REACTOR OPERATOR Page 1 of 100 QUESTION: #001 The Unit 1 Reactor was operating at 55% power when the following occurred:

1P-1B RCPs shaft sheared just above the No. 3 seal. The sheared shaft does not adversely affect RCP seal or pump alignment.

Unit 1 Reactor tripped.

Immediately following the Reactor Trip, the 1A02 Unit 1 Non-Vital Train B 4160V bus was de-energized.

Based on these occurrences how will RCS flow in the 1B RCS Loop respond?

a. Initially decrease to zero, then reverses to a flow rate equal to that of a normally idle RCP loop.
b. Initially decrease to zero, then reverses to a flow rate greater than that of a normally idle RCP loop.
c. Initially decrease to zero, then reverses to a flow rate less than that of a normally idle RCP loop.
d. Initially decrease to zero, but then increases in normal direction as natural circulation begins.

ANSWER

b.

REACTOR OPERATOR Page 2 of 100 QUESTION

  1. 002 The following Unit 1 plant conditions exist:
  • Reactor Power is 90%
  • Containment Area Radiation Monitor count rate is rising
  • RCS Pressure is rapidly lowering
  • Pressurizer level is slowly rising
  • Condenser Steam Dump Mode Selector Switch is in MANUAL (Pressure Mode)
  • Condenser Steam Dump hand controller 1HC-484 is in AUTO and set at 990 psig Based on the information provided, the SRO decides to trip the reactor. Assuming no other manual operator actions are taken:
1) What event is occurring?
2) What RCS temperature will steam dumps try to maintain?
a.
1) A Pressurizer Liquid space leak is occurring
2) 545°F
b.
1) A Pressurizer Vapor space leak is occurring
2) 545°F
c.
1) A Pressurizer Liquid space leak is occurring
2) 547°F
d.
1) A Pressurizer Vapor space leak is occurring
2) 547°F ANSWER
b.

REACTOR OPERATOR Page 3 of 100 QUESTION

  1. 003 During execution of the Emergency Operating Procedures, RCP Trip Criteria has been established to mitigate the consequences of a.
a. Small Break LOCA by limiting the RCS inventory loss that could occur if the RCPs were tripped later in the event.
b. Steam Generator Tube Rupture by limiting the amount of the RCS inventory transferred to the ruptured Steam Generator.
c. Rod Ejection Event by increasing the void fraction within the core.
d. Large Break LOCA by limiting the heat input into the RCS.

ANSWER

a.

REACTOR OPERATOR Page 4 of 100 QUESTION

  1. 004 A Large Break LOCA has occurred on Unit 2. After the reactor trip the following plant conditions exist:

RCS Pressure is 50 psig and lowering Containment Pressure is 35 psig and rising The operating crew has completed the required actions in EOP-0 (including Attachment A, Automatic Action Verification), and is transitioning to EOP-1.3 Based on the information provided, select the answer that lists the current combined flow from both trains of any operating pumps from highest flowrate to lowest flowrate.

a. RCPs, Containment Spray Pumps, RHR Pumps, SI Pumps
b. RCPs, RHR Pumps, Containment Spray Pumps, SI Pumps
c. RHR Pumps, SI Pumps, Containment Spray Pumps, RCPs
d. Containment Spray Pumps, RHR Pumps, SI Pumps, RCPs ANSWER
c.

REACTOR OPERATOR Page 5 of 100 QUESTION

  1. 005 Unit 1 was operating at 100% reactor power when a failure in the 1P-1A, RCP thermal barrier heat exchanger caused high flow rates into the Component Cooling (CC) Water return header.

How will the CC System respond to the thermal barrier heat exchanger failure? The high flow switch will isolate...

a. the thermal barrier heat exchanger and actuate the 1P-1A RCP Cooling Water Flow Low Alarm on 1C-03; the RCP may remain running with continued monitoring of RCP seal parameters.
b. all CC system flow from the 1P-1A RCP which will require a reactor trip and the RCP to be shutdown immediately.
c. the thermal barrier heat exchanger and actuate the 1P-1A RCP Cooling Water Flow High Alarm on 1C-03; the RCP may remain running with continued monitoring of RCP seal parameters.
d. CC system flow from the thermal barrier heat exchanger and the lower oil cooler which will require the RCP to be shutdown when bearing temperatures exceed their limits.

ANSWER

a.

REACTOR OPERATOR Page 6 of 100 QUESTION

  1. 006 Given the following plant conditions on Unit 1:
  • The reactor was at full power with the plant in a normal lineup
  • 1LT-112, VCT level transmitter, developed an erroneous signal with constant output corresponding to a VCT level of 80%

Actual VCT level will start to drop immediately and will continue to drop until the VCT (Assume NO operator action)

a. is empty. No auto swap over to the RWST will occur. The charging pumps will likely become gas bound.
b. level reaches 4%. At this point, an automatic swap over to the RWST will occur. After a period of a few minutes, RCS temperature will start to drop.
c. level reaches 17%, then auto makeup will raise VCT level until the VCT reaches 78%.
d. level reaches 17%, then auto makeup will raise VCT level until the VCT reaches 28%.

ANSWER

a.

REACTOR OPERATOR Page 7 of 100 QUESTION

  1. 007 Unit 1 is shutdown and currently in MODE 4 at 300°F and 300 psig:

RHR cooling is established and a cooldown rate of 25°F/Hr has been initiated using 1HX-11A, Residual Heat Removal Heat Exchanger.

The 1P-1B RCP is running.

The RCS is solid with PCV-135, Letdown Line Backpressure CV maintaining RCS pressure in MANUAL.

If 1RH-624, HX-11A RHR HX Outlet FCV, were to have its instrument air supply line rupture, what alarm would the operator be expected to address first for this malfunction?

(Assume NO operator action)

a. RHR Low Flow
b. NRHX Outlet Temperature High
c. 1P-1B RCP No. 1 Seal P Low
d. Low Temperature Overpressure ANSWER
c.

REACTOR OPERATOR Page 8 of 100 QUESTION

  1. 008 The 1P-11A, Component Cooling (CC) Water Pump just tripped while in a normal system alignment with flow through the Component Cooling Heat Exchanger, 1HX-12A.

CC System pressure has dropped to 32 psig and is continuing to drop CCW Surge tank level is stable.

Based on the information provided, what actions should the operator be taking?

The Operator should...

a. manually start the 1P-11B, Component Cooling Water Pump to restore CC System pressure and advise the SRO to enter Tech Spec Action Condition 3.7.7.A, One CC pump INOPERABLE.
b. manually start the 1P-11B, Component Cooling Water Pump to restore the CC System pressure and advise the SRO to enter Tech Spec 3.0.3 because two CC Pumps are INOPERABLE.
c. wait for the automatic start of the standby CC pump. Then the Operator should advise the SRO to enter Tech Spec Action Condition 3.7.7.A, One CC pump INOPERABLE.
d. wait for the automatic start of the standby CC pump. If the automatic start does not occur the Operator should then advise the SRO to enter Tech Spec 3.0.3 because two CC Pumps are INOPERABLE.

ANSWER

a.

REACTOR OPERATOR Page 9 of 100 QUESTION # 009 A Main Steam Line Break occurs on Unit 1, which results in a reactor trip and automatic Safety Injection. Sixty seconds after the trip, a loss of offsite power occurs.

What means of RCS pressure control will be available immediately following the loss of offsite power?

a. Pressurizer Safety valves ONLY
b. PORVs and Pressurizer Safety valves
c. Pressurizer Spray Valves, PORVs and Pressurizer Safety valves
d. Auxiliary charging, Pressurizer Spray valves, PORVs and Pressurizer Safety valves ANSWER
b.

REACTOR OPERATOR Page 10 of 100 QUESTION # 010 Unit 1 was at 100% power when a loss of offsite power (LOOP) and a steam generator tube rupture (SGTR) occurred. The crew is responding per EOP-3 Unit 1, 'Steam Generator Tube Rupture.'

Safety Injection has been reset The RCS cooldown to target temperature has just been completed Preparations are being made to depressurize the RCS to refill the PZR The reactor operator notes that the ruptured SG level is trending higher Which of the following actions are required?

a. Depressurize the RCS and refill the pressurizer (PZR) using maximum normal spray flow.
b. Transition to ECA-3.1 UNIT 1, 'SGTR With Loss of Reactor Coolant-Subcooled Recovery Desired.'
c. Depressurize the RCS and refill the PZR using Auxiliary Spray.
d. Depressurize the RCS and refill the PZR using one or more PZR PORVs.

