Text
ENT000048 Submitted: March 28, 2012 United States Nuclear Regulatory Commission Official Hearing Exhibit In the Matter of:
Entergy Nuclear Operations, Inc.
(Indian Point Nuclear Generating Units 2 and 3)
ASLBP #: 07-858-03-LR-BD01 Docket #: 05000247 l 05000286 Exhibit #:
Identified:
Admitted:
Withdrawn:
Rejected:
Stricken:
Other:
ENT000048-00-BD01 10/15/2012 10/15/2012 (S I TECHNOLOGIES, INC.
Consulting Engineers REPORT APPROVAL COVER SHEET Document
Title:
Indian Point Energy Center Unit 2 FAC System Susceptibility Evaluation (SSE)
Document No.:
0700.104-02 Client:
Entergy Nuclear Project No.:
0705.111 This report has been prepared in accordance with Section 4.4 of the CSI Quality System Manual, Revision 2.
~
...........:;....-~_-==--______ Date: '0;' J /11 r
I Verified:
Date: IO;1~;1,
-~~------~~~-----------------
Approved: ~'""=-~.::.....-=--=-__________ Date: Ie IN/I(
Approved: __________________________________ Date: _____ _
Ian D. Mew (lPEC)
( S I TECHNOLOGIES, INC.
Project Number:
Project Name:
Client:
Document
Title:
Document Number:
Rev.
Date 0
1211112009 I
112212010 2
10114/2011 Revision Control Sheet 0705.111 IPEC FAC Support 2011 Entergy Nuclear Indian Point Energy Center Unit 2 FAC System Susceptibility Evaluation (SSE) 0700.104-02 Description of Changes Initial Issue-For Use Revision to incorporate new system list - For Use Revision to incorporate replacement history - For Use ConsultilZg Engineers CSI Client Approval Approval B. Trudeau I. Mew B. Trudeau I. Mew f(..Do~""tJ
Indian Point Energy Center Unit 2 FAC System Susceptibility Evaluation (SSE)
Report No. 0700.104-02 Revision 2 Issued For-Use October 14, 2011 prepared for:
Entergy Nuclear Indian Point Energy Center 450 Broadway Buchanan, NY 10511 prepared by:
CSI TECHNOLOGIES, INC.
1 Douglas Ave., Suite 300 Elgin, IL 60120
Copyright © 2011 CSI Technologies, Inc. All rights reserved.
The information in this document belongs to CSI Technologies, Inc. It may not be used, reproduced, or disclosed without the written approval of CSI Technologies, Inc.
Disclaimer and Limitation of Liability CSI Technologies, Inc. (CSI) has made efforts to ensure the accuracy and completeness of the information in this document. However, CSI makes no warranties of any kind (whether express, implied, or statutory) with respect to the information contained herein. CSI assumes no liability to any party for any loss or damage (whether direct or indirect) caused by any errors, omissions, or statements of any kind contained in this document.
Further, CSI assumes no liability arising from the application or use of the product, service, or results described herein and specifically disclaims any representation that the products, services, or results described herein do not infringe upon any existing or future intellectual property rights. Nothing herein grants the reader any license to make, use, or sell equipment or products constructed in accordance with this document. Finally, all rights and privileges related to any intellectual property right described herein are vested in the patent, trademark, or service mark owner, and no other person may exercise such rights without express permission, authority, or license secured from the patent, trademark, or service mark owner.
Trademarks CSI Technologies, Inc., the CSI logo, and other trademarks, service marks, and logos are registered or unregistered trademarks of CSI and its subsidiaries in the United States and in foreign countries. Other trademarks and service marks in this document are the property of their respective owners.
CSI TECHNOLOGIES, INC.
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
Report No. 0700.104-02, Revision 2 Page 1 of 19 Table of Contents 1.
INTRODUCTION............................................................................................................................................... 2
2.
PURPOSE............................................................................................................................................................ 3
3.
SCOPE.................................................................................................................................................................. 4
4.
ASSUMPTIONS.................................................................................................................................................. 5
4.1.GENERAL ASSUMPTIONS................................................................................................................................ 5
4.2.SYSTEM, SUBSYSTEM, AND LINE SPECIFIC ASSUMPTIONS.............................................................................. 5
5.
METHODOLOGY.............................................................................................................................................. 7
5.1.SUSCEPTIBILITY EXCLUSION CRITERIA.......................................................................................................... 8
5.2. SUSCEPTIBLE NON-MODELED (SNM) CRITERIA.......................................................................................... 11
6.
RESULTS........................................................................................................................................................... 13
6.1.SYSTEM SUSCEPTIBILITY EVALUATION........................................................................................................ 13
6.2.SUBSYSTEM SUSCEPTIBILITY EVALUATION.................................................................................................. 13
6.3.LINE SUSCEPTIBILITY EVALUATION............................................................................................................. 14
6.4.COLOR-CODED FLOW DIAGRAMS................................................................................................................. 16
6.5.REVISION HISTORY....................................................................................................................................... 16
6.6.INDUSTRY FAC EXPERIENCE TABLE............................................................................................................ 16
6.7.FAC-SUSCEPTIBLE LINES CONTAINING ORIFICES........................................................................................ 16
7.
REFERENCES.................................................................................................................................................. 18
APPENDIX A:
SYSTEM SUSCEPTIBILITY EVALUATION REPORT APPENDIX B:
SUBSYSTEM SUSCEPTIBILITY EVALUATION REPORT APPENDIX C:
LINE SUSCEPTIBILITY EVALUATION REPORT APPENDIX D:
REVISION HISTORY ATTACHMENT A: INDUSTRY FAC EXPERIENCE TABLE ATTACHMENT B: REFERENCED CORRESPONDENCE AND COMMUNICATIONS
CSI TECHNOLOGIES, INC.
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
Report No. 0700.104-02, Revision 2 Page 2 of 19
- 1.
Introduction Flow-Accelerated Corrosion (FAC) is a form of material degradation that results in thinning of the inside pipe wall in carbon steel piping and fittings under certain flow and chemistry conditions. If undetected, FAC may result in piping rupture and subsequent fatalities, injuries, equipment damage, unplanned plant shutdown, and transients that pose undesirable challenges to plant operators. Consequently, all US nuclear plants, including Indian Point, have FAC programs in place to detect and mitigate FAC before piping failure in accordance with Generic Letter 89-08 [7.1].
An effective FAC program includes three key elements: the System Susceptibility Evaluation (SSE), which defines and controls the program scope; the CHECWORKS computer model, which predicts wear rates for every modeled component; and the Susceptible Non-Modeled (SNM) Program, which prioritizes non-modeled but susceptible lines according to FAC potential.
CSI TECHNOLOGIES, INC.
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
Report No. 0700.104-02, Revision 2 Page 3 of 19
- 2.
Purpose This document contains the development and results of an FAC System Susceptibility Evaluation (SSE) for Indian Point Energy Center Unit 2. Each plant system, subsystem, and line is classified as either susceptible or non-susceptible to FAC. Susceptible piping forms the scope of the Indian Point FAC program, while non-susceptible piping is excluded from the FAC program. Susceptible piping is further categorized as either modelable in the EPRI computer program CHECWORKS Steam/Feedwater Application (SFA) or non-modelable. Susceptible Non-Modeled (SNM) piping falls outside the capabilities of CHECWORKS SFA.
The purpose of this document is to:
- Define the scope of the Flow-Accelerated Corrosion (FAC) program.
- Identify all plant lines to be modeled in the EPRI computer program CHECWORKS Steam/Feedwater Application (SFA).
- Identify all plant lines that form the scope of the Susceptible Non-Modeled (SNM) program.
CSI TECHNOLOGIES, INC.
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
Report No. 0700.104-02, Revision 2 Page 4 of 19
- 3.
Scope The scope of this System Susceptibility Evaluation is all plant piping. This includes piping in all systems, subsystems, and lines. This document reflects the current operating status of the plant. Periodic review and update of this document is recommended by EPRIS Recommendations for an Effective Flow-Accelerated Corrosion Program, NSAC 202L [7.2].
Section 4 of this document contains a record of all assumptions made. Section 5 describes the methodology employed in this analysis. The results obtained are documented in Section 6 and in the Appendices. Finally, Section 7 includes a list of all references used in this analysis.
CSI TECHNOLOGIES, INC.
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
Report No. 0700.104-02, Revision 2 Page 5 of 19
- 4.
Assumptions 4.1.
General Assumptions The following assumptions apply to all plant systems, subsystems, or lines.
4.1.1.
Piping with nominal pipe size less than or equal to 2 is assumed to be socket welded. Likewise, lines over 2 in diameter are assumed butt-welded.
4.1.2.
If piping material is unknown, carbon steel material is assumed.
4.1.3.
If a portion of a system, subsystem, or line is susceptible, then the entire system, subsystem, or line is considered susceptible. An exception is made for lines where valves are the only susceptible components. Since valves are inspected by the Preventative Maintenance or Corrective Action programs, they are considered outside the FAC program.
4.1.4.
Lines on the Indian Point P&IDs [7.3] containing normally closed valves are assumed to operate less than 2% of the time. Likewise, lines containing valves that are normally open are assumed to operate greater than 2% of the time. This assumption is used when specific valve information is not found in the System Descriptions [7.4], Plant Operating Manuals [7.5], or responses to questions by Indian Point personnel [7.6].
4.1.5.
It is assumed that no normally closed valves leak, unless confirmed otherwise by plant operating history.
4.1.6.
Lines that exist in non-susceptible systems or subsystems are excluded from further analysis on the system or subsystem level, respectively.
These lines may or may not appear in the Appendices.
4.2.
System, Subsystem, and Line Specific Assumptions Assumptions and susceptibility decisions made specifically for a single system, subsystem, or line appear in the Comments field of the Susceptibility Evaluation reports in the Appendices.
4.2.1.
Instrumentation, level control lines, and indicator lines are assumed to have insufficient flow to be susceptible to FAC.
4.2.2.
Floor drains, miscellaneous capped drain and vent lines, and miscellaneous vent lines to the atmosphere are assumed to have insufficient flow to be susceptible to FAC (or operate infrequently).
4.2.3.
Multiple line names are used for the same line in cases where susceptibility changed along the line and in cases where relationships to CHECWORKS are simplified by separating sections of lines.
CSI TECHNOLOGIES, INC.
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
Report No. 0700.104-02, Revision 2 Page 6 of 19 4.2.4.
The supply and return headers for multiple unit heaters, lines 2-UH-003 and 2-UH-071, are continued on a drawing that could not be located by Indian Point personnel. The continuations of these lines, as well as any lines fed by these headers should be considered FAC-susceptible until proven otherwise.
4.2.5.
It is assumed that Boiler Feed Pump seal water lines from the Condensate system do not increase to above 200ºF when passing through the Boiler Feed Pumps.
4.2.6.
Judging by the flow configuration on drawing A209775 [7.3], the header containing steam from several unit heaters (24UHR, 211UHR, 219UHR, 221UHR), steam traps (UHT-2-2, UHT-4-1), and the oil preheater does not appear to have an outlet. If an outlet exists that is not shown on the drawing, it should be assumed susceptible to FAC until proven otherwise through further evaluation.
4.2.7.
Judging by the flow configuration on drawing B193201 [7.3], lines 2-UH-002 and 2-UH-079 appear to have no inlet. If an inlet exists that is not shown on the drawing, it should be assumed susceptible to FAC until proven otherwise by further evaluation.
CSI TECHNOLOGIES, INC.
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
Report No. 0700.104-02, Revision 2 Page 7 of 19
- 5.
Methodology The methodology employed in this analysis consisted of a number of successive steps.
Each step is explained in detail in the following sections. A flowchart of the methodology used is included in the Figure 5.1 Each plant system, subsystem, and line was reviewed against FAC susceptibility criteria and CHECWORKS modelability criteria (as defined in Section 5.1 and Section 5.2) to determine its susceptibility category. If an entire system or subsystem was determined to be non-susceptible, a line-by-line review was not conducted; however, where that was not the case, each line was evaluated and categorized accordingly and individually.
Excluded No further evaluation Yes Can be Modeled in CHECWORKS SNM Program CHECWORKS Modeled No Yes Figure 5.1 Susceptibility Evaluation Methodology All Plant Systems Meets System Susceptibility Exclusion Criteria Excluded No further evaluation Yes No Determine Subsystem Susceptibility No Meets Subsystem Susceptibility Exclusion Criteria Meets Line Susceptibility Exclusion Criteria Excluded No further evaluation Yes Determine Line Susceptibility No
CSI TECHNOLOGIES, INC.
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
Report No. 0700.104-02, Revision 2 Page 8 of 19 5.1.
Susceptibility Exclusion Criteria The criteria used to determine susceptibility to FAC was taken from Section 4.2 of EPRI NSAC 202L [7.2]. Systems, subsystems, and/or lines are not considered susceptible to FAC if one or more of the conditions discussed below apply.
5.1.1. FAC Resistant Material Stainless steel or low-alloy steel with chromium content equal or greater than 1.25% are FAC-resistant [7.2 and 7.7]. Lines or systems made, or replaced with, such materials are not sufficiently susceptible to FAC to warrant further analysis. It should be noted, however, that resistance to FAC does not ensure against other corrosion mechanisms such as cavitation or impingement. Therefore, even if components are replaced with FAC-resistant material, the root cause of wear should be determined before excluding the replaced components from the inspection program.
Wholesale replacement of a line with FAC resistant material would cause that line to be excluded from the FAC program. However, if one component on a line is susceptible, then the whole line was considered susceptible.
Piping material was obtained from the Piping Specifications [7.8], P&IDs
[7.3], or the Indian Point isometric drawings [7.9].
5.1.2. Superheated Steam Piping transporting superheated steam with no moisture content was classified as non-susceptible. According to EPRIs Recommendations for an Effective Flow-Accelerated Corrosion Program, FAC is known to occur only under flowing water or wet steam conditions, and has not been documented in superheated steam piping [7.2].
Steam quality was obtained from the PEPSE Model [7.10] first, followed by the operating conditions found in the Piping Specification [7.8].
5.1.3. Single-Phase Piping at Low Temperature Piping with single-phase flow and an operating temperature below 200oF does not experience FAC and was classified as non-susceptible. No temperature exclusion exists for two-phase lines [7.2]. Other degradation mechanisms, such as cavitation, may occur at low temperatures but such mechanisms are outside the scope of this analysis.
Operating temperature was obtained from the PEPSE Model [7.10] first, followed by the operating conditions found in the Piping Specification
[7.8].
5.1.4. Low Operating Frequency Piping that operates less than 2% of the plant operating time was deemed non-susceptible. In general, such piping does not experience the amount of flow required to make FAC a legitimate concern and is excluded from further analysis in favor of piping with greater FAC susceptibility. Piping
CSI TECHNOLOGIES, INC.
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
Report No. 0700.104-02, Revision 2 Page 9 of 19 in this category includes lines with normally closed valves and those feeding or emerging from equipment that operate less than 2% of the plant operating time.
Exceptions to this rule are made when the operating frequency may be low, but the service is especially severe [7.2].
All lines excluded due to infrequent operation would be susceptible to FAC if operating frequency is increased above the 2% threshold.
Therefore, if operating frequency is increased, these lines should be reviewed for inclusion in the FAC Program.
Operating frequency was determined by information from Plant Operating Manuals [7.5], by information found in the System Descriptions [7.4],
responses to questions by Indian Point personnel [7.6], and by valve position on the P&IDs [7.3]. See Assumption 4.1.3 for more details.
5.1.5. Combination Single-Phase Piping with Low Temperature and Operating Frequency This category is a derivative of the two previous susceptibility criteria described in Sections 5.1.3 and 5.1.4. It may be used for a system, subsystem, or a line that operates >2% of total plant operating time but only occasionally (<2% of the time) will the temperature of the single-phase fluid, within the piping, exceed 200oF. Thus, piping containing a single-phase flow that operates less than 2% of the time above 200oF was classified as non-susceptible to FAC.
5.1.6. Non-Water/Steam Piping Piping that transports fluids other than water or steam, such as air or oil, are not susceptible to FAC.
5.1.7. Dissolved Oxygen Concentration Lines containing water with high levels of dissolved oxygen (typically greater than 1000 ppb) are considered immune to FAC and can be excluded from further analysis [7.2]. Systems normally meeting this criterion include Service Water, Circulating Water, and Fire Protection.
5.1.8. Low or No Flow While instrumentation and/or sensing lines may operate continuously, they experience very limited fluid flow. Such piping does not experience the amount of flow required to make FAC a legitimate concern and is excluded from further analysis in favor of piping with greater FAC susceptibility.
5.1.9. Non-Piping Systems that do not contain piping (e.g. computer system) were excluded from the FAC program.
CSI TECHNOLOGIES, INC.
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
Report No. 0700.104-02, Revision 2 Page 10 of 19 5.1.10. Piping Removed from Service Piping that has been removed from service and capped was excluded from the FAC program. Degradation mechanisms may occur in such piping, but for Flow-Accelerated Corrosion to occur, flow is required [7.2].
Table 5.1 provides a summary of the FAC susceptibility exclusion parameters discussed in this section. Also provided is the abbreviation used for each criterion.
Table 5.1 Susceptibility Exclusion Criteria Abbreviation Reason Description EM Material Excluded due to FAC-resistant Material EQ Superheated Excluded due to high steam Quality (superheated steam)
ET Single Phase, T<200°F Excluded due to Temperature EI Time <2%
Excluded due to Infrequent operation (note:
would be FAC susceptible if operated at a higher frequency)
EC Single Phase, T>200°F for time<2%
Excluded due to a Combination of infrequent operation above temperature threshold EW Non-water/steam Excluded due to no Water or steam present EO High D.O.
Excluded due to dissolved O2 content >1000 ppb EF Low or No Flow Excluded due to Low or No Flow EP Non-Piping Excluded due to no Piping components present ER Pipe Removed Excluded due to Removal of piping from service
CSI TECHNOLOGIES, INC.
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
Report No. 0700.104-02, Revision 2 Page 11 of 19 5.2.
Susceptible Non-Modeled (SNM) Criteria Each line that was not excluded due to criteria listed in Table 5.1 was determined to be susceptible to FAC. An explicit determination of suitability for CHECWORKS modeling was made for these lines. For each line that is susceptible but unsuitable for modeling, the basis for that determination was recorded. Lines were determined to be non-modelable in CHECWORKS if one or more of the conditions discussed below apply.
5.2.1. Weld Type Lines with socket-welded fittings were classified as non-modelable.
Almost all small bore lines (less than or equal to 2 in diameter) are constructed using socket-welded fittings. The socket weld uses a fit-up gap of variable size. This gap can greatly impact turbulence in piping, which in turn has a significant impact on wear rate. Since the size of the fit-up gap is unknown, CHECWORKS cannot accurately predict wear for socket-welded components [7.11].
For this analysis, all small bore lines were considered socket-welded and therefore non-modelable (see 4.1.1). In addition, the extremely large linear footage of small-bore lines and the often unknown thermodynamic conditions combine to make detailed modeling of small-bore piping inefficient and sometimes inaccurate.
5.2.2. Unknown Operating Conditions In cases where operating conditions cannot be accurately obtained or calculated, accurate modeling cannot be performed. In addition to chemistry, CHECWORKS requires a value for flow, frequency of operation, and two thermodynamic values (pressure, temperature, quality, or enthalpy) to predict wear. The PEPSE Model was the primary source of flow and thermodynamic conditions [7.10]. Thermodynamic conditions were also obtained from the operating conditions found in the Piping Specification [7.8]. Operating frequency was determined by valve position in the Plant Operating Manuals [7.5], on the P&IDs [7.3], from information found in System Descriptions [7.4], and through responses to questions by Indian Point personnel [7.6].
Where operating conditions were unknown or varied, the lines were classified as SNM.
5.2.3. Conditions outside CHECWORKS Modeling Capabilities Lines that operate with conditions outside of CHECWORKS modeling capabilities were considered SNM. For example, lines with entrained moisture or vent lines containing non-condensable gases were classified as non-modelable.
CSI TECHNOLOGIES, INC.
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
Report No. 0700.104-02, Revision 2 Page 12 of 19 5.2.4. Visually Inspected Lines Lines that are visually inspected during outages do not require modeling.
For many plants, this criterion applies to the Turbine crossunder piping.
5.2.5. Localized FAC Susceptibility Lines that were classified as FAC susceptible only at a single location were deemed non-modelable. Examples include carbon steel nozzles and valves in a low alloy line.
5.2.6. High Steam Quality Lines that contain very high quality (but not superheated) steam were classified as SNM. Modeling such lines is of little value as CHECWORKS predictions would be trivial.
Steam quality was primarily obtained from the PEPSE model [7.10],
followed by the operating conditions found in the Pipe Class Specifications [7.8].
Table 5.2 provides a summary of the CHECWORKS model exclusion parameters discussed in this section. Also provided is the abbreviation used for each criterion.
Table 5.2 CHECWORKS Model Exclusion Criteria Abbreviation Reason Description NS Socket-welded Non-modeled due to Socket-welds NC Unknown conditions Non-modeled due to unknown or varying operating Conditions NM Conditions outside CHECWORKS modeling capabilities Non-modeled due to conditions outside CHECWORKS Modeling capabilities NV Visual inspections Non-modeled due to Visual inspections NL Localized FAC Non-modeled due to Localized FAC susceptibility NQ High Steam Quality Non-modeled due to high steam Quality resulting in CHECWORKS predictions of little value
CSI TECHNOLOGIES, INC.
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
Report No. 0700.104-02, Revision 2 Page 13 of 19
- 6.
Results The following sections contain a description of the data found in the appendices.
6.1.
System Susceptibility Evaluation The results of the System Susceptibility Evaluation appear in Appendix A. The report in this appendix lists all plant systems and classifies each as susceptible or non-susceptible to FAC. For those deemed non-susceptible, the reason for exclusion from the FAC program is provided. The following fields appear in this report.
6.1.1. System Code This field contains the common two-letter designation for the system.
6.1.2. System Name This field contains a brief description or name of the system.
6.1.3. Susceptible?
This field states if the system is FAC susceptible.
6.1.4. Exclusion Criteria (Excl. Crit.)
This field contains the reason the system is non-susceptible to FAC (see Table 5.1), if applicable.
6.1.5. Comments Pertinent information about the system appears in this field.
6.1.6. Reference References used in determining susceptibility appear in this field.
6.2.
Subsystem Susceptibility Evaluation Susceptible systems were divided into subsystems by grouping lines of similar function. The results of the Subsystem Susceptibility Evaluation appear in Appendix B. Only subsystems from susceptible systems were analyzed. The reports in these appendices classify each subsystem as susceptible or non-susceptible to FAC. For those deemed non-susceptible, the reason for exclusion from the FAC program is provided. The following fields appear in this report.
6.2.1. Subsystem Number This field contains the number of the subsystem, where a subsystem is a subset of the system piping with similar operating parameters. Subsystem names were created for this evaluation and include the unit number, common system designation and a sequential number in the following format.
CSI TECHNOLOGIES, INC.
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
Report No. 0700.104-02, Revision 2 Page 14 of 19 A-BBBB-CC A
Unit Number BBBB System Abbreviation CC Sequential Number Example: 2-BFD-01, 2-3EX-02 6.2.2. Subsystem Name This field contains the name of the subsystem preceded by the system (represented by the system code) that it falls into.
6.2.3. Subsystem Boundary A description of the lines that are grouped in this subsystem is shown here.
6.2.4. Flow Diagram (P&ID)
This field lists the flow diagram(s) on which the subsystem is found.
6.2.5. FAC Susceptible? (FAC. Sus.?)
This field states if the subsystem is FAC susceptible.
6.2.6. Exclusion Criteria (Excl. Crit.)
This field contains the reason the subsystem is non-susceptible to FAC (see Table 5.1), if applicable.
6.2.7. Comments Pertinent information about the subsystem appears in this field.
6.2.8. Reference References used in determining susceptibility appear in this field.
6.3.
Line Susceptibility Evaluation Lines in FAC susceptible systems were placed into one of three categories:
- Excluded lines (non-susceptible)
- Susceptible lines to be modeled in CHECWORKS
- Susceptible non-modeled (SNM) lines Appendix C contains the results of the line susceptibility evaluation for Indian Point Energy Center Unit 2. Appendix C is organized into sections with Section A listing CHECWORKS modeled lines, Section B listing SNM program lines, and Section C listing excluded lines. For SNM lines, the reason for exclusion from the CHECWORKS model is provided. For excluded lines, the reason for exclusion from the FAC program is provided. Not every line in a non-susceptible subsystem was explicitly analyzed and therefore only selected lines will appear in the report (see Section 4.1.6).
The following fields appear in this report.
CSI TECHNOLOGIES, INC.
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
Report No. 0700.104-02, Revision 2 Page 15 of 19 6.3.1. Line Number Indian Point does not maintain a complete piping line list. Therefore, line names needed to be created. The majority of main piping lines, depending on susceptibility, were assigned a unique Line Number. The naming convention follows a format which includes unit number, system abbreviation, a sequential number, and, if necessary, a section designator used either for parts of the same line with different susceptibility characteristics or specifications or for preventing duplicate line names:
A-BBBB-CCC-D A
Unit Number BBBB System Abbreviation CCC Sequential Number D
Section Designator Examples: 2-1EST-014, 2-MS-011-A 6.3.2. Size The diameter, in inches, of the majority of the line is listed here.
6.3.3. Flow Diagram This field lists the flow diagram(s) on which that the line is found.
6.3.4. Susceptibility Category (Sus. Cat.)
The susceptibility category is listed in this field. Table 6.1 defines the three susceptibility categories.
Table 6.1 Susceptibility Categories Abbreviation Category M
CHECWORKS Modeled S
Susceptible non-modeled (SNM)
E Excluded from the FAC program (non-susceptible) 6.3.5. Model Exclusion Criteria (Mod. Ex. Crit.)
This field appears only for SNM lines. It contains the reason each line is not modeled in CHECWORKS (see Table 5.2) when applicable.
6.3.6. Susceptibility Exclusion Criteria (FAC Ex. Crit.)
This field appears only for excluded lines. It contains the reason each line is non-susceptible to FAC (see Table 5.1) when applicable.
6.3.7. Comments Pertinent information about the line appears in this field.
CSI TECHNOLOGIES, INC.
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
Report No. 0700.104-02, Revision 2 Page 16 of 19 6.3.8. Reference References used in determining susceptibility or modelability appear in this field.
6.3.9. Line Description This field contains a description of the line.
6.4.
Color-Coded Flow Diagrams Flow diagrams of all FAC susceptible systems addressed in this document are included in the Color-Coded Flow Diagrams document. The flow diagrams are color-coded based upon FAC susceptibility category and labeled to indicate line numbers. Line numbers were added to the flow diagrams. See the Color-Coded Flow Diagrams Document 0700.104-04 for the color-code convention.
6.5.
Revision History Changes made for each revision of this report are documented in Appendix D.
6.6.
Industry FAC Experience Table Attachment A contains a table of important industry FAC events. This table was used as an aide in determining FAC susceptibility.
6.7.
FAC-Susceptible Lines Containing Orifices As a subtask of the project, a list of FAC-susceptible lines containing orifices was gathered and is shown in Table 6.2 below.
CSI TECHNOLOGIES, INC.
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
Report No. 0700.104-02, Revision 2 Page 17 of 19 Table 6.2 FAC Susceptible Lines Containing Orifices Line Number Line Description P&ID Coord.
2-3HD-027 FWH 23A Vent to 3EX-53 A235304 H4 2-3HD-028 FWH 23A Vent to 3EX-534 A235304 H4 2-3HD-029 FWH 23B Vent to 3EX-536 A235304 H5 2-3HD-030 FWH 23B Vent to 3EX-539 A235304 H5 2-3HD-031 FWH 23C Vent to 3EX-541 A235304 H6 2-3HD-032 FWH 23C Vent to 3EX-544 A235304 H6 2-5HD-047 FWH 25A Vent 9321-F-2022 I4 2-5HD-048 FWH 25B Vent 9321-F-2022 I5 2-5HD-049 FWH 25C Vent 9321-F-2022 I6 2-AF-011-A
- 21 BFP discharge overflow line upstream of orifice 9321-F-2120 H3 2-AF-012-A
- 22 BFP discharge overflow line upstream of orifice 9321-F-2120 G3 2-AF-013-A
- 23 BFP discharge overflow line upstream of orifice 9321-F-2120 G3 2-AF-043 Service Boiler Deaerator Drain to Service Boiler Feed Pumps B193201 C2 2-AF-053 AF57 Vent to Service Boiler Deaerator B193201 D2 2-AS-003 Aux. Steam from #22 LH Boiler 9321-F-2120 E5 2-AS-004 Aux. Steam from #21 RH Boiler 9321-F-2120 B5 2-AS-009 Steam to AST-26 9321-F-2120 A5 2-AS-031 Steam Header to Barge Steam Connections B192490 C4 2-AS-066 Steam to and from FP-1198 192491 G5 2-CD-025 Condensate from Header to BFP No. 21 A235307 B5 2-CD-026 Condensate from Header to BFP No. 22 A235307 E5 2-HD-001
- 21 HDP to Heater Drain Pump Header 9321-F-2022 D1 2-HD-002
- 22 HDP to Heater Drain Pump Header 9321-F-2022 D1 2-MS-143 Main Steam Stop Valve drain to 23 Cond. West Side A235308 D1 2-MS-144 Main Steam Stop Valve drain to 23 Cond. East Side A235308 D2 2-MSD-157 Reheater Drain Tank 21A Drain to Header 9321-F-2023 G2 2-MSD-158 Reheater Drain Tank 22A Drain to Header 9321-F-2023 E2 2-MSD-159 Reheater Drain Tank 23A Drain to Header 9321-F-2023 D2 2-MSD-166 Reheater Drain Tank 21B Drain to Header 9321-F-2023 H5 2-MSD-167 Reheater Drain Tank 22B Drain to Header 9321-F-2023 F5 2-MSD-168 Reheater Drain Tank 23B Drain to Header 9321-F-2023 D5
CSI TECHNOLOGIES, INC.
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
Report No. 0700.104-02, Revision 2 Page 18 of 19
- 7.
References 7.1.
Erosion/Corrosion-Induced Pipe Wall Thinning, Generic Letter 89-08, U.S.
Nuclear Regulatory Commission (NRC), May 2, 1989.
7.2.
Recommendations for an Effective Flow-Accelerated Corrosion Program, EPRI NSAC 202L-R3, 1011838, May 2006.
7.3.
Indian Point 2 FAC Susceptible Piping and Instrumentation Diagrams.
System (Drawing Title)
P&ID #
Rev #
Main Steam 9321-F-2017 84 Main Steam A235308 49 Main Steam 227780 53 Main Steam Traps (Sheet 1) 9321-F-2041 35 Main Steam Traps (Sheet 2) 9321-F-2042 21 Steam Drain and Gland Seal for Low and High Pressure Turbines B237144 4
Steam Drain and Gland Seal for Low and High Pressure Turbines B237145 6
Boiler Feed Pump Turbine Steam Lines Drains & Vents 9321-H-2024 23 Moisture Separator and Reheater Drains & Vents 9321-F-2023 35 Moisture Preseparator A228272 16 Extraction Steam 9321-F-2020 43 Extraction Steam Trap System 9321-F-2031 17 Heater Drains & Vents 9321-F-2022 53 Heater Drains & Vents A235304 23 Moisture Separator Reheaters Vent Chamber Discharge A209847 13 Superheater Building Service Boilers 9321-F-2120 69 Auxiliary Steam Supply and Condensate Return System A209775 45 Auxiliary Steam System (Sheet 1)
B192490 22 Auxiliary Steam System (Sheet 2) 192491 39 Auxiliary Steam System (Sheet 3)
B192493 8
Water Treatment System (Sheet 3)
A192496 18 Steam Activated Carbon Filter B227209 16 Auxiliary Boiler Feed B193201 15 Condensate & Boiler Feed Pump Suction (Sheet 1) 9321-2018 141 Condensate & Boiler Feed Pump Suction (Sheet 2)
A235307 32 Boiler Feedwater 9321-F-2019 113 Steam Generator Blowdown & Blowdown Sample System 9321-F-2729 69 7.4.
Indian Point System Descriptions/Design Manuals.
System Name SD No.
Main and Reheat Steam Supply 18.00 Extraction Steam and Heater Drains and Vents 19.02 Condensate 20.00 Feedwater 21.00 Circulating Water 23.04 Service Water 24.00
CSI TECHNOLOGIES, INC.
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
Report No. 0700.104-02, Revision 2 Page 19 of 19 System Name SD No.
Main Turbine Lube Oil 26.00 Auxiliary Steam 29.01 Instrument Air 29.02 7.5.
Indian Point Plant Operating Manuals Operating Manual Doc. No Rev.
Auxiliary Steam 2-SOP-29-01 19 House Service Boilers 2-SOP-29-01-01 17 House Service Boilers Fuel Oil 2-SOP-29-01-02 18 House Service Boilers Feedwater 2-SOP-29-01-03 14 7.6.
Electronic correspondence between CSI and Indian Point personnel (see Attachment B).
7.6.1. Email from Ryan Doremus (CSI) to Ian Mew (IPEC) regarding a Line Naming Convention, dated 7/27/2009.
7.6.2. Email from Ian Mew (IPEC) to Ryan Doremus (CSI) regarding responses to information requests, dated 8/10/2009.
7.6.3. Email from Ian Mew (IPEC) to Ryan Doremus (CSI) regarding responses to information requests, dated 8/13/2009.
7.7.
EPRI, Flow-Accelerated Corrosion in Power Plants, B. Chexal et al, EPRI TR-106611-R1, 1998.
7.8.
Entergy Nuclear Northeast Indian Point Energy Center - Unit No. 2:
Specification For Fabrication of Piping Systems Turbine Generator Plant; Specification No. 9321-01-248-18; Revision 18; January 15, 2010.
7.9.
Indian Point Isometric Drawings for FAC-susceptible piping, gathered by CSI on 4/3/2009.
7.10. Indian Point Uprate PEPSE Model with New HP Turbine High Pressure Turbine Expansion, Run Date 10/26/06.
7.11. CHECWORKS Steam/Feedwater Application Guidelines for Plant Modeling and Evaluation of Component Inspection Data. EPRI, Palo Alto, CA and CSI Technologies, Inc., Elgin, IL: 2009. 1019176.
7.12. Flow Accelerated Corrosion Program Plan Supplement; Edited by Hazel Pearsall, FAC Program Engineer; Dated April 28, 2003 (For information only).
7.13. Indian Point FAC Program History Outage Reports, transmitted to CSI on 7/15/2009 (For information only).
7.14. CHUG Industry Experience Documents (see Attachment A) (For information only).
7.15. Indian Point System List. Transmitted to CSI on 1/6/2010 (For information only).
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
System Susceptibility Evaluation Report Appendix A CSI TECHNOLOGIES, INC.
Report No. 0700.104-02, Appendix A, Revision 2 Page A-1 of 14
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
System Code System Name Susceptible?
Excl. Crit.
Comments Reference System Number CSI TECHNOLOGIES, INC.
Text19:
AF Auxiliary Feedwater Yes This system delivers feedwater to the Service Boilers P&ID Text19:
AS Auxiliary Steam Yes This system generates and distributes steam to the various auxiliaries requiring steam for operation.
SD No. 29.01 Text19:
AST Auxiliary Steam Traps Yes This system includes all steam trap lines for the Auxiliary Steam System SD No. 29.01 Text19:
BD Steam Generator Blowdown Yes This system takes water from the steam generators for maintaining proper Steam Generator Chemistry.
P&ID Text19:
CD Condensate Pump Discharge Yes This system includes piping from some high temperature Feedwater Heaters.
SD No. 20.0 Text19:
EST Extraction Steam Traps Yes This system includes all steam trap lines originating from extraction steam, heater drains, heater vents, and moisture separator drains.
SD No. 19.02 Text19:
EX Extraction Steam Yes This system includes extraction steam to the Feedwater Heaters SD No. 19.02 Text19:
FW Main Feed Water Yes This system supplies feedwater to the steam generators.
SD No. 21.0 Text19:
GS Gland Sealing Steam Yes This system supplies sealing steam to the HP, LP, and BFP Turbines.
P&IDs Text19:
GST Gland Steam Traps Yes This system includes all steam trap lines for the Gland Steam System P&ID Text19:
HD Heater Drains & Vents Yes This system includes Feedwater Heater Drains and Vents, and piping from the Heater Drain Pumps to the Boiler Feed Pump suction.
SD No. 19.02 Report No. 0700.104-02, Appendix A, Revision 2 Page A-2 of 14
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
System Code System Name Susceptible?
Excl. Crit.
Comments Reference System Number CSI TECHNOLOGIES, INC.
Text19:
MS Main Steam Yes This system supplies steam to the HP and BFP Turbines and the MSRs.
SD No. 18.0 Text19:
MSD Moisture Separator Reheater Drains Yes This system includes MSR Drains to the Heater Drain Tank, No. 25 Feedwater Heaters, and the Drains Collecting Tank P&ID Text19:
MST Main Steam Traps Yes This system includes all steam trap lines for the Main Steam System SD No. 18.0 Text19:
PD Moisture Preseparator Drains Yes This system removes moisture from piping upstream of the HP Turbine Crossunder Piping.
P&ID Text19:
RST Reheat Steam Traps Yes This system includes all steam trap lines from the Reheater Steam system.
SD No. 18.0 Text19:
SB Service Boiler Yes This system contains some steam piping from the Service Boiler.
P&ID Text19:
UH Condensate Return Unit Heaters to Service Boiler D Yes This system contains condensate from the condensate return unit heaters to the service boiler deaerator.
Pipe Spec Text19:
UHT Condensate Return Unit Heater Steam Traps Yes This system includes all steam trap lines for the Condensate Return Unit Heaters to Service Boiler Deaerator system.
P&ID Text19:
VCD MSR Vent Chamber Discharge Yes This system contains steam from the MSRs.
P&ID Text19:
A 4160 VAC No EP This is an electrical system that does not contain piping.
Text19:
AAC AAC EDG Controls & Excitation No EP This system does not contain piping.
Text19:
AAC Alternate AC Diesel Generator No EP This system contains only the generator and not the associated piping.
Report No. 0700.104-02, Appendix A, Revision 2 Page A-3 of 14
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
System Code System Name Susceptible?
Excl. Crit.
Comments Reference System Number CSI TECHNOLOGIES, INC.
Text19:
AB Auxiliary Building No EP This system includes the building and not the associated piping.
Text19:
ABS Auxiliary Building Sump No ET This system handles low temperature water from floor drains.
Text19:
ABV Auxiliary Building Ventilations No EW This system vents non-condensable gases.
Text19:
AC Chill Water System No ET This system operates at under 200 degF Text19:
ACW Auxiliary Cooling Water No ET This system operates at under 200 degF P&ID Text19:
ADM Admin Building No EP This system includes the building and not the associated piping.
Text19:
ARMS Area Radiation Monitoring Systems No EP This system does not contain piping.
Text19:
B 480 VAC No EP This is an electrical system that does not contain piping.
Text19:
BA Breathing Air No EW This system does not contain water or steam.
Text19:
BMS Boron Management No EW This system does not contain water or steam.
Text19:
BS Containment (Building) Spray No EI Containment spray only operates in emergency situations.
SD No. 10.2 Text19:
CA Secondary Chemical Addition No EW This system does not contain water or steam.
Text19:
CCW Component Cooling Water System No ET This system provides low-temperature water to various equipment in the plant.
P&ID Report No. 0700.104-02, Appendix A, Revision 2 Page A-4 of 14
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
System Code System Name Susceptible?
Excl. Crit.
Comments Reference System Number CSI TECHNOLOGIES, INC.
Text19:
CEDM Control Element Drive Mechanism Control No EP This system does not contain piping.
Text19:
CF Chemical Feed No EW This system does not contain water or steam.
P&IDs Text19:
CL Chlorination No EW This system does not contain water or steam.
P&ID Text19:
COMM Communications No EP This system does not contain piping.
Text19:
CP Cathodic Protection No EP This is an electrical system that does not contain piping.
Text19:
CPC Core Protection Calculators No EP This system does not contain piping.
Text19:
CPV Penetration Room Ventilation No EW This system vents non-condensable gases.
Text19:
CRDX Cardox (CO2 Fire Protection System)
No EW This system does not contain water or steam.
P&ID Text19:
CRV Control Room Ventilation No EW This system vents non-condensable gases.
