or finer, as determined by the method in ASTM El 12, is maintained.

Another way of minimizing any changes (elevating) to the NDT temperature is by reducing the integrated neutron exposure at the inner surface of the reactor vessel.

The coolant annulus between the vessel and core shroud and the core location in the vessel limit the integrated neutron exposure of reactor vessel material to less than 1 x 1019 nvt from neutrons with energy levels greater than 1 MeV, within the 40-year design lifetime of the vessel. TLAAs have been identified and evaluated for the reactor vessel 60 year operating life. Summaries of these evaluations for the reactor vessel life are provided in Appendix 0, Sections 0.3.1 and 0.3.2. This is not the expected exposure, nor is it the absolute limit of safe exposure; it is an exposure value that can be demonstrated to be safe and practical to maintain. The maximum per GEH Report No.

calculated exposure for neutrons of 1 MeV or greater is 2 9

nvt.P 0000-0166-0632-RO I 4.2-3

4cr- _,4 akerycI ttX'C COPO.Ale BFN-25.2 demonstrate that all materials and weld metal mee brittle fracture requirements at test temperature. Test specimens ere prepared and tested with minimum impact energy requirements in accordance with Table N-421 and the general provisions of N-313, N-331, N-

-5 1 of Secti the ASME Boiler and Pressure Vessel Code.

nrior to the Summer 1972 F.--*

6 Addenda of the 1971 ASME Section III Boiler and Pressure Vessel Code, O

pul..d i, impact testing was not required on materials with a nominal section thicknes

201, of 1/2 inch or less. However, this 1/2 inch thickness exclusion was increase

. pe to 5/8 inch by the ASME Boiler and Pressure Vessel Code,Section III, 1971 1, ftrj:P,,.7. NP Edition, Summer 1972 Addenda. Therefore, after issuance of the Summer Were 1972 Addenda, impact testing is not required on materials with a nominal

.,coodlr3

,.1 section thickness of 5/8 inch or less. The welding procedures used were 000

!ý qualified by impact testing of weld metal and heat affected zone to the samý A*WA sj..

requirements as the base metal in accordance with N-541.

E195..2 B.

Impact tests were not required for the following:

1.

Bolting, including nuts, 1-inch nominal diameter or less,

2.

Bars with a nominal cross-sectional area not exceeding 1 square inch,

3.

Materials with a nominal (section) wall thickness of less than 1/2 inch or 5/8 inch (refer to paragraph 4.2.4.10.A),

4.

Components including pumps, valves, piping, and fittings with a nominal inlet pipe size of 6-inch-diameter and less, regardless of thickness, and

5.

Consumable insert material, austenitic stainless steel, and nonferrous materials.

C.

Impact testing was not required on components or equipment pressure parts having a minimum service temperature of 250°F or more when pressured over 20 percent of the design pressure. Example: Steam line is excluded from brittle fracture test requirement since the steam temperature will be over 2501F when the steam line pressure is at the 20 percent design pressure.

D.

Impact testing was not required on components or equipment pressure parts whose rupture could not result in a loss of coolant exceeding the capability of normal makeup systems to maintain adequate core cooling for the duration of a reactor shutdown and orderly cooldown.

E.

These criteria apply to components and equipment pressure parts, including flange bolts of the reactor coolant pressure boundary, and do not apply to 4.2-9

BFN-25.2 Type of Cycle Boltup Design hydrostatic test at 1250 psig Startup (100°F/hr heatup rate)

Daily reduction to 75 percent power Weekly reduction to 50 percent power Control rod worth test Loss of feedwater heaters (80 cycles total)

Turbine trip at 25 percent power Feedwater heater bypass Scram (200 cycles total)

Loss of feedwater pumps, isolation valves close Turbine trip, feedwater on, isolation valves stay open Reactor overpressure with delayed scram, feedwater stays on, isolation valves stay open Single safety relief valve blowdown All other scrams Improper start of cold recirculation loop Sudden start of pump in cold recirculation loop Shutdown (100°F/hr cooldown rate)

Hydrostatic test at 1563 psig Unbolt No. of Cy~cles 123 130 120 10,000 2,000 400 10 70 10 40 1

2 147 5

5 118 3

123 Stress analysis and load combinations for the reactor vessel are evaluated for the cycles listed above, with the conclusion that ASME code limits are satisfied. The details of assumed loading combinations are described in Appendix C for Class 1 equipment. It is possible that the specified number of cycles for some of the events listed above may be exceeded over the life of the plant. A plant procedure has been implemented at Browns Ferry to maintain surveillance on the number of cycles which have occurred and the resulting fatigue usage factors. When the fatigue usage factor reaches a value of 0.7, the procedure requires a reevaluation to be completed in a timely manner to assure that the allowable fatigue usage factor of 1.0 is not exceeded. Operating limits on pressure and temperature during inservice hydrostatic testing were established using as a guide Appendix G to the ASME Boiler and Pressure Vessel Code,Section III, 1971, which was first added to the code in the summer 1972 addenda. The intent of Appendix G is to set criteria based on fracture toughness to provide a margin of safety against a nonductile failure.