ANSWER

d.

REACTOR OPERATOR Page 11 of 100 QUESTION # 011 An uncontrolled depressurization of both steam generators (S/Gs) event is occurring with the following plant conditions:

Levels in both S/Gs are less than 29%

RCS cooldown rate is greater than 100°F/hour Why is feed flow throttled to maintain 50 gpm to each S/G?

a. To prevent S/G tube dry out and to minimize RCS cooldown.
b. To prevent runout from occurring on the operating auxiliary feed water pump(s) and to minimize RCS cooldown.
c. To minimize the unmonitored release of the S/G contents to the environment and to maximize feedwater inventory to the faulted S/Gs.
d. To minimize the temperature stress in the faulted S/G and to prevent runout from occurring on the operating auxiliary feedwater pump(s).

ANSWER

a.

REACTOR OPERATOR Page 12 of 100 QUESTION# 012 Unit 1 was at power when a loss of all Main Feedwater occurred. Auxiliary Feedwater (AFW) also failed and the crew transitioned to CSP-H.1 Unit 1, 'Response to Loss of Secondary Heat Sink.'

Restoration of AFW and MFW was unsuccessful.

The crew is depressurizing a Steam Generator (SG) to less than 350 psig.

CSP-H.1 directs the crew to repeat steps, as necessary, to maintain the SG less than 350 psig.

Steps are repeated in order to......?

a. keep SG pressure below the shutoff head of a condensate pump.
b. minimize the risk of causing tube creep rupture in the hot, dry SG.
c. minimize the risk of causing pressurized thermal shock in the hot, dry SG.
d. prevent a cooldown greater than 100°F per hour.

ANSWER

a.

REACTOR OPERATOR Page 13 of 100 QUESTION# 013 Unit 1 was at 100% power when a loss of all AC Power occurred, and ECA-0.0 Unit 1, 'Loss of All AC Power,' was entered.

Once the initial actions are performed, which of the following DC loads, if any, must be shed?

a. Unit 2 Non-Nuclear Room Lighting.
b. Switchgear Room Lighting.
c. PBX Telephone System.
d. No DC Loads need to be shed.

ANSWER

d.

REACTOR OPERATOR Page 14 of 100 QUESTION# 014 Unit 1 was recovering from a Steam Generator Tube Rupture (SGTR) and loss of offsite power (LOOP) when offsite power was restored.

EOP-3.1 Unit 1, 'Post-Steam Generator Tube Rupture Cooldown Using Backfill', is in progress.

The Operating Supervisor suggests starting the reactor coolant pump (RCP) in the ruptured loop to enhance the recovery process.

What is your response?

a. Agree with starting the RCP.

RCP operation is preferred during backfill to ensure homogeneous fluid temperatures.

b. Disagree with starting the RCP.

RCP operation in the ruptured loop may result in an inadvertent criticality.

c. Agree with starting the RCP.

RCP operation is preferred during backfill to ensure homogeneous boron concentration.

d. Disagree with starting the RCP.

RCP operation may result in RCP seal damage.

ANSWER

b.

REACTOR OPERATOR Page 15 of 100 QUESTION# 015 Both White Instrument Buses 1Y-03/1Y-103 experienced ground faults and de-energized.

If both Yellow Instrument Buses 1Y-04/1Y-104 experience similar failures and also de-energize, what would be the status of both Unit 1 Subcooling Margin Monitors on the 1C20 ASIP Panel?

They would both...

a. remain functional with good data output but each would lose one channel of input data.
b. remain functional with good data output but each would lose two channels of input data.
c. become unreliable; their data output would be suspect.
d. become unavailable; no output would be provided.

ANSWER

d.

REACTOR OPERATOR Page 16 of 100 QUESTION# 016 When energizing Battery Charger D-07, what is the order in which charger breakers should be closed and the reason for this specific order?

a. DC Breaker should be closed before the AC Breaker to prevent voltage surges from damaging charger components.
b. DC Breaker should be closed before the AC Breaker to prevent charging currents from tripping the DC Breaker.
c. AC Breaker should be closed before the DC Breaker to prevent voltage surges from damaging charger components.
d. AC Breaker should be closed before the DC Breaker to prevent charging currents from tripping the DC Breaker.

ANSWER

d.

REACTOR OPERATOR Page 17 of 100 QUESTION# 017 An unisolable LOCA outside containment has occurred.

The control room operators entered EOP-0, 'Reactor Trip or SI', then transitioned to ECA-1.2, 'LOCA Outside Containment.'

The Unit Supervisor has now entered ECA-1.1, 'Loss of Containment Sump Recirculation', because RCS pressure was still decreasing after all attempts to isolate the leak had failed.

All plant equipment has operated as designed for this event.

The Unit Supervisor is at the ECA-1.1 step to Verify Containment Accident Cooling Units Running. The step checks if they are running and aligned properly. If not, it starts them.

The Unit Supervisor notes that containment conditions are normal.

Which one of the following actions should the operators take?

a. Exit ECA-1.1, 'Loss of Containment Sump Recirculation'. The Unit Supervisor should direct the actions in the higher priority procedure ECA-1.2, 'LOCA Outside Containment'.
b. The crew should hold at the step in effect until the Technical Support Center (TSC) can assess the impact of performing the step under these conditions.
c. The Unit Supervisor should direct performance of the step.
d. The Unit Supervisor should exercise discretion and bypass this step based on having normal containment conditions.

ANSWER

c.

REACTOR OPERATOR Page 18 of 100 QUESTION# 018 Given the following plant conditions on Unit 2:

An automatic Reactor Trip and Safety Injection has occurred The crew is implementing EOP-0, 'Reactor Trip or Safety Injection' The crew is verifying secondary heat sink per step 6 Containment Pressure is 1.5 psig and stable Which of the following meets the criteria for transition to CSP-H.1, 'Response to Loss of Secondary Heat Sink' from step 6 of EOP-0?

a. 'A' Steam Generator level at 20% NR

'B' Steam Generator level at 35% NR Total auxiliary feed flow of 150 gpm

b. 'A' Steam Generator level at 20% NR

'B' Steam Generator level at 25% NR Total auxiliary feed flow of 200 gpm

c. 'A' Steam Generator level at 25% NR

'B' Steam Generator level at 25% NR Total auxiliary feed flow of 100 gpm

d. 'A' Steam Generator level at 30% NR

'B' Steam Generator level at 30% NR Total auxiliary feed flow of 175 gpm ANSWER

c.

REACTOR OPERATOR Page 19 of 100 QUESTION# 019 Unit 1 was operating at 100% power with all systems in their normal alignment except for Rod Control, which was in MANUAL, when the following plant conditions were noted:

Reactor Power dropped to 98% and is now stable.

Pressurizer Pressure dropped to 2225 and is now slowly rising.

RCS Tavg dropped but is now stable.

Steam flow dropped but is now stable.

All systems are in their normal full power alignment and are working correctly Containment pressure and radiation levels are normal.

Of the choices below which is the most likely cause of these plant conditions?

a. A small steam line leak is occurring in the turbine building.
b. A single control rod dropped into the core.
c. A turbine control valve has drifted closed.
d. The Non-Regenerative Heat Exchanger CCW temperature control valve has failed open.

ANSWER

b.

REACTOR OPERATOR Page 20 of 100 QUESTION# 020 The following conditions exist on Unit 1:

The unit is in Mode 6, Refueling, with core offload in progress.

A containment purge supply (1W-2A) and exhaust fan (1W-6A) is in operation.

During refueling operations an assembly scheduled for replacement is dropped and seriously damaged.

A Containment Ventilation Isolation signal is actuated, closing supply and exhaust isolation valves 1CV-3212 and 1CV-3244.

Which of the following statements correctly describes the radiation monitor operation for producing the CVI signal?

(1RE-211 Containment Air Particulate Monitor)

(1RE-212 Containment Noble Gas Monitor)

(1RE-305 Containment Purge Exhaust Low Range Gas Monitor)

a. 1RE-211 in high alarm could have caused the actuation.
b. 1RE-212 in high alarm could have caused the actuation.
c. Both 1RE-211 and 1RE-212 in high alarm are required to cause the actuation.
d. Both 1RE-212 and 1RE-305 in high alarm are required to cause the actuation.