Text19:
CS Condensate Pump Suction No ET This system transports low-temperature water from the Condensers to the Condensate Pump.
SD No. 20.0 Text19:
CT Condensate Storage & Transfer No ET Condensate transfer is a low-temperature system used to ensure there is no raw water contamination of the condensate.
SD No. 20.0 Text19:
CV Condenser Air Vents No EW This system does not contain water or steam.
Text19:
CVCS Chemical and Volume Control System No EM This system is comprised entirely of FAC-resistant piping.
P&IDs Report No. 0700.104-02, Appendix A, Revision 2 Page A-5 of 14
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
System Code System Name Susceptible?
Excl. Crit.
Comments Reference System Number CSI TECHNOLOGIES, INC.
Text19:
CVH Containment Vent Header No EW This system vents non-condensable gases.
Text19:
CW Circulating Water No EO This system provides river water to cool the steam in the condensers.
SD No. 23.0 Text19:
D 125 VDC No EP This is an electrical system that does not contain piping.
Text19:
DA Diesel Generator Starting Air No EW This system does not contain water or steam.
P&ID Text19:
DCH Drain Collection Header No EF Flow in this system is too low to facilitate FAC.
Text19:
DF Diesel Generator Fuel Oil No EW This system does not contain water or steam.
P&ID Text19:
DFAS Diverse Emergency Feed Actuation No EP This system does not contain piping.
Text19:
DSS Diverse Scram System No EP This system does not contain piping.
Text19:
DW Domestic Water No EO This system contains highly oxygenated water from the city supply.
Text19:
EC Plant Computer No EP This system does not contain piping.
Text19:
EDG Emergency Diesel Generator No EP This system does not contain piping.
Text19:
EDG EDG Controls & Excitation No EP This system does not contain piping.
Text19:
EFW Emergency Feed Water No EI This system only operates in emergency situations.
Text19:
EHC Electro-Hydraulic (Mechanical)
No EP This system does not contain piping.
Report No. 0700.104-02, Appendix A, Revision 2 Page A-6 of 14
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
System Code System Name Susceptible?
Excl. Crit.
Comments Reference System Number CSI TECHNOLOGIES, INC.
Text19:
EHC MFP EHC Controls No EP This system does not contain piping.
Text19:
EHC MTG EHC Controls No EP This system does not contain piping.
Text19:
EL Emergency Lighting (Safe Shutdown)
No EP This system does not contain piping.
Text19:
EOF Emergency Operations Facility No EP This system does not contain piping.
Text19:
ES ESFAS No EP This system does not contain piping.
Text19:
EXCT Main Generator Excitation &
Protection No EP This system does not contain piping.
Text19:
F Switchyard No EP This system does not contain piping.
Text19:
FD Fire Detection No EP This system does not contain piping.
Text19:
FHS Fuel Handling System No EW This system does not contain water or steam.
Text19:
FO Diesel Fuel Oil Storage and Transfer No EW This system does not contain water or steam.
P&ID Text19:
FP Spent Fuel Pool Cooling No ET This system operates at under 200 degF Text19:
FS Fire Protection (Water)
No ET This system uses low-temperature city water.
P&IDs Text19:
FWCS Feed Water Control System No EF This system contains low-flow instrumentation lines.
Text19:
GCH Gas Collection Header No EW This system does not contain water or steam.
Report No. 0700.104-02, Appendix A, Revision 2 Page A-7 of 14
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
System Code System Name Susceptible?
Excl. Crit.
Comments Reference System Number CSI TECHNOLOGIES, INC.
Text19:
GG Generator Gas No EW This system does not contain water or steam.
Text19:
GSO Hydrogen Seal Oil (Mechanical)
No EW This system does not contain water or steam.
Text19:
GZ Gaseous Radwaste No EW This system does not contain water or steam.
Text19:
H 6900 VAC No EP This is an electrical system that does not contain piping.
Text19:
H2 Hydrogen No EW This system does not contain water or steam.
Text19:
HAL Halon No EW This system does not contain water or steam.
Text19:
HPA Hydrogen Purge System No EW This system does not contain water or steam.
Text19:
HPSI High Pressure Safety Injection No EM Lines in this system are composed of FAC-resistant material.
Pipe Spec Text19:
HR H2 Recombiners No EW This system does not contain water or steam.
Text19:
HS Generator Hydrogen Supply No EW This system provides hydrogen to the steam generators.
P&ID Text19:
HT Heat Tracking No EP This system does not contain piping.
Text19:
IA Instrument Air No EW This system does not contain water or steam.
SD No. 29.02 Text19:
IB Isophase Bus No EP This system does not contain piping.
Text19:
IBC Isophase Bus Cooling No ET This system operates at under 200 degF Report No. 0700.104-02, Appendix A, Revision 2 Page A-8 of 14
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
System Code System Name Susceptible?
Excl. Crit.
Comments Reference System Number CSI TECHNOLOGIES, INC.
Text19:
IC Incore Instrumentation No EF This system contains low-flow instrumentation lines.
Text19:
ICC Reactor Vessel Level Monitoring &
CETs No EF This system contains low-flow instrumentation lines.
Text19:
IS Intake Structure No EO This system contains highly oxygenated water.
Text19:
JW Diesel Generator Jacket Water No EO This system is fed with raw water.
P&ID Text19:
K Annunciators No EP This system does not contain piping.
Text19:
LA 120/208 VAC Misc. Lighting &
Power Dist.
No EP This is an electrical system that does not contain piping.
Text19:
LLRW Low Level Radwaste Bldg No EP This system does not contain piping.
Text19:
LO Main Turbine Lube Oil No EW This system does not contain water or steam.
P&ID Text19:
LPSI Low Pressure Safety Injection No EM Lines in this system are composed of FAC-resistant material.
Pipe Spec Text19:
LRBV Low Level Radwaste Building Ventilation No EW This system vents non-condensable gases.
Text19:
LRW Liq Radwaste Mgmt No EW This system does not contain water or steam.
Text19:
MET Meteorological Instrumentation No EP This system does not contain piping.
Text19:
MW City Water Make-Up No EO This system contains highly oxygenated water from the city supply.
P&ID Text19:
N2 Nitrogen No EW This system does not contain water or steam.
P&ID Report No. 0700.104-02, Appendix A, Revision 2 Page A-9 of 14
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
System Code System Name Susceptible?
Excl. Crit.
Comments Reference System Number CSI TECHNOLOGIES, INC.
Text19:
NI Nuclear Instrumentation No EP This system does not contain piping.
Text19:
NT Neutralizing System No EP This system does not contain piping.
Text19:
PA Reactor Building Purge Air No EW This system does not contain water or steam.
Text19:
PASS Post Accident Sampling No EI This system only operates in post-accident conditions Text19:
PCA Penetration Cooling Air No EW This system does not contain water or steam.
P&ID Text19:
PH Plant Heating No EW This system does not contain water or steam.
Text19:
PMU Makeup Demineralizer System No ET This system operates at under 200 degF Text19:
PPS Plant Protection System No EP This system does not contain piping.
Text19:
PS Primary Sampling No EI This system operates less than 2% of plant operation Text19:
PW Primary Water No ET This system contains low-temperature water P&ID Text19:
RB Reactor Building No EP This system does not contain piping.
Text19:
RBHV Reactor Building Ventilation No EW This system vents non-condensable gases.
Text19:
RCP Reactor Coolant Pumps No EP This system does not contain piping.
Text19:
RCS Reactor Coolant System No EM All lines in the RCS system are composed of FAC-resistant piping P&ID Report No. 0700.104-02, Appendix A, Revision 2 Page A-10 of 14
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
System Code System Name Susceptible?
Excl. Crit.
Comments Reference System Number CSI TECHNOLOGIES, INC.
Text19:
RDAC/S PING RDAC (Radiation Dose Assessment Computer)/SPING (S No EP This system does not contain piping.
Text19:
RHR Residual Heat Removal System No EM All lines in the RHR system are stainless steel.
Pipe Spec Text19:
RMS Radiation Monitoring No EP This system does not contain piping.
Text19:
RPS Reactor Protection System No EP This system does not contain piping.
Text19:
RRS Reactor Regulating System No EP This system does not contain piping.
Text19:
RS Reheat Steam No EQ Reheater Steam provides superheated steam to the LP and BFP Turbines.
SD No. 18.0 Text19:
RT Resin Transfer No EW This system does not contain water or steam.
Text19:
RWB Radwaste Building No EP This system does not contain piping.
Text19:
RX Reactor Core No EP This system does not contain piping.
Text19:
RZ Regen Waste No EP This system does not contain piping.
Text19:
SA Service Air No EW This system does not contain water or steam.
P&ID Text19:
SDBC Steam Dump Bypass Control System No EP This system does not contain piping.
Text19:
SDC Shutdown Cooling No EI This system only operates during shutdown.
Text19:
SEC Security No EP This system does not contain piping.
Report No. 0700.104-02, Appendix A, Revision 2 Page A-11 of 14
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
System Code System Name Susceptible?
Excl. Crit.
Comments Reference System Number CSI TECHNOLOGIES, INC.
Text19:
SFP Spent Fuel Pit No ET The water in this system is low-temperature.
Text19:
SGS Stm. Gen. Secondary No EP This system does not contain piping.
Text19:
SI Safety Injection System No EM This system is comprised entirely of FAC-resistant piping.
P&ID Text19:
SMS Seismic Monitoring System No EP This system does not contain piping.
Text19:
SP Sample System No EM Sample piping at IPEC is stainless steel.
Pipe Spec Text19:
SPDS Safety Parameter Display System No EP This system does not contain piping.
Text19:
SS Secondary Sampling No EM Sample piping at IPEC is stainless steel.
Pipe Spec Text19:
STP Sewage Treatment Plant No EP This system does not contain piping.
Text19:
SW Service Water No EO Service Water has a high concentration of dissolved oxygen.
P&ID Text19:
SWC Stator Water Cooling No ET This system operates at under 200 degF Text19:
SZ Solid Waste Management No EW This system does not contain water or steam.
Text19:
TB Turbine Building No EP This system does not contain piping.
Text19:
TBS Turbine Building Sump No EF Flow in this system is too low to facilitate FAC.
Text19:
TBV Turbine Building Ventilation No EW This system vents non-condensable gases.
Report No. 0700.104-02, Appendix A, Revision 2 Page A-12 of 14
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
System Code System Name Susceptible?
Excl. Crit.
Comments Reference System Number CSI TECHNOLOGIES, INC.
Text19:
TG Main Turbine & Generator No EP This system does not contain piping.
Text19:
TG MTG & MFPT Supervisory Instrumentation No EP This system does not contain piping.
Text19:
TS Traveling Screens No EP This system does not contain piping.
Text19:
VENT Miscellaneous Ventilation System No EW This system vents non-condensable gases.
Text19:
VLPM U2 Vibration & Loose Parts Monitoring System No EP This system does not contain piping.
Text19:
VS Condenser Vacuum No EW This system vents non-condensable gases.
Text19:
XFMR Main, Auxiliary & Startup Transformers No EP This system does not contain piping.
Text19:
Y Inverters & Vital 120 VAC No EP This is an electrical system that does not contain piping.
Report No. 0700.104-02, Appendix A, Revision 2 Page A-13 of 14
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
System Code System Name Susceptible?
Excl. Crit.
Comments Reference System Number CSI TECHNOLOGIES, INC.
Exclusion Criteria Legend:
EC EF EI EM EO EP EQ ER ET EW Excluded due to Combination of infrequent op above temp threshold Excluded due to low or no Flow Excluded due to Infrequent operation Excluded due to FAC-resistant Material Excluded due to high dissolved Oxygen content Exluded, does not contain Piping Excluded due to high steam Quality Excluded, Removed from service and "cut" and "capped" Excluded due to operating Temperature (single phase, < 200 deg F)
Excluded because system, subsytem, or line is non-Water Report No. 0700.104-02, Appendix A, Revision 2 Page A-14 of 14
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
Subsystem Susceptibility Evaluation Report Appendix B CSI TECHNOLOGIES, INC.
Indian Point Unit 2 Report No. 0700.104-02, Appendix B, Revision 2 Page B-1 of 22
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Auxiliary Feedwater (AF), Unit 2 Subsystem Number Subsystem Name FAC Sus?
Excl.
Crit.
Comments Reference Subsystem Boundary P&ID No.
Text19:
2-AF-01 Service Boiler Auxiliary Feedwater Lines Yes P&ID 9321-F-2120, B193201 Text19:
2-AF-02 Aux Feedwater to and from Sample Coolers No EI Valves to coolers shown closed on P&ID P&ID 9321-F-2120 Report No. 0700.104-02, Appendix B, Revision 2 Page B-2 of 22
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Auxiliary Steam (AS), Unit 2 Subsystem Number Subsystem Name FAC Sus?
Excl.
Crit.
Comments Reference Subsystem Boundary P&ID No.
Text19:
2-AS-01 Auxiliary Steam to Burner Atomizing Steam No EQ Atomizing steam is superheated SD No. 29.01 9321-F-2120 Text19:
2-AS-02 Auxiliary Steam to Fuel Oil Suction Heaters No ER Source line shown capped on P&ID P&ID B192493 Text19:
2-AS-03 Remainder of Auxiliary Steam Yes SD No. 29.01 9321-F-2120,
- A209775, B192490,
- B192491, B192493,
- B192496, B193201, B227209 Report No. 0700.104-02, Appendix B, Revision 2 Page B-3 of 22
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Auxiliary Steam Traps (AST), Unit 2 Subsystem Number Subsystem Name FAC Sus?
Excl.
Crit.
Comments Reference Subsystem Boundary P&ID No.
Text19:
2-AST-01 Steam Trap Lines from Auxiliary Steam Lines Yes P&ID 9321-F-2120,
- B192490, B192491 Report No. 0700.104-02, Appendix B, Revision 2 Page B-4 of 22
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Steam Generator Blowdown (BD), Unit 2 Subsystem Number Subsystem Name FAC Sus?
Excl.
Crit.
Comments Reference Subsystem Boundary P&ID No.
Text19:
2-BD-01 Steam Generator Blowdown to Sample Coolers and Blowdown Tank Yes SD No. 18.0 9321-F-2729 Report No. 0700.104-02, Appendix B, Revision 2 Page B-5 of 22
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Condensate Pump Discharge (CD), Unit 2 Subsystem Number Subsystem Name FAC Sus?
Excl.
Crit.
Comments Reference Subsystem Boundary P&ID No.
Text19:
2-CD-01 Condensate Lines Between Condensate Pumps and #22 Feedwater Heaters No ET Condensate is below 200 degF before passing through the #22 FWHs PEPSE 9321-2018, A235307 Text19:
2-CD-02 Condensate Lines Downstream of #22 Feedwater Heaters Yes PEPSE 9321-2018, A235307 Report No. 0700.104-02, Appendix B, Revision 2 Page B-6 of 22
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Extraction Steam Traps (EST), Unit 2 Subsystem Number Subsystem Name FAC Sus?
Excl.
Crit.
Comments Reference Subsystem Boundary P&ID No.
Text19:
2-1EST-01 Extraction Steam Trap Headers to the Drains Collecting Tank Yes P&ID 9321-F-2031 Text19:
2-3EST-01 Steam Trap lines from Extraction Steam to the #23 FWHs Yes P&ID 9321-F-2031 Text19:
2-4EST-01 Lines from Stm Traps to the Stm Trap Drains Header from Ext lines to #24 FWHs Yes P&IDs 9321-F-2031 Text19:
2-4EST-02 Lines upstream of the Stm Traps from #24 FWH's Ext Stm Header No EQ Lines upstream of the steam traps are superheated.
PEPSE 9321-F-2031 Text19:
2-5EST-01 Steam Trap lines from Extraction Steam to the #25 FWHs Yes P&ID 9321-F-2031 Text19:
2-6EST-01 Steam Trap lines from Extraction Steam to the #26 FWHs Yes P&ID 9321-F-2031 Report No. 0700.104-02, Appendix B, Revision 2 Page B-7 of 22
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Extraction Steam (EX), Unit 2 Subsystem Number Subsystem Name FAC Sus?
Excl.
Crit.
Comments Reference Subsystem Boundary P&ID No.
Text19:
2-1EX-01 LP Turb Ext Stm to
- 21 FWHs Yes PEPSE 9321-F-2020 Text19:
2-2EX-01 LP Turbine Extraction Steam to #22 Feedwater Heaters Yes PEPSE 9321-F-2020 Text19:
2-3EX-01 Boiler Feed Pump Turbine Drains to Condensers Yes PEPSE A227780 Text19:
2-3EX-02 LP Turbine Extraction Steam to #23 Feedwater Heaters Yes PEPSE 9321-F-2020, 9321-F-2031 Text19:
2-4EX-01 Extraction Steam Lines to #24 Feedwater Heaters No EQ Steam is superheated upstream of the steam traps.
P&IDs 9321-F-2020, 9321-F-2031 Text19:
2-5EX-01 HP Turbine Crossunder Piping Drip Pots to the Condenser Yes P&IDs A235308 Text19:
2-5EX-02 Small Bore Steam Drains to the Condenser via FCV-1156, 1157, 1164, 1165, and 1166.
No EI Control valves in these lines are normally closed.
SD No. 18.0 A235308 Text19:
2-5EX-03 Extraction Steam from Separating Tanks to
- 25 Feedwater Heaters Yes PEPSE 9321-F-2020, 9321-F-2031 Text19:
2-6EX-01 HP Turbine Extraction Steam to #26 Feedwater Heaters Yes PEPSE 9321-F-2020 Report No. 0700.104-02, Appendix B, Revision 2 Page B-8 of 22
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Main Feed Water (FW), Unit 2 Subsystem Number Subsystem Name FAC Sus?
Excl.
Crit.
Comments Reference Subsystem Boundary P&ID No.
Text19:
2-FW-01 Feedwater Lines from the Boiler Feed Pumps to the Steam Generators Yes PEPSE 9321-F-2019 Text19:
2-FW-02 Auxiliary Feedwater Lines to Steam Generator No EI Auxiliary Feedwater only operates during startup, shutdown, and emergency conditions.
SD No. 21.0 9321-F-2019 Text19:
2-FW-03 Boiler Feed Pump Recirc Lines to the Drains Collecting Tank Yes SD No. 21.0 9321-F-2019 Report No. 0700.104-02, Appendix B, Revision 2 Page B-9 of 22
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Gland Sealing Steam (GS), Unit 2 Subsystem Number Subsystem Name FAC Sus?
Excl.
Crit.
Comments Reference Subsystem Boundary P&ID No.
Text19:
2-GS-01 Gland Steam to and from HP, LP, and BFP Turbines Yes P&IDs
- A235308, B237144, B237145, 9321-H-2024 Report No. 0700.104-02, Appendix B, Revision 2 Page B-10 of 22
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Gland Steam Traps (GST), Unit 2 Subsystem Number Subsystem Name FAC Sus?
Excl.
Crit.
Comments Reference Subsystem Boundary P&ID No.
Text19:
2-GST-01 Steam Trap Lines from the Gland Seal System Yes P&ID 9321-H-2024 Report No. 0700.104-02, Appendix B, Revision 2 Page B-11 of 22
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Heater Drains & Vents (HD), Unit 2 Subsystem Number Subsystem Name FAC Sus?
Excl.
Crit.
Comments Reference Subsystem Boundary P&ID No.
Text19:
2-1HD-01
- 21 Feedwater Heater Drain Lines Yes PEPSE A235304 Text19:
2-1HD-02
- 21 Feedwater Heater Vents Yes P&ID A235304 Text19:
2-2HD-01
- 22 Feedwater Heater Drain Lines Yes PEPSE A235304 Text19:
2-2HD-02
- 22 Feedwater Heater Vents Yes P&ID A235304 Text19:
2-3HD-01
- 23 Feedwater Heater Drain Lines Yes PEPSE A235304 Text19:
2-3HD-02
- 23 Feedwater Heater Vents Yes P&ID A235304 Text19:
2-4HD-01
- 24 Feedwater Heater Drain Lines Yes PEPSE A235304 Text19:
2-4HD-02
- 24 Feedwater Heater Vents Yes P&ID A235304 Text19:
2-5HD-01 Heater Drains from
- 25 Feedwater Heaters Yes PEPSE 9321-F-2022 Text19:
2-5HD-02 Heater Vents from
- 25 Feedwater Heater and Heater Drain Tank vents to #25 Feedwater Heaters Yes P&ID 9321-F-2022, A235304 Text19:
2-5HD-03 HDT Drains to HDPs and Condensers and HDP Vents to HDT Yes PEPSE 9321-F-2022, A235304 Report No. 0700.104-02, Appendix B, Revision 2 Page B-12 of 22
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Heater Drains & Vents (HD), Unit 2 Subsystem Number Subsystem Name FAC Sus?
Excl.
Crit.
Comments Reference Subsystem Boundary P&ID No.
Text19:
2-6HD-01 Heater Drains from
- 26 Feedwater Heaters Yes PEPSE 9321-F-2022 Text19:
2-6HD-02 Heater Vents from
- 26 Feedwater Heater Yes P&ID 9321-F-2022, A235304 Text19:
2-HD-01 Heater Drain Pump discharge to Boiler Feed Pumps Yes PEPSE 9321-F-2022 Report No. 0700.104-02, Appendix B, Revision 2 Page B-13 of 22
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Main Steam (MS), Unit 2 Subsystem Number Subsystem Name FAC Sus?
Excl.
Crit.
Comments Reference Subsystem Boundary P&ID No.
Text19:
2-MS-01 Main Steam from Stm Gen to HP Turbine, BFP Turbine, MSRs, Aux. Steam, SJAEs, and Priming Ejectors.
Yes P&IDs 9321-F-2017,
- A227780, A235308 Text19:
2-MS-02 Main Steam to MSR Header Dumps to Condenser No EI These lines operate during startup and shutdown.
SD No. 18.0 A227780 Text19:
2-MS-03 Small Bore Turbine Steam Drains to the Condenser via FCV-1154, 1155, 1158, and 1159 No EI Control valves in these lines are normally closed.
SD No. 18.0 A235308 Text19:
2-MS-04 H.P. Cylinder Steam Heating and Seals No EI Control valves in line are closed during normal operation.
SD No. 18.0 A235308 Text19:
2-MS-05 Scavenging Steam from 6th Stage Extraction Steam No ER Piping is abandoned in place.
P&ID 9321-F-2023 Text19:
2-MS-06 Main Steam Supply to Gland Steam Header Yes P&ID A235308 Text19:
2-MS-07 HP Turbine Crossunder Piping to the Moisture Separators Yes PEPSE
- A235308, A227780 Report No. 0700.104-02, Appendix B, Revision 2 Page B-14 of 22
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Moisture Separator Reheater Drains (MSD), Unit 2 Subsystem Number Subsystem Name FAC Sus?
Excl.
Crit.
Comments Reference Subsystem Boundary P&ID No.
Text19:
2-MSD-01 Moisture Separator Drains to the Heater Drain Tank and Drains Collecting Tank Yes PEPSE 9321-F-2023 Text19:
2-MSD-02 Reheater Drains to
- 26 Feedwater Heaters and Condensers Yes PEPSE 9321-F-2023 Report No. 0700.104-02, Appendix B, Revision 2 Page B-15 of 22
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Main Steam Traps (MST), Unit 2 Subsystem Number Subsystem Name FAC Sus?
Excl.
Crit.
Comments Reference Subsystem Boundary P&ID No.
Text19:
2-MST-01 Steam Trap Lines from the Main Steam System Yes P&ID 9321-F-2041, 9321-F-2042 Report No. 0700.104-02, Appendix B, Revision 2 Page B-16 of 22
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Moisture Preseparator Drains (PD), Unit 2 Subsystem Number Subsystem Name FAC Sus?
Excl.
Crit.
Comments Reference Subsystem Boundary P&ID No.
Text19:
2-PD-01 Moisture Preseparator Drain Lines Yes PEPSE A228272 Report No. 0700.104-02, Appendix B, Revision 2 Page B-17 of 22
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Reheat Steam Traps (RST), Unit 2 Subsystem Number Subsystem Name FAC Sus?
Excl.
Crit.
Comments Reference Subsystem Boundary P&ID No.
Text19:
2-RST-01 Reheat Steam Trap Lines Downstream of Reheater Steam Traps Yes P&IDs 9321-H-2024 Text19:
2-RST-02 All other Reheater Steam Trap Lines No EQ Reheat Steam upstream of the steam traps is superheated.
PEPSE A227780, 9321-H-2024 Report No. 0700.104-02, Appendix B, Revision 2 Page B-18 of 22
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Service Boiler (SB), Unit 2 Subsystem Number Subsystem Name FAC Sus?
Excl.
Crit.
Comments Reference Subsystem Boundary P&ID No.
Text19:
2-SB-01 Service Boiler Lines Yes SD No. 29.01 9321-F-2120,
- A227780, A209775, B193201 Report No. 0700.104-02, Appendix B, Revision 2 Page B-19 of 22
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Condensate Return Unit Heaters to Service Boiler D (UH), Unit 2 Subsystem Number Subsystem Name FAC Sus?
Excl.
Crit.
Comments Reference Subsystem Boundary P&ID No.
Text19:
2-UH-01 Condensate Return from Unit Heaters to the Deaerator Yes P&IDs 9321-F-2120,
- A209775, B192491, B193201 Report No. 0700.104-02, Appendix B, Revision 2 Page B-20 of 22
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Condensate Return Unit Heater Steam Traps (UHT), Unit 2 Subsystem Number Subsystem Name FAC Sus?
Excl.
Crit.
Comments Reference Subsystem Boundary P&ID No.
Text19:
2-UHT-01 Steam Trap Lines from the Condensate Return from Unit Heaters to the Deaerator system Yes P&ID A209775 Report No. 0700.104-02, Appendix B, Revision 2 Page B-21 of 22
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
MSR Vent Chamber Discharge (VCD), Unit 2 Subsystem Number Subsystem Name FAC Sus?
Excl.
Crit.
Comments Reference Subsystem Boundary P&ID No.
Text19:
2-VCD-01 Moisture Separator Reheater Vent Chamber Discharge Lines Yes PEPSE A209847 Exclusion Criteria (Excl. Crit.) Legend:
EC EF EI EM EO EP EQ ER ET EW Excluded due to Combination of infrequent op above temp threshold Excluded due to low or no Flow Excluded due to Infrequent operation Excluded due to FAC-resistant Material Excluded due to high dissolved Oxygen content Exluded, does not contain Piping Excluded due to high steam Quality Excluded, Removed from service and "cut" and "capped" Excluded due to operating Temperature (single phase, < 200 deg F)
Excluded because system, subsytem, or line is non-Water Report No. 0700.104-02, Appendix B, Revision 2 Page B-22 of 22
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
Line Susceptibility Evaluation Report Appendix C CSI TECHNOLOGIES, INC.
Indian Point Unit 2 Report No. 0700.104-02, Appendix C, Revision 2 Page C-1 of 102
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Auxiliary Feedwater (AF), Unit 2 Section B: SNM Program Lines 2-AF-01: Service Boiler Auxiliary Feedwater Lines Line Number Size (in.)
Sus.
Cat.
Comments Reference Mod.
Ex. Crit.
P&ID No.
Line Description Text19:
2-AF-001 6
S Deaerator Header to Boiler Feed Pumps Operating conditions unknown.
P&ID NC 9321-F-2120 Text19:
2-AF-002 4
S Aux. Feed header to #23 Boiler Feed Pump and #10 House Service Deaerator Operating conditions unknown.
P&ID NC 9321-F-2120 Text19:
2-AF-003 4
S Aux. Feed header to #21 Boiler Feed Pump Operating conditions unknown.
P&ID NC 9321-F-2120 Text19:
2-AF-004 4
S Aux. Feed header to #22 Boiler Feed Pump Operating conditions unknown.
P&ID NC 9321-F-2120 Text19:
2-AF-005 4
S Aux. Feed header to #23 Boiler Feed Pump Operating conditions unknown.
P&ID NC 9321-F-2120 Text19:
2-AF-006 6
S Aux. Feed header to #10 House Service Deaerator Operating conditions unknown.
P&ID NC 9321-F-2120 Text19:
2-AF-007 1.5 S
Boiler Feed Pump overflow header to Deaerator Operating conditions unknown.
P&ID NS 9321-F-2120 Text19:
2-AF-008 1.5 S
Boiler Feed Pump discharge Unit #3 tie-in.
Operating conditions unknown.
P&ID NS 9321-F-2120 Text19:
2-AF-011-A 1
S
- 21 BFP discharge overflow line upstream of orifice Operating conditions unknown.
P&ID NS 9321-F-2120 Text19:
2-AF-011-B 1
S
- 21 BFP discharge overflow line downstream of orifice Operating conditions unknown.
P&ID NS 9321-F-2120 Text19:
2-AF-012-A 1
S
- 22 BFP discharge overflow line upstream of orifice Operating conditions unknown.
P&ID NS 9321-F-2120 Text19:
2-AF-012-B 1
S
- 22 BFP discharge overflow line downstream of orifice Operating conditions unknown.
P&ID NS 9321-F-2120 Text19:
2-AF-013-A 1
S
- 23 BFP discharge overflow line upstream of orifice Operating conditions unknown.
P&ID NS 9321-F-2120 Report No. 0700.104-02, Appendix C, Revision 2 Page C-2 of 102
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Auxiliary Feedwater (AF), Unit 2 Section B: SNM Program Lines 2-AF-01: Service Boiler Auxiliary Feedwater Lines Line Number Size (in.)
Sus.
Cat.
Comments Reference Mod.
Ex. Crit.
P&ID No.
Line Description Text19:
2-AF-013-B 1
S
- 23 BFP discharge overflow line downstream of orifice Operating conditions unknown.
P&ID NS 9321-F-2120 Text19:
2-AF-014 3
S
- 21 BFP discharge line Operating conditions unknown.
P&ID NC 9321-F-2120 Text19:
2-AF-015 3
S
- 22 BFP discharge line Operating conditions unknown.
P&ID NC 9321-F-2120 Text19:
2-AF-016 3
S
- 23 BFP discharge line Operating conditions unknown.
P&ID NC 9321-F-2120 Text19:
2-AF-017 4
S
- 21 and #22 BFP discharge header Operating conditions unknown.
P&ID NC 9321-F-2120 Text19:
2-AF-018 2.5 S
LH Boiler #22 Feed Line Operating conditions unknown.
P&ID NC 9321-F-2120 Text19:
2-AF-019 2.5 S
AF-144 bypass line Operating conditions unknown.
P&ID NC 9321-F-2120 Text19:
2-AF-020 4
S Unit 1 Service Boiler Feed Pump discharge tie-in line.
Operating conditions unknown.
P&ID NC B193201, 9321-F-2021 Text19:
2-AF-021 1
S BFP discharge header to Desuperheater Station Operating conditions unknown.
P&ID NS 9321-F-2120 Text19:
2-AF-022 2.5 S
RH Boiler #21 Feed Line Operating conditions unknown.
P&ID NC 9321-F-2120 Text19:
2-AF-023 2.5 S
AF-138 bypass line Operating conditions unknown.
P&ID NC 9321-F-2120 Text19:
2-AF-024 0.75 S
RH Boiler #21 Continuous Blowdown Line Operating conditions unknown.
P&ID NS 9321-F-2120 Text19:
2-AF-025 1.5 S
RH Boiler #21 Intermittent Blowdown Line Operating conditions unknown.
P&ID NS 9321-F-2120 Text19:
2-AF-026 0.75 S
LH Boiler #22 Continuous Blowdown Line Operating conditions unknown.
P&ID NS 9321-F-2120 Text19:
2-AF-027 1.5 S
LH Boiler #22 Intermittent Blowdown Line Operating conditions unknown.
P&ID NS 9321-F-2120 Text19:
2-AF-028 0.75 S
Continuous Blowdown line to HSBSPCLs Operating conditions unknown.
P&ID NS 9321-F-2120 Report No. 0700.104-02, Appendix C, Revision 2 Page C-3 of 102
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Auxiliary Feedwater (AF), Unit 2 Section B: SNM Program Lines 2-AF-01: Service Boiler Auxiliary Feedwater Lines Line Number Size (in.)
Sus.
Cat.
Comments Reference Mod.
Ex. Crit.
P&ID No.
Line Description Text19:
2-AF-029 1.5 S
Boiler Blowdown Tank Bottom Drain Operating conditions unknown.
P&ID NS 9321-F-2120 Text19:
2-AF-030 1.5 S
Boiler Blowdown Tank Drain Bypass Operating conditions unknown.
P&ID NS 9321-F-2120 Text19:
2-AF-031 1.25 S
Boiler Blowdown Tank Drain Vent Operating conditions unknown.
P&ID NS 9321-F-2120 Text19:
2-AF-032 6
S Boiler Blowdown Tank Drain Operating conditions unknown.
P&ID NC 9321-F-2120 Text19:
2-AF-033 S
ABSPCLB Aux. Feed Inlet Operating conditions unknown.
P&ID NS B193201, 9321-F-2120 Text19:
2-AF-034 S
ABSPCLB Aux. Feed Outlet to Dissolved O2 Analyzer Operating conditions unknown.
P&ID NS 9321-F-2120 Text19:
2-AF-035 S
ABSPCLB Aux. Feed Outlet to Cooling Bath Operating conditions unknown.
P&ID NS 9321-F-2120 Text19:
2-AF-037 2
S Flash Tank Drain to Service Boiler Deaerator Operating conditions unknown.
P&ID NC B193201 Text19:
2-AF-038 1.25 S
Service Boiler Deaerator Vent Operating conditions unknown.
P&ID NS B193201 Text19:
2-AF-039 6
S Service Boiler Deaerator 6" Drain to OB Operating conditions unknown.
P&ID NC B193201 Text19:
2-AF-040 4
S Service Boiler Deaerator Drain vent Operating conditions unknown.
P&ID NC B193201 Text19:
2-AF-041 2
S Service Boiler Deaerator 2" Drain to OB Operating conditions unknown.
P&ID NS B193201 Text19:
2-AF-042 0.75 S
Drain from multiport valve.
Operating conditions unknown.
P&ID NS B193201 Text19:
2-AF-043 6
S Service Boiler Deaerator Drain to Service Boiler Feed Pumps Operating conditions unknown.
P&ID NC B193201 Text19:
2-AF-044 4
S Service Boiler Pump No. 11 Feed Line Operating conditions unknown.
P&ID NC B193201 Text19:
2-AF-045 4
S Service Boiler Pump No. 12 Feed Line Operating conditions unknown.
P&ID NC B193201 Report No. 0700.104-02, Appendix C, Revision 2 Page C-4 of 102
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Auxiliary Feedwater (AF), Unit 2 Section B: SNM Program Lines 2-AF-01: Service Boiler Auxiliary Feedwater Lines Line Number Size (in.)
Sus.
Cat.
Comments Reference Mod.
Ex. Crit.
P&ID No.
Line Description Text19:
2-AF-046 4
S Service Boiler Pump No. 13 Feed Line Operating conditions unknown.
P&ID NC B193201 Text19:
2-AF-047 3
S Service Boiler Pump No. 11 Discharge Line Operating conditions unknown.
P&ID NC B193201 Text19:
2-AF-048 3
S Service Boiler Pump No. 12 Discharge Line Operating conditions unknown.
P&ID NC B193201 Text19:
2-AF-049 3
S Service Boiler Pump No. 13 Discharge Line Operating conditions unknown.
P&ID NC B193201 Text19:
2-AF-050 6
S Service Boiler Pump Discharge Header Operating conditions unknown.
P&ID NC B193201 Text19:
2-AF-051 1.5 S
AF59 Vent to Service Boiler Deaerator Operating conditions unknown.
P&ID NS B193201 Text19:
2-AF-052 1.5 S
AF58 Vent to Service Boiler Deaerator Operating conditions unknown.
P&ID NS B193201 Text19:
2-AF-053 1.5 S
AF57 Vent to Service Boiler Deaerator Operating conditions unknown.
P&ID NS B193201 Text19:
2-AF-054 1.5 S
Check valve vent header to Service Boiler Deaerator Operating conditions unknown.
P&ID NS B193201 Text19:
2-AF-057 S
Chemical Bench Sink Operating conditions unknown.
P&ID NS 9321-F-2120 Section C: Excluded Lines 2-AF-01: Service Boiler Auxiliary Feedwater Lines Line Number Size (in.)
Sus.
Cat.
Comments Reference FAC Ex. Crit.
P&ID No.
Line Description Text19:
2-AF-009 1.5 E
Boiler Feed Pump Bypass line to #22 BFP overflow line Valve shown closed on P&ID.
P&ID EI 9321-F-2120 Report No. 0700.104-02, Appendix C, Revision 2 Page C-5 of 102
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Auxiliary Feedwater (AF), Unit 2 Section C: Excluded Lines 2-AF-01: Service Boiler Auxiliary Feedwater Lines Line Number Size (in.)
Sus.
Cat.
Comments Reference FAC Ex. Crit.
P&ID No.
Line Description Text19:
2-AF-010 1
E Boiler Feed Pump Bypass line to #23 BFP overflow line Valve shown closed on P&ID.
P&ID EI 9321-F-2120 Text19:
2-AF-036 E
Cooling Bath Drain Low Temperature discharge from Cooling Bath P&ID ET 9321-F-2120 Text19:
2-AF-055 2
E Line from #20 House Service Boiler to Service Boiler Deaerator
- 20 HSB Removed from Service SD No. 29.01 ER B193201 Text19:
2-AF-056 2.5 E
Line to AF92 Piping retired in place P&ID ER B193201 Report No. 0700.104-02, Appendix C, Revision 2 Page C-6 of 102
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Auxiliary Steam (AS), Unit 2 Section B: SNM Program Lines 2-AS-03: Remainder of Auxiliary Steam Line Number Size (in.)
Sus.
Cat.
Comments Reference Mod.
Ex. Crit.
P&ID No.
Line Description Text19:
2-AS-001-A 10 S
10" Aux. Steam Header Operating conditions unknown.
P&ID NC B192493, B192490, 192491 Text19:
2-AS-002 10 S
Aux. Steam Header from Service Boilers Operating conditions unknown.
P&ID NC 9321-F-2120 Text19:
2-AS-003 8
S Aux. Steam from #22 LH Boiler Operating conditions unknown.
P&ID NC 9321-F-2120 Text19:
2-AS-004 8
S Aux. Steam from #21 RH Boiler Operating conditions unknown.
P&ID NC 9321-F-2120 Text19:
2-AS-005 4
S Aux. Steam Drain to Deaerator Operating conditions unknown.
P&ID NC 9321-F-2120 Text19:
2-AS-006 1.5 S
FCV-1148 Bypass Line Operating conditions unknown.
P&ID NS 9321-F-2120 Text19:
2-AS-008 1.25 S
Steam to 21 and 22 Air Tempering Units Operating conditions unknown.
P&ID NS A209775 Text19:
2-AS-009 8
S Steam to AST-26 Operating conditions unknown.
P&ID NC 9321-F-2120 Text19:
2-AS-015 1.5 S
- 21 RH Boiler Drain Operating conditions unknown.
P&ID NS 9321-F-2120 Text19:
2-AS-016 1.5 S
- 22 LH Boiler Drain Operating conditions unknown.
P&ID NS 9321-F-2120 Text19:
2-AS-017 1.5 S
Boiler Drain Header to Blowdown Tank Operating conditions unknown.
P&ID NS 9321-F-2120 Text19:
2-AS-018 1
S RH Boiler #21 Atomizing Steam bleed-off line Operating conditions unknown.
P&ID NS 9321-F-2120 Text19:
2-AS-019 1
S LH Boiler #22 Atomizing Steam bleed-off line Operating conditions unknown.
P&ID NS 9321-F-2120 Text19:
2-AS-025 1
S Oil Separator Tank outlet Operating conditions unknown.
P&ID NS 9321-F-2120 Text19:
2-AS-026 1
S Oil Separator Tank outlet to Carbon Filter Tank Operating conditions unknown.
P&ID NS 9321-F-2120 Text19:
2-AS-027 1
S Oil Separator Tank outlet to Floor Drain Operating conditions unknown.
P&ID NS 9321-F-2120 Report No. 0700.104-02, Appendix C, Revision 2 Page C-7 of 102
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Auxiliary Steam (AS), Unit 2 Section B: SNM Program Lines 2-AS-03: Remainder of Auxiliary Steam Line Number Size (in.)
Sus.
Cat.
Comments Reference Mod.
Ex. Crit.