The resulting operating limits ensure that a large postulated surface flaw, having a depth of one-quarter of the material thickness and a length of one and one-half of the material thickness, can be safely accommodated in regions of the reactor vessel shell remote from discontinuities. Operating limits on temperature and pressure when the core is critical were established by using 10 CFR 50, Appendix G, "Fracture Toughness Requirements," paragraph IV.A.2.C An exemption from

/ T.

1 o'

    • 6,., o**. AS+A9 Scja,*-.

.r 8Z ý dk" o

tV 6 v C,,

I,,4jr 2000 Ad*3d~OM64"' 46O diek.,re 4-410 UfV I P-Tftm"@.

711.

P-TrC..

e,4.4#",* 0

  • V ; 01cr 4*

-Pvto *w1A

t) 4#-- 4s v4 Kjhý -PR F;%.e Aijcwo-I.* AF"d A 6o e4C s i G

t 2) ec4#,* ~C Iý4, M C0 A 10c40,-P i At;ý QoII, pw i

!d!V.*

4

BFN-25.2 specific requirements of 10 CFR Part 50, Appendix G is taken by use of ASME Code Case N-640 for Unit 2 and Unit 3. ASME Code Case N-640 permits the use of an alternative reference fracture curve K1c for RPV materials for use in determining the PT limits. The PT limit curves based on the K1c fracture toughness curve enhance overall plant safety by minimizing challenges to operators since requirements for maintaining a high vessel temperature during pressure testing are lessened. ASME Code Case N-588 methodology was also used as a basis for the PT curves. This code case permits the use of an alternative procedure for calculating applied stress intensity factors during normal operation and pressure test conditions due to pressure and thermal gradients for axial flaws. This methodology is incorporated into the ASME,Section XI Code, 1995 Edition, 1996 Addenda, which is the current code of record for the Unit 2 inservice inspection program. Since Unit 3 uses an earlier code of record for the inservice inspection program, Unit 3 implements the requirements of only the 1995 Edition, 1996 Addenda of ASME Section XI, Appendix G to allow the use of the ASME Code Case N-588 methodology for PT curves. The operating limits are provided in the technical specifications for Browns Ferry. For the purpose of setting these operating limits, the initial RTNOT (nil-ductility reference temperature) was determined from the impact test data taken in accordance with the requirements of the code to which the reactor vessels were designed and manufactured. The maximum NDT temperature allowed by the vessel specifications was 400F. Although test data on beltline base material show lower NDT temperatures, an assumed RTNOT of 40OF was used in the vessel beltline area, as well as the areas remote from the beltline because the generally accepted NDT temperature for electroslag welds used in the beltline longitudinal seams is 400F.

he current operating limits on the pressure/temperature (P/T) curves in the Mil tl specifications are based on the following (RTNOT) values. Unit 1 has used 23.1,2oF f r the (RTNoT) value, Unit 2 has used 22°F for the (RTNoT) value, and Unit 3 a.sed 10'F for the (RTNDT) value.

For power uprated conditions, the estimated fluence was conservatively increased above the UFSAR end-of-life value. This fluence increase was estimated to be greater than proportional to the power increase, considering the changes in power distribution. The higher fluence was used to evaluate the vessel against the requirements of 10 CFR 50, Appendix G in accordance with Regulatory Guide 1.99, Revision 2. The results of these evaluations indicated that:

(a) The upper shelf energy will remain greater than 50 ft-lb for the design life of the vessel and maintain the margin requirements of Appendix G.

(b) The effective full power year (EFPY) shift is slightly increased and, consequently requires a change in the adjusted reference temperature (ART), which is the initial RTNDT plus the shift. The beltine material ART will remain within the 200 degree screening criterion.

4.2-12

BFN-25.2 The surveillance test plate 610-0127 was 139 in. long and 60 in. wide, and all excess material is under TVA control in the event that additional material is needed.

It is estimated that enough extra material is available for several hundred additional Charpy specimens.