ANSWER

b.

REACTOR OPERATOR Page 21 of 100 QUESTION# 021 Unit 1 reactor power is 75% and steady. The following stable plant conditions currently exist:

  • Pressurizer Level is 37% and stable
  • Letdown flow rate is 40 gpm
  • Charging flow is 44 gpm
  • RCP seal return flow is 1.5 gpm per pump
  • RCP Seal Injection supply flow is 8 gpm per pump Based on the information provided above which of the following statements is correct?
a. Charging flow is high for these conditions.
b. Steam Generator Level is low for these conditions.
c. RCP seal return flow is high for these conditions.
d. Pressurizer Level is low for these conditions.

ANSWER

d.

REACTOR OPERATOR Page 22 of 100 QUESTION# 022 Unit 1 is coming out of a refueling outage holding at 28% power for chemistry concerns.

1P-25A Condensate Pump is running.

1P-28A Steam Generator Main Feedwater Pump is running.

1P-30A Circulating Water Pump is running.

Assuming no operator actions, what will occur if the 1P-30A motor feeder breaker trips due to a ground fault?

a. The turbine will trip and cause a reactor trip.
b. Neither the turbine nor reactor will trip.
c. The reactor will trip but not cause a turbine trip.
d. The turbine will trip but not cause a reactor trip.

ANSWER

a.

REACTOR OPERATOR Page 23 of 100 QUESTION# 023 Control Room Monitor RE-101 just went into high alarm. As the Reactor Operator you have pulled RMSASRB CI RE-101 for the Control Room Monitor.

The Operator Response section will have you

a. verify the Control Room ventilation system has aligned to Mode 2, Accident Condition 100% recirculation.
b. verify the Control Room ventilation system has aligned to Mode 3, Accident condition 25%

filtered air return.

c. verify the Control Room ventilation system has aligned to Mode 4, Accident condition 25%

filtered outside air.

d. check RE-235, Control Room Monitor, because it must reach its high alarm setpoint before any Control Room ventilation actuation occurs.

ANSWER

c.

REACTOR OPERATOR Page 24 of 100 QUESTION# 024 The control room has been evacuated due to a carbon dioxide leak causing levels greater than allowable limits for habitability. Prior to evacuation, all control room actions were taken in accordance with AOP-10, 'Control Room Inaccessibility.'

The 1P-29 Turbine Driven AFW Pump tripped on overspeed and cannot be restarted The Unit 1 AFW Pump Operator has locally started the P-38A Motor Driven AFW Pump Which of the following additional actions should the Unit 1 AFW Pump Operator take, and what is the basis for these actions?

a. Feed the Unit 1A steam generator only; due to the limited capacity of one motor driven AFW pump.
b. Feed the Unit 1B steam generator only; due to the limited capacity of one motor driven AFW pump.
c. Feed the Unit 1A S/G and Unit 2A S/G; due to all atmospheric steam dump controllers being set at 1005 psig thus requiring both steam generators to be fed.
d. Feed the Unit 1A S/G and Unit 1B S/G; due to all atmospheric steam dump controllers being set at 1005 psig thus requiring both steam generators to be fed.

ANSWER

a.

REACTOR OPERATOR Page 25 of 100 QUESTION# 025 Operators are responding to a degraded core cooling event on Unit 2.

Core Exit Thermocouples are reading 850°F and rising.

The SRO has transitioned to CSP-C.2, 'Response to Degraded Core Cooling.'

The crew has reached the point in the procedure to attempt to inject SI accumulators.

CSP-C.2 directs reducing RCS pressure to inject SI accumulators by (1), and the cooldown rate should be (2).

( 1 )

( 2 )

a. opening BOTH Pressurizer PORVs at the maximum rate achievable
b. opening BOTH Pressurizer PORVs less than 100°F per hour rate and establish Aux Spray
c. depressurizing ALL intact S/Gs to at the maximum rate achievable 200 psig and establish Aux Spray
d. depressurizing ALL intact S/Gs to less than 100°F per hour rate 200 psig ANSWER
d.

REACTOR OPERATOR Page 26 of 100 QUESTION# 026 The Unit 2 operators are carrying out actions in AOP-8A, 'High Reactor Coolant Activity', in response to an alarm on 2RE-109, 'Failed Fuel Monitor.'

Which of the following would be an expected action to be performed in AOP-8A?

a. Establish maximum allowed letdown purification flow to reduce Unit 2 RCS activity levels.
b. Lower Unit 2 reactor power by lowering turbine load to see if trends on 2RE-109 follow reactor power.
c. Secure both Unit 1 and Unit 2 letdown gas strippers to prevent the spread of contamination to off-site areas.
d. Raise Unit 2 RCS temperature to the maximum value allowed by Technical Specifications to retain I-131 in solution.

ANSWER

a.

REACTOR OPERATOR Page 27 of 100 QUESTION# 027 Given the following conditions:

A Main Steam Line Break has occurred in the Turbine Building.

Both MSIVs on the affected unit failed to close.

The crew has just transitioned to CSP-P.1, 'Response to Imminent Pressurized Thermal Shock Condition.'

If the RCS begins to repressurize once the Steam Generators completely depressurize, what part of the RCS pressure boundary is most at risk to brittle fracture and why?

a. The Pressurizer Nozzle welds because they are in the area subject to the greatest cyclic temperature stresses.
b. Reactor Pressure Vessel Bottom Head welds because they will experience the lowest temperature due to SI flow.
c. Reactor Pressure Vessel Upper Head penetrations because they are the area where the maximum residual tensile stresses are found in the RCS.
d. Reactor Pressure Vessel Beltline region because it is subjected to significant neutron irradiation.

ANSWER

d.

REACTOR OPERATOR Page 28 of 100 QUESTION# 028 Two IDENTICAL units with identical power histories have tripped from the same power level.

Unit 1 RCPs are running.

Unit 2 RCPs have tripped.

Following stabilization, the units are being maintained at the same RCS temperature using AFW and SG atmospheric steam dumps.

Which unit will have the HIGHER RCS loop delta-T? Which unit will have the HIGHER AFW flow?

HIGHER DELTA T HIGHER AFW FLOW

a.

Unit 1 Unit 1

b.

Unit 1 Unit 2

c.

Unit 2 Unit 1

d.

Unit 2 Unit 2 ANSWER

c.

REACTOR OPERATOR Page 29 of 100 QUESTION# 029 Per OP-4B, 'Reactor Coolant Pump Operation', select the procedurally allowed condition(s) below for starting a Reactor Coolant Pump.

a. The RCS is solid, LTOP is in service, and RCS pressure is 250 psig.
b. The RCS Cold Leg temperature is 230°F and the associated Steam Generator is at 270°F.
c. The RCP Lift Pump has been running for 60 seconds, the amber RCP Lift Pressure light is illuminated.
d. The Reactor Coolant Pump was started, run for one minute then stopped. 15 minutes has elapsed since the pump was shutdown.

ANSWER

b.

REACTOR OPERATOR Page 30 of 100 QUESTION# 030 When degassing the Reactor Coolant System during cooldown from Hot Standby to Cold Shutdown, the Pressurizer gas space is vented through the ___________.

a. Reactor Coolant Gas Vent System to the PRT
b. Pressurizer PORVs to the PRT
c. Primary Sample System to the VCT
d. Letdown Gas Stripper and the Cryogenic Noble Gas Removal System to the VCT ANSWER
c.

REACTOR OPERATOR Page 31 of 100 QUESTION# 031 Following a plant heatup, operators are removing the A train of RHR from service per OP-7B, Removing A Train RHR from Operation. It is necessary to adjust the boron concentration of the RHR system.

Which one of the following describes the RHR system lineup to perform the boron concentration adjustment?

a. Suction from the RWST, discharge through the RHR mini-recirculation valves back to the RWST.
b. Suction from the BAST, discharge through CVCS letdown.
c. Suction from the Spent Fuel Pool (SFP), discharge back to the SFP.
d. Suction from the RWST, discharge through the SI pump recirculation valves back to the RWST.

ANSWER

d.

REACTOR OPERATOR Page 32 of 100 QUESTION# 032 1P-10A RHR Pump is operating in the shutdown cooling mode with the following stable plant conditions:

RCS temperature is 300°F RCS pressure is 300 psig PZR level is 70%

Which of the following states the effects, if any, that 1PT-420 RC Loop A Pressure failing high would have on the Pressurizer Heaters?