P&ID No.
Line Description Text19:
2-AS-030 2
S Steam to Water Heater Operating conditions unknown.
P&ID NS B192490 Text19:
2-AS-031 6
S Steam Header to Barge Steam Connections Operating conditions unknown.
P&ID NC B192490 Text19:
2-AS-032 4
S Steam to AS845 Operating conditions unknown.
P&ID NC B192490 Text19:
2-AS-033 1.5 S
Steam to AS840 Operating conditions unknown.
P&ID NS B192490 Text19:
2-AS-036 4
S Steam line to UH-1239 Operating conditions unknown.
P&ID NC B192490 Text19:
2-AS-037 1
S PRV-7343 Bypass Operating conditions unknown.
P&ID NS B192490 Text19:
2-AS-039 S
Steam to Screens Operating conditions unknown.
P&ID NS B192490 Text19:
2-AS-046 4
S Steam header to Service Boiler Feed Pump No. 13 Operating conditions unknown.
P&ID NC 192491 Text19:
2-AS-047 6
S Steam header to Carbon Filter Tanks Operating conditions unknown.
P&ID NC 192491 Text19:
2-AS-048 2
S Steam to Service Boiler Phosphate Mix Tanks and Continuous Heaters Operating conditions unknown.
P&ID NS 192491 Text19:
2-AS-051 2
S Steam to Service Boiler Feed Pump No. 13 Operating conditions unknown.
P&ID NS 192491 Text19:
2-AS-053 4
S Steam from Service Boiler Feed Pump No. 13 Operating conditions unknown.
P&ID NC 192491 Text19:
2-AS-054 8
S Steam from Service Boiler Feed Pump No. 13 to #10 Service Deaerator Operating conditions unknown.
P&ID NC 192491 Text19:
2-AS-055 8
S Steam from Service Boiler Feed Pump No. 13 to Atmospheric Vent header Operating conditions unknown.
P&ID NC 192491 Text19:
2-AS-057 10 S
Steam drain to #10 Service Deaerator via AS484 Operating conditions unknown.
P&ID NC 192491 Report No. 0700.104-02, Appendix C, Revision 2 Page C-8 of 102
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Auxiliary Steam (AS), Unit 2 Section B: SNM Program Lines 2-AS-03: Remainder of Auxiliary Steam Line Number Size (in.)
Sus.
Cat.
Comments Reference Mod.
Ex. Crit.
P&ID No.
Line Description Text19:
2-AS-058 4
S Steam to Heating and Ventilation Pressure Reducing Station Operating conditions unknown.
P&ID NC 192491 Text19:
2-AS-060 2
S Steam from Heating and Ventilation Pressure Reducing Station Operating conditions unknown.
P&ID NS 192491 Text19:
2-AS-070 3
S Steam header to Carbon Filter Tanks Operating conditions unknown.
P&ID NC 192491, B227209 Text19:
2-AS-073 2
S Header to Service Boiler Phosphate Mix Tanks Operating conditions unknown.
P&ID NS 192491 Text19:
2-AS-074 0.75 S
Steam to Service Boiler Phosphate Mix Tank No. 11 Operating conditions unknown.
P&ID NS 192491 Text19:
2-AS-075 0.75 S
Steam to Service Boiler Phosphate Mix Tank No. 12 Operating conditions unknown.
P&ID NS 192491 Text19:
2-AS-076 2
S Steam to Continuous Heaters via AS568 Operating conditions unknown.
P&ID NS 192491 Text19:
2-AS-077 2
S Steam to Continuous Heaters via AS112 Operating conditions unknown.
P&ID NS 192491 Text19:
2-AS-079 2
S Steam header to Continuous Heaters via AS568 Operating conditions unknown.
P&ID NS 192491 Text19:
2-AS-080 1
S Steam to Continuous Heater No. 11 Operating conditions unknown.
P&ID NS 192491 Text19:
2-AS-081 1
S Steam to Continuous Heater No. 12 Operating conditions unknown.
P&ID NS 192491 Text19:
2-AS-082-A 8
S Floor trench drain to cap Operating conditions unknown.
P&ID NC 192491 Text19:
2-AS-082-B 1.5 S
Floor trench drain downstream of cap Operating conditions unknown.
P&ID NS 192491 Text19:
2-AS-083 16 S
Aux Steam Vent to Atmosphere Operating conditions unknown.
P&ID NC 192491 Text19:
2-AS-087 3
S Steam to 21ACFT Operating conditions unknown.
P&ID NC B227209 Text19:
2-AS-088 3
S Steam to 22ACFT Operating conditions unknown.
P&ID NC B227209 Report No. 0700.104-02, Appendix C, Revision 2 Page C-9 of 102
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Auxiliary Steam (AS), Unit 2 Section B: SNM Program Lines 2-AS-03: Remainder of Auxiliary Steam Line Number Size (in.)
Sus.
Cat.
Comments Reference Mod.
Ex. Crit.
P&ID No.
Line Description Text19:
2-AS-091 0.75 S
Port Basin drain from Aux. Steam supply to ACFTs Operating conditions unknown.
P&ID NS B227209 Text19:
2-AS-093 1.5 S
PRV-5245 Bypass Operating conditions unknown.
P&ID NS B227209 Text19:
2-AS-096 4
S Aux. Steam to Flash Tank Operating conditions unknown.
P&ID NC 192491, B193201 Section C: Excluded Lines 2-AS-03: Remainder of Auxiliary Steam Line Number Size (in.)
Sus.
Cat.
Comments Reference FAC Ex. Crit.
P&ID No.
Line Description Text19:
2-AS-001-B 10 E
10" Aux. Steam Header Line capped.
P&ID ER B192493, 141718 Text19:
2-AS-013 0.75 E
- 21 RH Boiler Relief Valve Drain Valve shown closed on P&ID.
P&ID EI 9321-F-2120 Text19:
2-AS-014 0.75 E
- 22 LH Boiler Relief Valve Drain Valve shown closed on P&ID.
P&ID EI 9321-F-2120 Text19:
2-AS-020 1
E Aux. Steam to Fuel Oil Heaters Superheated Steam from steam drum SD No. 29.01 EQ 9321-F-2120 Text19:
2-AS-026-A 1
E Oil Separator Tank outlet line between floor drain line and Carbon Filter Tank Line Valve shown closed on P&ID P&ID EI 9321-F-2120 Text19:
2-AS-028 1
E Oil Separator Tank outlet line between floor drain line and Carbon Filter Tank Line Valve shown closed on P&ID.
P&ID EI 9321-F-2120 Text19:
2-AS-029 2.5 E
LH Boiler #22 Soot Blower Line Soot Blowers are used infrequently SD No. 29.01 EI 9321-F-2120 Text19:
2-AS-040 6
E Barge Steam connections header Valve shown closed on P&ID.
P&ID EI B192490 Text19:
2-AS-045 2
E Line to House Service Fuel Oil Heaters Downstream equipment retired in place.
P&ID ER B192490 Text19:
2-AS-056 3
E AS527 Bypass Relief Valve Line Relief valve normally closed P&ID EI 192491 Report No. 0700.104-02, Appendix C, Revision 2 Page C-10 of 102
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Auxiliary Steam (AS), Unit 2 Section C: Excluded Lines 2-AS-03: Remainder of Auxiliary Steam Line Number Size (in.)
Sus.
Cat.
Comments Reference FAC Ex. Crit.
P&ID No.
Line Description Text19:
2-AS-059 2.5 E
AS484 Bypass Line Valve shown closed on P&ID.
P&ID EI 192491 Text19:
2-AS-071 3
E Relief line from Steam header to Carbon Filter Tanks Relief valve normally closed P&ID EI B227209, 192491 Text19:
2-AS-072 10 E
Vent from Steam header to #10 Service Deaerator Valve normally closed.
Engineer Judgement; EI 192491 Text19:
2-AS-078 0.75 E
AS112 Bypass and Bypass Drain Valve shown closed on P&ID.
P&ID EI 192491 Text19:
2-AS-084 6
E Motor Gen. Unit No. 13 Turbine Drain line to Atmos. Vent Turbine retired in place.
P&ID ER 192491 Text19:
2-AS-086 6
E Aux. Steam to Steam Tracing in Fuel Oil Pump House Equipment retired in place P&ID ER B192490, B192493 Text19:
2-AS-094 4
E 21ACFT Aux. Steam Supply floor trench drain Valve normally closed.
P&ID EI B227209 Text19:
2-AS-095 4
E 22ACFT Aux. Steam Supply floor trench drain Valve shown closed on P&ID.
P&ID EI B227209 Report No. 0700.104-02, Appendix C, Revision 2 Page C-11 of 102
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Auxiliary Steam Traps (AST), Unit 2 Section B: SNM Program Lines 2-AST-01: Steam Trap Lines from Auxiliary Steam Lines Line Number Size (in.)
Sus.
Cat.
Comments Reference Mod.
Ex. Crit.
P&ID No.
Line Description Text19:
2-AST-002 0.75 S
Steam to and from AST-50 Operating conditions unknown.
P&ID NS A227780, A209775 Text19:
2-AST-006 1.5 S
Steam to Hot Water Heat Exchangers Operating conditions unknown.
P&ID NS 9321-F-2120 Text19:
2-AST-007 0.75 S
Steam to and from AS-1176 Operating conditions unknown.
P&ID NS 9321-F-2120 Text19:
2-AST-007-A 1
S Steam to Condensate Return via AST-35 Operating conditions unknown.
P&ID NS 9321-F-2120 Text19:
2-AST-009 2
S Hot Water Heat Exchangers Discharge Line Operating conditions unknown.
P&ID NS 9321-F-2120 Text19:
2-AST-010 4
S Condensate Return Header Operating conditions unknown.
P&ID NC 9321-F-2120 Text19:
2-AST-011 0.75 S
Steam to and from AS-1093 Operating conditions unknown.
P&ID NS 9321-F-2120 Text19:
2-AST-013 S
Steam Supply Drain to Condensate Return via AST-31 Operating conditions unknown.
P&ID NS 9321-F-2120 Text19:
2-AST-017 8
S Steam to AST-33 Operating conditions unknown.
P&ID NC A209775 Text19:
2-AST-019 1
S AST-33 Discharge Operating conditions unknown.
P&ID NS A209775 Text19:
2-AST-020 1
S Steam to AST-20 Operating conditions unknown.
P&ID NS A209775 Text19:
2-AST-021 1
S
- 21 Fuel Oil Heater heating steam outlet Operating conditions unknown.
P&ID NS 9321-F-2120 Text19:
2-AST-021-A 1
S AST-20 Discharge Operating conditions unknown.
P&ID NS A209775 Text19:
2-AST-022 1
S
- 22 Fuel Oil Heater heating steam outlet Operating conditions unknown.
P&ID NS 9321-F-2120 Text19:
2-AST-023 1
S
- 23 Fuel Oil Heater heating steam outlet Operating conditions unknown.
P&ID NS 9321-F-2120 Text19:
2-AST-024 1
S Fuel Oil heating steam outlet from steam traps to oil separator tank Operating conditions unknown.
P&ID NS 9321-F-2120 Text19:
2-AST-025 4
S Steam to AST-2 and 3 Operating conditions unknown.
P&ID NC A209775 Report No. 0700.104-02, Appendix C, Revision 2 Page C-12 of 102
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Auxiliary Steam Traps (AST), Unit 2 Section B: SNM Program Lines 2-AST-01: Steam Trap Lines from Auxiliary Steam Lines Line Number Size (in.)
Sus.
Cat.
Comments Reference Mod.
Ex. Crit.
P&ID No.
Line Description Text19:
2-AST-027 0.75 S
Steam to AST-6 Operating conditions unknown.
P&ID NS A209775 Text19:
2-AST-028 0.75 S
Steam to AST-7 Operating conditions unknown.
P&ID NS A209775 Text19:
2-AST-032 0.75 S
Steam to AST-4 Operating conditions unknown.
P&ID NS A209775 Text19:
2-AST-033 0.75 S
Steam to AST-5 Operating conditions unknown.
P&ID NS A209775 Text19:
2-AST-034 0.75 S
Steam to and from AS849 Operating conditions unknown.
P&ID NS B192490 Text19:
2-AST-035-A 0.75 S
AST-6 Discharge Operating conditions unknown.
P&ID NS A209775 Text19:
2-AST-036 0.75 S
AST-7 Discharge Operating conditions unknown.
P&ID NS A209775 Text19:
2-AST-037 1.5 S
AST-4 Discharge Operating conditions unknown.
P&ID NS A209775 Text19:
2-AST-038 0.75 S
Steam to and from UH-1238 Operating conditions unknown.
P&ID NS B192490 Text19:
2-AST-038-A 0.75 S
AST-5 Discharge Operating conditions unknown.
P&ID NS A209775 Text19:
2-AST-041 1
S Steam to and from AST-27 Operating conditions unknown.
P&ID NS B192490 Text19:
2-AST-042 1
S AST-27 Bypass Operating conditions unknown.
P&ID NS B192490 Text19:
2-AST-043 1
S Steam to and from AST-42 Operating conditions unknown.
P&ID NS B192490 Text19:
2-AST-044 1
S AST-42 Bypass Operating conditions unknown.
P&ID NS B192490 Text19:
2-AST-049-A 0.5 S
Steam to and from AST-38 Operating conditions unknown.
P&ID NS 192491 Text19:
2-AST-050-A 0.5 S
Steam to and from AST-37 Operating conditions unknown.
P&ID NS 192491 Text19:
2-AST-052 0.75 S
Steam to and from AST-45 Operating conditions unknown.
P&ID NS 192491 Text19:
2-AST-058 1
S AST-2 Discharge Operating conditions unknown.
P&ID NS A209775 Text19:
2-AST-059 1
S AST-3 Discharge Operating conditions unknown.
P&ID NS A209775 Text19:
2-AST-061 1
S Steam to and from AST-39 Operating conditions unknown.
P&ID NS 192491 Report No. 0700.104-02, Appendix C, Revision 2 Page C-13 of 102
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Auxiliary Steam Traps (AST), Unit 2 Section B: SNM Program Lines 2-AST-01: Steam Trap Lines from Auxiliary Steam Lines Line Number Size (in.)
Sus.
Cat.
Comments Reference Mod.
Ex. Crit.
P&ID No.
Line Description Text19:
2-AST-063 1
S Steam to and from AST-32 Operating conditions unknown.
P&ID NS 192491 Text19:
2-AST-065 1
S AST-32 and 39 drain to Cond. Return Header Operating conditions unknown.
P&ID NS 192491 Text19:
2-AST-066 2
S Steam to and from FP-1198 Operating conditions unknown.
P&ID NS 192491 Text19:
2-AST-067 2
S Steam to and from UH-1300 Operating conditions unknown.
P&ID NS 192491 Text19:
2-AST-069-A 3
S Stub to AST-30 and drain Operating conditions unknown.
P&ID NC 192491 Text19:
2-AST-069-B 1
S Steam to and from AST-30 Operating conditions unknown.
P&ID NS 192491 Section C: Excluded Lines 2-AST-01: Steam Trap Lines from Auxiliary Steam Lines Line Number Size (in.)
Sus.
Cat.
Comments Reference FAC Ex. Crit.
P&ID No.
Line Description Text19:
2-AST-003 0.75 E
AST-50 Bypass Line Valve shown closed on P&ID.
P&ID EI A227780 Text19:
2-AST-008 1
E AST-35 Bypass Line Valve shown closed on P&ID.
P&ID EI 9321-F-2120 Text19:
2-AST-012 1
E AST-26 Bypass Line Valve normally closed.
Engineer Judgement EI 9321-F-2120 Text19:
2-AST-014 E
AST-31 bypass line Valve shown closed on P&ID.
P&ID EI 9321-F-2120 Text19:
2-AST-018 1
E AST-33 Bypass Valve shown closed on P&ID.
P&ID EI A209775 Text19:
2-AST-035 0.75 E
Steam Trap Bypass Valve shown closed on P&ID.
P&ID EI B192490 Text19:
2-AST-049-B 0.5 E
AST-38 Bypass Valve shown closed on P&ID.
P&ID EI 192491 Text19:
2-AST-050-B 0.5 E
AST-37 Bypass Valve shown closed on P&ID.
P&ID EI 192491 Text19:
2-AST-062 E
AST-39 Bypass Valve shown closed on P&ID.
P&ID EI 192491 Report No. 0700.104-02, Appendix C, Revision 2 Page C-14 of 102
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Auxiliary Steam Traps (AST), Unit 2 Section C: Excluded Lines 2-AST-01: Steam Trap Lines from Auxiliary Steam Lines Line Number Size (in.)
Sus.
Cat.
Comments Reference FAC Ex. Crit.
P&ID No.
Line Description Text19:
2-AST-064 1
E AST-32 Bypass Valve shown closed on P&ID.
P&ID EI 192491 Text19:
2-AST-068 1
E UH-1301 Bypass Line Valve shown closed on P&ID.
P&ID EI 192491 Text19:
2-AST-069-C 1
E AST-30 Bypass Valve shown closed on P&ID.
P&ID EI 192491 Text19:
2-AST-069-D 0.75 E
Stub drain Low flow to floor drain P&ID EF 192491 Text19:
2-AST-085 0.75 E
Motor Gen. Unit No. 13 Turbine Drain line to and from steam trap Turbine retired in place.
P&ID ER 192491 Report No. 0700.104-02, Appendix C, Revision 2 Page C-15 of 102
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Steam Generator Blowdown (BD), Unit 2 Section B: SNM Program Lines 2-BD-01: Steam Generator Blowdown to Sample Coolers and Blowdown Tank Line Number Size (in.)
Sus.
Cat.
Comments Reference Mod.
Ex. Crit.
P&ID No.
Line Description Text19:
2-BD-001 2
S SG 21 Blowdown via MS-67-A Small bore piping with unknown conditions.
P&ID NS 9321-F-2729 Text19:
2-BD-002 2
S SG 21 Blowdown via MS-67-B Small bore piping with unknown conditions.
P&ID NS 9321-F-2729 Text19:
2-BD-003 2
S SG 22 Blowdown via MS-67-C Small bore piping with unknown conditions.
P&ID NS 9321-F-2729 Text19:
2-BD-004 2
S SG 22 Blowdown via MS-67-D Small bore piping with unknown conditions.
P&ID NS 9321-F-2729 Text19:
2-BD-005 2
S SG 23 Blowdown via MS-67-E Small bore piping with unknown conditions.
P&ID NS 9321-F-2729 Text19:
2-BD-006 2
S SG 23 Blowdown via MS-67-F Small bore piping with unknown conditions.
P&ID NS 9321-F-2729 Text19:
2-BD-007 2
S SG 24 Blowdown via MS-67-G Small bore piping with unknown conditions.
P&ID NS 9321-F-2729 Text19:
2-BD-008 2
S SG 24 Blowdown via MS-67-H Small bore piping with unknown conditions.
P&ID NS 9321-F-2729 Text19:
2-BD-009-A 2
S SG 21 Blowdown Upstream of Line Spec Change Small bore piping with unknown conditions.
P&ID NS 9321-F-2729 Text19:
2-BD-010-A 2
S SG 22 Blowdown Upstream of Line Spec Change Small bore piping with unknown conditions.
P&ID NS 9321-F-2729 Text19:
2-BD-011-A 2
S SG 23 Blowdown Upstream of Line Spec Change Small bore piping with unknown conditions.
P&ID NS 9321-F-2729 Text19:
2-BD-012-A 2
S SG 24 Blowdown Upstream of Line Spec Change Small bore piping with unknown conditions.
P&ID NS 9321-F-2729 Text19:
2-BD-017 1
S SG 23 1" Blowdown Line Small bore piping with unknown conditions.
P&ID NS 9321-F-2729 Text19:
2-BD-018 1
S SG 24 1" Blowdown Line Small bore piping with unknown conditions.
P&ID NS 9321-F-2729 Text19:
2-BD-019 18 S
Blowdown Tank vent to Atmosphere Operating conditions unknown.
P&ID NC 9321-F-2729 Report No. 0700.104-02, Appendix C, Revision 2 Page C-16 of 102
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Steam Generator Blowdown (BD), Unit 2 Section C: Excluded Lines 2-BD-01: Steam Generator Blowdown to Sample Coolers and Blowdown Tank Line Number Size (in.)
Sus.
Cat.
Comments Reference FAC Ex. Crit.
P&ID No.
Line Description Text19:
2-BD-009-B 2
E SG 21 Blowdown Downstream of Line Spec Change Stainless Steel Piping Pipe Spec EM 9321-F-2729 Text19:
2-BD-010-B 2
E SG 22 Blowdown Downstream of Line Spec Change Stainless Steel Piping Pipe Spec EM 9321-F-2729 Text19:
2-BD-011-B 2
E SG 23 Blowdown Downstream of Line Spec Change Stainless Steel Piping Pipe Spec EM 9321-F-2729 Text19:
2-BD-012-B 2
E SG 24 Blowdown Downstream of Line Spec Change Stainless Steel Piping Pipe Spec EM 9321-F-2729 Text19:
2-BD-013 0.75 E
SG 21 Blowdown to Sample Cooler Sample lines are SS CSI Document No.
0700.104.C.010 EM 9321-F-2729 Text19:
2-BD-014 0.75 E
SG 22 Blowdown to Sample Cooler Sample lines are SS CSI Document No.
0700.104.C.010 EM 9321-F-2729 Text19:
2-BD-015 0.75 E
SG 23 Blowdown to Sample Cooler Sample lines are SS CSI Document No.
0700.104.C.010 EM 9321-F-2729 Text19:
2-BD-016 0.75 E
SG 24 Blowdown to Sample Cooler Sample lines are SS CSI Document No.
0700.104.C.010 EM 9321-F-2729 Text19:
2-BD-020 E
Line to Sample Cooler from Blowdown Tank Vent via MS-1102 Sample lines are SS CSI Document No.
0700.104.C.010 EM 9321-F-2729 Text19:
2-BD-021 E
Line to Sample Cooler from Blowdown Tank Vent via MS-1103 Sample lines are SS CSI Document No.
0700.104.C.010 EM 9321-F-2729 Text19:
2-BD-022 E
Line to Sample Cooler from Blowdown Tank Vent via MS-1104 Sample lines are SS CSI Document No.
0700.104.C.010 EM 9321-F-2729 Report No. 0700.104-02, Appendix C, Revision 2 Page C-17 of 102
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Condensate Pump Discharge (CD), Unit 2 Section A: CHECWORKS Model Lines 2-CD-02: Condensate Lines Downstream of #22 Feedwater Heaters Line Number Size (in.)
Sus.
Cat.
Comments Reference P&ID No.
Line Description Text19:
2-CD-001 14 M
CD80A-1-FWH 22A to HEADER:
Condensate from FWH 22-A to Condensate Header PEPSE 9321-2018 Text19:
2-CD-002 14 M
CD80A-2-FWH 22B to HEADER:
Condensate from FWH 22-B to Condensate Header PEPSE 9321-2018 Text19:
2-CD-003 14 M
CD80A-3-FWH 22C to HEADER:
Condensate from FWH 22-C to Condensate Header PEPSE 9321-2018 Text19:
2-CD-004 20 M
CD80A-4-FWH 22 OUTLET HEADER: Condensate Header from FWHs 22-A and 22-B PEPSE 9321-2018 Text19:
2-CD-005 24 M
CD80A-5-FWH 22 to FWH 23 HEAD: Condensate Header to #23 FWHs PEPSE 9321-2018, A235307 Text19:
2-CD-006 24 M
CD80A-6-FWH 23 INLET HEADER:
Condensate Header to FWHs 23-A and 23-B PEPSE A235307 Text19:
2-CD-007 14 M
CD80A-7-HEADER to FWH 23A:
Condensate line to FWH 23-A PEPSE A235307 Text19:
2-CD-008 14 M
CD80A-8-HEADER to FWH 23B:
Condensate line to FWH 23-B PEPSE A235307 Text19:
2-CD-009 14 M
CD80A-9-HEADER to FWH 23C:
Condensate line to FWH 23-C PEPSE A235307 Text19:
2-CD-013 14 M
CD80-1-FWH 23A to FWH 24A:
Condensate line to FWH 24-A PEPSE A235307 Text19:
2-CD-014 14 M
CD80-2-FWH 23B to FWH 24B:
Condensate line to FWH 24-B PEPSE A235307 Report No. 0700.104-02, Appendix C, Revision 2 Page C-18 of 102
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Condensate Pump Discharge (CD), Unit 2 Section A: CHECWORKS Model Lines 2-CD-02: Condensate Lines Downstream of #22 Feedwater Heaters Line Number Size (in.)
Sus.
Cat.
Comments Reference P&ID No.
Line Description Text19:
2-CD-015 14 M
CD80-3-FWH 23C to FWH 24C:
Condensate line to FWH 24-C PEPSE A235307 Text19:
2-CD-016 14 M
CD81-1-FWH 24A to FWH 25A:
Condensate line to FWH 25-A PEPSE A235307 Text19:
2-CD-017 14 M
CD81-2-FWH 24B to FWH 25B:
Condensate line to FWH 25-B PEPSE A235307 Text19:
2-CD-018 14 M
CD81-3-FWH 24C to FWH 25C:
Condensate line to FWH 25-C PEPSE A235307 Text19:
2-CD-019 14 M
CD82-1-FWH 25A to HDR:
Condensate from FWH 25-A to Condensate Header PEPSE A235307 Text19:
2-CD-020 14 M
CD82-2-FWH 25B to HDR:
Condensate from FWH 25-B to Condensate Header PEPSE A235307 Text19:
2-CD-021 14 M
CD82-3-FWH 25C to HDR:
Condensate from FWH 25-C to Condensate Header PEPSE A235307 Text19:
2-CD-022 24 M
CD82-4-HDR 25BT to 25CT:
Condensate header from FWHs 25-A and 25-B PEPSE A235307 Text19:
2-CD-023 24 M
CD82-5-HDR 25CT to HDP OUT:
Condensate Header to BFPs Upstream of Heater Drain Pump inlet PEPSE A235307 Text19:
2-CD-024 30 M
CD83-1-HDR HDP to BFP21T:
Condensate Header to BFPs Downstream of Heater Drain Pump inlet PEPSE A235307 Text19:
2-CD-025 24 M
CD83-2-HDR to BFP21: Condensate from Header to BFP No. 21 PEPSE A235307 Report No. 0700.104-02, Appendix C, Revision 2 Page C-19 of 102
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Condensate Pump Discharge (CD), Unit 2 Section A: CHECWORKS Model Lines 2-CD-02: Condensate Lines Downstream of #22 Feedwater Heaters Line Number Size (in.)
Sus.
Cat.
Comments Reference P&ID No.
Line Description Text19:
2-CD-026 24 M
CD83-3-HDR to BFP22: Condensate from Header to BFP No. 22 PEPSE A235307 Section C: Excluded Lines 2-CD-02: Condensate Lines Downstream of #22 Feedwater Heaters Line Number Size (in.)
Sus.
Cat.
Comments Reference FAC Ex. Crit.
P&ID No.
Line Description Text19:
2-CD-010 1.5 E
CD-16 Bypass Line Valve shown closed on P&ID.
P&ID EI A235307 Text19:
2-CD-011 1.5 E
CD-16-1 Bypass Line Valve shown closed on P&ID.
P&ID EI A235307 Text19:
2-CD-012 1.5 E
CD-16-2 Bypass Line Valve shown closed on P&ID.
P&ID EI A235307 Text19:
2-CD-027 12 E
Feedwater Heater Bypass Line Valve shown closed on P&ID.
P&ID EI A235307 Text19:
2-CD-028 2
E CD-21 Bypass Line Valve shown closed on P&ID.
P&ID EI A235307 Text19:
2-CD-029 2
E CD-21-1 Bypass Line Valve shown closed on P&ID.
P&ID EI A235307 Report No. 0700.104-02, Appendix C, Revision 2 Page C-20 of 102
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Extraction Steam Traps (EST), Unit 2 Section B: SNM Program Lines 2-1EST-01: Extraction Steam Trap Headers to the Drains Collecting Tank Line Number Size (in.)
Sus.
Cat.
Comments Reference Mod.
Ex. Crit.
P&ID No.
Line Description Text19:
2-1EST-013-A 4
S Steam Trap Header from EST-1 and 1A Operating conditions unknown.
P&ID NC 9321-F-2031 Text19:
2-1EST-013-B 4
S Steam Trap Header from EST-1, 1A, 2, and 6 Operating conditions unknown.
P&ID NC 9321-F-2031 Text19:
2-1EST-014 6
S Main Extraction Steam Trap Header Operating conditions unknown.
P&ID NC 9321-F-2031 2-3EST-01: Steam Trap lines from Extraction Steam to the #23 FWHs Line Number Size (in.)
Sus.
Cat.
Comments Reference Mod.
Ex. Crit.
P&ID No.
Line Description Text19:
2-3EST-012-A 2
S Extraction Steam to EST-14 Operating conditions unknown.
P&ID NS 9321-F-2031 Text19:
2-3EST-012-B 2
S EST-14 to Steam Trap Header Operating conditions unknown.
P&ID NS 9321-F-2031 Text19:
2-3EST-013-A 0.75 S
Extraction Steam to EST-15 Operating conditions unknown.
P&ID NS 9321-F-2031 Text19:
2-3EST-013-B 0.75 S
Header from EST-15 to Steam Trap Header Operating conditions unknown.
P&ID NS 9321-F-2031 Text19:
2-3EST-014-A 0.75 S
Extraction Steam to EST-16 Operating conditions unknown.
P&ID NS 9321-F-2031 Text19:
2-3EST-014-B 0.75 S
Header from EST-16 to Steam Trap Header Operating conditions unknown.
P&ID NS 9321-F-2031 Text19:
2-3EST-015-A 2
S Extraction Steam to EST-17 Operating conditions unknown.
P&ID NS 9321-F-2031 Text19:
2-3EST-015-B 2
S EST-17 to Steam Trap Header Operating conditions unknown.
P&ID NS 9321-F-2031 Text19:
2-3EST-016-A 0.75 S
Extraction Steam to EST-18 Operating conditions unknown.
P&ID NS 9321-F-2031 Text19:
2-3EST-016-B 0.75 S
EST-18 to Steam Trap Header Operating conditions unknown.
P&ID NS 9321-F-2031 Text19:
2-3EST-017-A 0.75 S
Extraction Steam to EST-19 Operating conditions unknown.
P&ID NS 9321-F-2031 Text19:
2-3EST-017-B 0.75 S
EST-19 to Steam Trap Header Operating conditions unknown.
P&ID NS 9321-F-2031 Text19:
2-3EST-018-A 2
S Extraction Steam to EST-20 Operating conditions unknown.
P&ID NS 9321-F-2031 Report No. 0700.104-02, Appendix C, Revision 2 Page C-21 of 102
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Extraction Steam Traps (EST), Unit 2 Section B: SNM Program Lines 2-3EST-01: Steam Trap lines from Extraction Steam to the #23 FWHs Line Number Size (in.)
Sus.
Cat.
Comments Reference Mod.
Ex. Crit.
P&ID No.
Line Description Text19:
2-3EST-018-B 2
S EST-20 to Steam Trap Header Operating conditions unknown.
P&ID NS 9321-F-2031 Text19:
2-3EST-019-A 0.75 S
Extraction Steam to EST-21 Operating conditions unknown.
P&ID NS 9321-F-2031 Text19:
2-3EST-019-B 0.75 S
EST-21 to Steam Trap Header Operating conditions unknown.
P&ID NS 9321-F-2031 Text19:
2-3EST-020-A 0.75 S
Extraction Steam to EST-23 Operating conditions unknown.
P&ID NS 9321-F-2031 Text19:
2-3EST-020-B 0.75 S
EST-23 to Steam Trap Header Operating conditions unknown.
P&ID NS 9321-F-2031 2-4EST-01: Lines from Stm Traps to the Stm Trap Drains Header from Ext lines to #24 FWHs Line Number Size (in.)
Sus.
Cat.
Comments Reference Mod.
Ex. Crit.
P&ID No.
Line Description Text19:
2-4EST-001 0.75 S
EST-5 to Steam Trap Header Operating conditions unknown.
P&ID NS 9321-F-2031 Text19:
2-4EST-002 0.75 S
EST-6 to Steam Trap Header Operating conditions unknown.
P&ID NS 9321-F-2031 Text19:
2-4EST-003 0.75 S
EST-7 to Steam Trap Header Operating conditions unknown.
P&ID NS 9321-F-2031 Text19:
2-4EST-004 0.75 S
EST-8 to Steam Trap Header Operating conditions unknown.
P&ID NS 9321-F-2031 Text19:
2-4EST-005 0.75 S
EST-9 to Steam Trap Header Operating conditions unknown.
P&ID NS 9321-F-2031 Text19:
2-4EST-006 0.75 S
EST-10 to Steam Trap Header Operating conditions unknown.
P&ID NS 9321-F-2031 Text19:
2-4EST-007 0.75 S
EST-11 to Steam Trap Header Operating conditions unknown.
P&ID NS 9321-F-2031 Text19:
2-4EST-008 0.75 S
EST-12 to Steam Trap Header Operating conditions unknown.
P&ID NS 9321-F-2031 Text19:
2-4EST-009 0.75 S
EST-13 to Steam Trap Header Operating conditions unknown.
P&ID NS 9321-F-2031 2-5EST-01: Steam Trap lines from Extraction Steam to the #25 FWHs Line Number Size (in.)
Sus.
Cat.
Comments Reference Mod.
Ex. Crit.
P&ID No.
Line Description Text19:
2-5EST-040-A 0.75 S
Extraction steam to EST-4 Flow Conditions Unknown P&ID NS 9321-F-2031 Report No. 0700.104-02, Appendix C, Revision 2 Page C-22 of 102
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Extraction Steam Traps (EST), Unit 2 Section B: SNM Program Lines 2-5EST-01: Steam Trap lines from Extraction Steam to the #25 FWHs Line Number Size (in.)
Sus.
Cat.
Comments Reference Mod.
Ex. Crit.
P&ID No.
Line Description Text19:
2-5EST-040-B 0.75 S
EST-4 to Steam Trap Header Operating conditions unknown.
P&ID NS 9321-F-2031 2-6EST-01: Steam Trap lines from Extraction Steam to the #26 FWHs Line Number Size (in.)
Sus.
Cat.
Comments Reference Mod.
Ex. Crit.
P&ID No.
Line Description Text19:
2-6EST-015-A 2
S Extraction Steam to EST-1 Flow Conditions Unknown P&ID NS 9321-F-2031 Text19:
2-6EST-015-B 2
S Extraction Steam to EST-1A Flow Conditions Unknown P&ID NS 9321-F-2031 Text19:
2-6EST-015-C 2
S EST-1 to Steam Trap Header Operating conditions unknown.
P&ID NS 9321-F-2031 Text19:
2-6EST-015-D 2
S EST-1A to Steam Trap Header Operating conditions unknown.
P&ID NS 9321-F-2031 Text19:
2-6EST-016-A 0.75 S
Extraction Steam to EST-2 Flow Conditions Unknown P&ID NS 9321-F-2031 Text19:
2-6EST-016-B 0.75 S
EST-2 to Steam Trap Header Operating conditions unknown.
P&ID NS 9321-F-2031 Section C: Excluded Lines 2-3EST-01: Steam Trap lines from Extraction Steam to the #23 FWHs Line Number Size (in.)
Sus.
Cat.
Comments Reference FAC Ex. Crit.
P&ID No.
Line Description Text19:
2-3EST-012-C E
EST-14 Bypass Line Valve shown closed on P&ID.
P&ID EI 9321-F-2031 Text19:
2-3EST-013-C E
EST-15 Bypass Line Valve shown closed on P&ID.
P&ID EI 9321-F-2031 Text19:
2-3EST-014-C E
EST-16 Bypass Line Valve shown closed on P&ID.
P&ID EI 9321-F-2031 Text19:
2-3EST-015-C E
EST-17 Bypass Line Valve shown closed on P&ID.
P&ID EI 9321-F-2031 Text19:
2-3EST-016-C E
EST-18 Bypass Line Valve shown closed on P&ID.
P&ID EI 9321-F-2031 Text19:
2-3EST-017-C E
EST-19 Bypass Line Valve shown closed on P&ID.
P&ID EI 9321-F-2031 Report No. 0700.104-02, Appendix C, Revision 2 Page C-23 of 102
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Extraction Steam Traps (EST), Unit 2 Section C: Excluded Lines 2-3EST-01: Steam Trap lines from Extraction Steam to the #23 FWHs Line Number Size (in.)
Sus.
Cat.
Comments Reference FAC Ex. Crit.
P&ID No.
Line Description Text19:
2-3EST-018-C E
EST-20 Bypass Line Valve shown closed on P&ID.
P&ID EI 9321-F-2031 Text19:
2-3EST-019-C E
EST-21 Bypass Line Valve shown closed on P&ID.
P&ID EI 9321-F-2031 Text19:
2-3EST-020-C E
EST-23 Bypass Line Valve shown closed on P&ID.
P&ID EI 9321-F-2031 2-5EST-01: Steam Trap lines from Extraction Steam to the #25 FWHs Line Number Size (in.)
Sus.
Cat.
Comments Reference FAC Ex. Crit.
P&ID No.
Line Description Text19:
2-5EST-040-C E
EST-4 Bypass Line Valve shown closed on P&ID.
P&ID EI 9321-F-2031 2-6EST-01: Steam Trap lines from Extraction Steam to the #26 FWHs Line Number Size (in.)
Sus.
Cat.
Comments Reference FAC Ex. Crit.
P&ID No.
Line Description Text19:
2-6EST-015-E E
EST-1 Bypass Line Valve shown closed on P&ID.
P&ID EI 9321-F-2031 Text19:
2-6EST-015-F E
EST-1A Bypass Line Valve shown closed on P&ID.
P&ID EI 9321-F-2031 Text19:
2-6EST-016-C E
EST-2 Bypass Line Valve shown closed on P&ID.
P&ID EI 9321-F-2031 Report No. 0700.104-02, Appendix C, Revision 2 Page C-24 of 102
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Extraction Steam (EX), Unit 2 Section A: CHECWORKS Model Lines 2-1EX-01: LP Turb Ext Stm to #21 FWHs Line Number Size (in.)
Sus.
Cat.
Comments Reference P&ID No.
Line Description Text19:
2-1EX-001 26 M
ES?-1-1STPT ES TO FWH 21A: NE Extraction Steam to FWH 21A PEPSE 9321-F-2020 Text19:
2-1EX-002 26 M
NW Extraction Steam to FWH 21A PEPSE 9321-F-2020 Text19:
2-1EX-003 26 M
ES?-3-1STPT ES TO FWH 21A: SW Extraction Steam to FWH 21A PEPSE 9321-F-2020 Text19:
2-1EX-004 26 M
ES?-4-1STPT ES TO FWH 21A: SE Extraction Steam to FWH 21A PEPSE 9321-F-2020 Text19:
2-1EX-005 26 M
ES?-1-1STPT ES TO FWH 21B: NE Extraction Steam to FWH 21B PEPSE 9321-F-2020 Text19:
2-1EX-006 26 M
NW Extraction Steam to FWH 21B PEPSE 9321-F-2020 Text19:
2-1EX-007 26 M
ES?-3-1STPT ES TO FWH 21B: SW Extraction Steam to FWH 21B PEPSE 9321-F-2020 Text19:
2-1EX-008 26 M
ES?-4-1STPT ES TO FWH 21B: SE Extraction Steam to FWH 21B PEPSE 9321-F-2020 Text19:
2-1EX-009 26 M
ES?-1-1STPT ES TO FWH 21C: NE Extraction Steam to FWH 21C PEPSE 9321-F-2020 Text19:
2-1EX-010 26 M
NW Extraction Steam to FWH 21C PEPSE 9321-F-2020 Text19:
2-1EX-011 26 M
SW Extraction Steam to FWH 21C PEPSE 9321-F-2020 Text19:
2-1EX-012 26 M
ES?-4-1STPT ES TO FWH 21C: SE Extraction Steam to FWH 21C PEPSE 9321-F-2020 Report No. 0700.104-02, Appendix C, Revision 2 Page C-25 of 102
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Extraction Steam (EX), Unit 2 Section A: CHECWORKS Model Lines 2-2EX-01: LP Turbine Extraction Steam to #22 Feedwater Heaters Line Number Size (in.)
Sus.
Cat.
Comments Reference P&ID No.