No weak direction specimens were included in the reactor vessel material surveillance program. All Charpy V-notch specimens were taken parallel to the direction of rolling. The majority of developmental work on radiation effects has been with longitudinal specimens. This is considered the best specimen to be used for determination of changes in transition temperature. At the low neutron fluence levels of BWR plants, no change in transverse shelf level is expected and transition temperature changes are minimal.

The specimens and neutron monitor wires were placed near core midheight adjacent to the reactor vessel wall where the neutron exposure is similar to that of the vessel wall (see Subsection 3.3). The specimens were installed at startup or just prior to full-power operation. r-m iUii 1, 2, end 3.I\\

Iengrimtd 6vonslanne Plrngram (16P) impl"lnontalien atnd curtolbnco 6peme-sche&!n th Iihdra-al

-Ad t19SU'g for the Siuriel BWR 10 y em opoting perioda if gorlmepd and mAtav olem d by GWRVIPn6 A

IUpdated OMR Integrated Suoeildce Progra B

V1S2)Implme35ntIe ation Man),cend Pa~t hoNRC'csgafety Evaka2t-tion-ted Febrm-iant 12009 SamrvaiIIlnaom~'i~

mn+ C) schwiule withvura~*a anfetin dur.

ing thIe licenue renet*ii-pero is' goImad and cmtralled by MURVIP 116 (In~legratod-6-MA-MillMncO ProgriM (I612) lmplementetien (lfr. Liconco RnOwASl), and the MIARVIP response to NRC RA's dated Ian-levy 11, S1709 Surveillance and chemistry data for all representative materials in the BWRVIP ISP have been consolidated into BWRVIP-1 35 (integrated Surveillance

(-Program (ISP) Data Source Book and Plant Evaluations.) The withdrrvel.l.od'o (eFo the s...

nd Uni.2 21 sul.......*

.-.at.muth 200 (to be

.thd..

in 2011) end-Rq~l~ce te third Unil 2 copeule (t-e Ithdrnduring the Wicnse Fenowal period) v111 be in Wrt-ý mf e with the !SP. 0-se~nt here are ie plans to withdraw any espaules Ifrem Units I or 3, as the BFN U6it.-2-eeWesl proidohe bo66t Feproontatiyc we'd fn.

WW,.h t%*JYuV^ -,A O, m k%

r%

6

-J~

!-a-0

  • WSVV i

S I4t J~A

  • %SS

!aJ

%. Supplemental Surveillance Program (SSP) Capsules A, B, D, G, E, and I provide the best representative weld material for Unit 1. Test results will provide the necessary data to monitor embrittlement for Units 1, 2, and 3. Since the predicted adjusted reference temperature of the reactor vessel beltline steel is less than 1 00°F at end-of-life, the use of the capsules per the ISP meets the requirements of 10 CFR 50, Appendix H, and ASTM E185-82. Revisions to fluence calculations using data obtained from the surveillance capsule specimens will use an NRC approved methodology that meets Regulatory Guide 1.190. {By letter dated August 14, 2008 (EDMS Number L44 080828 014), NRC issued License Amendment 273 for BFN Unit 1, and by letter dated January 28, 2003 (EDMS Number L44 030204 001), NRC issued License Amendment Numbers 279 and 238, for BFN Units 2 and 3 4.2-16

For Units 1, 2, and 3, Integrated Surveillance Program (ISP) implementation and surveillance specimen schedule withdrawal and testing is governed and controlled by BWRVIP-86 Revision 1-A, the BWRVIP responses to NRC RAIs Q dated May 30, 2001, December 22, 2001, and January 11, 2005, and the NRC's Safety Evaluation dated February 1, 2002 (NOTE: BWRVIP-86, Revision 1-A was approved by the NRC and issued in October 2012, superseding both BWRVIP-86-A and BWRVIP-1 16).

A test specimen surveillance capsule (the second set of Unit 2 test specimens located at Azimuth 1200) was withdrawn in accordance with the ISP in 2011 during Unit 2 Refueling Outage 16 (U2R16) at approximately 23 EFPY of operation. An additional test specimen surveillance capsule is scheduled for withdrawal during the license renewal period, this being the third set of Unit 2 test specimens located at Azimuth 3000, which are currently scheduled for removal in the refueling outage closest to without exceeding 40 EFPY of operation. At the present time, this would correspond to Unit 2 Refueling Outage 24 (U2R24) in 2027. Presently, there are no plans to withdrawal any capsules from either Unit 1 or Unit 3, as per BWRVIP-135 the BFN Unit 2 capsules provide the best representative plate material for all three units and the best representative weld material for Units 2 and 3.