The Pressurizer...

a. Variable Heaters will energize due to a 5% rise in Pressurizer Level.
b. Back Up Heaters will energize due to Low Pressurizer Pressure.
c. Variable Heaters will energize due to a 5% decrease in Pressurizer Level.
d. Back Up and Variable Heaters will not be affected by this failure.

ANSWER

d.

REACTOR OPERATOR Page 33 of 100 QUESTION# 033 Given the following:

  • A large break LOCA has occurred on Unit 2.
  • 480 volt Safeguards Bus 2B04 is deenergized.
  • The crew is performing actions of EOP 1, "Loss of Reactor or Secondary Coolant."

To isolate the accumulators you dispatch an operator to energize...

a. both SI Accumulator outlet valves from safeguards power and then manually close both accumulator outlet valves from the control room.
b. one of the SI Accumulator outlet valves from safeguards power and then manually close that accumulator outlet valve. The other accumulator is vented to containment.
c. both SI Accumulator outlet valves via B08/B09 Alternate Shutdown Load Center, and then manually close both accumulator outlet valves. Both accumulators must be vented to containment.
d. one of the SI Accumulator outlet valves from safeguards power and the other from B08/09 Alternate Shutdown Load Center, then manually close both accumulator outlet valves.

ANSWER

b.

REACTOR OPERATOR Page 34 of 100 QUESTION# 034 Which of the following describes the adverse effects of NOT maintaining the Pressurizer Relief Tank (PRT) within its design level band?

a. If the level is too low, there would be insufficient water volume to absorb and condense a design discharge of PZR safety leading to possible over temperature and overpressure of the PRT.
b. If the level is too high, the tank will overflow to the RCDT causing possible false indications of RCS leakage.
c. If the level is too low the radioactive gases that leak from the top of the PZR would not be adequately scrubbed, thus causing subsequent elevated gaseous activity levels inside containment.
d. If the level is too high, the sparger pipe will be too far underwater rendering the cooling affect of makeup water ineffective.

ANSWER

a.

REACTOR OPERATOR Page 35 of 100 QUESTION# 035 Unit 2 is at full power and is lowering the Pressurizer Relief Tank (PRT) level per OP 4C,

'Pressurizer Relief Tank Operation Unit 2'.

Prior to opening 2RC-596, T-2 PRT Drain to T-16 RCDT, the PAB Auxiliary Operator will be directed to...

a. bypass the RCDT to allow the PRT to drain directly to Sump A.
b. align the RCDT Pumps/valves and monitor tank level for proper response.
c. align the RCDT to allow the PRT to drain directly to T-19, Waste Holdup Tank.
d. monitor RCDT level which eventually will have to be drained, as it is sized for several PRT volumes.

ANSWER

b.

REACTOR OPERATOR Page 36 of 100 QUESTION# 036 Unit 2 is operating at 100% power and is in a normal full power alignment.

2CV-142, Charging Flow Control Valve, has failed full open.

Which of the following is the expected plant response for this event?

a. Reactor Coolant Pump labyrinth seal delta P will lower Pressurizer level will remain constant
b. Reactor Coolant Pump labyrinth seal delta P will rise Pressurizer level will steadily rise
c. Reactor Coolant Pump labyrinth seal delta P will rise Pressurizer level will remain constant
d. Reactor Coolant Pump labyrinth seal delta P will lower Pressurizer level will steadily lower ANSWER
a.

REACTOR OPERATOR Page 37 of 100 QUESTION# 037 Given the following plant conditions:

Unit 1 had been operating for an extended period of time when a steam generator tube leak occurred on the 'A' S/G.

The pressurizer has emptied, RCS pressure and S/G pressure is 800 psig.

The steam in the pressurizer steam space is being heated by the residual heat in the pressurizer metal. The temperature of the steam in the steam space is 650°F.

Operators have succeeded in reducing RCS pressure to slightly less than 800 psig.

The pressurizer begins to refill with back-flow from the 'A' S/G.

RCS temperature is approximately 520°F.

As the pressurizer fills with water from the RCS, what will be the condition of the steam and water entering the pressurizer? What are the effects of pressurizer sprays under these conditions?

a. The steam in the pressurizer will be superheated, the water entering the pressurizer is saturated. Pressurizer sprays will not reduce pressurizer pressure until the steam bubble temperature is reduced by approximately 130°F.
b. The steam in the pressurizer will be superheated, the water entering the pressurizer will be subcooled. Pressurizer sprays will control pressurizer pressure normally.
c. The steam in the pressurizer will be saturated, the water entering the pressurizer will be subcooled. Pressurizer sprays will control pressurizer pressure normally.
d. The steam in the pressurizer will be saturated, the water entering the pressurizer will be slightly above saturation and will cause RCS pressure to rise. Pressurizer sprays will be ineffective and pressure control will be manually with the pressurizer PORVs.

ANSWER

a.

REACTOR OPERATOR Page 38 of 100 QUESTION# 038 Unit 1 was operating near full power when one channel of Pressurizer pressure failed LOW.

The crew responded appropriately per AOP-24, 'Response to Instrument Malfunctions' and 0-SOP-IC-001, 'Routine Maintenance Procedure Removal of Safeguards or Protection Sensor from Service', tripping the required bistables.

What is the Pressurizer low pressure reactor trip logic using the remaining channels and the current status of the failed channel Pressurizer low pressure bistable proving lamp?

The reactor trip logic is now...

a. 1 out of 3, and the proving lamp is lit.
b. 1 out of 2, and the proving lamp is lit.
c. 1 out of 3, and the proving lamp is NOT lit.
d. 1 out of 2, and the proving lamp is NOT lit.

ANSWER

c.

REACTOR OPERATOR Page 39 of 100 QUESTION# 039 A total of _(1)_ separate instrument channels monitor containment pressure.

If one of the channels that provides input to the High Containment Pressure Safety Injection actuation logic fails, there are _(2)_ channels remaining in that train to provide the function.

(1)

(2)

a.

Six (6) Two (2)

b.

Eight (8)

Two (2)

c.

Eight (8)

Three (3)

d.

Six (6)

Three (3)

ANSWER

b.

REACTOR OPERATOR Page 40 of 100 QUESTION# 040 Given the following:

A Safety Injection (SI) occurred on Unit 1.

Five minutes later, the control operator checks the status of 1W-1A1, Containment Accident Recirculation Fan.

The operator expects the fan to be (1) because its power supply is (2).

(assume no operator actions are taken)

(1)

(2)

a. De-energized 1B31
b. Energized 1B31
c. Energized 1B04
d. Energized 1B03 ANSWER
d.

REACTOR OPERATOR Page 41 of 100 QUESTION# 041 Which of the following correctly describes the minimum necessary equipment and corresponding containment pressure setpoint(s) to prevent exceeding design containment pressure following a design basis LOCA?

a. Two (2) Containment Accident Recirculation Fans started at 5 psig AND Two (2) Containment Spray pumps started at 25 psig.
b. Two (2) Containment Accident Recirculation Fans started at 4 psig AND One (1) Containment Spray pump starts at 25 psig.
c. Four (4) Containment Accident Recirculation Fans started at 5 psig.
d. Four (4) Containment Accident Recirculation Fans started at 4 psig.

ANSWER

c.

REACTOR OPERATOR Page 42 of 100 QUESTION# 042 A large break Loss of Coolant Accident (LOCA) occurred on Unit 1, which resulted in the crew performing EOP-1.3 Unit 1, 'Transfer to Containment Sump Recirculation - Low Head Injection'.

Which of the following describes the procedural requirements for securing the two Containment Spray Pumps?

a. One pump is secured per EOP-0 Attachment A, 'Automatic Action Verification'.

The second pump is secured when RWST Level is LESS than 9 percent

b. One pump is secured per EOP-0 Attachment A, 'Automatic Action Verification'.

The second pump is secured when 16 percent of the spray additive tank has been added to containment.

c. One pump is secured when containment pressure is less than 15 psig.

The second pump is secured when RWST Level is LESS than 9 percent.

d. One pump is secured when containment pressure is less than 15 psig.

The second pump is secured when 16 percent of the spray additive tank has been added to containment.

ANSWER

a.

REACTOR OPERATOR Page 43 of 100 QUESTION# 043 Which of the following lists the components, in order, through which steam flows from the Steam Generator to the 1P-29, Turbine Driven Auxiliary Feedwater Pump in response to an auto start?