Line Description Text19:
2-2EX-001-A 22 M
ES?-1-2NDPT ES TO FWH 22A: NE Extraction Steam to FWH 22A upstream of Exp. Joint PEPSE 9321-F-2020 Text19:
2-2EX-002-A 22 M
SW Extraction Steam to FWH 22A upstream of Exp. Joint PEPSE 9321-F-2020 Text19:
2-2EX-003-A 22 M
ES?-1-2NDPT ES TO FWH 22B: NE Extraction Steam to FWH 22B upstream of Exp. Joint PEPSE 9321-F-2020 Text19:
2-2EX-004-A 22 M
SW Extraction Steam to FWH 22B upstream of Exp. Joint PEPSE 9321-F-2020 Text19:
2-2EX-005-A 22 M
ES?-1-2NDPT ES TO FWH 22C: NE Extraction Steam to FWH 22C upstream of Exp. Joint PEPSE 9321-F-2020 Text19:
2-2EX-006-A 22 M
SW Extraction Steam to FWH 22C upstream of Exp. Joint PEPSE 9321-F-2020 2-3EX-01: Boiler Feed Pump Turbine Drains to Condensers Line Number Size (in.)
Sus.
Cat.
Comments Reference P&ID No.
Line Description Text19:
2-3EX-001 48 M
BFP #21 Drain to Condenser PEPSE A227780 Text19:
2-3EX-002 48 M
BFP #22 Drain to Condenser PEPSE A227780 Report No. 0700.104-02, Appendix C, Revision 2 Page C-26 of 102
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Extraction Steam (EX), Unit 2 Section A: CHECWORKS Model Lines 2-3EX-02: LP Turbine Extraction Steam to #23 Feedwater Heaters Line Number Size (in.)
Sus.
Cat.
Comments Reference P&ID No.
Line Description Text19:
2-3EX-003-A 20 M
ES1-1-3RDPT ES to FWH 23A: NW Extraction Steam to FWH 23A PEPSE 9321-F-2020 Text19:
2-3EX-003-B 20 M
ES1-2-3RDPT ES to FWH 23A: SE Extraction Steam to FWH 23A PEPSE 9321-F-2020 Text19:
2-3EX-003-C 28 M
Extraction Steam to FWH 23A Sections of this line were replaced with CrMo. These sections are modeled for continuity within the model.
PEPSE 9321-F-2020 Text19:
2-3EX-004 20 M
Extraction Steam to FWH 23A Sections of this line were replaced with CrMo. These sections are modeled for continuity within the model.
PEPSE 9321-F-2020 Text19:
2-3EX-005 20 M
Extraction Steam to FWH 23A Sections of this line were replaced with CrMo. These sections are modeled for continuity within the model.
PEPSE 9321-F-2020 Text19:
2-3EX-006-A 20 M
ES2-1-3RDPT ES to FWH 23B: NW Extraction Steam to FWH 23B PEPSE 9321-F-2020 Text19:
2-3EX-006-B 20 M
ES2-2-3RDPT ES to FWH 23B: SE Extraction Steam to FWH 23B PEPSE 9321-F-2020 Text19:
2-3EX-006-C 28 M
Extraction Steam to FWH 23B Sections of this line were replaced with CrMo. These sections are modeled for continuity within the model.
PEPSE 9321-F-2020 Text19:
2-3EX-007 20 M
Extraction Steam to FWH 23B Sections of this line were replaced with CrMo. These sections are modeled for continuity within the model.
PEPSE 9321-F-2020 Text19:
2-3EX-008 20 M
Extraction Steam to FWH 23B Sections of this line were replaced with CrMo. These sections are modeled for continuity within the model.
PEPSE 9321-F-2020 Text19:
2-3EX-009-A 20 M
ES3-1-3RDPT ES to FWH 23C: NW Extraction Steam to FWH 23C PEPSE 9321-F-2020 Report No. 0700.104-02, Appendix C, Revision 2 Page C-27 of 102
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Extraction Steam (EX), Unit 2 Section A: CHECWORKS Model Lines 2-3EX-02: LP Turbine Extraction Steam to #23 Feedwater Heaters Line Number Size (in.)
Sus.
Cat.
Comments Reference P&ID No.
Line Description Text19:
2-3EX-009-B 20 M
ES3-2-3RDPT ES to FWH 23C: SE Extraction Steam to FWH 23C PEPSE 9321-F-2020 Text19:
2-3EX-009-C 28 M
Extraction Steam to FWH 23C Sections of this line were replaced with CrMo. These sections are modeled for continuity within the model.
PEPSE 9321-F-2020 Text19:
2-3EX-010 20 M
Extraction Steam to FWH 23C Sections of this line were replaced with CrMo. These sections are modeled for continuity within the model.
PEPSE 9321-F-2020 Text19:
2-3EX-011 20 M
Extraction Steam to FWH 23C Sections of this line were replaced with CrMo. These sections are modeled for continuity within the model.
PEPSE 9321-F-2020 Section B: SNM Program Lines 2-3EX-01: Boiler Feed Pump Turbine Drains to Condensers Line Number Size (in.)
Sus.
Cat.
Comments Reference Mod.
Ex. Crit.
P&ID No.
Line Description Text19:
2-3EX-021 1.5 S
Continuous Drain from #21 Steam Generator Feed Pump Turbine drain to #21 Condenser Unknown conditions in drip pocket to condenser P&ID NC A227780 Text19:
2-3EX-022 1.5 S
Continuous Drain from #22 Steam Generator Feed Pump Turbine drain to #22 Condenser Unknown conditions in drip pocket to condenser P&ID NC A227780 2-5EX-01: HP Turbine Crossunder Piping Drip Pots to the Condenser Line Number Size (in.)
Sus.
Cat.
Comments Reference Mod.
Ex. Crit.
P&ID No.
Line Description Text19:
2-5EX-025-A 2
S Crossunder Piping leakoff from Moisture Preseparator A upstream of Pipe Spec Change Flow Conditions Unknown PEPSE NS A235308 Report No. 0700.104-02, Appendix C, Revision 2 Page C-28 of 102
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Extraction Steam (EX), Unit 2 Section B: SNM Program Lines 2-5EX-01: HP Turbine Crossunder Piping Drip Pots to the Condenser Line Number Size (in.)
Sus.
Cat.
Comments Reference Mod.
Ex. Crit.
P&ID No.
Line Description Text19:
2-5EX-026-A 2
S Crossunder Piping leakoff from Moisture Preseparator B upstream of Pipe Spec Change Flow Conditions Unknown PEPSE NS A235308 Text19:
2-5EX-027-A 2
S Crossunder Piping leakoff from Moisture Preseparator C upstream of Pipe Spec Change Flow Conditions Unknown PEPSE NS A235308 Text19:
2-5EX-028-A 2
S Crossunder Piping leakoff from Moisture Preseparator D upstream of Pipe Spec Change Flow Conditions Unknown PEPSE NS A235308 Text19:
2-5EX-117 1.5 S
HP Turbine Drain Operating conditions unknown.
P&ID NS B237145 Text19:
2-5EX-118 1.5 S
Crossunder piping leakoff to FCV-1156 Operating conditions unknown.
P&ID NS B237145 Text19:
2-5EX-119 1.5 S
Crossunder piping leakoff to FCV-1164 Operating conditions unknown.
P&ID NS B237145 Text19:
2-5EX-120 1.5 S
Crossunder piping leakoff to FCV-1157 Operating conditions unknown.
P&ID NS B237145 Text19:
2-5EX-121 1.5 S
Crossunder piping leakoff to FCV-1165 Operating conditions unknown.
P&ID NS B237145 Text19:
2-5EX-122 S
Crossunder piping to Moisture Separator Outlet Line Operating conditions unknown.
P&ID NS B237145 Text19:
2-5EX-123 S
Crossunder piping to Moisture Separator Outlet Line Operating conditions unknown.
P&ID NS B237145 Text19:
2-5EX-124 S
Crossunder piping to Moisture Separator Outlet Line Operating conditions unknown.
P&ID NS B237145 Text19:
2-5EX-125 S
Crossunder piping to Moisture Separator Outlet Line Operating conditions unknown.
P&ID NS B237145 Text19:
2-5EX-128 S
LP Leakoff Header to Gland Condenser Operating conditions unknown.
P&ID NC B237145, B237144 Report No. 0700.104-02, Appendix C, Revision 2 Page C-29 of 102
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Extraction Steam (EX), Unit 2 Section B: SNM Program Lines 2-5EX-01: HP Turbine Crossunder Piping Drip Pots to the Condenser Line Number Size (in.)
Sus.
Cat.
Comments Reference Mod.
Ex. Crit.
P&ID No.
Line Description Text19:
2-5EX-129 1.5 S
Crossunder piping leakoff to FCV1154 Operating conditions unknown.
P&ID NS B237145 2-6EX-01: HP Turbine Extraction Steam to #26 Feedwater Heaters Line Number Size (in.)
Sus.
Cat.
Comments Reference Mod.
Ex. Crit.
P&ID No.
Line Description Text19:
2-6EX-001-A 12 S
ES8-1-6THPT ES to HDR: HP Turbine Extraction Nozzle to #26 FWHs.
The nozzle is the only susceptible component in this line.
SFA Model NL 9321-F-2020 Text19:
2-6EX-002-A 12 S
ES8-2-6THPT ES to HDR: HP Turbine Extraction Nozzle to #26 FWHs.
The nozzle is the only susceptible component in this line.
SFA Model NL 9321-F-2020 Text19:
2-6EX-006-B 12 S
ES8-7-6THPT ESHDR to FWH 26A:
Extraction Steam Inlet Nozzle to FWH 26A.
The nozzle is the only susceptible component in this line.
SFA Model NL 9321-F-2020 Text19:
2-6EX-008-B 12 S
ES8-6-6THPT ESHDR to FWH 26B:
Extraction Steam Inlet Nozzle to FWH 26B.
The nozzle is the only susceptible component in this line.
SFA Model NL 9321-F-2020 Text19:
2-6EX-010-B 12 S
ES8-4-6THPT ESHDR to FWH 26C:
Extraction Steam Inlet Nozzle to FWH 26C.
The nozzle is the only susceptible component in this line.
SFA Model NL 9321-F-2020 Section C: Excluded Lines 2-2EX-01: LP Turbine Extraction Steam to #22 Feedwater Heaters Line Number Size (in.)
Sus.
Cat.
Comments Reference FAC Ex. Crit.
P&ID No.
Line Description Text19:
2-2EX-001-B 22 E
ES?-1-2NDPT ES TO FWH 22A: NE Extraction Steam to FWH 22A downstream of Exp. Joint This section of piping was replaced with CrMo in 2R18 Replacement History EM 9321-F-2020 Report No. 0700.104-02, Appendix C, Revision 2 Page C-30 of 102
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Extraction Steam (EX), Unit 2 Section C: Excluded Lines 2-2EX-01: LP Turbine Extraction Steam to #22 Feedwater Heaters Line Number Size (in.)
Sus.
Cat.
Comments Reference FAC Ex. Crit.
P&ID No.
Line Description Text19:
2-2EX-002-B 22 E
SW Extraction Steam to FWH 22A downstream of Exp. Joint This section of piping was replaced with CrMo in 2R18 Replacement History EM 9321-F-2020 Text19:
2-2EX-003-B 22 E
ES?-1-2NDPT ES TO FWH 22B: NE Extraction Steam to FWH 22B downstream of Exp. Joint This section of piping was replaced with CrMo in 2R18 Replacement History EM 9321-F-2020 Text19:
2-2EX-004-B 22 E
SW Extraction Steam to FWH 22B downstream of Exp. Joint This section of piping was replaced with CrMo in 2R18 Replacement History EM 9321-F-2020 Text19:
2-2EX-005-B 22 E
ES?-1-2NDPT ES TO FWH 22C: NE Extraction Steam to FWH 22C downstream of Exp. Joint Piping is CrMo.
2-2EX-006-B 22 E
SW Extraction Steam to FWH 22C downstream of Exp. Joint Piping is CrMo.
P&ID EM 9321-F-2020 2-5EX-01: HP Turbine Crossunder Piping Drip Pots to the Condenser Line Number Size (in.)
Sus.
Cat.
Comments Reference FAC Ex. Crit.
P&ID No.
Line Description Text19:
2-5EX-025-B 2
E Crossunder Piping leakoff from Moisture Preseparator A downstream of Pipe Spec Change Line is stainless steel.
2-5EX-026-B 2
E Crossunder Piping leakoff from Moisture Preseparator B downstream of Pipe Spec Change Line is stainless steel.
2-5EX-027-B 2
E Crossunder Piping leakoff from Moisture Preseparator C downstream of Pipe Spec Change Line is stainless steel.
2-5EX-028-B 2
E Crossunder Piping leakoff from Moisture Preseparator D downstream of Pipe Spec Change Line is stainless steel.
P&ID EM A235308 Report No. 0700.104-02, Appendix C, Revision 2 Page C-31 of 102
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Extraction Steam (EX), Unit 2 Section C: Excluded Lines 2-5EX-01: HP Turbine Crossunder Piping Drip Pots to the Condenser Line Number Size (in.)
Sus.
Cat.
Comments Reference FAC Ex. Crit.
P&ID No.
Line Description Text19:
2-5EX-029 2
E Crossunder Piping Leakoff Header from Moisture Preseparators A and B Line is stainless steel.
2-5EX-030 2
E Crossunder Piping Leakoff Header from Moisture Preseparators C and D Line is stainless steel.
2-5EX-115 1.5 E
HP Turbine Drain from Far Side Inlet Piping is SS P&ID EM B237145 Text19:
2-5EX-116 1.5 E
HP Turbine Drain from Near Side Inlet Piping is SS P&ID EM B237145 Text19:
2-5EX-126 1.5 E
Crossunder piping leakoff to 2-MS-200 Piping is SS P&ID EM B237145 Text19:
2-5EX-127 1.5 E
Balancing line leakoff to 2-MS-201 Piping is SS P&ID EM B237145 2-5EX-03: Extraction Steam from Separating Tanks to #25 Feedwater Heaters Line Number Size (in.)
Sus.
Cat.
Comments Reference FAC Ex. Crit.
P&ID No.
Line Description Text19:
2-5EX-031 28 E
Extraction Steam Header to #25 Heaters Line is stainless steel.
SFA Model EM 9321-F-2020 Text19:
2-5EX-032 1.5 E
5EX-1 Bypass Line Valve shown closed on P&ID.
P&ID EI 9321-F-2020 Text19:
2-5EX-033 28 E
ES7-3-5THPT ESHDR 25CT to BT:
Extraction Steam Header to FWH 25A and 25B Line is stainless steel.
SFA Model EM 9321-F-2020 Text19:
2-5EX-034 18 E
ES7-5-5THPT ESHDR to FWH 25A:
Extraction Steam Line to FWH 25A Line is stainless steel.
SFA Model EM 9321-F-2020 Text19:
2-5EX-035 18 E
ES7-4-5THPT ESHDR to FWH 25B:
Extraction Steam Line to FWH 25B Line is stainless steel.
SFA Model EM 9321-F-2020 Text19:
2-5EX-036 18 E
ES7-2-5THPT ESHDR to FWH 25C:
Extraction Steam Line to FWH 25C Line is stainless steel.
SFA Model EM 9321-F-2020 Text19:
2-5EX-037 1.5 E
5EX-5 Bypass Line Valve shown closed on P&ID.
P&ID EI 9321-F-2020 Report No. 0700.104-02, Appendix C, Revision 2 Page C-32 of 102
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Extraction Steam (EX), Unit 2 Section C: Excluded Lines 2-5EX-03: Extraction Steam from Separating Tanks to #25 Feedwater Heaters Line Number Size (in.)
Sus.
Cat.
Comments Reference FAC Ex. Crit.
P&ID No.
Line Description Text19:
2-5EX-038 1.5 E
5EX-5-1 Bypass Line Valve shown closed on P&ID.
P&ID EI 9321-F-2020 Text19:
2-5EX-039 1.5 E
5EX-5-2 Bypass Line Valve shown closed on P&ID.
P&ID EI 9321-F-2020 2-6EX-01: HP Turbine Extraction Steam to #26 Feedwater Heaters Line Number Size (in.)
Sus.
Cat.
Comments Reference FAC Ex. Crit.
P&ID No.
Line Description Text19:
2-6EX-001-B 12 E
ES8-1-6THPT ES to HDR: HP Turbine Extraction Line to #26 FWHs.
Components in this line have been clad with Stainless Steel.
SFA Model EM 9321-F-2020 Text19:
2-6EX-002-B 12 E
ES8-2-6THPT ES to HDR: HP Turbine Extraction Line to #26 FWHs.
Components in this line have been clad with Stainless Steel.
SFA Model EM 9321-F-2020 Text19:
2-6EX-003 18 E
ES8-3-6THPT ESHDR to FWH 26:
HP Turbine Extraction Line to #26 FWHs.
Components in this line have been clad with Stainless Steel.
SFA Model EM 9321-F-2020 Text19:
2-6EX-004 18 E
ES8-5-6THPT ESHDR 26CT to BT:
Extraction Steam header to FWH 26A and 26B Components in this line have been clad with Stainless Steel.
SFA Model EM 9321-F-2020 Text19:
2-6EX-005 12 E
ES8-7-6THPT ESHDR to FWH 26A:
Extraction Steam to FWH 26A Upstream of VCD tie-in.
Components in this line have been clad with Stainless Steel.
SFA Model EM 9321-F-2020 Text19:
2-6EX-006-A 12 E
ES8-7-6THPT ESHDR to FWH 26A:
Extraction Steam to FWH 26A Downstream of VCD tie-in.
Components in this line have been clad with Stainless Steel.
SFA Model EM 9321-F-2020 Text19:
2-6EX-007 12 E
ES8-6-6THPT ESHDR to FWH 26B:
Extraction Steam to FWH 26B Upstream of VCD tie-in.
Components in this line have been clad with Stainless Steel.
SFA Model EM 9321-F-2020 Text19:
2-6EX-008-A 12 E
ES8-6-6THPT ESHDR to FWH 26B:
Extraction Steam to FWH 26B Downstream of VCD tie-in.
Components in this line have been clad with Stainless Steel.
SFA Model EM 9321-F-2020 Report No. 0700.104-02, Appendix C, Revision 2 Page C-33 of 102
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Extraction Steam (EX), Unit 2 Section C: Excluded Lines 2-6EX-01: HP Turbine Extraction Steam to #26 Feedwater Heaters Line Number Size (in.)
Sus.
Cat.
Comments Reference FAC Ex. Crit.
P&ID No.
Line Description Text19:
2-6EX-009 12 E
ES8-4-6THPT ESHDR to FWH 26C:
Extraction Steam to FWH 26C Upstream of VCD tie-in.
Components in this line have been clad with Stainless Steel.
SFA Model EM 9321-F-2020 Text19:
2-6EX-010-A 12 E
ES8-4-6THPT ESHDR to FWH 26C:
Extraction Steam to FWH 26C Downstream of VCD tie-in.
Components in this line have been clad with Stainless Steel.
SFA Model EM 9321-F-2020 Text19:
2-6EX-011 1
E 6EX-6 Bypass Line Valve shown closed on P&ID.
P&ID EI 9321-F-2020 Text19:
2-6EX-012 1
E 6EX-6-1 Bypass Line Valve shown closed on P&ID.
P&ID EI 9321-F-2020 Text19:
2-6EX-013 1
E 6EX-6-2 Bypass Line Valve shown closed on P&ID.
P&ID EI 9321-F-2020 Text19:
2-6EX-014 1.5 E
6EX-1 Bypass Line Valve shown closed on P&ID.
P&ID EI 9321-F-2020 Text19:
2-6EX-017 1
E FWH 26A Extraction Steam Line Drain Valve shown closed on P&ID.
P&ID EI 9321-F-2020 Text19:
2-6EX-018 1
E FWH 26B Extraction Steam Line Drain Valve shown closed on P&ID.
P&ID EI 9321-F-2020 Text19:
2-6EX-019 1.5 E
FWH 26A and 26B Extraction Steam Line Drain Header Valve shown closed on P&ID.
P&ID EI 9321-F-2020 Text19:
2-6EX-020 1
E FWH 26C Extraction Steam Line Drain Valve shown closed on P&ID.
P&ID EI 9321-F-2020 Text19:
2-6EX-021 2
E
- 26 FWH Extraction Steam Line Drain Header Valve shown closed on P&ID.
P&ID EI 9321-F-2020 Report No. 0700.104-02, Appendix C, Revision 2 Page C-34 of 102
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Main Feed Water (FW), Unit 2 Section A: CHECWORKS Model Lines 2-FW-01: Feedwater Lines from the Boiler Feed Pumps to the Steam Generators Line Number Size (in.)
Sus.
Cat.
Comments Reference P&ID No.
Line Description Text19:
2-FW-001 20 M
FW71-1-BFP21 DISCH to HDR:
BFP No. 21 Discharge Upstream of Recirc Line PEPSE 9321-F-2019 Text19:
2-FW-002 20 M
FW71-1-BFP21 DISCH to HDR:
BFP No. 21 Discharge Downstream of Recirc Line PEPSE 9321-F-2019 Text19:
2-FW-003 20 M
FW72-1-BFP22 DISCH to HDR:
BFP No. 22 Discharge Upstream of Recirc Line PEPSE 9321-F-2019 Text19:
2-FW-004 20 M
FW72-1-BFP22 DISCH to HDR:
BFP No. 22 Discharge Downstream of Recirc Line PEPSE 9321-F-2019 Text19:
2-FW-005 30 M
FW73-1-BFPHDR to FWH26ABC:
BFP Discharge Header to #26 FWHs Upstream of High Pr. FWH Bypass Line PEPSE 9321-F-2019 Text19:
2-FW-006 30 M
FW73-2-BFPHDR to FWH26ABC:
BFP Discharge Header to #26 FWHs Downstream of High Pr. FWH Bypass Line PEPSE 9321-F-2019 Text19:
2-FW-007 30 M
FW73-4-BFPHDR to FWH26ABC:
BFP Discharge Header to FWHs 26A and 26B PEPSE 9321-F-2019 Text19:
2-FW-008 18 M
FW73-6-BFPHDR to FWH26A:
Feedwater to FWH 26A PEPSE 9321-F-2019 Text19:
2-FW-009 18 M
FW73-5-BFPHDR to FWH26B:
Feedwater to FWH 26B PEPSE 9321-F-2019 Text19:
2-FW-010 18 M
FW73-3-BFPHDR to FWH26C:
Feedwater to FWH 26C PEPSE 9321-F-2019 Report No. 0700.104-02, Appendix C, Revision 2 Page C-35 of 102
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Main Feed Water (FW), Unit 2 Section A: CHECWORKS Model Lines 2-FW-01: Feedwater Lines from the Boiler Feed Pumps to the Steam Generators Line Number Size (in.)
Sus.
Cat.
Comments Reference P&ID No.
Line Description Text19:
2-FW-020 18 M
FW74-1-FWH26A to DISHDR:
Feedwater from FWH 26A PEPSE 9321-F-2019 Text19:
2-FW-021 18 M
FW74-2-FWH26B to DISHDR:
Feedwater from FWH 26B PEPSE 9321-F-2019 Text19:
2-FW-022 18 M
FW74-4-FWH26C to DISHDR:
Feedwater from FWH 26C PEPSE 9321-F-2019 Text19:
2-FW-023 30 M
FW74-3-FWH26 to DISHDR:
Feedwater Header from FWH 26A and 26B PEPSE 9321-F-2019 Text19:
2-FW-024 30 M
FW74-5-FWH26 to DISHDR: #26 FWH Feedwater Discharge Header Upstream of Bypass Line PEPSE 9321-F-2019 Text19:
2-FW-025 30 M
FW74-5-FWH26 to DISHDR: #26 FWH Feedwater Discharge Header Downstream of Bypass Line PEPSE 9321-F-2019 Text19:
2-FW-026 30 M
FW76-2-DISHDR to SG22:
Feedwater Header to Steam Generators PEPSE 9321-F-2019 Text19:
2-FW-027 30 M
FW76-2-DISHDR to SG22:
Feedwater Header to Steam Generators PEPSE 9321-F-2019 Text19:
2-FW-028 30 M
FW77-2-DISHDR to SG24:
Feedwater Header to Steam Generators PEPSE 9321-F-2019 Text19:
2-FW-029 30 M
FW77-2-DISHDR to SG24:
Feedwater Header to Steam Generators PEPSE 9321-F-2019 Text19:
2-FW-030 30 M
FW78-1-DISHDR to SG23:
Feedwater Header to Steam Generators PEPSE 9321-F-2019 Report No. 0700.104-02, Appendix C, Revision 2 Page C-36 of 102
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Main Feed Water (FW), Unit 2 Section A: CHECWORKS Model Lines 2-FW-01: Feedwater Lines from the Boiler Feed Pumps to the Steam Generators Line Number Size (in.)
Sus.
Cat.
Comments Reference P&ID No.
Line Description Text19:
2-FW-031 30 M
FW78-1-DISHDR to SG23:
Feedwater Header to Steam Generators PEPSE 9321-F-2019 Text19:
2-FW-032 18 M
FW75-1-DISHDR to SG21:
Feedwater to 21 Steam Generator PEPSE 9321-F-2019 Text19:
2-FW-034 18 M
FW76-1-DISHDR to SG22:
Feedwater to 22 Steam Generator PEPSE 9321-F-2019 Text19:
2-FW-036 18 M
FW77-1-DISHDR to SG24:
Feedwater to 24 Steam Generator PEPSE 9321-F-2019 Text19:
2-FW-038 18 M
FW78-1-DISHDR to SG23:
Feedwater to 23 Steam Generator PEPSE 9321-F-2019 Text19:
2-FW-058-A 18 M
FW75-1-DISHDR to SG21:
Feedwater to 21 Steam Generator Upstream of BFD-6 PEPSE 9321-F-2019 Text19:
2-FW-058-B 18 M
FW75-1-DISHDR to SG21:
Feedwater to 21 Steam Generator Downstream of BFD-6 Operating pressure from PEPSE model exceeds design pressure.
PEPSE 9321-F-2019 Text19:
2-FW-059-A 18 M
FW76-1-DISHDR to SG22:
Feedwater to 22 Steam Generator Upstream of BFD-6-1 PEPSE 9321-F-2019 Text19:
2-FW-059-B 18 M
FW76-1-DISHDR to SG22:
Feedwater to 22 Steam Generator Downstream of BFD-6-1 Operating pressure from PEPSE model exceeds design pressure.
PEPSE 9321-F-2019 Text19:
2-FW-060-A 18 M
FW77-1-DISHDR to SG24:
Feedwater to 24 Steam Generator Upstream of BFD-6-3 PEPSE 9321-F-2019 Text19:
2-FW-060-B 18 M
FW77-1-DISHDR to SG24:
Feedwater to 24 Steam Generator Downstream of BFD-6-3 Operating pressure from PEPSE model exceeds design pressure.
PEPSE 9321-F-2019 Report No. 0700.104-02, Appendix C, Revision 2 Page C-37 of 102
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Main Feed Water (FW), Unit 2 Section A: CHECWORKS Model Lines 2-FW-01: Feedwater Lines from the Boiler Feed Pumps to the Steam Generators Line Number Size (in.)
Sus.
Cat.
Comments Reference P&ID No.
Line Description Text19:
2-FW-061-A 18 M
FW78-1-DISHDR to SG23:
Feedwater to 23 Steam Generator Upstream of BFD-6-2 PEPSE 9321-F-2019 Text19:
2-FW-061-B 18 M
FW78-1-DISHDR to SG23:
Feedwater to 23 Steam Generator Downstream of BFD-6-2 Operating pressure from PEPSE model exceeds design pressure.
PEPSE 9321-F-2019 Section B: SNM Program Lines 2-FW-01: Feedwater Lines from the Boiler Feed Pumps to the Steam Generators Line Number Size (in.)
Sus.
Cat.
Comments Reference Mod.
Ex. Crit.
P&ID No.
Line Description Text19:
2-FW-031-A 30 S
Feedwater Header to Steam Generators downstream of Main Line to SG 23 Flow Conditions Unknown P&ID NC 9321-F-2019 Text19:
2-FW-062 0.75 S
Feedwater to Sampling Upstream of BFD-1138 Operating conditions unknown.
P&ID NS 9321-F-2019 2-FW-03: Boiler Feed Pump Recirc Lines to the Drains Collecting Tank Line Number Size (in.)
Sus.
Cat.
Comments Reference Mod.
Ex. Crit.
P&ID No.
Line Description Text19:
2-FW-063 6
S BFP No. 21 Recirc to Drains Collecting Tank Flow Conditions Unknown P&ID NC 9321-F-2019 Text19:
2-FW-064 6
S BFP No. 22 Recirc to Drains Collecting Tank Flow Conditions Unknown P&ID NC 9321-F-2019 Report No. 0700.104-02, Appendix C, Revision 2 Page C-38 of 102
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Main Feed Water (FW), Unit 2 Section C: Excluded Lines 2-FW-01: Feedwater Lines from the Boiler Feed Pumps to the Steam Generators Line Number Size (in.)
Sus.
Cat.
Comments Reference FAC Ex. Crit.
P&ID No.
Line Description Text19:
2-FW-013 1
E BFD-2-21 Bypass Line Valve shown closed on P&ID.
P&ID EI 9321-F-2019 Text19:
2-FW-014 1
E BFD-2-22 Bypass Line Valve shown closed on P&ID.
P&ID EI 9321-F-2019 Text19:
2-FW-015 18 E
High Pr. FWH Bypass Line Valve normally closed.
CSI Doc# 0700.104.C.8 EI 9321-F-2019 Text19:
2-FW-016 1.5 E
BFD-8 Bypass Line Valve shown closed on P&ID.
P&ID EI 9321-F-2019 Text19:
2-FW-017 1.5 E
BFD-3 Bypass Line Valve shown closed on P&ID.
P&ID EI 9321-F-2019 Text19:
2-FW-018 1.5 E
BFD-3-1 Bypass Line Valve shown closed on P&ID.
P&ID EI 9321-F-2019 Text19:
2-FW-019 1.5 E
BFD-3-2 Bypass Line Valve shown closed on P&ID.
P&ID EI 9321-F-2019 Text19:
2-FW-033 6
E Feedwater min-flow line to 21 Steam Generator Piping Replaced with SS Previous SSE EM 9321-F-2019 Text19:
2-FW-035 6
E Feedwater min-flow line to 22 Steam Generator Piping Replaced with SS Previous SSE EM 9321-F-2019 Text19:
2-FW-037 6
E Feedwater min-flow line to 24 Steam Generator Piping Replaced with SS Previous SSE EM 9321-F-2019 Text19:
2-FW-039 6
E Feedwater min-flow line to 23 Steam Generator Piping Replaced with SS Previous SSE EM 9321-F-2019 Text19:
2-FW-040 0.75 E
Drain A from SG 23 Feedwater min-flow line.
Valve shown closed on P&ID.
P&ID EI 9321-F-2019 Text19:
2-FW-041 0.75 E
Drain A from SG 24 Feedwater min-flow line.
Valve shown closed on P&ID.
P&ID EI 9321-F-2019 Text19:
2-FW-042 0.75 E
Drain A header from SG 23 & 24 Feedwater min-flow lines.
Valve shown closed on P&ID.
P&ID EI 9321-F-2019 Text19:
2-FW-043 0.75 E
Drain A from SG 22 Feedwater min-flow line.
Valve shown closed on P&ID.
P&ID EI 9321-F-2019 Text19:
2-FW-044 0.75 E
Drain A header from SG 22, 23 & 24 Feedwater min-flow lines.
Valve shown closed on P&ID.
P&ID EI 9321-F-2019 Report No. 0700.104-02, Appendix C, Revision 2 Page C-39 of 102
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Main Feed Water (FW), Unit 2 Section C: Excluded Lines 2-FW-01: Feedwater Lines from the Boiler Feed Pumps to the Steam Generators Line Number Size (in.)
Sus.
Cat.
Comments Reference FAC Ex. Crit.
P&ID No.
Line Description Text19:
2-FW-045 0.75 E
Drain A from SG 21 Feedwater min-flow line.
Valve shown closed on P&ID.
P&ID EI 9321-F-2019 Text19:
2-FW-046 0.75 E
Drain A header from Feedwater min-flow lines.
Valve shown closed on P&ID.
P&ID EI 9321-F-2019 Text19:
2-FW-047 0.75 E
Drain B from SG 23 Feedwater min-flow line.
Valve shown closed on P&ID.
P&ID EI 9321-F-2019 Text19:
2-FW-048 0.75 E
Drain B from SG 24 Feedwater min-flow line.
Valve shown closed on P&ID.
P&ID EI 9321-F-2019 Text19:
2-FW-049 0.75 E
Drain B header from SG 23 & 24 Feedwater min-flow lines.
Valve shown closed on P&ID.
P&ID EI 9321-F-2019 Text19:
2-FW-050 0.75 E
Drain B from SG 22 Feedwater min-flow line.
Valve shown closed on P&ID.
P&ID EI 9321-F-2019 Text19:
2-FW-051 0.75 E
Drain B header from SG 22, 23 & 24 Feedwater min-flow lines.
Valve shown closed on P&ID.
P&ID EI 9321-F-2019 Text19:
2-FW-052 0.75 E
Drain B from SG 21 Feedwater min-flow line.
Valve shown closed on P&ID.
P&ID EI 9321-F-2019 Text19:
2-FW-053 0.75 E
Drain B header from Feedwater min-flow lines.
Valve shown closed on P&ID.
P&ID EI 9321-F-2019 Text19:
2-FW-054 1.5 E
BFD-5 Bypass Line Valve shown closed on P&ID.
P&ID EI 9321-F-2019 Text19:
2-FW-055 1.5 E
BFD-5-1 Bypass Line Valve shown closed on P&ID.
P&ID EI 9321-F-2019 Text19:
2-FW-056 1.5 E
BFD-5-3 Bypass Line Valve shown closed on P&ID.
P&ID EI 9321-F-2019 Text19:
2-FW-057 1.5 E
BFD-5-2 Bypass Line Valve shown closed on P&ID.
P&ID EI 9321-F-2019 Report No. 0700.104-02, Appendix C, Revision 2 Page C-40 of 102
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Gland Sealing Steam (GS), Unit 2 Section B: SNM Program Lines 2-GS-01: Gland Steam to and from HP, LP, and BFP Turbines Line Number Size (in.)
Sus.
Cat.
Comments Reference Mod.
Ex. Crit.
P&ID No.
Line Description Text19:
2-GS-001 12 S
Gland Seal Steam Header to HP and LP Turbines Operating conditions unknown.
P&ID NC A235308 Text19:
2-GS-002 10 S
Gland Seal to HP Turbine Operating conditions unknown.
P&ID NC A235308 Text19:
2-GS-003 10 S
Gland Seal to HP Turbine Operating conditions unknown.
P&ID NC A235308 Text19:
2-GS-004 6
S Gland Seal to LP Turbine 21 Operating conditions unknown.
P&ID NC A235308 Text19:
2-GS-005 2
S Gland Seal to LP Turbine 21 Operating conditions unknown.
P&ID NC A235308 Text19:
2-GS-006 6
S Gland Seal to LP Turbine 21 Operating conditions unknown.
P&ID NC A235308 Text19:
2-GS-007 2
S Gland Seal to LP Turbine 21 Operating conditions unknown.
P&ID NC A235308 Text19:
2-GS-008 6
S Gland Seal to LP Turbine 22 Operating conditions unknown.
P&ID NC A235308 Text19:
2-GS-009 2
S Gland Seal to LP Turbine 22 Operating conditions unknown.
P&ID NC A235308 Text19:
2-GS-010 6
S Gland Seal to LP Turbine 22 Operating conditions unknown.
P&ID NC A235308 Text19:
2-GS-011 2
S Gland Seal to LP Turbine 22 Operating conditions unknown.
P&ID NC A235308 Text19:
2-GS-012 6
S Gland Seal to LP Turbine 23 Operating conditions unknown.
P&ID NC A235308 Text19:
2-GS-013 2
S Gland Seal to LP Turbine 23 Operating conditions unknown.
P&ID NC A235308 Text19:
2-GS-014 6
S Gland Seal to LP Turbine 23 Operating conditions unknown.
P&ID NC A235308 Text19:
2-GS-015 2
S Gland Seal to LP Turbine 23 Operating conditions unknown.
P&ID NC A235308 Text19:
2-GS-016 6
S Gland Seal supply to BFP Turbines Operating conditions unknown.
P&IDs NC 9321-H-2024 Text19:
2-GS-020 4
S Steam to BFPT #22 Operating conditions unknown.
P&IDs NC 9321-H-2024 Text19:
2-GS-021 4
S Steam to BFPT #21 Operating conditions unknown.
P&IDs NC 9321-H-2024 Text19:
2-GS-022 3
S Steam to BFPT #22 Operating conditions unknown.
P&IDs NC 9321-H-2024 Text19:
2-GS-023 3
S Steam to BFPT #21 Operating conditions unknown.
P&IDs NC 9321-H-2024 Report No. 0700.104-02, Appendix C, Revision 2 Page C-41 of 102
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Gland Sealing Steam (GS), Unit 2 Section B: SNM Program Lines 2-GS-01: Gland Steam to and from HP, LP, and BFP Turbines Line Number Size (in.)
Sus.
Cat.
Comments Reference Mod.
Ex. Crit.
P&ID No.
Line Description Text19:
2-GS-032 3
S BFPT #22 Gland Steam Discharge Operating conditions unknown.
P&IDs NC 9321-H-2024 Text19:
2-GS-034 3
S BFPT #21 Gland Steam Discharge Operating conditions unknown.
P&IDs NC 9321-H-2024 Text19:
2-GS-036 6
S BFPT Gland Steam Discharge Header to Gland Condenser Operating conditions unknown.
P&IDs NC 9321-H-2024 Text19:
2-GS-038 1
S BFPT Gland Steam Discharge Header drain to waste header Operating conditions unknown.
P&ID NS 9321-H-2024, B237144 Text19:
2-GS-039 2
S BFPT #21 Exhaust Cylinder Drain Operating conditions unknown.
P&ID NS 9321-H-2024 Text19:
2-GS-040 2
S BFPT #22 Exhaust Cylinder Drain Operating conditions unknown.
P&ID NS 9321-H-2024 Text19:
2-GS-041 3
S BFPT Exhaust Cylinder Drain header to Boiler Feed Pump Drip Tank Operating conditions unknown.
P&IDs NC 9321-H-2024 Text19:
2-GS-042 1
S BFPT Exhaust Cylinder Drain header line to Boiler Feed Pump Drip Tank vent Operating conditions unknown.
P&ID NS 9321-H-2024 Text19:
2-GS-043 3
S BFPT Drip Tank vent to Condenser
- 21 Operating conditions unknown.
P&ID NC 9321-H-2024 Text19:
2-GS-047 S
Gland Seal Return from HP Turbine Operating conditions unknown.
P&ID NC B237145 Text19:
2-GS-048 S
Gland Seal Return from HP Turbine Operating conditions unknown.
P&ID NC B237145 Text19:
2-GS-049 S
Gland Seal Return from #21 LP Turbine Operating conditions unknown.
P&ID NC B237144 Text19:
2-GS-050 S
Gland Seal Return from #21 LP Turbine Operating conditions unknown.
P&ID NC B237144 Text19:
2-GS-051 S
Gland Seal Return from #22 LP Turbine Operating conditions unknown.
P&ID NC B237144 Text19:
2-GS-052 S
Gland Seal Return from #22 LP Turbine Operating conditions unknown.
P&ID NC B237144 Report No. 0700.104-02, Appendix C, Revision 2 Page C-42 of 102
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Gland Sealing Steam (GS), Unit 2 Section B: SNM Program Lines 2-GS-01: Gland Steam to and from HP, LP, and BFP Turbines Line Number Size (in.)
Sus.
Cat.
Comments Reference Mod.
Ex. Crit.
P&ID No.
Line Description Text19:
2-GS-053 S
Gland Seal Return from #23 LP Turbine Operating conditions unknown.
P&ID NC B237144 Text19:
2-GS-054 S
Gland Seal Return from #23 LP Turbine Operating conditions unknown.
P&ID NC B237144 Text19:
2-GS-055 S
Gland Seal return header to Gland Condenser Operating conditions unknown.
P&ID NC B237145, B237144 Text19:
2-GS-056 S
Gland Condenser Drain to Main Condenser Outside modeling capabilities.
PEPSE NM B237144 Section C: Excluded Lines 2-GS-01: Gland Steam to and from HP, LP, and BFP Turbines Line Number Size (in.)
Sus.
Cat.
Comments Reference FAC Ex. Crit.
P&ID No.
Line Description Text19:
2-GS-033 0.75 E
BFPT #22 Gland Steam Discharge Drain Low flow in waste drain P&ID EF 9321-H-2024 Text19:
2-GS-035 0.75 E
BFPT #21 Gland Steam Discharge Drain Low flow in waste drain P&ID EF 9321-H-2024 Text19:
2-GS-037 0.75 E
BFPT Gland Steam Discharge Header waste drain Valve shown closed on P&ID.
P&ID EI 9321-H-2024 Text19:
2-GS-057 E
Gland Condenser Waste Drain Valve normally closed.
Engineer Judgement EI B237144 Report No. 0700.104-02, Appendix C, Revision 2 Page C-43 of 102
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Gland Steam Traps (GST), Unit 2 Section B: SNM Program Lines 2-GST-01: Steam Trap Lines from the Gland Seal System Line Number Size (in.)
Sus.
Cat.
Comments Reference Mod.
Ex. Crit.
P&ID No.
Line Description Text19:
2-GST-017 0.75 S
Steam to GST-1 Operating conditions unknown.
P&ID NS 9321-H-2024 Text19:
2-GST-019 0.75 S
GST-1 Discharge to Header Operating conditions unknown.
P&ID NS 9321-H-2024 Text19:
2-GST-024 0.75 S
Steam to GST-3 Operating conditions unknown.
P&ID NS 9321-H-2024 Text19:
2-GST-026 0.75 S
GST-3 Discharge to Header Operating conditions unknown.
P&ID NS 9321-H-2024 Text19:
2-GST-027 0.75 S
Steam to GST-2 Operating conditions unknown.
P&ID NS 9321-H-2024 Text19:
2-GST-029 0.75 S
GST-2 Discharge to Header Operating conditions unknown.
P&ID NS 9321-H-2024 Text19:
2-GST-030 2
S Header from GST-1 and 3 Operating conditions unknown.
P&ID NS 9321-H-2024 Text19:
2-GST-031 2
S Gland Steam Trap Header to Boiler Feed Pump Drip Tank Operating conditions unknown.
P&ID NS 9321-H-2024 Section C: Excluded Lines 2-GST-01: Steam Trap Lines from the Gland Seal System Line Number Size (in.)
Sus.
Cat.
Comments Reference FAC Ex. Crit.
P&ID No.
Line Description Text19:
2-GST-018 0.75 E
GST-1 Bypass Valve shown closed on P&ID.
P&ID EI 9321-H-2024 Text19:
2-GST-025 0.75 E
GST-3 Bypass Valve shown closed on P&ID.
P&ID EI 9321-H-2024 Text19:
2-GST-028 0.75 E
GST-2 Bypass Valve shown closed on P&ID.
P&ID EI 9321-H-2024 Report No. 0700.104-02, Appendix C, Revision 2 Page C-44 of 102
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Heater Drains & Vents (HD), Unit 2 Section A: CHECWORKS Model Lines 2-1HD-01: #21 Feedwater Heater Drain Lines Line Number Size (in.)
Sus.
Cat.
Comments Reference P&ID No.
Line Description Text19:
2-1HD-015 12 M
FWH 21A to Condenser 23 via LCV 1124 Low temperature line with potential for flashing PEPSE A235304 Text19:
2-1HD-016 12 M
FWH 21B to Condenser 22 via LCV 1125 Low temperature line with potential for flashing PEPSE A235304 Text19:
2-1HD-017 12 M
FWH 21C to Condenser 21 via LCV 1126 Low temperature line with potential for flashing PEPSE A235304 2-2HD-01: #22 Feedwater Heater Drain Lines Line Number Size (in.)
Sus.
Cat.
Comments Reference P&ID No.
Line Description Text19:
2-2HD-007 12 M
FWH 22A Drain to FWH 21A Low temperature line with potential for flashing PEPSE A235304 Text19:
2-2HD-008 12 M
FWH 22A Drain to FWH 21A Low temperature line with potential for flashing PEPSE A235304 Text19:
2-2HD-009 12 M
FWH 22A Drain to FWH 21A Low temperature line with potential for flashing PEPSE A235304 Text19:
2-2HD-010 12 M
FWH 22B Drain to FWH 21B Low temperature line with potential for flashing PEPSE A235304 Text19:
2-2HD-011 12 M
FWH 22B Drain to FWH 21B Low temperature line with potential for flashing PEPSE A235304 Text19:
2-2HD-012 12 M
FWH 22B Drain to FWH 21B Low temperature line with potential for flashing PEPSE A235304 Text19:
2-2HD-013 12 M
FWH 22C Drain to FWH 21C Low temperature line with potential for flashing PEPSE A235304 Text19:
2-2HD-014 12 M
FWH 22C Drain to FWH 21C Low temperature line with potential for flashing PEPSE A235304 Text19:
2-2HD-015 12 M
FWH 22C Drain to FWH 21C Low temperature line with potential for flashing PEPSE A235304 Report No. 0700.104-02, Appendix C, Revision 2 Page C-45 of 102
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Heater Drains & Vents (HD), Unit 2 Section A: CHECWORKS Model Lines 2-3HD-01: #23 Feedwater Heater Drain Lines Line Number Size (in.)
Sus.
Cat.
Comments Reference P&ID No.
Line Description Text19:
2-3HD-021 8
M HD24A-1-FWH23A to CV, HD242A FWH23A CV to FWH22A: FWH 23A Drain to FWH 22A PEPSE A235304 Text19:
2-3HD-022 8
M HD25A-1-FWH23B to CV, HD243A FWH23B CV to FWH22B: FWH 23B Drain to FWH 22B PEPSE A235304 Text19:
2-3HD-023 8
M HD26A-1-FWH23C to CV, HD244A FWH23C CV to FWH22C: FWH 23C Drain to FWH 22C PEPSE A235304 2-4HD-01: #24 Feedwater Heater Drain Lines Line Number Size (in.)
Sus.
Cat.
Comments Reference P&ID No.
Line Description Text19:
2-4HD-010 6
M HD21A-1-FWH24A to CV, HD21A FWH24A CV to FWH23A: FWH 24A Drain to FWH 23A PEPSE A235304 Text19:
2-4HD-011 6
M HD22A-1-FWH24B to CV, HD22A FWH24B CV to FWH23B: FWH 24B Drain to FWH 23B PEPSE A235304 Text19:
2-4HD-012 6
M HD23A-1-FWH24C to CV, HD23A FWH24C CV to FWH23C: FWH 24C Drain to FWH 23C PEPSE A235304 2-5HD-01: Heater Drains from #25 Feedwater Heaters Line Number Size (in.)
Sus.
Cat.
Comments Reference P&ID No.
Line Description Text19:
2-5HD-041 10 M
HD9-1-FWH25A to HTR DRN TK:
FWH 25A Drain to Heater Drain Tank PEPSE 9321-F-2022 Text19:
2-5HD-042 10 M
HD9-2-FWH25B to HTR DRN TK:
FWH 25B Drain to Heater Drain Tank PEPSE 9321-F-2022 Report No. 0700.104-02, Appendix C, Revision 2 Page C-46 of 102
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Heater Drains & Vents (HD), Unit 2 Section A: CHECWORKS Model Lines 2-5HD-01: Heater Drains from #25 Feedwater Heaters Line Number Size (in.)
Sus.
Cat.
Comments Reference P&ID No.
Line Description Text19:
2-5HD-043 10 M
HD9-3-FWH25C to HTR DRN TK:
FWH 25C Drain to Heater Drain Tank PEPSE 9321-F-2022 2-5HD-03: HDT Drains to HDPs and Condensers and HDP Vents to HDT Line Number Size (in.)
Sus.
Cat.
Comments Reference P&ID No.
Line Description Text19:
2-5HD-055 18 M
HD19-1-HDT to HDP 21 SUCT: HDT to #21 HDP PEPSE 9321-F-2022 Text19:
2-5HD-056 18 M
HD19-2-HDT to HDP 22 SUCT: HDT to #22 HDP PEPSE 9321-F-2022 2-6HD-01: Heater Drains from #26 Feedwater Heaters Line Number Size (in.)
Sus.
Cat.
Comments Reference P&ID No.
Line Description Text19:
2-6HD-022-A 10 M
HD12-1-FWH26A to CV: Heater Drain from FWH 26A to LCV-1101 PEPSE 9321-F-2022 Text19:
2-6HD-022-B 10 M
HD12-4-FWH26A CV to HTR DR TK: Heater Drain from LCV-1101 to Heater Drain Tank This portion of line is CrMo. Modeled for continuity in SFA.
Pipe Spec 9321-F-2022 Text19:
2-6HD-023-A 10 M
HD12-2-FWH26B to CV: Heater Drain from FWH 26B to LCV-1102 PEPSE 9321-F-2022 Text19:
2-6HD-023-B 10 M
HD12-5-FWH26B CV to HTR DR TK: Heater Drain from LCV-1102 to Heater Drain Tank This portion of line is CrMo. Modeled for continuity in SFA.
Pipe Spec 9321-F-2022 Text19:
2-6HD-024-A 10 M
HD12-3-FWH26C to CV: Heater Drain from FWH 26C to LCV-1103 PEPSE 9321-F-2022 Text19:
2-6HD-024-B 10 M
HD12-6-FWH26C CV to HTR DR TK: Heater Drain from LCV-1103 to Heater Drain Tank This portion of line is CrMo. Modeled for continuity in SFA.
Pipe Spec 9321-F-2022 Report No. 0700.104-02, Appendix C, Revision 2 Page C-47 of 102
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Heater Drains & Vents (HD), Unit 2 Section A: CHECWORKS Model Lines 2-HD-01: Heater Drain Pump discharge to Boiler Feed Pumps Line Number Size (in.)
Sus.
Cat.
Comments Reference P&ID No.
Line Description Text19:
2-HD-001 12 M
HD20-1-HDP21 to BFP SUCTION:
- 21 HDP to Heater Drain Pump Header PEPSE 9321-F-2022 Text19:
2-HD-002 12 M
HD20-2-HDP22 to BFP SUCTION:
- 22 HDP to Heater Drain Pump Header PEPSE 9321-F-2022 Text19:
2-HD-003 16 M
HD20-3-HDP DIS T to BFP SUC:
Heater Drain Pump Header to Boiler Feed Pumps PEPSE 9321-F-2022 Section B: SNM Program Lines 2-1HD-02: #21 Feedwater Heater Vents Line Number Size (in.)
Sus.
Cat.
Comments Reference Mod.
Ex. Crit.
P&ID No.
Line Description Text19:
2-1HD-021 6
S FWH 21A High Level Dump to Condenser 23 Operating conditions unknown.
P&ID NC A235304 Text19:
2-1HD-022 6
S FWH 21B High Level Dump to Condenser 22 Operating conditions unknown.
P&ID NC A235304 Text19:
2-1HD-023 6
S FWH 21C High Level Dump to Condenser 21 Operating conditions unknown.
P&ID NC A235304 Text19:
2-1HD-024 5
S FWH 21A 5" Vent to Condenser 23 Operating conditions unknown.
P&ID NC A235304 Text19:
2-1HD-025 5
S FWH 21B 5" Vent to Condenser 22 Operating conditions unknown.
P&ID NC A235304 Text19:
2-1HD-026 5
S FWH 21C 5" Vent to Condenser 21 Operating conditions unknown.
P&ID NC A235304 Text19:
2-1HD-027 1
S FWH 21A 1" Vent to Condenser 23 Operating conditions unknown.
P&ID NS A235304 Text19:
2-1HD-028 1
S FWH 21B 1" Vent to Condenser 22 Operating conditions unknown.
P&ID NS A235304 Report No. 0700.104-02, Appendix C, Revision 2 Page C-48 of 102
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Heater Drains & Vents (HD), Unit 2 Section B: SNM Program Lines 2-1HD-02: #21 Feedwater Heater Vents Line Number Size (in.)
Sus.
Cat.
Comments Reference Mod.
Ex. Crit.
P&ID No.
Line Description Text19:
2-1HD-029 1
S FWH 21C 1" Vent to Condenser 21 Operating conditions unknown.
P&ID NS A235304 2-2HD-02: #22 Feedwater Heater Vents Line Number Size (in.)
Sus.
Cat.
Comments Reference Mod.
Ex. Crit.
P&ID No.
Line Description Text19:
2-2HD-019 6
S FWH 22A High Level Dump to Condenser 23 Operating conditions unknown.
P&ID NC A235304 Text19:
2-2HD-020 6
S FWH 22B High Level Dump to Condenser 22 Operating conditions unknown.
P&ID NC A235304 Text19:
2-2HD-021 6
S FWH 22C High Level Dump to Condenser 21 Operating conditions unknown.
P&ID NC A235304 Text19:
2-2HD-022 2.5 S
FWH 22A 2-1/2" Vent to Condenser 23 Operating conditions unknown.
P&ID NC A235304 Text19:
2-2HD-023 2.5 S
FWH 22B 2-1/2" Vent to Condenser 22 Operating conditions unknown.
P&ID NC A235304 Text19:
2-2HD-024 2.5 S
FWH 22C 2-1/2" Vent to Condenser 21 Operating conditions unknown.
P&ID NC A235304 Text19:
2-2HD-025 1
S FWH 22A 1" Vent to Condenser 23 Operating conditions unknown.
P&ID NS A235304 Text19:
2-2HD-026 1
S FWH 22B 1" Vent to Condenser 22 Operating conditions unknown.
P&ID NS A235304 Text19:
2-2HD-027 1
S FWH 22C 1" Vent to Condenser 21 Operating conditions unknown.
P&ID NS A235304 2-3HD-02: #23 Feedwater Heater Vents Line Number Size (in.)
Sus.
Cat.
Comments Reference Mod.
Ex. Crit.
P&ID No.
Line Description Text19:
2-3HD-027 2
S FWH 23A Vent to 3EX-53 Operating conditions unknown.
P&ID NS A235304 Text19:
2-3HD-028 2
S FWH 23A Vent to 3EX-534 Operating conditions unknown.
P&ID NS A235304 Report No. 0700.104-02, Appendix C, Revision 2 Page C-49 of 102
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Heater Drains & Vents (HD), Unit 2 Section B: SNM Program Lines 2-3HD-02: #23 Feedwater Heater Vents Line Number Size (in.)
Sus.
Cat.
Comments Reference Mod.
Ex. Crit.
P&ID No.
Line Description Text19:
2-3HD-029 2
S FWH 23B Vent to 3EX-536 Operating conditions unknown.
P&ID NS A235304 Text19:
2-3HD-030 2
S FWH 23B Vent to 3EX-539 Operating conditions unknown.
P&ID NS A235304 Text19:
2-3HD-031 2
S FWH 23C Vent to 3EX-541 Operating conditions unknown.
P&ID NS A235304 Text19:
2-3HD-032 2
S FWH 23C Vent to 3EX-544 Operating conditions unknown.
P&ID NS A235304 Text19:
2-3HD-039 3
S FWH 23A 3" Vent Header Operating conditions unknown.
P&ID NC A235304 Text19:
2-3HD-040 3
S FWH 23B 3" Vent Header Operating conditions unknown.
P&ID NC A235304 Text19:
2-3HD-041 3
S FWH 23C 3" Vent Header Operating conditions unknown.
P&ID NC A235304 Text19:
2-3HD-042 4
S 4" Vent Header from FWH 23A and 23B Operating conditions unknown.
P&ID NC A235304 Text19:
2-3HD-043 4
S 4" Vent Header from #23 FWHs Operating conditions unknown.
P&ID NC A235304 Text19:
2-3HD-044 1
S FWH 23A 1" Vent Operating conditions unknown.
P&ID NS A235304 Text19:
2-3HD-045 1
S FWH 23B 1" Vent Operating conditions unknown.
P&ID NS A235304 Text19:
2-3HD-046 1
S FWH 23C 1" Vent Operating conditions unknown.
P&ID NS A235304 Text19:
2-3HD-047 2
S 2" Vent From FWH 23A and 23B Operating conditions unknown.
P&ID NS A235304 Text19:
2-3HD-048 2
S 2" Vent From #23 FWHs Operating conditions unknown.
P&ID NS A235304 2-4HD-02: #24 Feedwater Heater Vents Line Number Size (in.)
Sus.
Cat.
Comments Reference Mod.
Ex. Crit.
P&ID No.
Line Description Text19:
2-4HD-016 1
S FWH 24A 1" Vent Operating conditions unknown.
P&ID NS A235304 Text19:
2-4HD-017 1
S FWH 24B 1" Vent Operating conditions unknown.
P&ID NS A235304 Text19:
2-4HD-018 1
S FWH 24C 1" Vent Operating conditions unknown.
P&ID NS A235304 Report No. 0700.104-02, Appendix C, Revision 2 Page C-50 of 102
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Heater Drains & Vents (HD), Unit 2 Section B: SNM Program Lines 2-4HD-02: #24 Feedwater Heater Vents Line Number Size (in.)
Sus.
Cat.
Comments Reference Mod.
Ex. Crit.
P&ID No.
Line Description Text19:
2-4HD-019 2
S 2" Vent Header from FWH 24A and 24B Operating conditions unknown.
P&ID NS A235304 Text19:
2-4HD-020 2
S 2" Vent Header from #24 FWHs to Condenser 22 Operating conditions unknown.
P&ID NS A235304 Text19:
2-4HD-021 2
S FWH 24A 2" Vent Operating conditions unknown.
P&ID NS A235304 Text19:
2-4HD-022 2
S FWH 24B 2" Vent Operating conditions unknown.
P&ID NS A235304 Text19:
2-4HD-023 2
S FWH 24B 2" Vent Operating conditions unknown.
P&ID NS A235304 Text19:
2-4HD-024 3
S 3" Vent Header from FWH 24A and 24B Operating conditions unknown.
P&ID NC A235304 Text19:
2-4HD-025 3
S 3" Vent Header from #24 FWHs to Condenser 22 Operating conditions unknown.
P&ID NC A235304 2-5HD-02: Heater Vents from #25 Feedwater Heater and Heater Drain Tank vents to #25 Feedwater Heaters Line Number Size (in.)
Sus.
Cat.
Comments Reference Mod.
Ex. Crit.
P&ID No.
Line Description Text19:
2-5HD-044 10 S
Heater Drain Tank vent to FWH 25A Operating conditions unknown.
PEPSE NC 9321-F-2022 Text19:
2-5HD-045 10 S
Heater Drain Tank vent to FWH 25B Operating conditions unknown.
PEPSE NC 9321-F-2022 Text19:
2-5HD-046 10 S
Heater Drain Tank vent to FWH 25C Operating conditions unknown.
PEPSE NC 9321-F-2022 Text19:
2-5HD-047 1.5 S
FWH 25A Vent Operating conditions unknown.
PEPSE NS 9321-F-2022 Text19:
2-5HD-048 1.5 S
FWH 25B Vent Operating conditions unknown.
PEPSE NS 9321-F-2022 Text19:
2-5HD-049 1.5 S
FWH 25C Vent Operating conditions unknown.
PEPSE NS 9321-F-2022 Text19:
2-5HD-050 2
S Vent header from FWH 25A and 25B Operating conditions unknown.
PEPSE NS 9321-F-2022 Text19:
2-5HD-051 2.5 S
PEPSE NS 9321-F-2022, A235304 Report No. 0700.104-02, Appendix C, Revision 2 Page C-51 of 102
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Heater Drains & Vents (HD), Unit 2 Section B: SNM Program Lines 2-5HD-03: HDT Drains to HDPs and Condensers and HDP Vents to HDT Line Number Size (in.)
Sus.
Cat.
Comments Reference Mod.
Ex. Crit.
P&ID No.
Line Description Text19:
2-5HD-057 2
S
- 21 HDP vent to HDT Operating conditions unknown.
P&ID NS 9321-F-2022 Text19:
2-5HD-058 2
S
- 22 HDP vent to HDT Operating conditions unknown.
P&ID NS 9321-F-2022 Text19:
2-5HD-059 24 S
Heater Drain Tank drain to Condensers Operating conditions unknown.
PEPSE NC 9321-F-2022, A235304 Text19:
2-5HD-060 24 S
HDT Drain Header to Condensers 21 and 22 Operating conditions unknown.
PEPSE NC A235304 Text19:
2-5HD-061-A 14 S
HDT Drain to LCV-5003 Operating conditions unknown.
PEPSE NC A235304 Text19:
2-5HD-061-B 8
S LCV-5003 to Condenser 21 Operating conditions unknown.
PEPSE NC A235304 Text19:
2-5HD-062-A 14 S
HDT Drain to LCV-5002 Operating conditions unknown.
PEPSE NC A235304 Text19:
2-5HD-062-B 8
S LCV-5002 to Condenser 22 Operating conditions unknown.
PEPSE NC A235304 Text19:
2-5HD-063-A 14 S
HDT Drain to LCV-5001 Operating conditions unknown.
PEPSE NC A235304 Text19:
2-5HD-063-B 8
S LCV-5001 to Condenser 23 Operating conditions unknown.
PEPSE NC A235304 2-6HD-02: Heater Vents from #26 Feedwater Heater Line Number Size (in.)
Sus.
Cat.
Comments Reference Mod.
Ex. Crit.
P&ID No.
Line Description Text19:
2-6HD-025 1
S FWH 26A vent via 6EX-10 Operating conditions unknown.
P&IDs NS 9321-F-2022 Text19:
2-6HD-026 1
S FWH 26A vent via 6EX-500 Operating conditions unknown.
P&IDs NS 9321-F-2022 Text19:
2-6HD-027 1
S FWH 26A vent from 6EX-10 and 6EX-500 Operating conditions unknown.
P&IDs NS 9321-F-2022 Text19:
2-6HD-028 1
S FWH 26A vent via 6EX-9 Operating conditions unknown.
P&IDs NS 9321-F-2022 Text19:
2-6HD-029 1
S FWH 26B vent via 6EX-10-1 Operating conditions unknown.
P&IDs NS 9321-F-2022 Text19:
2-6HD-030 1
S FWH 26B vent via 6EX-501 Operating conditions unknown.
P&IDs NS 9321-F-2022 Report No. 0700.104-02, Appendix C, Revision 2 Page C-52 of 102
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Heater Drains & Vents (HD), Unit 2 Section B: SNM Program Lines 2-6HD-02: Heater Vents from #26 Feedwater Heater Line Number Size (in.)
Sus.
Cat.
Comments Reference Mod.
Ex. Crit.
P&ID No.
Line Description Text19:
2-6HD-031 1
S FWH 26B vent from 6EX-10-1 and 6EX-501 Operating conditions unknown.
P&IDs NS 9321-F-2022 Text19:
2-6HD-032 1
S FWH 26B vent via 6EX-9-1 Operating conditions unknown.
P&IDs NS 9321-F-2022 Text19:
2-6HD-033 1
S FWH 26C vent via 6EX-10-2 Operating conditions unknown.
P&IDs NS 9321-F-2022 Text19:
2-6HD-034 1
S FWH 26C vent via 6EX-502 Operating conditions unknown.
P&IDs NS 9321-F-2022 Text19:
2-6HD-035 1
S FWH 26C vent from 6EX-10-2 and 6EX-502 Operating conditions unknown.
P&IDs NS 9321-F-2022 Text19:
2-6HD-036 1
S FWH 26C vent via 6EX-9-2 Operating conditions unknown.
P&IDs NS 9321-F-2022 Text19:
2-6HD-037 1.5 S
Heater Start Up Vent Header from FWH 26A and 26B Operating conditions unknown.
P&IDs NS 9321-F-2022 Text19:
2-6HD-038 2
S
P&IDs NS 9321-F-2022, A235304 Text19:
2-6HD-039 1.5 S
Heater Vent Header from FWH 26A and 26B Operating conditions unknown.
P&IDs NS 9321-F-2022 Text19:
2-6HD-040 2
S
P&IDs NS 9321-F-2022, A235304 2-HD-01: Heater Drain Pump discharge to Boiler Feed Pumps Line Number Size (in.)
Sus.
Cat.
Comments Reference Mod.
Ex. Crit.
P&ID No.
Line Description Text19:
2-HD-004-A 0.5 S
- 21 HDP to HDP Water Chem.
Monitor Upstream of Root Isolation Valve Flow Conditions Unknown PEPSE NS 9321-F-2022 Text19:
2-HD-005-A 0.5 S
- 22 HDP to HDP Water Chem.
Monitor Upstream of Root Isolation Valve Flow Conditions Unknown PEPSE NS 9321-F-2022 Report No. 0700.104-02, Appendix C, Revision 2 Page C-53 of 102
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Heater Drains & Vents (HD), Unit 2 Section C: Excluded Lines 2-1HD-01: #21 Feedwater Heater Drain Lines Line Number Size (in.)
Sus.
Cat.
Comments Reference FAC Ex. Crit.
P&ID No.
Line Description Text19:
2-1HD-018 12 E
FWH 21A to Condenser 23 via LCV 1124A Valve shown closed on P&ID.
P&ID EI A235304 Text19:
2-1HD-019 12 E
FWH 21B to Condenser 22 via LCV 1125A Valve shown closed on P&ID.
P&ID EI A235304 Text19:
2-1HD-020 12 E
FWH 21C to Condenser 21 via LCV 1126A Valve shown closed on P&ID.
P&ID EI A235304 2-2HD-01: #22 Feedwater Heater Drain Lines Line Number Size (in.)
Sus.
Cat.
Comments Reference FAC Ex. Crit.
P&ID No.
Line Description Text19:
2-2HD-016 12 E
FWH 22A Drain to Condenser 23 Valve shown closed on P&ID.
P&ID EI A235304 Text19:
2-2HD-017 12 E
FWH 22B Drain to Condenser 22 Valve shown closed on P&ID.
P&ID EI A235304 Text19:
2-2HD-018 12 E
FWH 22C Drain to Condenser 21 Valve shown closed on P&ID.
P&ID EI A235304 2-3HD-01: #23 Feedwater Heater Drain Lines Line Number Size (in.)
Sus.
Cat.
Comments Reference FAC Ex. Crit.
P&ID No.
Line Description Text19:
2-3HD-024 8
E FWH 23A Drain to Condenser 23 Valve shown closed on P&ID.
P&ID EI A235304 Text19:
2-3HD-025 8
E FWH 23B Drain to Condenser 22 Valve shown closed on P&ID.
P&ID EI A235304 Text19:
2-3HD-026 8
E FWH 23C Drain to Condenser 21 Valve shown closed on P&ID.
P&ID EI A235304 2-3HD-02: #23 Feedwater Heater Vents Line Number Size (in.)
Sus.
Cat.
Comments Reference FAC Ex. Crit.
P&ID No.
Line Description Text19:
2-3HD-033 E
Orifice Bypass via 3EX-11 Valve shown closed on P&ID.
P&ID EI A235304 Text19:
2-3HD-034 E
Orifice Bypass via 3EX-533 Valve shown closed on P&ID.
P&ID EI A235304 Report No. 0700.104-02, Appendix C, Revision 2 Page C-54 of 102
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Heater Drains & Vents (HD), Unit 2 Section C: Excluded Lines 2-3HD-02: #23 Feedwater Heater Vents Line Number Size (in.)
Sus.
Cat.
Comments Reference FAC Ex. Crit.
P&ID No.
Line Description Text19:
2-3HD-035 E
Orifice Bypass via 3EX-11-1 Valve shown closed on P&ID.
P&ID EI A235304 Text19:
2-3HD-036 E
Orifice Bypass via 3EX-538 Valve shown closed on P&ID.
P&ID EI A235304 Text19:
2-3HD-037 E
Orifice Bypass via 3EX-11-2 Valve shown closed on P&ID.
P&ID EI A235304 Text19:
2-3HD-038 E
Orifice Bypass via 3EX-543 Valve shown closed on P&ID.
P&ID EI A235304 2-4HD-01: #24 Feedwater Heater Drain Lines Line Number Size (in.)
Sus.
Cat.
Comments Reference FAC Ex. Crit.
P&ID No.
Line Description Text19:
2-4HD-013-A 6
E FWH 24A Drain to LCV-1115A Valve shown closed on P&ID.
P&ID EI A235304 Text19:
2-4HD-013-B 6
E LCV-1115A to Condenser 23 Valve shown closed on P&ID.
P&ID EI A235304 Text19:
2-4HD-014-A 6
E FWH 24B Drain to LCV-1116A Valve shown closed on P&ID.
P&ID EI A235304 Text19:
2-4HD-014-B 6
E LCV-1116A to Condenser 22 Valve shown closed on P&ID.
P&ID EI A235304 Text19:
2-4HD-015-A 6
E FWH 24C Drain to LCV-1117A Valve shown closed on P&ID.
P&ID EI A235304 Text19:
2-4HD-015-B 6
E LCV-1117A to Condenser 21 Valve shown closed on P&ID.
P&ID EI A235304 2-5HD-02: Heater Vents from #25 Feedwater Heater and Heater Drain Tank vents to #25 Feedwater Heaters Line Number Size (in.)
Sus.
Cat.
Comments Reference FAC Ex. Crit.
P&ID No.
Line Description Text19:
2-5HD-052 E
FE-7635 Bypass Line Valve shown closed on P&ID.
P&ID EI 9321-F-2022 Text19:
2-5HD-053 E
FE-7636 Bypass Line Valve shown closed on P&ID.
P&ID EI 9321-F-2022 Text19:
2-5HD-054 E
FE-7637 Bypass Line Valve shown closed on P&ID.
P&ID EI 9321-F-2022 Report No. 0700.104-02, Appendix C, Revision 2 Page C-55 of 102
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Heater Drains & Vents (HD), Unit 2 Section C: Excluded Lines 2-5HD-03: HDT Drains to HDPs and Condensers and HDP Vents to HDT Line Number Size (in.)
Sus.
Cat.
Comments Reference FAC Ex. Crit.
P&ID No.
Line Description Text19:
2-5HD-064 14 E
LCV-5003 Bypass Line Valve shown closed on P&ID.
P&ID EI A235304 Text19:
2-5HD-065 14 E
LCV-5002 Bypass Line Valve shown closed on P&ID.
P&ID EI A235304 Text19:
2-5HD-066 14 E
LCV-5001 Bypass Line Valve shown closed on P&ID.
P&ID EI A235304 2-HD-01: Heater Drain Pump discharge to Boiler Feed Pumps Line Number Size (in.)
Sus.
Cat.
Comments Reference FAC Ex. Crit.
P&ID No.
Line Description Text19:
2-HD-004-B 0.25 E
- 21 HDP to HDP Water Chem.
Monitor Downstream of Root Isolation Valve Downstream of root isolation valve is SS CSI Document No.
0700.104.C.010 EM 9321-F-2022 Text19:
2-HD-005-B 0.25 E
- 22 HDP to HDP Water Chem.
Monitor Downstream of Root Isolation Valve Downstream of root isolation valve is SS CSI Document No.
0700.104.C.010 EM 9321-F-2022 Report No. 0700.104-02, Appendix C, Revision 2 Page C-56 of 102
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Main Steam (MS), Unit 2 Section A: CHECWORKS Model Lines 2-MS-07: HP Turbine Crossunder Piping to the Moisture Separators Line Number Size (in.)
Sus.
Cat.
Comments Reference P&ID No.
Line Description Text19:
2-MS-204 32 M
HP Turbine Crossunder to Moisture Preseparator A PEPSE A235308 Text19:
2-MS-205 32 M
HP Turbine Crossunder to Moisture Preseparator B PEPSE A235308 Text19:
2-MS-206 32 M
HP Turbine Crossunder to Moisture Preseparator C PEPSE A235308 Text19:
2-MS-207 32 M
HP Turbine Crossunder to Moisture Preseparator D PEPSE A235308 Section B: SNM Program Lines 2-MS-01: Main Steam from Stm Gen to HP Turbine, BFP Turbine, MSRs, Aux. Steam, SJAEs, and Priming Ejectors.
Line Number Size (in.)
Sus.
Cat.
Comments Reference Mod.
Ex. Crit.
P&ID No.
Line Description Text19:
2-MS-001 28 S
Main Steam from Steam Generator 21 Shell High quality main steam line.
PEPSE NQ 9321-F-2017, A235308 Text19:
2-MS-002 28 S
Main Steam from Steam Generator 22 Shell High quality main steam line.
PEPSE NQ 9321-F-2017, A235308 Text19:
2-MS-003 28 S
Main Steam from Steam Generator 23 Shell High quality main steam line.
PEPSE NQ 9321-F-2017, A235308 Text19:
2-MS-004 28 S
Main Steam from Steam Generator 24 Shell High quality main steam line.
PEPSE NQ 9321-F-2017, A235308 Text19:
2-MS-005 24 S
Line from 2-MS-001 to Seal Steam and MSR Header.
High quality main steam line.
PEPSE NQ A235308 Text19:
2-MS-006 24 S
Line from 2-MS-002 to Gland Seal Steam and MSR B Header.
High quality main steam line.
PEPSE NQ A235308 Text19:
2-MS-007 20 S
Gland Seal Steam, MSR B, and Aux.
Steam Header.
High quality main steam line.
PEPSE NQ A235308, A227780 Report No. 0700.104-02, Appendix C, Revision 2 Page C-57 of 102
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Main Steam (MS), Unit 2 Section B: SNM Program Lines 2-MS-01: Main Steam from Stm Gen to HP Turbine, BFP Turbine, MSRs, Aux. Steam, SJAEs, and Priming Ejectors.
Line Number Size (in.)
Sus.
Cat.
Comments Reference Mod.
Ex. Crit.
P&ID No.
Line Description Text19:
2-MS-008 24 S
Line from 2-MS-001 (3) to MSR A Header High quality main steam line.
PEPSE NQ A235308 Text19:
2-MS-009 24 S
Line from 2-MS-004 to MSR A Header High quality main steam line.
PEPSE NQ A235308 Text19:
2-MS-010 20 S
MSR A, BFP Turbine, SJAE, and Priming Ejector Header High quality main steam line.
PEPSE NQ A235308, A227780 Text19:
2-MS-011 28 S
Main Steam to NE HP Turbine Inlet High quality main steam line.
PEPSE NQ A235308 Text19:
2-MS-011-A 4
S MS-863 Bypass High quality main steam line.
PEPSE NQ A235308 Text19:
2-MS-012 28 S
Main Steam to SE HP Turbine Inlet High quality main steam line.
PEPSE NQ A235308 Text19:
2-MS-012-A 4
S MS-864 Bypass High quality main steam line.
PEPSE NQ A235308 Text19:
2-MS-013 28 S
Main Steam to NW HP Turbine Inlet High quality main steam line.
PEPSE NQ A235308 Text19:
2-MS-013-A 4
S MS-865 Bypass High quality main steam line.
PEPSE NQ A235308 Text19:
2-MS-014 28 S
Main Steam to SW HP Turbine Inlet High quality main steam line.
PEPSE NQ A235308 Text19:
2-MS-014-A 4
S MS-866 Bypass High quality main steam line.
PEPSE NQ A235308 Text19:
2-MS-015 20 S
Main Steam Balancing Line between 2-MS-001 and 2-MS-003 High quality main steam line.
PEPSE NQ A235308 Text19:
2-MS-016 12 S
Main Steam to Reheater Steam Control Station A.
High quality main steam line.
PEPSE NQ A227780 Text19:
2-MS-017 8
S Reheater Steam Control Station A line to PCV 1175-1 High quality main steam line.
PEPSE NQ A227780 Text19:
2-MS-018 8
S Reheater Steam Control Station A line to PCV 1175-2 High quality main steam line.
PEPSE NQ A227780 Text19:
2-MS-019 1
S Reheater Steam Control Station A line to PCV 1108 High quality main steam line.
PEPSE NS A227780 Text19:
2-MS-020 12 S
Reheater Steam Header A High quality main steam line.
PEPSE NQ A227780 Report No. 0700.104-02, Appendix C, Revision 2 Page C-58 of 102
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Main Steam (MS), Unit 2 Section B: SNM Program Lines 2-MS-01: Main Steam from Stm Gen to HP Turbine, BFP Turbine, MSRs, Aux. Steam, SJAEs, and Priming Ejectors.
Line Number Size (in.)
Sus.
Cat.
Comments Reference Mod.
Ex. Crit.
P&ID No.
Line Description Text19:
2-MS-021 6
S Reheater Header to MSR 21A High quality main steam line.
PEPSE NQ A227780 Text19:
2-MS-022 6
S Reheater Header to MSR 22A High quality main steam line.
PEPSE NQ A227780 Text19:
2-MS-023 6
S Reheater Header to MSR 23A High quality main steam line.
PEPSE NQ A227780 Text19:
2-MS-024 12 S
Main Steam to Reheater Steam Control Station B.
High quality main steam line.
PEPSE NQ A227780 Text19:
2-MS-025 8
S Reheater Steam Control Station B line to PCV 1175-3 High quality main steam line.
PEPSE NQ A227780 Text19:
2-MS-026 8
S Reheater Steam Control Station B line to PCV 1175-4 High quality main steam line.
PEPSE NQ A227780 Text19:
2-MS-027 1
S Reheater Steam Control Station B line to PCV 1109 High quality main steam line.
PEPSE NS A227780 Text19:
2-MS-028 12 S
Reheater Steam Header B High quality main steam line.
PEPSE NQ A227780 Text19:
2-MS-029 6
S Reheater Header to MSR 21B High quality main steam line.
PEPSE NQ A227780 Text19:
2-MS-030 6
S Reheater Header to MSR 22B High quality main steam line.
PEPSE NQ A227780 Text19:
2-MS-031 6
S Reheater Header to MSR 23B High quality main steam line.
PEPSE NQ A227780 Text19:
2-MS-032 1
S Reheater Cal. Line High quality main steam line.
PEPSE NS A227780 Text19:
2-MS-033 4
S Main Steam to BFP #21 Turbine High quality main steam line.
PEPSE NQ A227780 Text19:
2-MS-034 4
S Main Steam to BFP #22 Turbine High quality main steam line.
PEPSE NQ A227780 Text19:
2-MS-035 6
S Main Steam to SJAEs and Priming Ejectors High quality main steam line.
PEPSE NQ A227780 Text19:
2-MS-036-A 3
S SJAE Steam Supply Upstream of PCV 1132 High quality main steam line.
PEPSE NQ A227780 Text19:
2-MS-036-B 3
S SJAE Steam Supply Downstream of PCV 1132 Operating conditions unknown.
SD No. 18.0 NC A227780 Report No. 0700.104-02, Appendix C, Revision 2 Page C-59 of 102
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Main Steam (MS), Unit 2 Section B: SNM Program Lines 2-MS-01: Main Steam from Stm Gen to HP Turbine, BFP Turbine, MSRs, Aux. Steam, SJAEs, and Priming Ejectors.
Line Number Size (in.)
Sus.
Cat.
Comments Reference Mod.
Ex. Crit.
P&ID No.
Line Description Text19:
2-MS-037 3
S SJAE Header Operating conditions unknown.
SD No. 18.0 N
A227780 Text19:
2-MS-038 2
S Header to SJAE 21 Operating conditions unknown.
SD No. 18.0 NS A227780 Text19:
2-MS-039 2
S Header to SJAE 22 Operating conditions unknown.
SD No. 18.0 NS A227780 Text19:
2-MS-040 2
S Header to SJAE 23 Operating conditions unknown.
SD No. 18.0 NS A227780 Text19:
2-MS-041 S
SJAE Steam Supply via MS-797 Operating conditions unknown.
SD No. 18.0 NS A227780 Text19:
2-MS-042 S
SJAE Steam Supply via MS-798 Operating conditions unknown.
SD No. 18.0 NS A227780 Text19:
2-MS-043 S
SJAE Steam Supply via MS-799 Operating conditions unknown.
SD No. 18.0 NS A227780 Text19:
2-MS-044 S
SJAE Steam Supply via MS-800 Operating conditions unknown.
SD No. 18.0 NS A227780 Text19:
2-MS-045 S
SJAE Steam Supply via MS-801 Operating conditions unknown.
SD No. 18.0 NS A227780 Text19:
2-MS-046 S
SJAE Steam Supply via MS-802 Operating conditions unknown.
SD No. 18.0 NS A227780 Text19:
2-MS-047 S
SJAE Steam Supply via MS-803 Operating conditions unknown.
SD No. 18.0 NS A227780 Text19:
2-MS-048 S
SJAE Steam Supply via MS-804 Operating conditions unknown.