Governor Valve Motor Operated Valve (MS-2019/2020)

Header Manual Isolation Valve (MS-235/237)

Low Suction/Overspeed Trip Throttle Valve (MS-2082)

Steam flows from...

a. Unit 1 'B' Steam Generator ONLY to a tap upstream of the MSIV, then - 2, 4, 3, 1.
b. Unit 1 AND Unit 2 'A' Steam Generators, to a tap downstream of the MSIV, then - 4, 1, 3, 2.
c. Unit 1 'A' AND 'B' Steam Generators, to a tap upstream of the MSIV, then 3, 2, 4, 1.
d. Unit 1 'A' AND Unit 2 'B' Steam Generators, to a tap upstream of the MSIV, then - 3, 4, 2, 1.

ANSWER

c.

REACTOR OPERATOR Page 44 of 100 QUESTION# 044 Given the following information:

Unit 2 has just transitioned from Mode 3 to Mode 4.

One Condensate Pump is in operation supplying feed to both steam generators via Steam Generator Feedwater Regulating Valve bypasses.

Both Main Feedwater Pumps control switches have been placed in PULLOUT.

If a LO-LO SG LEVEL occurs in SG A...

a. Neither Motor Driven Auxiliary Feedwater Pump will start.
b. Only the A Motor Driven Auxiliary Feedwater Pump (P-38A) will start.
c. Only the B Motor Driven Auxiliary Feedwater Pump (P-38B) will start.
d. Both Motor Driven Auxiliary Feedwater Pumps (P-38A & B) will start.

ANSWER

a.

REACTOR OPERATOR Page 45 of 100 QUESTION# 045 The SGBD Isolation Defeat Switch on the C03 panel defeats the automatic isolation of the Steam Generator Blowdown Lines that is normally initiated upon...

a. Blowdown sample line high radiation.
b. Blowdown Tank discharge line high pressure.
c. the manual start of any Auxiliary Feedwater Pump.
d. any start of the Turbine Driven Auxiliary Feedwater Pump.

ANSWER

d.

REACTOR OPERATOR Page 46 of 100 QUESTION# 046 Which one of the following flowpaths describes the NORMAL supply of power to a reactor protection instrument bus?

a. 480 VAC from safeguards bus, transformed to 120 VAC, and supplied to the instrument bus.
b. 480 VAC from safeguards bus, rectified to 125 VDC, inverted to 120 VAC and supplied to the instrument bus.
c. 480 VAC from non-safeguards bus, inverted to 120 VAC, and supplied to the instrument bus.
d. 480 VAC from non-safeguards bus, rectified to 125 VDC, inverted to 120 VAC and supplied to the instrument bus.

ANSWER

b.

REACTOR OPERATOR Page 47 of 100 QUESTION# 047 Which of the following Vital DC Distribution parameters are indicated in the Main Control Room?

Bus Voltage Battery current (Charge/Discharge)

Bus Feed Breaker position Battery Charger output current

a. 1, 2, and 3
b. 1, 2, and 4
c. 1, 3, and 4
d. 2, 3, and 4 ANSWER
a.

REACTOR OPERATOR Page 48 of 100 QUESTION# 048 After an automatic start of the AFW pumps, annunciator C01A 4-9, "AUX FEED PUMP SUCTION PRESSURE LOW," alarmed. P-38B, Motor Driven Auxiliary Feedwater Pump, tripped due to a failed low AFW pump suction pressure switch.

What actions are required to override P-38B, Motor Driven Auxiliary Feedwater Pump, low suction pressure trip?

a. Place the pump control switch for P-38B to START and return the switch to the AUTO position.
b. Select a different pressure switch for P-38B and return the switch to the AUTO position.
c. Place the pump control switch for P-38B to STOP, and then place the switch in the AUTO position.
d. Place the pump control switch for P-38B to PULLOUT, and then dispatch an AO to locally reset the low suction pressure trip device.

ANSWER

a.

REACTOR OPERATOR Page 49 of 100 QUESTION# 049 Which of the following switch combinations will result in an idle start of G01 Emergency Diesel Generator?

MODE SELECTOR ENGINE START DIESEL CONTROL ENGINE START SWITCH SELECTOR SWITCH SWITCH PUSHBUTTON (C02) (C64) (C02) (C64)

a. AUTO LOCAL START NOT DEPRESSED
b. EXERCISE AUTO START NOT DEPRESSED
c. EXERCISE LOCAL START NOT DEPRESSED D. EXERCISE AUTO AUTO DEPRESSED ANSWER
b.

REACTOR OPERATOR Page 50 of 100 QUESTION# 050 Given the following plant conditions:

Unit 1 is at 100% power The A Gas Decay Tank is being discharged per OP-9D, Discharge of Gas Decay Tanks Which of the following would cause an automatic isolation of the Waste Gas Decay Tank discharge?

a. RE-214, Aux Building Vent Exhaust Monitor high alarm.
b. Containment or Aux Bldg Vent System Air Flow Low alarm (1C04 1C 2-9).
c. RE-315, Aux Building Exhaust Low Range Gas high alarm.
d. RE-325, Drumming Area Exhaust Low Range Gas high alarm ANSWER
a.

REACTOR OPERATOR Page 51 of 100 QUESTION# 051 Given the following:

Both units are at full power with the Letdown Gas Strippers in service 2HX-12D and HX-12C CCW Heat Exchangers are aligned to Unit 2 with 2HX-12D controlling CCW temperature in AUTO Unit 2 was placed on two letdown orifices for downpower preparations PPCS trends are showing Unit 2 CCW HX outlet temp at 100ºF and rising The PAB AO reports that 2HX-12D CCW HX SW TCV is full open What operator actions should be taken to address the rising CC HX outlet temperature?

a. Start the standby CCW Pump.
b. Align Unit 2 CCW HX SW blowdown valves per 2-SOP-CC-001, Component Cooling System.
c. Perform 2-SOP-CC-001, Component Cooling System Attachment D, CCW HX Flushing.
d. Align 2SW-12C, HX-12C CCW HX SW TCV to AUTO at the same setpoint as 2SW-12D, 2HX-12D CCX HX SW TCV.

ANSWER

b.

REACTOR OPERATOR Page 52 of 100 QUESTION# 052 Consider the following plant conditions:

Both units are at 100% reactor power C01 A 1-5, "SERVICE WATER STRAINER DP HIGH" Alarm is LIT C01 A 2-5, "NORTH OR SOUTH SW HEADER STRAINERS" alarm is LIT SW Header Pressure is 60 PSIG The TH AO is dispatched to investigate the alarms:

AO reports that the South SW Main Zurn strainer had stopped backwashing and the DP on the strainer was 4 psid.

AO reports that he has opened SW-3, South SW Main Zurn Bypass valve, and that DP has returned to normal.

What direction should be given to the AO and what is the reason for this action?

a. Direct AO to immediately close Strainer Bypass valve. An open Strainer Bypass valve requires the SW and AFW Systems to be declared inoperable.
b. Direct AO to immediately close Strainer Bypass valve. An open Strainer Bypass valve prevents the strainer from operating in continuous backwash mode.
c. Maintain bypass open to ensure South SW Water header has sufficient flow for required heat loads. Contact System Engineer to evaluate system flow conditions.
d. Maintain bypass open to ensure SW is available to safety related components normally supplied from the South SW header. SW supply to these components should be aligned to the alternate header as soon as possible.

ANSWER

a.

REACTOR OPERATOR Page 53 of 100 QUESTION# 053 Given the following conditions:

K-2A Instrument Air Compressor is in CONSTANT K-2B Instrument Air Compressor is OOS Z-31, Instrument Air Dryer relief valve is failing Which of the following correctly states the expected response of the Instrument Air System as the leak worsens?

(Assume no operator actions)

Instrument Air header pressures will.....

a. eventually return to normal after Z-31 Instrument Air Dryer automatically isolates the leak on high DP.
b. continue to lower due to the leak. PCV-3079, Service Air/Instrument Air Cross-connect valve will eventually open to try and restore Instrument Air header pressure.
c. lower and IA-3000-S, Z-39 IA Dryer Bypass valve, will open cross-connecting the north and south Instrument Air Headers.
d. lower and IA-3094-S, Z-31 IA Dryer Bypass valve, will open to isolate the leak.

ANSWER

b.