SD No. 18.0 NS A227780 Text19:
2-MS-049 S
SJAE Steam Supply via MS-805 Operating conditions unknown.
SD No. 18.0 NS A227780 Text19:
2-MS-050 S
SJAE Steam Supply via MS-806 Operating conditions unknown.
SD No. 18.0 NS A227780 Text19:
2-MS-051 S
SJAE Steam Supply via MS-807 Operating conditions unknown.
SD No. 18.0 NS A227780 Text19:
2-MS-052 S
SJAE Steam Supply via MS-808 Operating conditions unknown.
SD No. 18.0 NS A227780 Text19:
2-MS-053 S
SJAE Steam Supply via MS-809 Operating conditions unknown.
SD No. 18.0 NS A227780 Text19:
2-MS-054 S
SJAE Steam Supply via MS-810 Operating conditions unknown.
SD No. 18.0 NS A227780 Text19:
2-MS-055 S
SJAE Steam Supply via MS-811 Operating conditions unknown.
SD No. 18.0 NS A227780 Text19:
2-MS-056 S
SJAE Steam Supply via MS-812 Operating conditions unknown.
SD No. 18.0 NS A227780 Report No. 0700.104-02, Appendix C, Revision 2 Page C-60 of 102
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Main Steam (MS), Unit 2 Section B: SNM Program Lines 2-MS-01: Main Steam from Stm Gen to HP Turbine, BFP Turbine, MSRs, Aux. Steam, SJAEs, and Priming Ejectors.
Line Number Size (in.)
Sus.
Cat.
Comments Reference Mod.
Ex. Crit.
P&ID No.
Line Description Text19:
2-MS-057 S
SJAE Steam Supply via MS-813 Operating conditions unknown.
SD No. 18.0 NS A227780 Text19:
2-MS-058 S
SJAE Steam Supply via MS-814 Operating conditions unknown.
SD No. 18.0 NS A227780 Text19:
2-MS-059-A 6
S Main Steam to Priming Ejectors Header Upstream of PCV 1133 High quality main steam line.
PEPSE NQ A227780 Text19:
2-MS-059-B 6
S Main Steam to Priming Ejectors Header Downstream of PCV 1133 Operating conditions unknown.
SD No. 18.0 N
A227780 Text19:
2-MS-060 6
S Priming Ejectors Header Operating conditions unknown.
SD No. 18.0 N
A227780 Text19:
2-MS-061 3
S Priming Ejectors Header to PE 21 Operating conditions unknown.
SD No. 18.0 N
A227780 Text19:
2-MS-062 3
S Priming Ejectors Header to PE 22 Operating conditions unknown.
SD No. 18.0 N
A227780 Text19:
2-MS-063 3
S Priming Ejectors Header to PE 23 Operating conditions unknown.
SD No. 18.0 N
A227780 Text19:
2-MS-064 12 S
Balancing line between SE and SW HP Turbine Steam Feed Lines.
High quality main steam line.
PEPSE NQ A235308 Text19:
2-MS-076 3
S MS-863 Valve leakoff to condenser.
Operating conditions unknown.
P&ID NC A235308 Text19:
2-MS-077 3
S MS-864 Valve leakoff to condenser.
Operating conditions unknown.
P&ID NC A235308 Text19:
2-MS-078 3
S MS-865 Valve leakoff to condenser.
Operating conditions unknown.
P&ID NC A235308 Text19:
2-MS-079 3
S MS-866 Valve leakoff to condenser.
Operating conditions unknown.
P&ID NC A235308 Text19:
2-MS-143 0.75 S
Main Steam Stop Valve drain to 23 Cond. West Side Operating conditions unknown.
P&ID NS A235308 Text19:
2-MS-144 0.75 S
Main Steam Stop Valve drain to 23 Cond. East Side Operating conditions unknown.
P&ID NS A235308 Text19:
2-MS-192 4
S Main Steam Header to Aux. Steam Upstream of PCV-1015 High quality main steam line.
PEPSE NQ A227780 Text19:
2-MS-198 S
LH Control Valve Stem Leak-off Lines Operating conditions unknown.
P&ID NS B237145 Report No. 0700.104-02, Appendix C, Revision 2 Page C-61 of 102
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Main Steam (MS), Unit 2 Section B: SNM Program Lines 2-MS-01: Main Steam from Stm Gen to HP Turbine, BFP Turbine, MSRs, Aux. Steam, SJAEs, and Priming Ejectors.
Line Number Size (in.)
Sus.
Cat.
Comments Reference Mod.
Ex. Crit.
P&ID No.
Line Description Text19:
2-MS-199 S
RH Control Valve Stem Leak-off Lines Operating conditions unknown.
P&ID NS B237145 Text19:
2-MS-200 1.5 S
Upper LH HP Turbine Feed Leakoff Operating conditions unknown.
P&ID NS B237145 Text19:
2-MS-201 1.5 S
Lower LH HP Turbine Feed Leakoff Operating conditions unknown.
P&ID NS B237145 Text19:
2-MS-202 1.5 S
Upper RH HP Turbine Feed Leakoff Operating conditions unknown.
P&ID NS B237145 Text19:
2-MS-203 1.5 S
Lower LH HP Turbine Feed Leakoff Operating conditions unknown.
P&ID NS B237145 2-MS-06: Main Steam Supply to Gland Steam Header Line Number Size (in.)
Sus.
Cat.
Comments Reference Mod.
Ex. Crit.
P&ID No.
Line Description Text19:
2-MS-187 4
S Main Steam Supply to Gland Seal Regulator Station High quality main steam line.
PEPSE NQ A235308 Text19:
2-MS-188-A 3
S Gland Seal Steam Supply upstream of PCV-1145-1 High quality main steam line.
PEPSE NQ A235308 Text19:
2-MS-188-B 12 S
Gland Seal Steam Supply downstream of PCV-1145-1 Operating conditions unknown.
P&ID NC A235308 Text19:
2-MS-189-A 3
S Gland Seal Steam Supply upstream of PCV-1145-2 High quality main steam line.
PEPSE NQ A235308 Text19:
2-MS-189-B 12 S
Gland Seal Steam Supply downstream of PCV-1145-2 Operating conditions unknown.
P&ID NC A235308 Text19:
2-MS-191 12 S
Main Steam to Gland Seal Steam Header.
Operating conditions unknown.
P&ID NC A235308 Report No. 0700.104-02, Appendix C, Revision 2 Page C-62 of 102
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Main Steam (MS), Unit 2 Section C: Excluded Lines 2-MS-01: Main Steam from Stm Gen to HP Turbine, BFP Turbine, MSRs, Aux. Steam, SJAEs, and Priming Ejectors.
Line Number Size (in.)
Sus.
Cat.
Comments Reference FAC Ex. Crit.
P&ID No.
Line Description Text19:
2-MS-036-C 2
E PCV 1132 Bypass Line Valve shown closed on P&ID.
P&ID EI A227780 Text19:
2-MS-059-C 6
E PCV 1133 Bypass Line Valve shown closed on P&ID.
P&ID EI A227780 Text19:
2-MS-065 4
E Aux. Feed Pump Turbine Drive Steam Supply from SG 22 Shell Aux. FW Turbine does not run during normal operation.
SD No. 18.0 EI 9321-F-2017 Text19:
2-MS-066 4
E Aux. Feed Pump Turbine Drive Steam Supply from SG 23 Shell Aux. FW Turbine does not run during normal operation.
SD No. 18.0 EI 9321-F-2017 Text19:
2-MS-067-A 4
E Aux. Feed Pump Turbine Drive Steam Header Upstream of PCV 1139 Aux. FW Turbine does not run during normal operation.
SD No. 18.0 EI 9321-F-2017 Text19:
2-MS-067-B 4
E Aux. Feed Pump Turbine Drive Steam Header Downstream of PCV 1139 Aux. FW Turbine does not run during normal operation.
SD No. 18.0 EI 9321-F-2017 Text19:
2-MS-068 1
E PCV 1310A Bypass Line Valve shown closed on P&ID.
P&ID EI 9321-F-2017 Text19:
2-MS-069 1
E PCV 1310A and 1310B Equalization Line Valve shown closed on P&ID.
P&ID EI 9321-F-2017 Text19:
2-MS-070 1
E PCV 1310B Bypass Line Valve shown closed on P&ID.
P&ID EI 9321-F-2017 Text19:
2-MS-071 12 E
Aux. Feed Pump Turbine Drive Vent to Atmosphere.
Aux. FW Turbine does not run during normal operation.
SD No. 18.0 EI 9321-F-2017 Text19:
2-MS-072 0.75 E
Aux. Feed Pump Turbine Drive Vent Drip Leg The Aux. Feed Turbine operates less than 2% of the time.
SD No. 21.0 EI 9321-F-2041 Text19:
2-MS-181 1
E PCV-1175-1 Leakoff Line to Condenser FCV-5066B normally closed SD No. 18.0 EI A209847 Text19:
2-MS-182 1
E PCV-1175-2 Leakoff Line to Condenser FCV-5066A normally closed SD No. 18.0 EI A209847 Text19:
2-MS-183 1
E PCV-1175-3 Leakoff Line to Condenser FCV-5065B normally closed SD No. 18.0 EI A209847 Report No. 0700.104-02, Appendix C, Revision 2 Page C-63 of 102
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Main Steam (MS), Unit 2 Section C: Excluded Lines 2-MS-01: Main Steam from Stm Gen to HP Turbine, BFP Turbine, MSRs, Aux. Steam, SJAEs, and Priming Ejectors.
Line Number Size (in.)
Sus.
Cat.
Comments Reference FAC Ex. Crit.
P&ID No.
Line Description Text19:
2-MS-184 1
E PCV-1175-4 Leakoff Line to Condenser FCV-5065A normally closed SD No. 18.0 EI A209847 Text19:
2-MS-185 2
E PCV-1175-1 and 2 Leakoff Header to Condenser Upstream valves normally closed SD No. 18.0 EI A209847 Text19:
2-MS-186 2
E PCV-1175-3 and 4 Leakoff Header to Condenser Upstream valves normally closed SD No. 18.0 EI A209847 Text19:
2-MS-194 1
E MS-1133 Bypass Valve shown closed on P&ID.
P&ID EI A227780 Text19:
2-MS-195 0.75 E
MST-100 Bypass via MS-1139 and MS-1140 Valve shown closed on P&ID.
P&ID EI A227780 Text19:
2-MS-197 3
E PCV-1015 Bypass Valve shown closed on P&ID.
P&ID EI A227780 2-MS-06: Main Steam Supply to Gland Steam Header Line Number Size (in.)
Sus.
Cat.
Comments Reference FAC Ex. Crit.
P&ID No.
Line Description Text19:
2-MS-190 3
E PCV-1145-1 and 2 bypass line Valve shown closed on P&ID.
P&ID EI A235308 2-MS-07: HP Turbine Crossunder Piping to the Moisture Separators Line Number Size (in.)
Sus.
Cat.
Comments Reference FAC Ex. Crit.
P&ID No.
Line Description Text19:
2-MS-208 32 E
MS56-1-PRESEP to MSR-A:
Moisture Preseparator A to MSR Header Line is clad with Stainless Steel.
SFA Model EM A235308 Text19:
2-MS-209 32 E
MS57-1-PRESEP to MSR-B:
Moisture Preseparator B to MSR Header Line is clad with Stainless Steel.
SFA Model EM A235308 Text19:
2-MS-210 32 E
MS56-2-PRESEP to MSR-A:
Moisture Preseparator C to MSR Header Line is clad with Stainless Steel.
SFA Model EM A235308 Report No. 0700.104-02, Appendix C, Revision 2 Page C-64 of 102
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Main Steam (MS), Unit 2 Section C: Excluded Lines 2-MS-07: HP Turbine Crossunder Piping to the Moisture Separators Line Number Size (in.)
Sus.
Cat.
Comments Reference FAC Ex. Crit.
P&ID No.
Line Description Text19:
2-MS-211 32 E
MS57-2-PRESEP to MSR-B:
Moisture Preseparator D to MSR Header Line is clad with Stainless Steel.
SFA Model EM A235308 Text19:
2-MS-212 46.5 E
MS56-3-PRESEP to MSR-A:
Moisture Preseparator Header to A MSRs Line is clad with Stainless Steel.
SFA Model EM A235308, A227780 Text19:
2-MS-213 46.5 E
MS57-3-PRESEP to MSR-B:
Moisture Preseparator Header to B MSRs Line is clad with Stainless Steel.
SFA Model EM A235308, A227780 Text19:
2-MS-214 37 E
MS56-5-PRESEP to MSR-A:
Moisture Preseparator Header to MSR 21A and 22A Line is clad with Stainless Steel.
SFA Model EM A227780 Text19:
2-MS-215 37 E
MS57-5-PRESEP to MSR-B:
Moisture Preseparator Header to MSR 21B and 22B Line is clad with Stainless Steel.
SFA Model EM A227780 Text19:
2-MS-216 26.5 E
MS56-7-PRESEP to MSR21A:
Moisture Preseparator Header to MSR 21A Line is clad with Stainless Steel.
SFA Model EM A227780 Text19:
2-MS-217 26.5 E
MS56-6-PRESEP to MSR22A:
Moisture Preseparator Header to MSR 22A Line is clad with Stainless Steel.
SFA Model EM A227780 Text19:
2-MS-218 26.5 E
MS56-4-PRESEP to MSR23A:
Moisture Preseparator Header to MSR 23A Line is clad with Stainless Steel.
SFA Model EM A227780 Text19:
2-MS-219 26.5 E
MS57-7-PRESEP to MSR21B:
Moisture Preseparator Header to MSR 21B Line is clad with Stainless Steel.
SFA Model EM A227780 Text19:
2-MS-220 26.5 E
MS57-6-PRESEP to MSR22B:
Moisture Preseparator Header to MSR 22B Line is clad with Stainless Steel.
SFA Model EM A227780 Report No. 0700.104-02, Appendix C, Revision 2 Page C-65 of 102
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Main Steam (MS), Unit 2 Section C: Excluded Lines 2-MS-07: HP Turbine Crossunder Piping to the Moisture Separators Line Number Size (in.)
Sus.
Cat.
Comments Reference FAC Ex. Crit.
P&ID No.
Line Description Text19:
2-MS-221 26.5 E
MS57-4-PRESEP to MSR23B:
Moisture Preseparator Header to MSR 23B Line is clad with Stainless Steel.
SFA Model EM A227780 Report No. 0700.104-02, Appendix C, Revision 2 Page C-66 of 102
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Moisture Separator Reheater Drains (MSD), Unit 2 Section A: CHECWORKS Model Lines 2-MSD-01: Moisture Separator Drains to the Heater Drain Tank and Drains Collecting Tank Line Number Size (in.)
Sus.
Cat.
Comments Reference P&ID No.
Line Description Text19:
2-MSD-067 12 M
MSD27-1-MS21A to MSDT 21A:
MSR 21A Drain from 16N PEPSE 9321-F-2023 Text19:
2-MSD-068 12 M
MSD27-2-MS21A to MSDT 21A:
MSR 21A Drain from 17N PEPSE 9321-F-2023 Text19:
2-MSD-069 12 M
MSD27-4-MS21A to MSDT 21A:
MSR 21A Drain Header from 16N and 17N PEPSE 9321-F-2023 Text19:
2-MSD-070 12 M
MSD27-3-MS21A to MSDT 21A:
MSR 21A Drain from 19N PEPSE 9321-F-2023 Text19:
2-MSD-071 12 M
MSD27-5-MS21A to MSDT 21A:
MSR 21A Drain to MSR Drain Tank 21A PEPSE 9321-F-2023 Text19:
2-MSD-072 12 M
MSD28-1-MS22A to MSDT 22A:
MSR 22A Drain from 16N PEPSE 9321-F-2023 Text19:
2-MSD-073 12 M
MSD28-2-MS22A to MSDT 22A:
MSR 22A Drain from 17N PEPSE 9321-F-2023 Text19:
2-MSD-074 12 M
MSD28-4-MS22A to MSDT 22A:
MSR 22A Drain Header from 16N and 17N PEPSE 9321-F-2023 Text19:
2-MSD-075 12 M
MSD28-3-MS22A to MSDT 22A:
MSR 22A Drain from 19N PEPSE 9321-F-2023 Text19:
2-MSD-076 12 M
MSD28-5-MS22A to MSDT 22A:
MSR 22A Drain to MSR Drain Tank 22A PEPSE 9321-F-2023 Text19:
2-MSD-077 12 M
MSD29-1-MS23A to MSDT 23A:
MSR 23A Drain from 16N PEPSE 9321-F-2023 Text19:
2-MSD-078 12 M
MSD29-2-MS23A to MSDT 23A:
MSR 23A Drain from 17N PEPSE 9321-F-2023 Report No. 0700.104-02, Appendix C, Revision 2 Page C-67 of 102
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Moisture Separator Reheater Drains (MSD), Unit 2 Section A: CHECWORKS Model Lines 2-MSD-01: Moisture Separator Drains to the Heater Drain Tank and Drains Collecting Tank Line Number Size (in.)
Sus.
Cat.
Comments Reference P&ID No.
Line Description Text19:
2-MSD-079 12 M
MSD29-4-MS23A to MSDT 23A:
MSR 23A Drain Header from 16N and 17N PEPSE 9321-F-2023 Text19:
2-MSD-080 12 M
MSD29-3-MS23A to MSDT 23A:
MSR 23A Drain from 19N PEPSE 9321-F-2023 Text19:
2-MSD-081 12 M
MSD29-5-MS23A to MSDT 23A:
MSR 23A Drain to MSR Drain Tank 23A PEPSE 9321-F-2023 Text19:
2-MSD-082 12 M
MSD30-1-MS21B to MSDT 21B:
MSR 21B Drain from 19N PEPSE 9321-F-2023 Text19:
2-MSD-083 12 M
MSD30-2-MS21B to MSDT 21B:
MSR 21B Drain from 18N PEPSE 9321-F-2023 Text19:
2-MSD-084 12 M
MSD30-4-MS21B to MSDT 21B:
MSR 21B Drain Header from 18N and 19N PEPSE 9321-F-2023 Text19:
2-MSD-085 12 M
MSD30-3-MS21B to MSDT 21B:
MSR 21B Drain from 16N PEPSE 9321-F-2023 Text19:
2-MSD-086 12 M
MSD30-5-MS21B to MSDT 21B:
MSR 21B Drain to MSR Drain Tank 21B PEPSE 9321-F-2023 Text19:
2-MSD-087 12 M
MSD31-1-MS22B to MSDT 22B:
MSR 22B Drain from 19N PEPSE 9321-F-2023 Text19:
2-MSD-088 12 M
MSD31-2-MS22B to MSDT 22B:
MSR 22B Drain from 18N PEPSE 9321-F-2023 Text19:
2-MSD-089 12 M
MSD31-4-MS22B to MSDT 22B:
MSR 22B Drain Header from 18N and 19N PEPSE 9321-F-2023 Text19:
2-MSD-090 12 M
MSD31-3-MS22B to MSDT 22B:
MSR 22B Drain from 16N PEPSE 9321-F-2023 Report No. 0700.104-02, Appendix C, Revision 2 Page C-68 of 102
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Moisture Separator Reheater Drains (MSD), Unit 2 Section A: CHECWORKS Model Lines 2-MSD-01: Moisture Separator Drains to the Heater Drain Tank and Drains Collecting Tank Line Number Size (in.)
Sus.
Cat.
Comments Reference P&ID No.
Line Description Text19:
2-MSD-091 12 M
MSD31-5-MS22B to MSDT 22B:
MSR 22B Drain to MSR Drain Tank 22B PEPSE 9321-F-2023 Text19:
2-MSD-092 12 M
MSD32-1-MS23B to MSDT 23B:
MSR 23B Drain from 19N PEPSE 9321-F-2023 Text19:
2-MSD-093 12 M
MSD32-2-MS23B to MSDT 23B:
MSR 23B Drain from 18N PEPSE 9321-F-2023 Text19:
2-MSD-094 12 M
MSD32-4-MS23B to MSDT 23B:
MSR 23B Drain Header from 18N and 19N PEPSE 9321-F-2023 Text19:
2-MSD-095 12 M
MSD32-3-MS23B to MSDT 23B:
MSR 23B Drain from 16N PEPSE 9321-F-2023 Text19:
2-MSD-096 12 M
MSD32-5-MS23B to MSDT 23B:
MSR 23B Drain to MSR Drain Tank 23B PEPSE 9321-F-2023 2-MSD-02: Reheater Drains to #26 Feedwater Heaters and Condensers Line Number Size (in.)
Sus.
Cat.
Comments Reference P&ID No.
Line Description Text19:
2-MSD-151 6
M MSD39-1-RHTR 21A to RHDT 21A:
Reheater 21A to Reheater Drain Tank PEPSE 9321-F-2023 Text19:
2-MSD-152 6
M MSD40-1-RHTR 22A to RHDT 22A:
Reheater 22A to Reheater Drain Tank PEPSE 9321-F-2023 Text19:
2-MSD-153 6
M MSD41-1-RHTR 23A to RHDT 23A:
Reheater 23A to Reheater Drain Tank PEPSE 9321-F-2023 Text19:
2-MSD-154 6
M MSD42-1-RHTR 21B to RHDT 21B:
Reheater 21B to Reheater Drain Tank PEPSE 9321-F-2023 Text19:
2-MSD-155 6
M MSD43-1-RHTR 22B to RHDT 22B:
Reheater 22B to Reheater Drain Tank PEPSE 9321-F-2023 Report No. 0700.104-02, Appendix C, Revision 2 Page C-69 of 102
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Moisture Separator Reheater Drains (MSD), Unit 2 Section A: CHECWORKS Model Lines 2-MSD-02: Reheater Drains to #26 Feedwater Heaters and Condensers Line Number Size (in.)
Sus.
Cat.
Comments Reference P&ID No.
Line Description Text19:
2-MSD-156 6
M MSD44-1-RHTR 23B to RHDT 23B:
Reheater 23B to Reheater Drain Tank PEPSE 9321-F-2023 Text19:
2-MSD-157 6
M MSD45A-1-RHDT21A to CV, MSD45B-1-RHDT21A CV to FWH26: Reheater Drain Tank 21A Drain to Header Components downstream of the control valve in this line have been replaced with stainless steel. These components are modeled for continuity.
PEPSE 9321-F-2023 Text19:
2-MSD-158 8
M MSD46A-1-RHDT22A to CV, MSD46A-2-RHDT22A CV to FWH26: Reheater Drain Tank 22A Drain to Header Components downstream of the control valve in this line have been replaced with stainless steel. These components are modeled for continuity.
PEPSE 9321-F-2023 Text19:
2-MSD-159 6
M MSD47-1-RHDT23A to CV, MSD47 RHDT23A CV to FWH26: Reheater Drain Tank 23A Drain to Header PEPSE 9321-F-2023 Text19:
2-MSD-160 10 M
MSD45C-1-RHDT A HDR to FWH26, MSD45C-2-RHDT A HDR to FWH26: Reheater Drain Tank Header PEPSE 9321-F-2023 Text19:
2-MSD-161 10 M
MSD45C-3-RHDT A HDR to FWH26: "A" Reheater Drain Tank Header to #26 FWHs PEPSE 9321-F-2023 Text19:
2-MSD-162 8
M MSD45C-5-RHDT A HDR to FWH26: "A" Reheater Drain Tank Header to FWH 26A and 26B PEPSE 9321-F-2023 Text19:
2-MSD-163 6
M MSD45D-2-RHDT A HDR to FWH26A: "A" Reheater Drain Tank Header to FWH 26A PEPSE 9321-F-2023 Text19:
2-MSD-164 6
M MSD45D-1-RHDT A HDR to FWH26B: "A" Reheater Drain Tank Header to FWH 26B PEPSE 9321-F-2023 Report No. 0700.104-02, Appendix C, Revision 2 Page C-70 of 102
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Moisture Separator Reheater Drains (MSD), Unit 2 Section A: CHECWORKS Model Lines 2-MSD-02: Reheater Drains to #26 Feedwater Heaters and Condensers Line Number Size (in.)
Sus.
Cat.
Comments Reference P&ID No.
Line Description Text19:
2-MSD-165 6
M MSD45C-4-RHDT A HDR to FWH26C: "A" Reheater Drain Tank Header to FWH 26C A portion of this line has been replaced with stainless steel. These components are modeled for continuity.
PEPSE 9321-F-2023 Text19:
2-MSD-166 6
M MSD48A-1-RHDT21B to CV, MSD48B-1-RHDT21B CV to FWH26: Reheater Drain Tank 21B Drain to Header PEPSE 9321-F-2023 Text19:
2-MSD-167 10 M
MSD49A-1-RHDT22B to CV, MSD49B-1-RHDT22B CV to FWH26: Reheater Drain Tank 22B Drain to Header PEPSE 9321-F-2023 Text19:
2-MSD-168 6
M MSD50A-1-RHDT23B to CV, MSD50C-1-RHDT23B CV to FWH26: Reheater Drain Tank 23B Drain to Header PEPSE 9321-F-2023 Text19:
2-MSD-169 8
M MSD48B-2-RHDT B HDR to FWH26: Reheater Drain Tank Header Downstream of Reheater 22B and 23B Inlet PEPSE 9321-F-2023 Text19:
2-MSD-170 10 M
MSD49C-1-RHDT B HDR to FWH26: "B" Reheater Drain Tank Header to #26 FWHs PEPSE 9321-F-2023 Text19:
2-MSD-171 10 M
MSD49C-3-RHDT B HDR: "B" Reheater Drain Tank Header to FWH 26A and 26B PEPSE 9321-F-2023 Text19:
2-MSD-172 6
M MSD49C-5-RHDT B HDR to FWH26A: "B" Reheater Drain Tank Header to FWH 26A PEPSE 9321-F-2023 Text19:
2-MSD-173 6
M MSD49C-4-RHDT B HDR to FWH26B: "B" Reheater Drain Tank Header to FWH 26B PEPSE 9321-F-2023 Report No. 0700.104-02, Appendix C, Revision 2 Page C-71 of 102
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Moisture Separator Reheater Drains (MSD), Unit 2 Section A: CHECWORKS Model Lines 2-MSD-02: Reheater Drains to #26 Feedwater Heaters and Condensers Line Number Size (in.)
Sus.
Cat.
Comments Reference P&ID No.
Line Description Text19:
2-MSD-174 6
M MSD49C-2-RHDT B HDR to FWH26C: "B" Reheater Drain Tank Header to FWH 26C PEPSE 9321-F-2023 Section B: SNM Program Lines 2-MSD-01: Moisture Separator Drains to the Heater Drain Tank and Drains Collecting Tank Line Number Size (in.)
Sus.
Cat.
Comments Reference Mod.
Ex. Crit.
P&ID No.
Line Description Text19:
2-MSD-097 2.5 S
MS Drain Tank 21A vent to MSR Operating conditions unknown.
PEPSE NC 9321-F-2023 Text19:
2-MSD-098 2.5 S
MS Drain Tank 22A vent to MSR Operating conditions unknown.
PEPSE NC 9321-F-2023 Text19:
2-MSD-099 2.5 S
MS Drain Tank 23A vent to MSR Operating conditions unknown.
PEPSE NC 9321-F-2023 Text19:
2-MSD-100 2.5 S
MS Drain Tank 21B vent to MSR Operating conditions unknown.
PEPSE NC 9321-F-2023 Text19:
2-MSD-101 2.5 S
MS Drain Tank 22B vent to MSR Operating conditions unknown.
PEPSE NC 9321-F-2023 Text19:
2-MSD-102 2.5 S
MS Drain Tank 23B vent to MSR Operating conditions unknown.
PEPSE NC 9321-F-2023 Text19:
2-MSD-103-A 6
S MSD33A-1-MSDT 21A to HDT: MS Drain Tank 21A Nozzle to Heater Drain Tank The nozzles are the only susceptible components in this line.
SFA Model NL 9321-F-2023 Text19:
2-MSD-103-C 6
S MSD33A-1-MSDT 21A to HDT:
Heater Drain Tank Nozzle from MS Drain Tank 21A The nozzles are the only susceptible components in this line.
SFA Model NL 9321-F-2023 Text19:
2-MSD-104-A 6
S MSD34A-1-MSDT 22A to HDT: MS Drain Tank 22A Nozzle to Heater Drain Tank The nozzles are the only susceptible components in this line.
SFA Model NL 9321-F-2023 Text19:
2-MSD-104-C 6
S MSD34A-1-MSDT 22A to HDT:
Heater Drain Tank Nozzle from MS Drain Tank 22A The nozzles are the only susceptible components in this line.
SFA Model NL 9321-F-2023 Report No. 0700.104-02, Appendix C, Revision 2 Page C-72 of 102
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Moisture Separator Reheater Drains (MSD), Unit 2 Section B: SNM Program Lines 2-MSD-01: Moisture Separator Drains to the Heater Drain Tank and Drains Collecting Tank Line Number Size (in.)
Sus.
Cat.
Comments Reference Mod.
Ex. Crit.
P&ID No.
Line Description Text19:
2-MSD-105-A 6
S MSD35A-1-MSDT 23A to HDT: MS Drain Tank 23A Nozzle to Heater Drain Tank The nozzles are the only susceptible components in this line.
SFA Model NL 9321-F-2023 Text19:
2-MSD-105-C 6
S MSD35A-1-MSDT 23A to HDT:
Heater Drain Tank Nozzle from MS Drain Tank 23A The nozzles are the only susceptible components in this line.
SFA Model NL 9321-F-2023 Text19:
2-MSD-106-A 6
S MSD36A-1-MSDT 21B to HDT: MS Drain Tank 21B Nozzle to Heater Drain Tank The nozzles are the only susceptible components in this line.
SFA Model NL 9321-F-2023 Text19:
2-MSD-106-C 6
S MSD36A-1-MSDT 21B to HDT:
Heater Drain Tank Nozzle from MS Drain Tank 21B The nozzles are the only susceptible components in this line.
SFA Model NL 9321-F-2023 Text19:
2-MSD-107-A 6
S MSD37A-1-MSDT 22B to HDT: MS Drain Tank 22B Nozzle to Heater Drain Tank The nozzles are the only susceptible components in this line.
SFA Model NL 9321-F-2023 Text19:
2-MSD-107-C 6
S MSD37A-1-MSDT 22B to HDT:
Heater Drain Tank Nozzle from MS Drain Tank 22B The nozzles are the only susceptible components in this line.
SFA Model NL 9321-F-2023 Text19:
2-MSD-108-A 6
S MSD38A-1-MSDT 23B to HDT: MS Drain Tank 23B Nozzle to Heater Drain Tank The nozzles are the only susceptible components in this line.
SFA Model NL 9321-F-2023 Text19:
2-MSD-108-C 6
S MSD38A-1-MSDT 23B to HDT:
Heater Drain Tank Nozzle from MS Drain Tank 23B The nozzles are the only susceptible components in this line.
SFA Model NL 9321-F-2023 2-MSD-02: Reheater Drains to #26 Feedwater Heaters and Condensers Line Number Size (in.)
Sus.
Cat.
Comments Reference Mod.
Ex. Crit.
P&ID No.
Line Description Text19:
2-MSD-145 2.5 S
Reheater Drain Tank 21A Vent to MSR Operating conditions unknown.
P&ID NC 9321-F-2023 Report No. 0700.104-02, Appendix C, Revision 2 Page C-73 of 102
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Moisture Separator Reheater Drains (MSD), Unit 2 Section B: SNM Program Lines 2-MSD-02: Reheater Drains to #26 Feedwater Heaters and Condensers Line Number Size (in.)
Sus.
Cat.
Comments Reference Mod.
Ex. Crit.
P&ID No.
Line Description Text19:
2-MSD-146 2.5 S
Reheater Drain Tank 22A Vent to MSR Operating conditions unknown.
P&ID NC 9321-F-2023 Text19:
2-MSD-147 2.5 S
Reheater Drain Tank 23A Vent to MSR Operating conditions unknown.
P&ID NC 9321-F-2023 Text19:
2-MSD-148 2.5 S
Reheater Drain Tank 21B Vent to MSR Operating conditions unknown.
P&ID NC 9321-F-2023 Text19:
2-MSD-149 2.5 S
Reheater Drain Tank 22B Vent to MSR Operating conditions unknown.
P&ID NC 9321-F-2023 Text19:
2-MSD-150 2.5 S
Reheater Drain Tank 23B Vent to MSR Operating conditions unknown.
P&ID NC 9321-F-2023 Text19:
2-MSD-175 8
S Reheater 21A to Condenser 23 Operating conditions unknown.
P&ID NC 9321-F-2023 Text19:
2-MSD-176 8
S Reheater 22A to Condenser 22 Operating conditions unknown.
P&ID NC 9321-F-2023 Text19:
2-MSD-177 8
S Reheater 23A to Condenser 23 Operating conditions unknown.
P&ID NC 9321-F-2023 Text19:
2-MSD-178 6
S Reheater 21B to Condenser 21 Operating conditions unknown.
P&ID NC 9321-F-2023 Text19:
2-MSD-179 6
S Reheater 22B to Condenser 22 Operating conditions unknown.
P&ID NC 9321-F-2023 Text19:
2-MSD-180 6
S Reheater 23B to Condenser 21 Operating conditions unknown.
P&ID NC 9321-F-2023 Section C: Excluded Lines 2-MSD-01: Moisture Separator Drains to the Heater Drain Tank and Drains Collecting Tank Line Number Size (in.)
Sus.
Cat.
Comments Reference FAC Ex. Crit.
P&ID No.
Line Description Text19:
2-MSD-103-B 6
E MSD33A-1-MSDT 21A to HDT: MS Drain Tank 21A Drain to Heater Drain Tank This line has been clad with Stainless Steel.
SFA Model EM 9321-F-2023 Report No. 0700.104-02, Appendix C, Revision 2 Page C-74 of 102
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Moisture Separator Reheater Drains (MSD), Unit 2 Section C: Excluded Lines 2-MSD-01: Moisture Separator Drains to the Heater Drain Tank and Drains Collecting Tank Line Number Size (in.)
Sus.
Cat.
Comments Reference FAC Ex. Crit.
P&ID No.
Line Description Text19:
2-MSD-104-B 6
E MSD34A-1-MSDT 22A to HDT: MS Drain Tank 22A Drain to Heater Drain Tank This line has been clad with Stainless Steel.
SFA Model EM 9321-F-2023 Text19:
2-MSD-105-B 6
E MSD35A-1-MSDT 23A to HDT: MS Drain Tank 23A Drain to Heater Drain Tank This line has been clad with Stainless Steel.
SFA Model EM 9321-F-2023 Text19:
2-MSD-106-B 6
E MSD36A-1-MSDT 21B to HDT: MS Drain Tank 21B Drain to Heater Drain Tank This line has been clad with Stainless Steel.
SFA Model EM 9321-F-2023 Text19:
2-MSD-107-B 6
E MSD37A-1-MSDT 22B to HDT: MS Drain Tank 22B Drain to Heater Drain Tank This line has been clad with Stainless Steel.
SFA Model EM 9321-F-2023 Text19:
2-MSD-108-B 6
E MSD38A-1-MSDT 23B to HDT: MS Drain Tank 23B Drain to Heater Drain Tank This line has been clad with Stainless Steel.
SFA Model EM 9321-F-2023 Text19:
2-MSD-109 6
E MS Drain Tank 21A Drain to Drains Collecting Tank Line operates less than 2% of the time CSI Document 0700.104.C.008 EI 9321-F-2023 Text19:
2-MSD-110 6
E MS Drain Tank 22A Drain to Drains Collecting Tank Line operates less than 2% of the time CSI Document 0700.104.C.008 EI 9321-F-2023 Text19:
2-MSD-111 6
E MS Drain Tank 23A Drain to Drains Collecting Tank Line operates less than 2% of the time CSI Document 0700.104.C.008 EI 9321-F-2023 Text19:
2-MSD-112 6
E MS Drain Tank 21B Drain to Drains Collecting Tank Line operates less than 2% of the time CSI Document 0700.104.C.008 EI 9321-F-2023 Text19:
2-MSD-113 6
E MS Drain Tank 22B Drain to Drains Collecting Tank Line operates less than 2% of the time CSI Document 0700.104.C.008 EI 9321-F-2023 Text19:
2-MSD-114 6
E MS Drain Tank 23B Drain to Drains Collecting Tank Line operates less than 2% of the time CSI Document 0700.104.C.008 EI 9321-F-2023 Report No. 0700.104-02, Appendix C, Revision 2 Page C-75 of 102
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Main Steam Traps (MST), Unit 2 Section B: SNM Program Lines 2-MST-01: Steam Trap Lines from the Main Steam System Line Number Size (in.)
Sus.
Cat.
Comments Reference Mod.
Ex. Crit.
P&ID No.
Line Description Text19:
2-MST-019-A 12 S
Crossunder Steam Trap to Condenser 21 Flow Conditions Unknown PEPSE NC A227780 Text19:
2-MST-020-A 12 S
Crossunder Steam Trap to Condenser 21 Flow Conditions Unknown PEPSE NC A227780 Text19:
2-MST-021-A 12 S
Crossunder Steam Trap to Condenser 22 Flow Conditions Unknown PEPSE NC A227780 Text19:
2-MST-022-A 12 S
Crossunder Steam Trap to Condenser 22 Flow Conditions Unknown PEPSE NC A227780 Text19:
2-MST-023-A 12 S
Crossunder Steam Trap to Condenser 23 Flow Conditions Unknown PEPSE NC A227780 Text19:
2-MST-024-A 12 S
Crossunder Steam Trap to Condenser 23 Flow Conditions Unknown PEPSE NC A227780 Text19:
2-MST-080-A 1.5 S
Main steam to MST-1 High quality main steam line.
PEPSE NS 9321-F-2041 Text19:
2-MST-080-B 1.5 S
MST-1 to Steam Trap Header Operating conditions unknown.
P&ID NS 9321-F-2041 Text19:
2-MST-081-A 1.5 S
Main steam to MST-2 High quality main steam line.
PEPSE NS 9321-F-2041 Text19:
2-MST-081-B 1.5 S
MST-2 to Steam Trap Header Operating conditions unknown.
P&ID NS 9321-F-2041 Text19:
2-MST-082-A 1.5 S
Main steam to MST-3 High quality main steam line.
PEPSE NS 9321-F-2041 Text19:
2-MST-082-B 1.5 S
MST-3 to Steam Trap Header Operating conditions unknown.
P&ID NS 9321-F-2041 Text19:
2-MST-083-A 1.5 S
Main Steam from Drain Pot to MST-4 High quality main steam line.
PEPSE NS 9321-F-2041 Text19:
2-MST-083-B 1
S Main Steam from MS-1-24 US Leakoff to MST-4.
High quality main steam line.
PEPSE NS 9321-F-2041 Text19:
2-MST-083-C S
MST-4 to Steam Trap Header Operating conditions unknown.
P&ID NS 9321-F-2041 Text19:
2-MST-084-A 1.25 S
Main Steam from MS-1-21 US Leakoff to MST-5 High quality main steam line.
PEPSE NS 9321-F-2041 Report No. 0700.104-02, Appendix C, Revision 2 Page C-76 of 102
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Main Steam Traps (MST), Unit 2 Section B: SNM Program Lines 2-MST-01: Steam Trap Lines from the Main Steam System Line Number Size (in.)
Sus.
Cat.
Comments Reference Mod.
Ex. Crit.
P&ID No.
Line Description Text19:
2-MST-084-B 1.25 S
MST-5 to Steam Trap Header Operating conditions unknown.
P&ID NS 9321-F-2041 Text19:
2-MST-085-A 1
S Main Steam from MS-2A US Leakoff to MST-6 High quality main steam line.
PEPSE NS 9321-F-2041 Text19:
2-MST-085-B 1
S Main Steam from MS-1-21 DS Leakoff to MST-6 High quality main steam line.
PEPSE NS 9321-F-2041 Text19:
2-MST-085-C 1
S MST-6 to Steam Trap Header Operating conditions unknown.
P&ID NS 9321-F-2041 Text19:
2-MST-086-A 1
S Main Steam from MS-2A DS Leakoff to MST-8 High quality main steam line.
PEPSE NS 9321-F-2041 Text19:
2-MST-086-B 1
S MST-8 to Steam Trap Header Operating conditions unknown.
P&ID NS 9321-F-2041 Text19:
2-MST-087-A 1
S Main Steam from MS-2B DS Leakoff to MST-9 High quality main steam line.