REACTOR OPERATOR Page 54 of 100 QUESTION# 054 While monitoring IA Header pressures on C01 with PI-3083A and PI-3084A, you observe the pressure cycling.

Which of the following explains why the pressure cycles?

a. The Total Closure Valve OPENS when pressure drops to 95 psig and then CLOSES when pressure rises to 105 psig. The compressor runs continuously.
b. The compressor starts and loads when pressure drops to 95 psig. The compressor unloads and stops when pressure rises to 105 psig.
c. The Total Closure Valve CLOSES when pressure drops to 85 psig and then OPENS when pressure rises to 95 psig. The compressor runs continuously.
d. The compressor starts and loads when pressure drops to 85 psig. The compressor unloads and stops when pressure rises to 95 psig.

ANSWER

a.

REACTOR OPERATOR Page 55 of 100 QUESTION# 055 How is containment closure capability ensured during a refueling outage when RCS temperature is <200°F and movement of irradiated fuel assemblies for core reload is in progress?

a. Containment closure capability is not required below 200°F as long as we maintain >23 feet of water above the vessel flange.
b. CL-1E, Containment Closure Checklist is maintained by the control room tracking all open penetrations.
c. Personnel and equipment hatch interlocks mechanisms are maintained in an operable status.
d. The Containment Isolation system is operable.

ANSWER

b.

REACTOR OPERATOR Page 56 of 100 QUESTION# 056 Unit 2 was operating at 100% reactor power when a Loss of Offsite Power caused the RCPs to trip. The crew is performing EOP-0.1, 'Reactor Trip Response.'

Identify the proper indications that natural circulation has been ESTABLISHED.

(Assume subcooling is 50ºF and Stable) 1 - Core Exit Thermocouples - Lowering 2 - Core Exit Thermocouples - Rising 3 - RCS Hot Leg temperature - Lowering 4 - RCS Hot Leg temperature - Rising 5 - SG pressure - Lowering 6 - SG pressure - Rising 7 - RCS HOT Leg temperature - near saturation for SG pressure 8 - RCS COLD Leg temperature - near saturation for SG pressure

a. 1, 3, 5, 8
b. 1, 3, 6, 7
c. 2, 4, 5, 7
d. 2, 4, 6, 8 ANSWER
a.

REACTOR OPERATOR Page 57 of 100 QUESTION# 057 Given the following plant conditions:

Unit 2 was operating at 95% power with all indications for Group D rods at 210 steps.

Group D individual rod position indication on 2C04 and the Plant Process Computer (PPCS) increased to 213 steps over a 15 minute period.

RCS Tavg has remained stable Rod control is in AUTO Which of the following could explain the change in indicated individual rod position?

(Assume no operator action)

a. A power range NI failed low.
b. A high worth rod in Control Bank C dropped into the core.
c. First Stage Impulse Pressure, PT-485, failed high.
d. The running CRDM cooling fan tripped on thermal overload.

ANSWER

d.

REACTOR OPERATOR Page 58 of 100 QUESTION# 058 Unit 1 is performing a reactor shutdown. Reactor power, as indicated on the intermediate range nuclear instruments, is as follows:

N-35 = 1.7x10-10 amps and lowering N-36 = 1.3x10-10 amps and lowering Channel N-35 compensating voltage has failed low rods begin to continuously withdraw due to a failed relay Assuming no operator action, how does the plant respond?

N-35 reads......

a. lower than actual level; a source range trip occurs.
b. higher than actual level; a source range trip occurs.
c. lower than actual level; a source range trip does not occur.
d. higher than actual level; a source range trip does not occur.

ANSWER

d.

REACTOR OPERATOR Page 59 of 100 QUESTION# 059 What is the reason that the quantity of aluminum metal components in containment must be minimized?

a. Aluminum melts in a high temperature fire.
b. Aluminum reacts with sodium hydroxide to produce hydrogen.
c. Aluminum combines with elemental iodine to form a soluble salt.
d. Aluminum loses structural strength in a high energy line break environment.

ANSWER

b.

REACTOR OPERATOR Page 60 of 100 QUESTION# 060 With Unit 1 in Cold Shutdown, the Operations Supervisor directs the Containment Purge Supply and Exhaust System be placed in service in accordance with Section 5.3.1 of OP-9C, "Containment Venting and Purging Unit 1.

(Exhaust Fan - 1W6A/B, Purge Exhaust Fans)

(Supply Fan - 1W2A/B, Purge Supply Fans)

(Exhaust Valve - 1VNPSE-3212, Purge Exhaust Fan Suction Containment Isolation)

(Supply Valve - 1VNPSE-3244, Purge Supply Fan Discharge Containment Isolation)

In order to start the......

a. purge SUPPLY fan, the purge EXHAUST fan must be running and SUPPLY valve must be closed.
b. purge EXHAUST fan, the purge SUPPLY fan must be running and EXHAUST valve must be closed.
c. purge EXHAUST fan, the purge SUPPLY fan must be running and EXHAUST and SUPPLY valves must be open.
d. purge SUPPLY fan, the purge EXHAUST fan must be running and EXHAUST and SUPPLY valves must be open.

ANSWER

d.

REACTOR OPERATOR Page 61 of 100 QUESTION# 061 Which of the following conditions would allow new fuel movement in the spent fuel pool?

a. Spent Fuel Pool water temperature is 48°F.
b. RE-221, Drumming Area Vent Gas Monitor, and RE-325, Drumming Area Exhaust Low-range Gas Monitor out of service.
c. Spent Fuel Pool water level is 63 feet.
d. Communications between the SFP area and the Control Room are lost.

ANSWER

c.

REACTOR OPERATOR Page 62 of 100 QUESTION# 062 During operation at 100% power PT-486, Turbine First Stage Pressure failed LOW.

Which of the following describes the response of the Condenser Steam Dump System to this failure and why?

a. The steam dump valves remain closed but are "armed" due to a loss of load condition being sensed.
b. The dump valves modulate open immediately due to a Tavg/Tref deviation.
c. The steam dump valves blow open immediately due to a turbine trip signal.
d. The instrument failure will only have an effect on the steam dumps if the steam dump mode selector switch is in MANUAL.

ANSWER

a.

REACTOR OPERATOR Page 63 of 100 QUESTION# 063 Consider the following Unit 1 conditions:

Unit 1 is at 100% reactor power Rod control is in automatic A single set of Main Air Ejectors is in service 1MS-2074, Z-53C-H Air Ejector Main Steam Supply control valve fails closed Which of the following conditions will result if NO operator action is taken?

a. Lowering megawatt output and rising hotwell temperature.
b. Rising megawatt output and rising gland seal header pressure.
c. Rising megawatt output and rising condenser hotwell level.
d. Lowering megawatt output and lowering hotwell temperature.

ANSWER

a.

REACTOR OPERATOR Page 64 of 100 QUESTION# 064 Given the following plant conditions:

Unit 2 is operating at 100% power Condensate Pump 2P-25A trips Which of the following is correct regarding the status of the Main Feedwater system 5 minutes after the condensate pump trip?

(Assume NO operator action)

a. Both Main Feedwater Pumps are tripped due to low suction pressure.
b. All Main Feedwater Pumps and Heater Drain Tank Pumps are tripped due to a Safety Injection signal.
c. Both Main Feedwater Pumps are running and Low Pressure Feedwater Heater Bypass Valve (2CS-2273) is open.
d. Both Main Feedwater Pumps are tripped due to a loss of seal water.

ANSWER

a.

REACTOR OPERATOR Page 65 of 100 QUESTION# 065 Both Units are in their normal full power alignments when the following is noted:

The site has experienced a Loss of Offsite Power There is a lockout on 4160 Safeguards Bus 1A05 The deluge system for 1X01 Main Transformers has actuated Water is being supplied to the Fire Header by the (1) and system pressure is being maintained via (2) ?

(1)

(2)

a. P-35A Electric Fire Pump its full flow relief valve.
b. P-35B Diesel Fire Pump its full flow relief valve.
c. P-35A Electric Fire Pump and flow out of the transformer deluge valves.

P-35B Diesel Fire Pump

d. P-35B Diesel Fire Pump the engine governor speed control.

ANSWER

b.

REACTOR OPERATOR Page 66 of 100 QUESTION# 066 Given the following information:

You are assuming the midshift watch on Unit 2 Rod control is in MANUAL due to a failed TAVE/TREF comparator Shortly after assuming the watch, you observe the following abnormal plant indications:

Reactor coolant system temperature has rapidly lowered approximately 2°F

'A' & 'B' S/G level deviation alarms on 2C03 are LIT Automatic charging pump speed is rising Overpower Delta-T runback alarm on 2C04 has LIT Which of the following events is the most likely cause of these indications?

a. Turbine Generator Governor valve drifted towards closed
b. Loss of external electrical load
c. Loss of normal Feedwater
d. Excessive load increase ANSWER
d.

REACTOR OPERATOR Page 67 of 100 QUESTION# 067 Consider the following Unit 1 conditions:

One Control Bank A control rod has become misaligned.

Crew is implementing AOP-6B, Stuck or Misaligned Control Rod, and is to the point of recovering the misaligned rod.

As the RO begins to withdraw the control rod, the "ROD CONTROL URGENT FAILURE" Alarm is received.

What actions should be taken as a result of this alarm?

a. Stop withdrawing control rod, immediately commence shutdown per Technical Specification requirements.
b. Stop withdrawing the control rod, place lift coil disconnect switch in disconnect, contact I & C to troubleshoot Rod Control system.
c. Immediately trip Unit 1 reactor and proceed to EOP-0, 'Reactor Trip or Safety Injection.'
d. Continue withdrawing the control rod, the Urgent Failure alarm is expected.

ANSWER

d.

REACTOR OPERATOR Page 68 of 100 QUESTION# 068 You as an RO on relief crew are to verify a valve lineup per the applicable system checklist and drawing. During performance of the checklist you discover that a valve shown on the system drawing is NOT listed on the applicable checklist.

Which of the following describes the required actions for this plant configuration situation?

Notify the relief crew OS, then initiate...

a. a Condition Report (CR) and pen and ink the checklist to continue.
b. a Condition Report (CR) and a Procedure Change Request (PCR) to update the checklist.
c. an Operator Workaround and pen and ink the checklist to continue.
d. a Work Request (WR) and an Engineering Change Request (ECR) to update the checklist.

ANSWER

b.

REACTOR OPERATOR Page 69 of 100 QUESTION# 069 Both units are in a normal 100% power electric plant lineup.

The Shift Manager just declared G02, Emergency Diesel Generator, INOPERABLE.

Prior to any operator action being taken, which of the following correctly states the status of LCO 3.8.1, AC Operating Sources for both units?

Unit 1 Unit 2

a. met not met
b. not met met
c. not met not met
d. met met ANSWER
c.

REACTOR OPERATOR Page 70 of 100 QUESTION# 070 The following plant conditions exist on Unit 1:

RHR has just been placed in service per OP-7A, Placing Residual Heat Removal System in Operation.

The Control Operator reports unstable RHR flow and discharge pressure.

The Operating Supervisor enters SEP-1, 'Degraded RHR System Capability' and directs RHR pumps secured.

The OS1 also directs the CO to have the PAB Operator reflood the RHR suction line.

Using the provided Figure 1 of SEP-1, analyze and choose which of the following water sources will be used to perform RHR suction line reflood?

a. The RHR Pump Suction from RWST MOV (1SI-856A).
b. The SI Accumulator Outlet MOV (1SI-841A).
c. The SFP to RHR valve (1SF-819) from the Spent Fuel Pool cooling system.
d. The Core Deluge MOV (1SI-852A) from the Safety Injection system.

ANSWER

c.

REACTOR OPERATOR Page 71 of 100 QUESTION# 071 Consider the following Unit 1 conditions:

B SG is ruptured.

Crew is performing EOP-3, 'Steam Generator Tube Rupture' Which of the following describes how 1HC-478, B Atmospheric Steam Dump Controller, will be aligned to minimize steam dumped from the B Steam Generator?

a. Controller in MANUAL, CO maintaining 'B' SG pressure <1085 PSIG.
b. Controller in MANUAL, Manually closed.
c. Controller in AUTO, Set at 1085 PSIG.
d. Controller in AUTO, Set at 1050 PSIG.

ANSWER

d.

REACTOR OPERATOR Page 72 of 100 QUESTION# 072 Operations and RP have just completed filling a High Integrity Container (HIC) with spent resin.

The results of a subsequent radiation survey is as follows:

Top of shielded HIC by fill head: 2500 mr/hr on contact and 1200 mr/hr @ 30 cm Sides of shield: 100 mr/hr on contact and 60 mr/hr @ 30 cm Which of the following describes the required radiological postings for the top of the HIC?

a. The HIC should be posted as a Locked High Radiation area.
b. The HIC should be posted as a High Radiation area.
c. No postings are required because you need a ladder to access the top of the shielded HIC.
d. The PAB truck bay should be barricaded with locked gate access and posted as a Very High Radiation area.

ANSWER

a.

REACTOR OPERATOR Page 73 of 100 QUESTION# 073 Given the following sequence of events:

A transient on Unit 1 has resulted in a Reactor Trip and Safety Injection.

  • The crew has entered EOP-0, transitioned to EOP-1, and is currently implementing EOP-1.1, 'SI Termination.'

The STA reports that an Orange Path on the Integrity status tree exists.

The OS transitions from EOP-1.1 to CSP-P.1, 'Response to Imminent Pressurized Thermal Shock Condition'.

While implementing CSP-P.1, which of the following is correct regarding foldout page applicability?

a. Only foldout page items from CSP-P.1 AND EOP-1.1 apply.
b. Only the foldout page items from CSP-P.1 apply.
c. The foldout page items in EOP-0, EOP-1, EOP-1.1, and CSP-P.1 ALL apply.
d. Only the foldout page items in EOP-0 AND CSP-P.1 apply.

ANSWER

b.

REACTOR OPERATOR Page 74 of 100 QUESTION# 074 Given the following plant conditions:

A reactor start-up is in progress.

Reactor criticality has been achieved and critical rod height data is being recorded.

A bank of rods suddenly drops into the core.

Intermediate Range power is lowering.

The operator immediately pushes the reactor trip pushbuttons, but the reactor trip breakers do not open.

Safety Injection actuates on low PZR pressure.

The correct course of action is described by which of the following statements?

(EOP-0, Reactor Trip or Safety Injection)

(EOP-0.1, Reactor Trip Response)

(CSP-S.1, Response to Nuclear Power Generation/ATWS)

a. Complete EOP-0 Immediate actions and continue until first transition out.
b. Transition from EOP-0 to CSP-S.1.
c. Complete EOP-0 Immediate Actions and transition to EOP- 0.1.
d. Locally open reactor trip breakers and once opened exit EOP-0.

ANSWER

a.

REACTOR OPERATOR Page 75 of 100 QUESTION# 075 Which of the following describes the steps necessary to reset the over-speed trip and restart 1P-29, Turbine-Driven Auxiliary Feedwater Pump?

a. The Auxiliary Operator must locally open the Low Suction Pressure/Overspeed Trip valve.
b. The Auxiliary Operator must manually reset the trip linkage. The Control Operator may then open the valve by placing the control switch to open.
c. The Auxiliary Operator must manually reset the trip linkage. The Control Operator may then place the control switch to close to relatch the valve, and then open to reopen the valve.
d. The Control Operator resets the trip and relatches the valve by placing the control switch to close. Once relatched, the valve can be reopened by placing the control switch to open.

ANSWER

c.

SENIOR REACTOR OPERATOR Page 76 of 100 QUESTION# 076 Unit 1 is operating in Mode 1 when the following is reported by the Control Operator:

Alarm 1C04 1C 3-11, 1P-1A or 1P-1B RCP UPPER or LOWER SUMP OIL LEVEL HIGH or LOW is LIT.

Alarm 1C04 1C 3-10, 1TR-2001 TEMPERATURE MONITOR is LIT.

1TR-2001 Point 3, A RCP Upper Guide Bearing Temperature is 85º C and slowly RISING.

CCW Surge Tank level is 49% and slowly LOWERING.

Based on the above conditions, which of the following states the correct actions to be taken by the Operating Supervisor?

a. Enter AOP-9B, 'Component Cooling System Malfunction' which will have you immediately secure both RCPs and then isolate cooling water to the RCPs.
b. Enter AOP-1B, 'Reactor Coolant Pump Malfunction' and AOP-9B, 'Component Cooling System Malfunction' in parallel to get 'A' RCP secured with cooling water isolated.
c. Enter AOP-1B, 'Reactor Coolant Pump Malfunction' which will have you immediately secure 'A' RCP.
d. Take all of the ARB actions in 1C04 1C 3-11 to determine which RCP brought in the alarm then enter AOP-1B, 'Reactor Coolant Pump Malfunction' to secure the 'A' RCP.