PEPSE NS 9321-F-2041 Text19:
2-MST-087-B 1
S MST-9 to Steam Trap Header Operating conditions unknown.
P&ID NS 9321-F-2041 Text19:
2-MST-088-A 1
S Main Steam from MS-1-22 DS Leakoff to MST-10 High quality main steam line.
PEPSE NS 9321-F-2041 Text19:
2-MST-088-B 1
S Main Steam from MS-2B US Leakoff to MST-10 High quality main steam line.
PEPSE NS 9321-F-2041 Text19:
2-MST-088-C 1
S MST-10 to Steam Trap Header Operating conditions unknown.
P&ID NS 9321-F-2041 Text19:
2-MST-089-A 1
S Main Steam from MS-1-22 US Leakoff to MST-12 High quality main steam line.
PEPSE NS 9321-F-2041 Text19:
2-MST-089-B 1
S MST-12 to Steam Trap Header Operating conditions unknown.
P&ID NS 9321-F-2041 Text19:
2-MST-090-A 1.25 S
Main Steam from MS-1-23 US Leakoff to MST-13 High quality main steam line.
PEPSE NS 9321-F-2041 Text19:
2-MST-090-B 1.25 S
MST-13 to Steam Trap Header Operating conditions unknown.
P&ID NS 9321-F-2041 Text19:
2-MST-091-A 1
S Main Steam from MS-1-23 DS Leakoff to MST-14 High quality main steam line.
PEPSE NS 9321-F-2041 Report No. 0700.104-02, Appendix C, Revision 2 Page C-77 of 102
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Main Steam Traps (MST), Unit 2 Section B: SNM Program Lines 2-MST-01: Steam Trap Lines from the Main Steam System Line Number Size (in.)
Sus.
Cat.
Comments Reference Mod.
Ex. Crit.
P&ID No.
Line Description Text19:
2-MST-091-B 1
S Main Steam from MS-2C US Leakoff to MST-14 High quality main steam line.
PEPSE NS 9321-F-2041 Text19:
2-MST-091-C 1
S MST-14 to Steam Trap Header Operating conditions unknown.
P&ID NS 9321-F-2041 Text19:
2-MST-092-A 1
S Main Steam from MS-2C DS Leakoff to MST-16 High quality main steam line.
PEPSE NS 9321-F-2041 Text19:
2-MST-092-B 1
S MST-16 to Steam Trap Header Operating conditions unknown.
P&ID NS 9321-F-2041 Text19:
2-MST-093-A 1
S Main Steam from MS-1-24 DS Leakoff to MST-18 High quality main steam line.
PEPSE NS 9321-F-2041 Text19:
2-MST-093-B 1
S Main Steam from MS-2D US Leakoff to MST-18 High quality main steam line.
PEPSE NS 9321-F-2041 Text19:
2-MST-093-C 1
S MST-18 to Steam Trap Header Operating conditions unknown.
P&ID NS 9321-F-2041 Text19:
2-MST-094-A 1
S Main Steam from MS-2D DS Leakoff to MST-20 High quality main steam line.
PEPSE NS 9321-F-2041 Text19:
2-MST-094-B 1
S MST-20 to Steam Trap Header Operating conditions unknown.
P&ID NS 9321-F-2041 Text19:
2-MST-095-A 1.5 S
Main Steam to MST-21 High quality main steam line.
PEPSE NS 9321-F-2041 Text19:
2-MST-095-B 1.5 S
MST-21 to Steam Trap Header Operating conditions unknown.
P&ID NS 9321-F-2041 Text19:
2-MST-096-A 1.5 S
Main Steam to MST-22 High quality main steam line.
PEPSE NS 9321-F-2041 Text19:
2-MST-096-B 1.5 S
MST-22 to Steam Trap Header Operating conditions unknown.
P&ID NS 9321-F-2041 Text19:
2-MST-097-A 1.5 S
Main Steam to MST-23 High quality main steam line.
PEPSE NS 9321-F-2041 Text19:
2-MST-097-B 1.5 S
MST-23 to Steam Trap Header Operating conditions unknown.
P&ID NS 9321-F-2041 Text19:
2-MST-098-A 1
S Exit Nozzle US of Valve MS-90-1 DS of nozzle Chrome-Moly PEPSE NS 9321-F-2041 Text19:
2-MST-099-A 1
S Main Steam to MST-25 via Steam Dump Lines Pressurized line with flow to steam trap.
PEPSE NS 9321-F-2041 Report No. 0700.104-02, Appendix C, Revision 2 Page C-78 of 102
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Main Steam Traps (MST), Unit 2 Section B: SNM Program Lines 2-MST-01: Steam Trap Lines from the Main Steam System Line Number Size (in.)
Sus.
Cat.
Comments Reference Mod.
Ex. Crit.
P&ID No.
Line Description Text19:
2-MST-099-B 1
S MST-25 to Steam Trap Header Operating conditions unknown.
P&ID NS 9321-F-2041 Text19:
2-MST-100-A 1.25 S
Main Steam to MST-26 via Steam Dump Lines Pressurized line with flow to steam trap.
PEPSE NS 9321-F-2042 Text19:
2-MST-100-B 1.25 S
MST-26 to Steam Trap Header Operating conditions unknown.
P&ID NS 9321-F-2042 Text19:
2-MST-101-A 1
S Main Steam to MST-27 via Steam Dump Lines Pressurized line with flow to steam trap.
PEPSE NS 9321-F-2041 Text19:
2-MST-101-B 1
S MST-27 to Steam Trap Header Operating conditions unknown.
P&ID NS 9321-F-2041 Text19:
2-MST-102-A 1.25 S
Main Steam to MST-28 via Steam Dump Lines Pressurized line with flow to steam trap.
PEPSE NS 9321-F-2042 Text19:
2-MST-102-B 1.25 S
MST-28 to Steam Trap Header Operating conditions unknown.
P&ID NS 9321-F-2042 Text19:
2-MST-103-A 1.25 S
Main Steam to MST-29 via Steam Dump Lines Pressurized line with flow to steam trap.
PEPSE NS 9321-F-2042 Text19:
2-MST-103-B 1.25 S
MST-29 to Steam Trap Header Operating conditions unknown.
P&ID NS 9321-F-2042 Text19:
2-MST-104-A 1
S Main Steam to MST-30 High quality main steam line.
PEPSE NS 9321-F-2042 Text19:
2-MST-104-B 1
S MST-30 to Steam Trap Header Operating conditions unknown.
P&ID NS 9321-F-2042 Text19:
2-MST-105-A 1
S Main Steam to MST-31 High quality main steam line.
PEPSE NS 9321-F-2042 Text19:
2-MST-105-B 1
S MST-31 to Header Operating conditions unknown.
P&ID NS 9321-F-2042 Text19:
2-MST-105-D 1
S Header to Steam Trap Header Operating conditions unknown.
P&ID NS 9321-F-2042 Text19:
2-MST-106-A 1
S Main Steam to MST-32 High quality main steam line.
PEPSE NS 9321-F-2042 Text19:
2-MST-106-B 1
S MST-32 to Steam Trap Header Operating conditions unknown.
P&ID NS 9321-F-2042 Text19:
2-MST-107-A 1
S Steam to MST-33 Operating conditions unknown.
SD No. 18.0 NS 9321-F-2042 Text19:
2-MST-107-B 1
S MST-33 to Steam Trap Header Operating conditions unknown.
P&ID NS 9321-F-2042 Report No. 0700.104-02, Appendix C, Revision 2 Page C-79 of 102
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Main Steam Traps (MST), Unit 2 Section B: SNM Program Lines 2-MST-01: Steam Trap Lines from the Main Steam System Line Number Size (in.)
Sus.
Cat.
Comments Reference Mod.
Ex. Crit.
P&ID No.
Line Description Text19:
2-MST-108-A 1.25 S
Main Steam to MST-34 High quality main steam line.
PEPSE NS 9321-F-2042 Text19:
2-MST-108-B 1.25 S
MST-34 to Steam Trap Header Operating conditions unknown.
P&ID NS 9321-F-2042 Text19:
2-MST-109-A 1
S Main Steam to MST-35 High quality main steam line.
PEPSE NS 9321-F-2042 Text19:
2-MST-109-B 1
S MST-35 to Steam Trap Header Operating conditions unknown.
P&ID NS 9321-F-2042 Text19:
2-MST-110-A 1
S Main Steam to MST-36 High quality main steam line.
PEPSE NS 9321-F-2041 Text19:
2-MST-110-B 1
S MST-36 to Steam Trap Header Operating conditions unknown.
P&ID NS 9321-F-2041 Text19:
2-MST-111-A 1
S Main Steam to MST-37 High quality main steam line.
PEPSE NS 9321-F-2042 Text19:
2-MST-111-B 1
S MST-37 to Steam Trap Header Operating conditions unknown.
P&ID NS 9321-F-2042 Text19:
2-MST-112-A 1
S Main Steam to MST-38 High quality main steam line.
PEPSE NS 9321-F-2042 Text19:
2-MST-112-B 1
S MST-38 to Steam Trap Header Operating conditions unknown.
P&ID NS 9321-F-2042 Text19:
2-MST-113-A 1
S Main Steam to MST-39 High quality main steam line.
PEPSE NS 9321-F-2042 Text19:
2-MST-113-B 1
S MST-39 to Header Operating conditions unknown.
P&ID NS 9321-F-2042 Text19:
2-MST-113-D 1.25 S
Header to Steam Trap Header Operating conditions unknown.
P&ID NS 9321-F-2042 Text19:
2-MST-114-A 1
S Main Steam to MST-40 High quality main steam line.
PEPSE NS 9321-F-2042 Text19:
2-MST-114-B 1
S MST-40 to Header Operating conditions unknown.
P&ID NS 9321-F-2042 Text19:
2-MST-115-A 1
S Main Steam to MST-41 High quality main steam line.
PEPSE NS 9321-F-2041 Text19:
2-MST-115-B 1
S MST-41 to Header Operating conditions unknown.
P&ID NS 9321-F-2041 Text19:
2-MST-116-A 1.25 S
Main Steam to MST-42 via Steam Dump Lines Pressurized line with flow to steam trap.
PEPSE NS 9321-F-2042 Text19:
2-MST-116-B 1.25 S
MST-42 to Steam Trap Header Operating conditions unknown.
P&ID NS 9321-F-2042 Report No. 0700.104-02, Appendix C, Revision 2 Page C-80 of 102
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Main Steam Traps (MST), Unit 2 Section B: SNM Program Lines 2-MST-01: Steam Trap Lines from the Main Steam System Line Number Size (in.)
Sus.
Cat.
Comments Reference Mod.
Ex. Crit.
P&ID No.
Line Description Text19:
2-MST-117-A 1.25 S
Main Steam to MST-43 via Steam Dump Lines Pressurized line with flow to steam trap.
PEPSE NS 9321-F-2042 Text19:
2-MST-117-B 1.25 S
MST-43 to Steam Trap Header Operating conditions unknown.
P&ID NS 9321-F-2042 Text19:
2-MST-118-A 1.25 S
Main Steam to MST-44 via Steam Dump Lines Pressurized line with flow to steam trap.
PEPSE NS 9321-F-2042 Text19:
2-MST-118-B 1.25 S
MST-44 to Steam Trap Header Operating conditions unknown.
P&ID NS 9321-F-2042 Text19:
2-MST-119-A 1.25 S
Main Steam to MST-45 via Steam Dump Lines Pressurized line with flow to steam trap.
PEPSE NS 9321-F-2042 Text19:
2-MST-119-B 1.25 S
MST-45 to Steam Trap Header Operating conditions unknown.
P&ID NS 9321-F-2042 Text19:
2-MST-120-A 1
S Main Steam to MST-46 via Steam Dump Lines Pressurized line with flow to steam trap.
PEPSE NS 9321-F-2042 Text19:
2-MST-120-B 1
S MST-46 to Steam Trap Header Operating conditions unknown.
P&ID NS 9321-F-2042 Text19:
2-MST-121-A 1
S Main Steam to MST-47 via Steam Dump Lines Pressurized line with flow to steam trap.
PEPSE NS 9321-F-2042 Text19:
2-MST-121-B 1
S MST-47 to Steam Trap Header Operating conditions unknown.
P&ID NS 9321-F-2042 Text19:
2-MST-122-A 1
S Main Steam to MST-48 High quality main steam line.
PEPSE NS 9321-F-2042 Text19:
2-MST-122-B 1
S MST-48 to Steam Trap Header Operating conditions unknown.
P&ID NS 9321-F-2042 Text19:
2-MST-123-A 1
S Main Steam to MST-49 High quality main steam line.
PEPSE NS 9321-F-2042 Text19:
2-MST-123-B 1
S MST-49 to Steam Trap Header Operating conditions unknown.
P&ID NS 9321-F-2042 Text19:
2-MST-124-A 1
S Main Steam to MST-50 High quality main steam line.
PEPSE NS 9321-F-2042 Text19:
2-MST-124-B 1
S MST-50 to Steam Trap Header Operating conditions unknown.
P&ID NS 9321-F-2042 Text19:
2-MST-125-A 1
S Main Steam to MST-51 High quality main steam line.
PEPSE NS 9321-F-2042 Text19:
2-MST-125-B 1
S MST-51 to Steam Trap Header Operating conditions unknown.
P&ID NS 9321-F-2042 Report No. 0700.104-02, Appendix C, Revision 2 Page C-81 of 102
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Main Steam Traps (MST), Unit 2 Section B: SNM Program Lines 2-MST-01: Steam Trap Lines from the Main Steam System Line Number Size (in.)
Sus.
Cat.
Comments Reference Mod.
Ex. Crit.
P&ID No.
Line Description Text19:
2-MST-126-A 1
S Main Steam to MST-52 High quality main steam line.
PEPSE NS 9321-F-2042 Text19:
2-MST-126-B 1
S MST-52 to Steam Trap Header Operating conditions unknown.
P&ID NS 9321-F-2042 Text19:
2-MST-127-A 1
S Steam to MST-56 Operating conditions unknown.
SD No. 18.0 NS 9321-F-2042 Text19:
2-MST-127-B 1
S MST-56 to Steam Trap Header Operating conditions unknown.
P&ID NS 9321-F-2042 Text19:
2-MST-128-A 1
S Steam to MST-57 Operating conditions unknown.
SD No. 18.0 NS 9321-F-2042 Text19:
2-MST-128-B 1
S MST-57 to Steam Trap Header Operating conditions unknown.
P&ID NS 9321-F-2042 Text19:
2-MST-129-A 1
S Steam to MST-58 Operating conditions unknown.
SD No. 18.0 NS 9321-F-2042 Text19:
2-MST-129-B 1
S MST-58 to Steam Trap Header Operating conditions unknown.
P&ID NS 9321-F-2042 Text19:
2-MST-130-A 1
S Steam to MST-59 Operating conditions unknown.
SD No. 18.0 NS 9321-F-2042 Text19:
2-MST-130-B 1
S MST-59 to Steam Trap Header Operating conditions unknown.
P&ID NS 9321-F-2042 Text19:
2-MST-131-A 1
S Steam to MST-60 Operating conditions unknown.
SD No. 18.0 NS 9321-F-2042 Text19:
2-MST-131-B 1
S MST-60 to Header Operating conditions unknown.
P&ID NS 9321-F-2042 Text19:
2-MST-132-A 1
S Steam to MST-61 Operating conditions unknown.
SD No. 18.0 NS 9321-F-2042 Text19:
2-MST-132-B 1
S MST-61 to Steam Trap Header Operating conditions unknown.
P&ID NS 9321-F-2042 Text19:
2-MST-133-A 1
S Steam to MST-62 Operating conditions unknown.
SD No. 18.0 NS 9321-F-2042 Text19:
2-MST-133-B 1
S MST-62 to Steam Trap Header Operating conditions unknown.
P&ID NS 9321-F-2042 Text19:
2-MST-134-A 1
S Steam to MST-63 Operating conditions unknown.
SD No. 18.0 NS 9321-F-2042 Text19:
2-MST-134-B 1
S MST-63 to Steam Trap Header Operating conditions unknown.
P&ID NS 9321-F-2042 Text19:
2-MST-135-A 1
S Steam to MST-64 High quality main steam line.
PEPSE NS 9321-F-2041 Text19:
2-MST-135-B 1
S MST-64 to Header Operating conditions unknown.
P&ID NS 9321-F-2041 Report No. 0700.104-02, Appendix C, Revision 2 Page C-82 of 102
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Main Steam Traps (MST), Unit 2 Section B: SNM Program Lines 2-MST-01: Steam Trap Lines from the Main Steam System Line Number Size (in.)
Sus.
Cat.
Comments Reference Mod.
Ex. Crit.
P&ID No.
Line Description Text19:
2-MST-136-A 1
S Steam to MST-65 Operating conditions unknown.
SD No. 18.0 NS 9321-F-2041 Text19:
2-MST-136-B 1
S MST-65 to Header Operating conditions unknown.
P&ID NS 9321-F-2041 Text19:
2-MST-193-A 0.75 S
Main Steam to MST-100 High quality main steam line.
PEPSE NQ A227780 Text19:
2-MST-193-B 0.75 S
MST-100 to Steam Trap Header Operating conditions unknown.
P&ID NS A227780 Section C: Excluded Lines 2-MST-01: Steam Trap Lines from the Main Steam System Line Number Size (in.)
Sus.
Cat.
Comments Reference FAC Ex. Crit.
P&ID No.
Line Description Text19:
2-MST-019-B 10 E
Crossunder Steam Trap Bypass Line
& LP Turbine Steam Dump SD. 18 states FCV-1206 is closed until air is actuated to the operator upon a turbine trip or loss of electrical loading.
SD No. 18.0 EI A227780 Text19:
2-MST-020-B 10 E
Crossunder Steam Trap Bypass Line
& LP Turbine Steam Dump SD. 18 states FCV-1207 is closed until air is actuated to the operator upon a turbine trip or loss of electrical loading.
SD No. 18.0 EI A227780 Text19:
2-MST-021-B 10 E
Crossunder Steam Trap Bypass Line
& LP Turbine Steam Dump SD. 18 states FCV-1208 is closed until air is actuated to the operator upon a turbine trip or loss of electrical loading.
SD No. 18.0 EI A227780 Text19:
2-MST-022-B 10 E
Crossunder Steam Trap Bypass Line
& LP Turbine Steam Dump SD. 18 states FCV-1209 is closed until air is actuated to the operator upon a turbine trip or loss of electrical loading.
SD No. 18.0 EI A227780 Text19:
2-MST-023-B 10 E
Crossunder Steam Trap Bypass Line
& LP Turbine Steam Dump SD. 18 states FCV-1210 is closed until air is actuated to the operator upon a turbine trip or loss of electrical loading.
SD No. 18.0 EI A227780 Text19:
2-MST-024-B 10 E
Crossunder Steam Trap Bypass Line
& LP Turbine Steam Dump SD. 18 states FCV-1211 is closed until air is actuated to the operator upon a turbine trip or loss of electrical loading.
SD No. 18.0 EI A227780 Report No. 0700.104-02, Appendix C, Revision 2 Page C-83 of 102
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Main Steam Traps (MST), Unit 2 Section C: Excluded Lines 2-MST-01: Steam Trap Lines from the Main Steam System Line Number Size (in.)
Sus.
Cat.
Comments Reference FAC Ex. Crit.
P&ID No.
Line Description Text19:
2-MST-073 0.5 E
Aux. Feed Pump Turbine Drive Drain via MST-69 The Aux. Feed Turbine operates less than 2% of the time.
SD No. 21.0 EI 9321-F-2041 Text19:
2-MST-074 0.75 E
Aux. Feed Pump Turbine Drive Drain via MST-68 The Aux. Feed Turbine operates less than 2% of the time.
SD No. 21.0 EI 9321-F-2041 Text19:
2-MST-075 0.75 E
Aux. Feed Pump Turbine Drive Drain via MST-67 The Aux. Feed Turbine operates less than 2% of the time.
SD No. 21.0 EI 9321-F-2041 Text19:
2-MST-080-C E
MST-1 Bypass Line Valve shown closed on P&ID.
P&ID EI 9321-F-2041 Text19:
2-MST-080-D 1.5 E
MST-1 Bypass Line to Steam Trap Header Valve shown closed on P&ID.
P&ID EI 9321-F-2041 Text19:
2-MST-080-E E
MS-91A Bypass Line Valve shown closed on P&ID.
P&ID EI 9321-F-2041 Text19:
2-MST-081-C E
MST-2 Bypass Line Valve shown closed on P&ID.
P&ID EI 9321-F-2041 Text19:
2-MST-081-D 1.5 E
MST-2 Bypass Line to Steam Trap Header Valve shown closed on P&ID.
P&ID EI 9321-F-2041 Text19:
2-MST-081-E 0.75 E
MS-91B Bypass Line Valve shown closed on P&ID.
P&ID EI 9321-F-2041 Text19:
2-MST-082-C E
MST-3 Bypass Line Valve shown closed on P&ID.
P&ID EI 9321-F-2041 Text19:
2-MST-082-D 1.5 E
MST-3 Bypass Line to Steam Trap Header Valve shown closed on P&ID.
P&ID EI 9321-F-2041 Text19:
2-MST-082-E 0.75 E
MS-91C Bypass Line Valve shown closed on P&ID.
P&ID EI 9321-F-2041 Text19:
2-MST-083-D E
MST-4 Bypass Line Valve shown closed on P&ID.
P&ID EI 9321-F-2041 Text19:
2-MST-083-E 1.5 E
MST-4 Bypass Line to Steam Trap Header Valve shown closed on P&ID.
P&ID EI 9321-F-2041 Text19:
2-MST-083-F 0.75 E
MS-91D Bypass Line Valve shown closed on P&ID.
P&ID EI 9321-F-2041 Text19:
2-MST-084-C E
MST-5 Bypass Line Valve shown closed on P&ID.
P&ID EI 9321-F-2041 Text19:
2-MST-085-D E
MST-6 Bypass Line Valve shown closed on P&ID.
P&ID EI 9321-F-2041 Report No. 0700.104-02, Appendix C, Revision 2 Page C-84 of 102
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Main Steam Traps (MST), Unit 2 Section C: Excluded Lines 2-MST-01: Steam Trap Lines from the Main Steam System Line Number Size (in.)
Sus.
Cat.
Comments Reference FAC Ex. Crit.
P&ID No.
Line Description Text19:
2-MST-085-E 3
E MST-6 Drain to Steam Trap Header Valve shown closed on P&ID.
P&ID EI 9321-F-2041 Text19:
2-MST-086-C E
MST-8 Bypass Line Valve shown closed on P&ID.
P&ID EI 9321-F-2041 Text19:
2-MST-087-C E
MST-9 Bypass Line Valve shown closed on P&ID.
P&ID EI 9321-F-2041 Text19:
2-MST-088-D E
MST-10 Bypass Line Valve shown closed on P&ID.
P&ID EI 9321-F-2041 Text19:
2-MST-088-E 1
E MST-10 Bypass to Steam Trap Header Valve shown closed on P&ID.
P&ID EI 9321-F-2041 Text19:
2-MST-089-C E
MST-12 Bypass Line Valve shown closed on P&ID.
P&ID EI 9321-F-2041 Text19:
2-MST-090-C 1.25 E
MST-13 Bypass Line Valve shown closed on P&ID.
P&ID EI 9321-F-2041 Text19:
2-MST-091-D E
MST-14 Bypass Line Valve shown closed on P&ID.
P&ID EI 9321-F-2041 Text19:
2-MST-091-E 0.5 E
MST-14 Drain to Drain Header Valve shown closed on P&ID.
P&ID EI 9321-F-2041 Text19:
2-MST-092-C E
MST-16 Bypass Line Valve shown closed on P&ID.
P&ID EI 9321-F-2041 Text19:
2-MST-093-D E
MST-18 Bypass Line Valve shown closed on P&ID.
P&ID EI 9321-F-2041 Text19:
2-MST-093-E 1
E MST-18 Drain to Drain Header Valve shown closed on P&ID.
P&ID EI 9321-F-2041 Text19:
2-MST-094-C E
MST-20 Bypass Line Valve shown closed on P&ID.
P&ID EI 9321-F-2041 Text19:
2-MST-095-C E
MST-21 Bypass Line Valve shown closed on P&ID.
P&ID EI 9321-F-2041 Text19:
2-MST-096-C E
MST-22 Bypass Line Valve shown closed on P&ID.
P&ID EI 9321-F-2041 Text19:
2-MST-097-C E
MST-23 Bypass Line Valve shown closed on P&ID.
P&ID EI 9321-F-2041 Text19:
2-MST-098 1
E MST-24 Steam Trap Line Piping is CrMo.
2-MST-099-C E
MST-25 Bypass Line Valve shown closed on P&ID.
P&ID EI 9321-F-2041 Text19:
2-MST-100-C 1.25 E
MST-26 Bypass Line Valve normally closed.
P&ID EI 9321-F-2042 Text19:
2-MST-101-C E
MST-27 Bypass Line Valve shown closed on P&ID.
P&ID EI 9321-F-2041 Report No. 0700.104-02, Appendix C, Revision 2 Page C-85 of 102
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Main Steam Traps (MST), Unit 2 Section C: Excluded Lines 2-MST-01: Steam Trap Lines from the Main Steam System Line Number Size (in.)
Sus.
Cat.
Comments Reference FAC Ex. Crit.
P&ID No.
Line Description Text19:
2-MST-102-C E
MST-28 Bypass Line Valve normally closed.
P&ID EI 9321-F-2042 Text19:
2-MST-103-C E
MST-29 Bypass Line Valve normally closed.
P&ID EI 9321-F-2042 Text19:
2-MST-104-C E
MST-30 Bypass Line Valve normally closed.
P&ID EI 9321-F-2042 Text19:
2-MST-105-C E
MST-31 Bypass Line Valve normally closed.
P&ID EI 9321-F-2042 Text19:
2-MST-106-C E
MST-32 Bypass Line Valve normally closed.
P&ID EI 9321-F-2042 Text19:
2-MST-107-C E
MST-33 Bypass Line Valve normally closed.
P&ID EI 9321-F-2042 Text19:
2-MST-108-C E
MST-34 Bypass Line Valve normally closed.
P&ID EI 9321-F-2042 Text19:
2-MST-109-C E
MST-35 Bypass Line Valve normally closed.
P&ID EI 9321-F-2042 Text19:
2-MST-110-C E
MST-36 Bypass Line Valve shown closed on P&ID.
P&ID EI 9321-F-2041 Text19:
2-MST-111-C E
MST-37 Bypass Line Valve normally closed.
P&ID EI 9321-F-2042 Text19:
2-MST-112-C E
MST-38 Bypass Line Valve normally closed.
P&ID EI 9321-F-2042 Text19:
2-MST-113-C E
MST-39 Bypass Line Valve normally closed.
P&ID EI 9321-F-2042 Text19:
2-MST-114-C E
MST-40 Bypass Line Valve normally closed.
P&ID EI 9321-F-2042 Text19:
2-MST-115-C E
MST-41 Bypass Line Valve shown closed on P&ID.
P&ID EI 9321-F-2041 Text19:
2-MST-116-C E
MST-42 Bypass Line Valve normally closed.
P&ID EI 9321-F-2042 Text19:
2-MST-117-C E
MST-43 Bypass Line Valve normally closed.
P&ID EI 9321-F-2042 Text19:
2-MST-118-C E
MST-44 Bypass Line Valve normally closed.
P&ID EI 9321-F-2042 Text19:
2-MST-119-C E
MST-45 Bypass Line Valve normally closed.
P&ID EI 9321-F-2042 Text19:
2-MST-120-C E
MST-46 Bypass Line Valve normally closed.
P&ID EI 9321-F-2042 Text19:
2-MST-121-C E
MST-47 Bypass Line Valve normally closed.
P&ID EI 9321-F-2042 Report No. 0700.104-02, Appendix C, Revision 2 Page C-86 of 102
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Main Steam Traps (MST), Unit 2 Section C: Excluded Lines 2-MST-01: Steam Trap Lines from the Main Steam System Line Number Size (in.)
Sus.
Cat.
Comments Reference FAC Ex. Crit.
P&ID No.
Line Description Text19:
2-MST-122-C E
MST-48 Bypass Line Valve normally closed.
P&ID EI 9321-F-2042 Text19:
2-MST-123-C E
MST-49 Bypass Line Valve normally closed.
P&ID EI 9321-F-2042 Text19:
2-MST-124-C E
MST-50 Bypass Line Valve normally closed.
P&ID EI 9321-F-2042 Text19:
2-MST-125-C E
MST-51 Bypass Line Valve normally closed.
P&ID EI 9321-F-2042 Text19:
2-MST-126-C E
MST-52 Bypass Line Valve normally closed.
P&ID EI 9321-F-2042 Text19:
2-MST-127-C E
MST-56 Bypass Line Valve normally closed.
P&ID EI 9321-F-2042 Text19:
2-MST-128-C E
MST-57 Bypass Line Valve normally closed.
P&ID EI 9321-F-2042 Text19:
2-MST-129-C E
MST-58 Bypass Line Valve normally closed.
P&ID EI 9321-F-2042 Text19:
2-MST-130-C E
MST-59 Bypass Line Valve normally closed.
P&ID EI 9321-F-2042 Text19:
2-MST-131-C E
MST-60 Bypass Line Valve normally closed.
P&ID EI 9321-F-2042 Text19:
2-MST-132-C E
MST-61 Bypass Line Valve normally closed.
P&ID EI 9321-F-2042 Text19:
2-MST-133-C E
MST-62 Bypass Line Valve normally closed.
P&ID EI 9321-F-2042 Text19:
2-MST-134-C E
MST-63 Bypass Line Valve normally closed.
P&ID EI 9321-F-2042 Text19:
2-MST-135-C E
MST-64 Bypass Line Valve shown closed on P&ID.
P&ID EI 9321-F-2041 Text19:
2-MST-136-C E
MST-65 Bypass Line Valve shown closed on P&ID.
P&ID EI 9321-F-2041 Text19:
2-MST-137 1
E MST-66 Lines Scavenging steam piping removed from service.
P&ID ER 9321-F-2041 Text19:
2-MST-138 3
E Main Steam Trap Drain and Bypass Header.
All feeding valves shown normally closed on P&ID P&ID EI 9321-F-2041 Text19:
2-MST-139 4
E Main Steam Trap Main Header to Drains Collecting Tank.
Line replaced with Stainless Steel FAC Program Plan Supplement EM 9321-F-2041, 9321-F-2042 Report No. 0700.104-02, Appendix C, Revision 2 Page C-87 of 102
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Main Steam Traps (MST), Unit 2 Section C: Excluded Lines 2-MST-01: Steam Trap Lines from the Main Steam System Line Number Size (in.)
Sus.
Cat.
Comments Reference FAC Ex. Crit.
P&ID No.
Line Description Text19:
2-MST-140 2
E Main Steam Traps Header to Main Header Line replaced with Stainless Steel FAC Program Plan Supplement EM 9321-F-2042 Text19:
2-MST-141 2
E Main Steam Traps Header to Main Header Line replaced with Stainless Steel FAC Program Plan Supplement EM 9321-F-2042 Text19:
2-MST-142 4
E Main Steam Traps Main Header Drain to Discharge Tunnel Valve shown closed on P&ID.
P&ID EI 9321-F-2042 Text19:
2-MST-196 0.75 E
MST-100 Bypass via MS-1144 Valve shown closed on P&ID.
P&ID EI A227780 Report No. 0700.104-02, Appendix C, Revision 2 Page C-88 of 102
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Moisture Preseparator Drains (PD), Unit 2 Section A: CHECWORKS Model Lines 2-PD-01: Moisture Preseparator Drain Lines Line Number Size (in.)
Sus.
Cat.
Comments Reference P&ID No.
Line Description Text19:
2-PD-001 20 M
Moisture Preseparator "A" to Separating Tank A PEPSE A228272 Text19:
2-PD-002 20 M
Moisture Preseparator "B" to Separating Tank A PEPSE A228272 Text19:
2-PD-003 20 M
Moisture Preseparator "C" to Separating Tank B PEPSE A228272 Text19:
2-PD-004 20 M
Moisture Preseparator "D" to Separating Tank B PEPSE A228272 Text19:
2-PD-011 10 M
Separating Tank A Drain to Control Valves PEPSE A228272 Text19:
2-PD-012 10 M
Separating Tank B Drain to Control Valves PEPSE A228272 Text19:
2-PD-013 10 M
Separating Tank A to LCV 5198 PEPSE A228272 Text19:
2-PD-014 10 M
Separating Tank A to LCV 5199 PEPSE A228272 Text19:
2-PD-015 10 M
Separating Tank B to LCV 5205 PEPSE A228272 Text19:
2-PD-016 10 M
Separating Tank B to LCV 5206 PEPSE A228272 Text19:
2-PD-017 10 M
Separating Tank A control valves to Heater Drain Tank PEPSE A228272 Text19:
2-PD-018 10 M
Separating Tank B control valves to Heater Drain Tank PEPSE A228272 Report No. 0700.104-02, Appendix C, Revision 2 Page C-89 of 102
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Moisture Preseparator Drains (PD), Unit 2 Section B: SNM Program Lines 2-PD-01: Moisture Preseparator Drain Lines Line Number Size (in.)
Sus.
Cat.
Comments Reference Mod.
Ex. Crit.
P&ID No.
Line Description Text19:
2-PD-005 3
S Moisture Preseparator "A" to 20" Line Flow Rate unknown.
PEPSE NC A228272 Text19:
2-PD-006 3
S Moisture Preseparator "B" to 20" Line Flow Rate unknown.
PEPSE NC A228272 Text19:
2-PD-007 3
S Moisture Preseparator "C" to 20" Line Flow Rate unknown.
PEPSE NC A228272 Text19:
2-PD-008 3
S Moisture Preseparator "D" to 20" Line Flow Rate unknown.
PEPSE NC A228272 Text19:
2-PD-009-A 20 S
ES7A-1-SEP TKA VNT to FWH25:
Separating Tank A Nozzle to Extraction Steam Header The nozzle is the only susceptible component in this line.
SFA Model NL A228272 Text19:
2-PD-010-A 20 S
ES7A-2-SEP TKB VNT to FWH25:
Separating Tank B Nozzle to Extraction Steam Header The nozzle is the only susceptible component in this line.
SFA Model NL A228272 Section C: Excluded Lines 2-PD-01: Moisture Preseparator Drain Lines Line Number Size (in.)
Sus.
Cat.
Comments Reference FAC Ex. Crit.
P&ID No.
Line Description Text19:
2-PD-009-B 20 E
ES7A-1-SEP TKA VNT to FWH25:
Separating Tank A to Extraction Steam Header This line was replaced with stainless steel in RFO13.
SFA Model EM A228272 Text19:
2-PD-010-B 20 E
ES7A-2-SEP TKB VNT to FWH25:
Separating Tank B to Extraction Steam Header This line was replaced with stainless steel in RFO13.
SFA Model EM A228272 Text19:
2-PD-019 1
E 1" Line from Separating Tank B Vent to Extraction header.
Valve shown closed on P&ID.
P&ID EI A228272 Report No. 0700.104-02, Appendix C, Revision 2 Page C-90 of 102
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Reheat Steam Traps (RST), Unit 2 Section B: SNM Program Lines 2-RST-01: Reheat Steam Trap Lines Downstream of Reheater Steam Traps Line Number Size (in.)
Sus.
Cat.
Comments Reference Mod.
Ex. Crit.
P&ID No.
Line Description Text19:
2-RST-001 0.75 S
RST-1 to BFP Turbine Drip Tank Header Operating conditions unknown.
PEPSE NS 9321-H-2024 Text19:
2-RST-002 0.75 S
RST-2 to BFP Turbine Drip Tank Header Operating conditions unknown.
PEPSE NS 9321-H-2024 Text19:
2-RST-003 0.75 S
RST-3 to BFP Turbine Drip Tank Header Operating conditions unknown.
PEPSE NS 9321-H-2024 Text19:
2-RST-004 2
S Reheat Steam Trap Header to BFP Turbine Drip Tank Operating conditions unknown.
PEPSE NS 9321-H-2024 Report No. 0700.104-02, Appendix C, Revision 2 Page C-91 of 102
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Service Boiler (SB), Unit 2 Section B: SNM Program Lines 2-SB-01: Service Boiler Lines Line Number Size (in.)
Sus.
Cat.
Comments Reference Mod.
Ex. Crit.
P&ID No.
Line Description Text19:
2-SB-001 6
S Auxiliary Steam from PCV-1015 Operating conditions unknown.
P&ID NC A227780, A209775 Text19:
2-SB-004 2
S Steam to Condensate Return, Hot Water Heat Exchangers, and Office Unit Heaters Operating conditions unknown.
P&ID NS 9321-F-2120 Text19:
2-SB-005 2
S Steam to Hot Water Heat Exchangers and Office Unit Heaters Operating conditions unknown.
P&ID NS 9321-F-2120 Text19:
2-SB-011 1
S Header Drain to AST-35 Operating conditions unknown.
P&ID NS 9321-F-2120 Text19:
2-SB-012 1.5 S
Steam to Office Unit Heaters Operating conditions unknown.
P&ID NS 9321-F-2120 Text19:
2-SB-015 8
S Steam from Aux. Steam Header Operating conditions unknown.
P&ID NC A209775 Text19:
2-SB-016 8
S Desuperheater Header Operating conditions unknown.
P&ID NC A209775 Text19:
2-SB-022 2
S Steam trap header to Cond. Receiver Operating conditions unknown.
P&ID NS A209775 Text19:
2-SB-023 4
S Header to Steam Traps Operating conditions unknown.
P&ID NC A209775 Text19:
2-SB-026 1
S Desuperheater Header Operating conditions unknown.
P&ID NS A209775 Text19:
2-SB-030 8
S Steam to Desuperheater Operating conditions unknown.
P&ID NC A209775 Text19:
2-SB-039 4
S Service Boiler Header to Air Tempering Units Operating conditions unknown.
P&ID NC A209775 Text19:
2-SB-042 6
S Line from #10 House Service Boiler Deaerator Operating conditions unknown.
P&ID NC 9321-F-2021, B193201 Text19:
2-SB-043 1.5 S
Line from #10 House Service Boiler Deaerator Operating conditions unknown.
P&ID NS 9321-F-2021, B193201 Report No. 0700.104-02, Appendix C, Revision 2 Page C-92 of 102
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Service Boiler (SB), Unit 2 Section C: Excluded Lines 2-SB-01: Service Boiler Lines Line Number Size (in.)
Sus.
Cat.
Comments Reference FAC Ex. Crit.
P&ID No.
Line Description Text19:
2-SB-010 1
E Cross Tie Between 2-SB-005 and 2-SB-007 Valve shown closed on P&ID.
P&ID EI 9321-F-2120 Text19:
2-SB-029 0.5 E
Desuperheater bypass Operating conditions unknown.
P&ID EI A209775 Text19:
2-SB-031 8
E PCV-1257 Bypass Valve shown closed on P&ID.
P&ID EI A209775 Text19:
2-SB-034 2
E Steam to floor drain via UH-575 Low flow to floor drain P&ID EF A209775 Text19:
2-SB-040 1
E PCV-1252 Bypass Valve shown closed on P&ID.
P&ID EI A209775 Text19:
2-SB-041 2
E Steam to UHT-514 Valve shown closed on P&ID.
P&ID EI A209775 Text19:
2-SB-044 1
E TCV-1257-B Bypass Line Valve shown closed on P&ID.
P&ID EI A209775 Text19:
2-SB-045 1
E TCV-1257-A Bypass Line Valve shown closed on P&ID.
P&ID EI A209775 Text19:
2-SB-046 2
E Floor Drain via UH-571 Valve shown closed on P&ID.
P&ID EI A209775 Text19:
2-SB-047 3
E Aux. Steam to Condenser Water Box Priming Steam Jet Air Ejectors Valve shown closed on P&ID.
P&ID EI A209775 Report No. 0700.104-02, Appendix C, Revision 2 Page C-93 of 102
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Condensate Return Unit Heaters to Service Boiler D (UH), Unit 2 Section B: SNM Program Lines 2-UH-01: Condensate Return from Unit Heaters to the Deaerator Line Number Size (in.)
Sus.
Cat.
Comments Reference Mod.
Ex. Crit.
P&ID No.
Line Description Text19:
2-UH-001 4
S Condensate return pumps to #20 House Service Deaerator Operating conditions unknown.
P&ID NC A209775, 9321-F-2120 Text19:
2-UH-002 4
S Condensate return to #10 House Service Deaerator Operating conditions unknown.
P&ID NC 9321-F-2120, B193201 Text19:
2-UH-003 10 S
Desuperheater outlet header to various unit heaters Operating conditions unknown.
SD No. 29.01 NC A209775 Text19:
2-UH-004 8
S Desuperheater outlet steam to Gland Seal Steam Header Operating conditions unknown.
SD No. 29.01 NC A209775 Text19:
2-UH-071 6
S Unit Heater Drain Header to Condensate Receiver Operating conditions unknown.
P&ID NC A209775 Text19:
2-UH-072 6
S Unit Heater Drain Header to Condensate Receiver Operating conditions unknown.
P&ID NC A209775 Text19:
2-UH-073 4
S Condensate Receiver Vent to Atmosphere Operating conditions unknown.
P&ID NC A209775 Text19:
2-UH-074 3
S Condensate Receiver Drain to Cond.
Return Pump #21 Operating conditions unknown.
P&ID NC A209775 Text19:
2-UH-075 3
S Condensate Receiver Drain to Cond.
Return Pump #22 Operating conditions unknown.
P&ID NC A209775 Text19:
2-UH-077 4
S Cond. Return Pump #21 Discharge Operating conditions unknown.
P&ID NC A209775 Text19:
2-UH-078 4
S Cond. Return Pump #21 Discharge Operating conditions unknown.
P&ID NC A209775 Text19:
2-UH-079 2
S Line from #20 House Service Boiler to Service Boiler Deaerator Operating conditions unknown.
P&ID NS B193201 Report No. 0700.104-02, Appendix C, Revision 2 Page C-94 of 102
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Condensate Return Unit Heaters to Service Boiler D (UH), Unit 2 Section C: Excluded Lines 2-UH-01: Condensate Return from Unit Heaters to the Deaerator Line Number Size (in.)
Sus.
Cat.
Comments Reference FAC Ex. Crit.
P&ID No.
Line Description Text19:
2-UH-054 2
E Drain line via UH-1103 Valve shown closed on P&ID.
P&ID EI A209775 Text19:
2-UH-055 2
E Steam to and from Dirty and Clean Oil Storage Tanks Valve shown closed on P&ID.
P&ID EI A209775 Text19:
2-UH-076 1
E Condensate Receiver Bottom Drain Valve shown closed on P&ID.
P&ID EI A209775 Text19:
2-UH-080 6
E PC-5289 Bypass Line Valve shown closed on P&ID.
P&ID EI A209775 Report No. 0700.104-02, Appendix C, Revision 2 Page C-95 of 102
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Condensate Return Unit Heater Steam Traps (UHT), Unit 2 Section B: SNM Program Lines 2-UHT-01: Steam Trap Lines from the Condensate Return from Unit Heaters to the Deaerator system Line Number Size (in.)
Sus.
Cat.
Comments Reference Mod.
Ex. Crit.
P&ID No.
Line Description Text19:
2-UHT-005 1
S Steam to UHT-510 Operating conditions unknown.
SD No. 29.01 NC A209775 Text19:
2-UHT-006 1
S Steam to UHT-511 Operating conditions unknown.
SD No. 29.01 NC A209775 Text19:
2-UHT-007 2
S Steam trap header to Cond. Receiver from UHT-510.
Operating conditions unknown.
P&ID NS A209775 Text19:
2-UHT-008 1
S Steam from gland steam supply steam traps Operating conditions unknown.
P&ID NS A209775 Text19:
2-UHT-009 2
S Steam to and from 215UHR Operating conditions unknown.
P&ID NS A209775 Text19:
2-UHT-010 2
S Steam to and from 217UHR Operating conditions unknown.
P&ID NS A209775 Text19:
2-UHT-011 2
S Steam to and from 29UHR Operating conditions unknown.
P&ID NS A209775 Text19:
2-UHT-012 2
S Steam to and from 22UHR Operating conditions unknown.
P&ID NS A209775 Text19:
2-UHT-013 1
S Steam to and from UHT-2-1 Operating conditions unknown.
P&ID NS A209775 Text19:
2-UHT-014 2
S Steam to and from 221UHR Operating conditions unknown. Flow direction is unclear and seems to indicate that no outlet exists.
P&ID NS A209775 Text19:
2-UHT-015 2
S Steam to and from 219UHR Operating conditions unknown. Flow direction is unclear and seems to indicate that no outlet exists.
P&ID NS A209775 Text19:
2-UHT-016 2
S Steam to and from 211UHR Operating conditions unknown. Flow direction is unclear and seems to indicate that no outlet exists.
P&ID NS A209775 Text19:
2-UHT-017 2
S Steam to and from 24UHR Operating conditions unknown. Flow direction is unclear and seems to indicate that no outlet exists.
P&ID NS A209775 Text19:
2-UHT-018 1
S Steam to and from UHT-2-2 Operating conditions unknown. Flow direction is unclear and seems to indicate that no outlet exists.
P&ID NS A209775 Report No. 0700.104-02, Appendix C, Revision 2 Page C-96 of 102
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Condensate Return Unit Heater Steam Traps (UHT), Unit 2 Section B: SNM Program Lines 2-UHT-01: Steam Trap Lines from the Condensate Return from Unit Heaters to the Deaerator system Line Number Size (in.)
Sus.
Cat.
Comments Reference Mod.
Ex. Crit.
P&ID No.
Line Description Text19:
2-UHT-019 2
S Steam to and from 225UHR Operating conditions unknown.
P&ID NS A209775 Text19:
2-UHT-020 2
S Steam to and from 224UHR Operating conditions unknown.
P&ID NS A209775 Text19:
2-UHT-021 2
S Steam to and from 223UHR Operating conditions unknown.
P&ID NS A209775 Text19:
2-UHT-022 2
S Steam to and from 213UHR Operating conditions unknown.
P&ID NS A209775 Text19:
2-UHT-023 2
S Steam to and from 27UHR Operating conditions unknown.
P&ID NS A209775 Text19:
2-UHT-024 1
S Steam to and from UHT-1-1 Operating conditions unknown.
P&ID NS A209775 Text19:
2-UHT-024-A 4
S Steam to UHT-512 and 513 Operating conditions unknown.
P&ID NC A209775 Text19:
2-UHT-025 1
S Steam to and from Oil Preheater Operating conditions unknown. Flow direction is unclear and seems to indicate that no outlet exists.
P&ID NS A209775 Text19:
2-UHT-026 1
S Steam to and from UHT-4-1 Operating conditions unknown. Flow direction is unclear and seems to indicate that no outlet exists.
P&ID NS A209775 Text19:
2-UHT-027 2
S Steam to and from 24AUHR Operating conditions unknown.
P&ID NS A209775 Text19:
2-UHT-028 1.5 S
Steam to and from UHT-2-3 Operating conditions unknown.
P&ID NS A209775 Text19:
2-UHT-029 1
S Steam to and from 248UHR Operating conditions unknown.
P&ID NS A209775 Text19:
2-UHT-030 1
S Steam to and from 250UHR Operating conditions unknown.
P&ID NS A209775 Text19:
2-UHT-031 1
S Steam to and from 249UHR Operating conditions unknown.
P&ID NS A209775 Text19:
2-UHT-032 1
S Steam to and from 252UHR Operating conditions unknown.
P&ID NS A209775 Text19:
2-UHT-033 1
S Steam to and from 251UHR Operating conditions unknown.
P&ID NS A209775 Text19:
2-UHT-034 1
S Steam to and from UHT-11-3 Operating conditions unknown.
P&ID NS A209775 Text19:
2-UHT-035 1
S Steam to and from 247UHR Operating conditions unknown.
P&ID NS A209775 Report No. 0700.104-02, Appendix C, Revision 2 Page C-97 of 102
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Condensate Return Unit Heater Steam Traps (UHT), Unit 2 Section B: SNM Program Lines 2-UHT-01: Steam Trap Lines from the Condensate Return from Unit Heaters to the Deaerator system Line Number Size (in.)
Sus.
Cat.
Comments Reference Mod.
Ex. Crit.
P&ID No.
Line Description Text19:
2-UHT-036 1
S Steam to and from 246UHR Operating conditions unknown.
P&ID NS A209775 Text19:
2-UHT-037 1
S Steam to and from 245UHR Operating conditions unknown.
P&ID NS A209775 Text19:
2-UHT-038 1
S Steam to and from UHT-11-2 Operating conditions unknown.
P&ID NS A209775 Text19:
2-UHT-039 2
S UHT-511 outlet Operating conditions unknown.
P&ID NS A209775 Text19:
2-UHT-040 2
S Steam to and from 214UHR Operating conditions unknown.
P&ID NS A209775 Text19:
2-UHT-041 2
S Steam to and from 216UHR Operating conditions unknown.
P&ID NS A209775 Text19:
2-UHT-042 2
S Steam to and from 218UHR Operating conditions unknown.
P&ID NS A209775 Text19:
2-UHT-043 2
S Steam to and from 220UHR Operating conditions unknown.
P&ID NS A209775 Text19:
2-UHT-044 2
S Steam to and from 222UHR Operating conditions unknown.
P&ID NS A209775 Text19:
2-UHT-045 1
S Steam to and from 260UHR Operating conditions unknown.
P&ID NS A209775 Text19:
2-UHT-046 1
S Steam to and from UHT-4-2 Operating conditions unknown.
P&ID NS A209775 Text19:
2-UHT-047 2
S Steam to and from 21UHR Operating conditions unknown.
P&ID NS A209775 Text19:
2-UHT-048 2
S Steam to and from 28UHR Operating conditions unknown.
P&ID NS A209775 Text19:
2-UHT-049 2
S Steam to and from 23UHR Operating conditions unknown.
P&ID NS A209775 Text19:
2-UHT-050 2
S Steam to and from 210UHR Operating conditions unknown.
P&ID NS A209775 Text19:
2-UHT-051 2
S Steam to and from 212UHR Operating conditions unknown.
P&ID NS A209775 Text19:
2-UHT-052 2
S Steam to and from 25UHR Operating conditions unknown.
P&ID NS A209775 Text19:
2-UHT-053 0.75 S
Steam to and from UHT-11-1 Operating conditions unknown.
P&ID NS A209775 Text19:
2-UHT-056 1
S UHT-513 Discharge Operating conditions unknown.
P&ID NS A209775 Text19:
2-UHT-057 0.5 S
UHT-512 Discharge Operating conditions unknown.
P&ID NS A209775 Report No. 0700.104-02, Appendix C, Revision 2 Page C-98 of 102
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
Condensate Return Unit Heater Steam Traps (UHT), Unit 2 Section B: SNM Program Lines 2-UHT-01: Steam Trap Lines from the Condensate Return from Unit Heaters to the Deaerator system Line Number Size (in.)
Sus.
Cat.
Comments Reference Mod.
Ex. Crit.
P&ID No.
Line Description Text19:
2-UHT-060 0.75 S
21 Air Tempering Unit Discharge Operating conditions unknown.
P&ID NS A209775 Text19:
2-UHT-061 0.75 S
22 Air Tempering Unit Discharge Operating conditions unknown.
P&ID NS A209775 Text19:
2-UHT-062 1
S Steam to various unit heaters Operating conditions unknown.
P&ID NS A209775 Text19:
2-UHT-063 0.75 S
Steam to and from UH-TSC-1 Operating conditions unknown.
P&ID NS A209775 Text19:
2-UHT-064 0.75 S
Steam to and from 242UHR Operating conditions unknown.
P&ID NS A209775 Text19:
2-UHT-065 0.75 S
Steam to and from 243UHR Operating conditions unknown.
P&ID NS A209775 Text19:
2-UHT-066 0.75 S
Steam to and from 244UHR Operating conditions unknown.
P&ID NS A209775 Text19:
2-UHT-067 0.75 S
Steam to and from UHT-8-246 Operating conditions unknown.
P&ID NS A209775 Text19:
2-UHT-068 0.75 S
Steam to and from 253UHR Operating conditions unknown.
P&ID NS A209775 Text19:
2-UHT-069 2
S Unit Heater Drain to Discharge Tunnel Operating conditions unknown.
P&ID NS A209775 Text19:
2-UHT-089 0.75 S
Steam to and from UH-1020 Operating conditions unknown.
P&ID NS B227209 Text19:
2-UHT-090 0.75 S
Steam to and from UH-1019 Operating conditions unknown.
P&ID NS B227209 Text19:
2-UHT-092 0.75 S
Steam to and from UH-1021 Operating conditions unknown.
P&ID NS B227209 Section C: Excluded Lines 2-UHT-01: Steam Trap Lines from the Condensate Return from Unit Heaters to the Deaerator system Line Number Size (in.)
Sus.
Cat.
Comments Reference FAC Ex. Crit.
P&ID No.
Line Description Text19:
2-UHT-070 0.75 E
Line to and from UHT-3-2 Pipe capped upstream of trap.
P&ID ER A209775 Report No. 0700.104-02, Appendix C, Revision 2 Page C-99 of 102
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
MSR Vent Chamber Discharge (VCD), Unit 2 Section C: Excluded Lines 2-VCD-01: Moisture Separator Reheater Vent Chamber Discharge Lines Line Number Size (in.)
Sus.
Cat.
Comments Reference FAC Ex. Crit.
P&ID No.
Line Description Text19:
2-VCD-001 3
E MSR 21A Vent Chamber Discharge Piping replaced with SS.
Previous SSE EM A209847 Text19:
2-VCD-002 3
E MSR 22A Vent Chamber Discharge Piping replaced with SS.
Previous SSE EM A209847 Text19:
2-VCD-003 3
E MSR 23A Vent Chamber Discharge Piping replaced with SS.
Previous SSE EM A209847 Text19:
2-VCD-004 3
E MSR 21B Vent Chamber Discharge Piping replaced with SS.
Previous SSE EM A209847 Text19:
2-VCD-005 3
E MSR 22B Vent Chamber Discharge Piping replaced with SS.
Previous SSE EM A209847 Text19:
2-VCD-006 3
E MSR 23B Vent Chamber Discharge Piping replaced with SS.
Previous SSE EM A209847 Text19:
2-VCD-007 4
E Vent Chamber Discharge Header to FWH 26A Stainless Steel Piping P&ID EM A209847 Text19:
2-VCD-008 4
E Vent Chamber Discharge Header to FWH 26B Stainless Steel Piping P&ID EM A209847 Text19:
2-VCD-009 4
E Vent Chamber Discharge Header to FWH 26C Stainless Steel Piping P&ID EM A209847 Text19:
2-VCD-010-A 3
E MSR 21A VCD through HCV-5067B Stainless Steel Piping P&ID, Replacement History EM A209847 Text19:
2-VCD-010-B 3
E MSR 21A VCD downstream of HCV-5067B Piping replaced with CrMo.
2-VCD-011-A 3
E MSR 22A VCD through HCV-5069B Stainless Steel Piping P&ID, Replacement History EM A209847 Text19:
2-VCD-011-B 3
E MSR 22A VCD downstream of HCV-5069B Piping replaced with CrMo.
2-VCD-012-A 3
E MSR 23A VCD through HCV-5071B Stainless Steel Piping P&ID, Replacement History EM A209847 Text19:
2-VCD-012-B 3
E MSR 23A VCD downstream of HCV-5071B Piping replaced with CrMo.
2-VCD-013-A 3
E MSR 21B VCD through HCV-5068B Stainless Steel Piping P&ID, Replacement History EM A209847 Text19:
2-VCD-013-B 3
E MSR 21B VCD downstream of HCV-5068B Piping replaced with CrMo.
P&ID EM A209847 Report No. 0700.104-02, Appendix C, Revision 2 Page C-100 of 102
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
MSR Vent Chamber Discharge (VCD), Unit 2 Section C: Excluded Lines 2-VCD-01: Moisture Separator Reheater Vent Chamber Discharge Lines Line Number Size (in.)
Sus.
Cat.
Comments Reference FAC Ex. Crit.
P&ID No.
Line Description Text19:
2-VCD-014-A 3
E MSR 22B VCD through HCV-5070B Stainless Steel Piping P&ID, Replacement History EM A209847 Text19:
2-VCD-014-B 3
E MSR 22B VCD downstream of HCV-5070B Piping replaced with CrMo.
2-VCD-015-A 3
E MSR 23B VCD through HCV-5072B Stainless Steel Piping P&ID, Replacement History EM A209847 Text19:
2-VCD-015-B 3
E MSR 23B VCD downstream of HCV-5072B Piping replaced with CrMo.
P&ID EM A209847 Report No. 0700.104-02, Appendix C, Revision 2 Page C-101 of 102
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
CSI TECHNOLOGIES, INC.
FAC Exclusion Criteria (FAC Ex. Crit.) Legend:
EC EF EI EM EO EP EQ ER ET EW Excluded due to Combination of infrequent op above temp threshold Excluded due to low or no Flow Excluded due to Infrequent operation Excluded due to FAC-resistant Material Excluded due to high dissolved Oxygen content Exluded, does not contain Piping Excluded due to high steam Quality Excluded, Removed from service and "cut" and "capped" Excluded due to operating Temperature (single phase, < 200 deg F)
Excluded because system, subsytem, or line is non-Water Susceptibility Category (Sus. Cat.) Legend:
M S
E CHECWORKS Modeled Susceptible, not modeled Excluded from the FAC program (non-susceptible)
Model Exclusion Criteria (Mod. Ex. Crit.) Legend:
NC NL NM NQ NS NV Not modeled due to unknown or varying operating Conditions Not to be modeled due to Localized FAC susceptibility Non-Modelable due to conditions outside CHECWORKS Modeling capabilities Not to be modeled due to high steam Quality, CHECWORKS predictions are of little value Non-modelable due to Socket-welded fittings Not to be modeled because line is Visually inspected Report No. 0700.104-02, Appendix C, Revision 2 Page C-102 of 102
CSI TECHNOLOGIES, INC.
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
Report No. 0700.104-02, Appendix D, Revision 2 Page D-1 of 4 Appendix D Revision History
CSI TECHNOLOGIES, INC.
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
Report No. 0700.104-02, Appendix D, Revision 2 Page D-2 of 4 Revision 0 Initial Issue of document.
Revision 1 Systems, subsystem names, and line names were updated to incorporate the new system list.
Revision 2 SSE was updated to incorporate line replacements. Tables D.1, D.2, and D.3 below detail the changes:
Table D.1 System Changes
MSR Vent Chamber Discharge
Table D.2 Subsystem Changes
2-5EX-03
2-VCD-01
Table D.3 Line Changes
!
""#$%%&
""#$%%&""#$%%&' (
""#$%%"
""#$%%"""#$%%"' (
")#$%*&
!
")#$%**
!
")#$%*+
!
")#$%*)
!
")#$%*,
!
",#$%%&
!
",#$%%&'
",#$%%&
--
CSI TECHNOLOGIES, INC.
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
Report No. 0700.104-02, Appendix D, Revision 2 Page D-3 of 4
!
",#$%%"
!
",#$%%"'
",#$%%"
--
",#$%%*
!
",#$%%+
!
",#$%%)
!
",#$%%,
!
",#$%%,
",#$%%,'
--
",#$%%.
!
",#$%%/
!
",#$%%/
",#$%%/'
--
",#$%%0
!
",#$%&%
!
",#$%&%
",#$%&%'
--
"("%/
!
"("%0
!
"("&%
!
"("&&
!
"("&"
!
"("&*
!
"("&+
!
"("&)
!
"("&,
!
"("&.
!
"("&/
!
"("&0
!
"(""%
!
"(""&
!
"( &%*
!
"( &%*'
"( &%*
--
"( &%*
--
"( &%+
!
"( &%+'
"( &%+
--
"( &%+
--
"( &%)
!
"( &%)'
CSI TECHNOLOGIES, INC.
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
Report No. 0700.104-02, Appendix D, Revision 2 Page D-4 of 4
!
"( &%)
--
"( &%)
--
"( &%,
!
"( &%,'
"( &%,
--
"( &%,
--
"( &%.
!
"( &%.'
"( &%.
--
"( &%.
--
"( &%/
!
"( &%/'
"( &%/
--
"( &%/
--
"1 %%0
!
"1 %%0'
"1 %%0
--
"1 %&%
!
"1 %&%'
"1 %&%
--
CSI TECHNOLOGIES, INC.
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
Report No. 0700.104-02, Attachment A, Revision 2 Page Attach A-1 of 6 Attachment A Industry FAC Experience Table
CSI TECHNOLOGIES, INC.
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
Report No. 0700.104-02, Attachment A, Revision 2 Page Attach A-2 of 6 Industry experience is an important factor in the identification of systems, subsystems, and lines susceptible to Flow-Accelerated Corrosion (FAC). A table of important industry events and their applicability to Indian Point 2 was compiled using the following sources:
- CHUG Plant Experience Database, Revision 2, December 1995.
- 26th CHUG Meeting Presentation by Jeff Horowitz "Review and Lessons Learned from Historical FAC Failures".
- 32th CHUG Meeting Presentation by Doug Munson "Update on Mihama-3".
- 33rd CHUG Meeting Presentation by Aaron Kelley "Results of L2R10 Inspections at LaSalle Unit 2".
- 33rd CHUG Meeting Presentation by Whit Gallman "Unisolable Steam Leak Downstream of Valve 2HM-23".
- CHUG Conference Meeting Minutes, FAC Experience Reports, and Presentations.
- FACnet Email Message Archive.
- Secondary Pipe Rupture (9 August 2004, Mihama Unit 3, Kansai EPC), WANO EAR TYO 04-013, October 8, 2004.
- Information Notice 82-2: Failures in Turbine Exhaust Lines, U.S. Nuclear Regulatory Commission (NRC), July 9, 1982.
- Information Notice 86-106: Feedwater Line Break, U.S. Nuclear Regulatory Commission (NRC), December 16, 1986.
- Information Notice 86-106, Supplement 1: Feedwater Line Break, U.S. Nuclear Regulatory Commission (NRC), February 13, 1987.
- Information Notice 86-106, Supplement 2: Feedwater Line Break, U.S. Nuclear Regulatory Commission (NRC), March 18, 1987.
- NRC Bulletin No. 87-01: Thinning of Pipe Walls in Nuclear Power Plants, U.S.
Nuclear Regulatory Commission (NRC), July 9, 1987.
- Information Notice 87-36, Significant Unexpected Erosion of Feedwater Lines, U.S.
Nuclear Regulatory Commission (NRC), August 4, 1987.
- Information Notice 88-17, Summary of Responses to NRC Bulletin 87-01, Thinning of Pipe Walls in Nuclear Power Plants, U.S. Nuclear Regulatory Commission (NRC),
April 22, 1988.
CSI TECHNOLOGIES, INC.
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
Report No. 0700.104-02, Attachment A, Revision 2 Page Attach A-3 of 6
- Information Notice 86-106, Supplement 3: Feedwater Line Break, U.S. Nuclear Regulatory Commission (NRC), November 10, 1988.
- Erosion/Corrosion-Induced Pipe Wall Thinning, Generic Letter 89-08, U.S. Nuclear Regulatory Commission (NRC), May 2, 1989.
- Investigation into Flow-Accelerated Corrosion at Low Temperatures, Document 1015070, Electric Power Research Institute (EPRI), November 2007.
- Flow-Accelerated Corrosion - The Entrance Effect, Document 1015072, Electric Power Research Institute (EPRI), November 2007.
- Erosive Attack, Technical Update 1015071, Electric Power Research Institute (EPRI),
November 2007.
CSI TECHNOLOGIES, INC.
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
Report No. 0700.104-02, Attachment A, Revision 2 Page Attach A-4 of 6 Item Number System Location/Area Plant Plant Type Year Notes 1
All Downstream of Flow Orifices and Flow Meters Many
- BWR, PWR Failures reported in piping immediately downstream of orifices and flow meters. This is a generic issue applicable to all systems.
2 All Downstream of Control Valves (level control valves)
Millstone 2&3, Surry
- BWR, PWR Many plants reported instances of FAC degradation and some significant failures (Millstone 2&3, Surry). This is a generic issue applicable to all systems.
3 All Downstream of Leaking Valves and Steam Traps Many All Leaking valves and steam traps may be found by plant thermal performance evaluation. Downstream piping may experience severe conditions and may have been excluded from FAC Program due to infrequent operation. This is a generic issue applicable to all systems.
4 All Miscellaneous Drains to Common Headers into Condenser Many All Extensive industry exp in miscellaneous drain headers from steam drains to the condenser. In addition to FAC, these headers are susceptible to liquid impingement erosion and/or flashing/cavitation as explained in EPRI Erosive Attack Technical Update 1015071.
5 Condensate Feedwater Pump Suction Surry Unit 2 PWR 1986 Pipe rupture at Surry Unit 2. Occurred in 18" OD, Tnom = 0.5" elbow upstream of feedwater pumps (first elbow off header to FWP). T=374 deg F.
6 Condensate Condensate (between 4th highest pressure FWH and dearator)
Mihama PWR 2004 Failure in condensate system at Mihama. Occurred in 22" pipe downstream of flow measuring orifice. 284 deg F 7
Extraction Steam (or Bleed Steam)
Extraction Steam (All stages carrying wet steam)
- Oconee, Vermont
- Yankee, Trojan, Zion, Browns Ferry
- BWR, PWR 1982 Failures in steam lines due to FAC. All extraction stages carrying wet steam are susceptible to FAC. In general, all plants have experience with thinning in the extraction steam system (plants listed appeared in NRC Information Notice 82-22) 8 Extraction Steam (or Bleed Steam)
HP Extraction 2nd Stage ANO 2 PWR 1989 Fishmouth failure at ANO 2. Occurred in 14" OD, 2-phase flow. Failure at Zion (1988), Oconee (1982).
9 Extraction Steam (or Bleed Steam)
HP Extraction Sequoyah 2 PWR 1993 Fishmouth failure at Sequoyah 2. Occurred in 10" straight pipe downstream of tee in HP extraction.
CSI TECHNOLOGIES, INC.
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
Report No. 0700.104-02, Attachment A, Revision 2 Page Attach A-5 of 6 Item Number System Location/Area Plant Plant Type Year Notes 10 Extraction Steam (or Bleed Steam)
Extraction (4th Stage)
Fort Calhoun PWR 1997 Fishmouth rupture at Fort Calhoun in third elbow (12" bent pipe R/D =
- 5) downstream of turbine in extraction steam system. Section of upstream piping had been replaced in 1985 due to FAC; this downstream section was not inspected. 411 deg F, 2 phase 11 Extraction Steam (or Bleed Steam)
Extraction (carbon steel components in Cr-Mo/Stainless/etc line)
LaSalle BWR 2004 Failure of LP Heater inlet nozzles (carbon steel nozzles in Cr-Mo line).
Also through-walls on carbon steel pup piece on bellows assembly in Cr-Mo line (bellows was stainless steel). The conclusion from these events is that to be non-susceptible to FAC the entire line (incl. nozzles, valves, pup pieces, etc.) must be of FAC-resistant material.
12 Feedwater Feedwater Pump Outlet
& DS of CVs Oyster Creek BWR 1978 Thinning caused by FAC at Oyster Creek in 1978. Cracking observed at feedwater pump outlet and downstream of flow/level control valves.
13 Feedwater Feedwater Pump Discharge Navajo Fossil 1982 Pipe rupture at Navajo. Occurred in 10" OD, Tnom = 0.365" elbow downstream of boiler feed pump. T=360 deg F.
14 Feedwater Final Feedwater (Safety-Related)
Trojan PWR 1987 Extensive thinning to min acceptable wall thickness at Trojan in safety related feedwater (and non-safety related). High velocity and large counterbores exacerbated FAC.
15 Feedwater Feedwater at Flow Measurement Orifice Loviisa PWR 1990 Rupture at Loviisa. Occurred in feedwater system at flow measurement orifice.
16 Feedwater Feedwater Pleasant Prairie Fossil 1995 Instantaneous double-ended pipe break at Pleasant Prairie. Occurred in 12" feedwater line downstream of valve station and upstream of economizer and boiler.
17 Feedwater Control Valve Bypass Lines San Onofre and Diablo Canyon
- BWR, PWR Serious thinning at San Onofre and Diablo Canyon (could be valve leakage, left open at full power-high velocity, or infrequent but severe conditions).
18 Feedwater Feedwater Pump Min Flow (Recirculation)
Lines Many All Feedwater pump min flow lines to condenser have experienced significant degradation.
19 Heater Drain Heater Drain Pump Recirc (Bypass)
Millstone 2 PWR 1995 Failure at Millstone 2. Occurred in 8" recirc line from heater drain pump to heater drain tank. Line operated during startup only (0-30% power).
CSI TECHNOLOGIES, INC.
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
Report No. 0700.104-02, Attachment A, Revision 2 Page Attach A-6 of 6 Item Number System Location/Area Plant Plant Type Year Notes 20 Heater Vents Feedwater Heater Vents to Condenser
- ANO, Kewaunee,
- McGuire, Point Beach, Waterford
- PWR, BWR Extensive FAC-induced thinning found throughout this system at many plants. Some plants have replaced the entire system with non-susceptible material (stainless steel or Cr-Mo).
21 Main Steam Cross-Under Piping (also called Cold Reheat, HP Turbine to Moisture Separator)
North Anna, ANO, Point Beach, D.C.
Cook
- BWR, PWR Significant FAC in cross-under piping at North Anna, ANO, and Point Beach. Some plants have small amounts of Cu/Cr in this lines which significantly reduces FAC.
22 Moisture Separator Drain Moisture Separator Drain Tank Drain Millstone 3 PWR 1990 Catastrophic failure at Millstone 3. Occurred in 6" OD Moisture Sep.
Drain Tank drain immediately downstream of level CV. 380 deg F, 0%
quality.
23 Reheater Drain Reheater Drain Tank Drain Millstone 2 PWR 1991 Rupture at Millstone 2. Occurred in 8" Reheater Drain Tank drain immediately downstream of level CV. 463 deg F, 0% quality.
24 Reheater Drain First Stage Reheater Drain Callaway PWR 1999 Failure at Callaway just downstream of long horizontal section in first stage reheater drain. 417 deg F, 4.5% quality 25 Reheater Drain Moisture Separator Reheater Drain/Vent to Drain Tank (Scavenging Steam)
McGuire PWR 2005 Unisolable steam leak occurred in 2" line that vents wet steam from MSR to drain tank. Flashing contributed to wear (pressure drop caused by "tortuous path" through many fittings in line). 540 deg F, wet steam 26 Multiple Systems Deoxygenated lines operating at 120ºF South Texas Project, Palo Verde, Surry
- PWR, BWR Some plants have experienced Low-Temperature FAC wear in deoxygenated, neutral water at about 120ºF as per EPRI Technical Report 1015170 Investigation into Flow-Accelerated Corrosion at Low Temperatures.
27 Multiple Systems Multiple Locations Diablo
- Canyon, Salem, V. C.
Summer
- PWR, BWR Pipes made of corrosive material have shown high corrosion rates downstream of welds connecting non-resistant material to the resistant material.
CSI TECHNOLOGIES, INC.
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
Report No. 0700.104-02, Attachment B, Revision 2 Page Attach B-1 of 7 Attachment B Referenced Correspondence and Communication
CSI TECHNOLOGIES, INC.
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
Report No. 0700.104-02, Attachment B, Revision 2 Page Attach B-2 of 7 Email from Ryan Doremus (CSI) to Ian Mew (IPEC) regarding a Line Naming Convention, dated 7/27/2009.
- Ian, Im close to the point where I will have to start assigning line names for categorization purposes. Since the P&IDs seem to be very good at giving line information (size, pipe class, etc.), I want to propose a simple naming convention that consists of Unit #, System Abbreviation, a sequential number, and if needed a sequential letter that would be used if susceptibility changes within a line.
U-SSS-000-A U = Unit Number SSS = System Abbreviation 000 = Sequential Number A = Section of line that is split for susceptibility.
For example: 2-6EX-003 or 2-BFD-002-A Let me know what you think.
Thank you, Ryan D. Doremus Engineer CSI Technologies, Inc.
(847) 836-3000 x796 rdoremus@csitechnologies.com
CSI TECHNOLOGIES, INC.
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
Report No. 0700.104-02, Attachment B, Revision 2 Page Attach B-3 of 7 Email from Ian Mew (IPEC) to Ryan Doremus (CSI) regarding responses to information requests, dated 8/10/2009.
Ryan, Answers to item 6, 9 & 10 will be sent shortly.
IPEC FAC Engineer Phone 914-827-7741
! "#$$ %$&'()*
!
!
"
# !
$
# !
%
# !
&
'
( ) *+
,
# !
-
# !
.
'
( ) *+
/
'
( ) *+
+(
,
-,
./! "#$$ %$&'()*
Can you answer Questions 1-10 or point me to a person who can.
IPEC FAC Engineer Phone 914-827-7741
0()1)0()2 3 )4
.(
56
6!
! "#$$ %$&'()*
CSI Document No. 0700.104.C.004
- Ian, I completed a cursory review of the SSE/SNM IP2 and have a few pieces of information that would be helpful:
CSI TECHNOLOGIES, INC.
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
Report No. 0700.104-02, Attachment B, Revision 2 Page Attach B-4 of 7
- 1. Do actual lines exist from the HP Turbine to the Moisture Preseparators or are the Preseparators connected directly to the turbine? If they exist, are they inspected visually or should they be included in the CHECWORKS model?
- 2. Is it safe to assume that all Main Steam steam trap bypass valves on 9321-F-2041 and 9321-F-2042 are normally closed despite the fact that some are shown open?
- 3. Does the Feedwater Heater Bypass line (A235307, G-5) operate more or less than 2% of the time?
- 4. Do the Boiler Feed Pump discharge lines to the Drains Collecting Tank (9321-F-2017, H-6) operate more or less than 2% of the time?
- 5. Does the 18 HP Feedwater Heater Bypass line (9321-F-2019, F-3) operate more or less than 2%
of the time?
- 6. Do the lines from the Heater Drain Pump Discharge to the HDP Water Chemistry Monitor (9321-F-2022, A2) operate more or less than 2% of the time?
- 7. Do the level control lines from the Heater Drain Tank to the Condenser (A235304, A-1 C-1 F-1) operate more or less than 2% of the time?
- 8. Do the Moisture Separator drains to the Drains Collecting Tank (9321-F-2023, H4) operate more or less than 2% of the time?
- 9. Do the SG Blowdown lines to the sample coolers (9321-F-2729, D-6) operate more or less than 2% of the time?
- 10. What is the outlet temperature of the SG Blowdown sample coolers (9321-F-2729, E-6)?
Any information on these would be helpful. Feel free to forward these questions on to system engineers or to send me operating procedures that might answer the questions. To maintain the integrity of the project schedule, we will need these answers by Wednesday, August 5.
In addition to the above, please send the Aux. Steam operating procedures (SOP 29.1.1, 29.1.2, and 29.1.3) and the following drawings:
9321-F-2027 9321-F-2028 9321-F-2033 9321-F-2067 9321-F-2720 9321-F-2722 9321-F-2723 9321-F-2745 9321-F-7020 A205957 B237144 192491 If its possible, I would like to have these drawings and the Aux. Steam OPs by next week, even if they come separately from the questions, to give me time to analyze them. If you have any questions, please feel free to contact me.
Thank you, Ryan D. Doremus Engineer CSI Technologies, Inc.
(847) 836-3000 x796 rdoremus@csitechnologies.com
CSI TECHNOLOGIES, INC.
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
Report No. 0700.104-02, Attachment B, Revision 2 Page Attach B-5 of 7 Email from Ian Mew (IPEC) to Ryan Doremus (CSI) regarding responses to information requests, dated 8/13/2009.
See Answers below.
IPEC FAC Engineer Phone 914-827-7741
6
!(
5)7
./! "#$$ %$&'()*
- Jim, Can you answer the following questions? I need the answer to develop a System Susceptibility Evaluation for the FAC program for IP2.
- 11. Do the lines from the Heater Drain Pump Discharge to the HDP Water Chemistry Monitor (9321-F-2022, A2) operate more or less than 2% of the time? Yes 1 month a year - all material is SS after the root isolation valve which is less than 1 foot long
- 12. Do the SG Blowdown lines to the sample coolers (9321-F-2729, D-6) operate more or less than 2% of the time? Sample lines are all SS from the blowdown lines thru the coolers
- 13. What is the outlet temperature of the SG Blowdown sample coolers (9321-F-2729, E-6)? - from CCW heat exchanger outlet temp is <140F
IPEC FAC Engineer Phone 914-827-7741
0()1)0()2 3 )4
.(
56
6!
! "#$$ %$&'()*
CSI Document No. 0700.104.C.004
- Ian, I completed a cursory review of the SSE/SNM IP2 and have a few pieces of information that would be helpful:
- 14. Do actual lines exist from the HP Turbine to the Moisture Preseparators or are the Preseparators connected directly to the turbine? If they exist, are they inspected visually or should they be included in the CHECWORKS model?
- 15. Is it safe to assume that all Main Steam steam trap bypass valves on 9321-F-2041 and 9321-F-2042 are normally closed despite the fact that some are shown open?
- 16. Does the Feedwater Heater Bypass line (A235307, G-5) operate more or less than 2% of the time?
- 17. Do the Boiler Feed Pump discharge lines to the Drains Collecting Tank (9321-F-2017, H-6) operate more or less than 2% of the time?
CSI TECHNOLOGIES, INC.
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
Report No. 0700.104-02, Attachment B, Revision 2 Page Attach B-6 of 7
- 18. Does the 18 HP Feedwater Heater Bypass line (9321-F-2019, F-3) operate more or less than 2%
of the time?
- 19. Do the lines from the Heater Drain Pump Discharge to the HDP Water Chemistry Monitor (9321-F-2022, A2) operate more or less than 2% of the time?
- 20. Do the level control lines from the Heater Drain Tank to the Condenser (A235304, A-1 C-1 F-1) operate more or less than 2% of the time?
- 21. Do the Moisture Separator drains to the Drains Collecting Tank (9321-F-2023, H4) operate more or less than 2% of the time?
- 22. Do the SG Blowdown lines to the sample coolers (9321-F-2729, D-6) operate more or less than 2% of the time?
- 23. What is the outlet temperature of the SG Blowdown sample coolers (9321-F-2729, E-6)?
Any information on these would be helpful. Feel free to forward these questions on to system engineers or to send me operating procedures that might answer the questions. To maintain the integrity of the project schedule, we will need these answers by Wednesday, August 5.
In addition to the above, please send the Aux. Steam operating procedures (SOP 29.1.1, 29.1.2, and 29.1.3) and the following drawings:
9321-F-2027 9321-F-2028 9321-F-2033 9321-F-2067 9321-F-2720 9321-F-2722 9321-F-2723 9321-F-2745 9321-F-7020 A205957 B237144 192491 If its possible, I would like to have these drawings and the Aux. Steam OPs by next week, even if they come separately from the questions, to give me time to analyze them. If you have any questions, please feel free to contact me.
Thank you, Ryan D. Doremus Engineer CSI Technologies, Inc.
(847) 836-3000 x796 rdoremus@csitechnologies.com
CSI TECHNOLOGIES, INC.
Indian Point 2 FAC System Susceptibility Evaluation (SSE)
Report No. 0700.104-02, Attachment B, Revision 2 Page Attach B-7 of 7 Email from Brian Trudeau (CSI) to Ian Mew (IPEC) regarding report comments, dated 11/23/2009.
CSI Doc. No. 0700.104.C.019
- Ian, This email captures our discussion today concerning your comments on the Unit 2 SSE & SNM. I understand that these two items are the extent of your comments. We will give you a call to go over these and inform you how we have incorporated them prior to sending the final version of the SSE & SNM on or before Dec 4.
- 1) Ian sent new data to CSIs Ryan Doremus on historical inspections and replacements that he would like incorporated. This may impact plant experience for SNM lines and susceptibility if the entire line has been replaced with FAC resistant material. CSI will assess this data, make the appropriate changes, and provide Ian with a list of impacted lines.
- 2) Ian requested that CSI provide comments on why SNM lines were evaluated for high consequence of failure. A reason code is given, such as plant shutdown (FT) or unable to isolate (FI), but Ian would like further comments/discussion of this reason. For example, Ian would like to know why a line would cause the plant to shutdown if it fails. For large bore SNM lines, CSI will add the note This large bore line is important to plant operation and/or may be a personnel safety issue upon failure.
CSI will apply comment 2, above to applicable lines in the Unit 3 SNM.
- Thanks,
!"