ANSWER

b.

SENIOR REACTOR OPERATOR Page 77 of 100 QUESTION# 077 Unit 1 is in Mode 5 and being cooled down per OP-3C 'Hot Standby to Cold Shutdown'.

The following plant conditions exist:

RCS temperature is 160ºF RCS pressure is 310 psig LTOP and RHR are in service 1SI-841A SI Accumulator MOV is SHUT with power REMOVED 1SI-841B SI Accumulator MOV is SHUT with power AVAILABLE 1T-34B, SI Accumulator is DRAINED and DEPRESSURIZED to atmosphere The crew just secured the last Reactor Coolant Pump The following plant conditions are then noted:

RCS pressure is lowering Alarm 1C03 1D 4-4 RHR LOOP FLOW LO is LIT Alarm C01 B 1-4 UNIT 1 CONTAINMENT SUMP A LEVEL HIGH is LIT 1RE-211 'U1 Containment Air Particulate Monitor' is in alarm The Operating Supervisor will direct actions to mitigate the RHR System leak in the...

a. containment per EOP-0, 'Reactor Trip or Safety Injection.'
b. RHR Pump cubicle per SEP 2.3, 'Cold Shutdown LOCA.'
c. 8' pipeway 2 per SEP 2.2, 'Shutdown LOCA with RHR Aligned for Decay Heat Removal.'
d. containment per SEP 2.3, 'Cold Shutdown LOCA.'

ANSWER

d.

SENIOR REACTOR OPERATOR Page 78 of 100 QUESTION# 078 Given the following conditions:

Unit 1 experienced an ATWS The turbine failed to trip when the turbine trip pushbutton was depressed while performing CSP-S.1, 'Response to Nuclear Power Generation/ATWS'.

While the Control Operator is addressing the failure of the turbine to trip, the STA reports that CST level is 8 feet and lowering.

(AOP-23 UNIT 1, 'ESTABLISHING ALTERNATE AFW SUCTION')

Which of the following actions are required?

a. IMMEDIATELY transition to AOP-23 from the Foldout Page, THEN return to CSP-S.1 when all AOP-23 actions are completed.
b. Continue performing CSP-S.1 actions until directed to return to procedure in effect, THEN branch to AOP-23 from the Foldout page and perform in parallel with procedure in effect.
c. Complete the remaining actions to trip the turbine, THEN branch to AOP-23 from the Foldout Page and perform in parallel with CSP-S.1.
d. Complete the remaining actions to trip the turbine, THEN transition to AOP-23 from the Foldout Page, returning to CSP-S.1 when all AOP-23 actions are completed.

ANSWER

c.

SENIOR REACTOR OPERATOR Page 79 of 100 QUESTION# 079 Given the following conditions:

Both Units were at rated power.

At 10:00 AM today, two (2) channels of 480 Volt loss of voltage relays for 1B03 Safeguards Bus sensed 256 volts on the bus due to a mis-calibration problem.

1B03 actual bus voltage was 480 volts.

It is now 11:00 AM and the relay calibration has not changed.

Which of the following is a complete list of TS 3.3.4 Technical Specification Action Conditions required to be entered AND what automatic action occurred?

a. TSAC 3.3.4.D Two or more 480V loss of voltage channels per bus inoperable TSAC 3.3.4.E RA and Completion Time not met for Condition A or Condition D 1B03 loads with undervoltage (27 device) protection were tripped
b. TSAC 3.3.4.A One or more functions with one channel per bus inoperable TSAC 3.3.4.D Two or more 480V loss of voltage channels per bus inoperable TSAC 3.3.4.E RA and Completion Time not met for Condition A or Condition D 1B03 feeder breaker tripped due to undervoltage (27 device) protection
c. TSAC 3.3.4.A One or more functions with one channel per bus inoperable TSAC 3.3.4.D Two or more 480V loss of voltage channels per bus inoperable TSAC 3.3.4.E RA and Completion Time not met for Condition A or Condition D 1B03 loads with undervoltage (27 device) protection were tripped
d. TSAC 3.3.4.A One or more functions with one channel per bus inoperable TSAC 3.3.4.E RA and Completion Time not met for Condition A or Condition D 1B03 feeder breaker tripped due to undervoltage (27 device) protection ANSWER
c.

SENIOR REACTOR OPERATOR Page 80 of 100 QUESTION# 080 Both units were at rated power in a normal electrical line up when lightning struck a 345 KV transmission line causing a transient:

Red Inverter 1DY01 failed due to a problem with the AC output breaker.

A short time later Yellow Inverter 1DY04 lost its synchronization and tripped off.

What is the status of the Instrument Buses after the electrical perturbation and what procedure(s) will be selected by the Operating Supervisor?

a. Unit 1 Red Instrument Buses are powered from their backup supply and the Yellow Instrument Buses are de-energized. Entry into AOP-0.2, 'Loss of Safety Related Instrument Buses' is required.
b. Unit 1 Red and Yellow Instrument Buses are powered from their backup supply. Entry into AOP-0.1, 'Declining Frequency on 345 KV Distribution System' is required.
c. Unit 1 Red and Yellow Instrument Buses are de-energized. Entry into EOP-0, 'Reactor Trip or Safety Injection' and parallel performance of AOP-0.2, 'Loss of Safety Related Instrument Buses' are required.
d. Unit 1 Red Instrument Buses are powered from their backup supply and the Yellow Instrument Buses are de-energized. Entry into AOP-0.1, 'Declining Frequency on 345 KV Distribution System' is required.

ANSWER

a.

SENIOR REACTOR OPERATOR Page 81 of 100 QUESTION# 081 Unit 2 was operating at 75% power when a plant transient resulted in a reactor trip and safety injection. EOP-0, 'Reactor Trip or Safety Injection', has been entered and the crew is carrying out actions of the procedure. The following plant conditions are noted:

RCS pressure 1100 psig and slowly lowering Pressurizer level 5% and slowly lowering Pressurizer PORVs closed Spray valves closed Steam Generator levels normal Steam Generator pressures normal Containment pressure normal Containment radiation normal Sump 'A' level normal RE 214, PAB Exhaust Monitor rising Several PAB area radiation monitors rising After assessing these conditions, the next procedure the OS will implement is:

a. ECA-1.2, 'LOCA Outside Containment'
b. EOP-1.1, 'SI Termination'
c. ECA-1.1, 'Loss of Containment Sump Recirculation'
d. EOP-1.2, 'Small Break LOCA' ANSWER
a.

SENIOR REACTOR OPERATOR Page 82 of 100 QUESTION# 082 Unit 1 is entering a refueling outage with the following conditions:

RCS temperature is 130°F and stable RCPs are secured Both trains of RHR are aligned for decay heat removal with 'A' train providing cooling Draindown to 40% Pressurizer level was just completed The Control Operator then reports the following information to you:

Pressurizer level is rising Source range counts are rising on both N-31 and N-32 1C04 1C 2-8 'BA FLOW DEVIATION OR POTENTIAL DILUTION IN PROGRESS' alarm is LIT As the Operations Supervisor of that unit what actions are you going to take?

a. Enter AOP-6F, 'Low Concentration Water Pockets in RCS' and borate the RCS from the RWST using a Safety Injection Pump.
b. Use OP-4A, 'Filling and Venting Reactor Coolant System' Attachment D 'Blending Operation for Unit 1 and Unit 2' to borate the RCS from the blender using an available Charging Pump.
c. Enter CSP-S.1, 'Response to Nuclear Power Generation/ATWS' and emergency borate the RCS from the RWST using all available Charging Pumps.
d. Enter SEP-1, 'Degraded RHR System Capability' in an effort to raise RHR flow to 3000 gpm ensuring prompt mixing of the RCS.

ANSWER

a.

SENIOR REACTOR OPERATOR Page 83 of 100 QUESTION# 083 Given the following conditions:

Fifteen minutes ago, an accidental release to the environment of a Waste Gas Decay tank began.

Operators have been taking actions to monitor the release and attempting to isolate it.

The release is currently about 10 times the Radiological Effluent Technical Specifications.

The control room has just been informed that the release cannot be isolated for approximately two more hours.

Which of the following describes the appropriate Emergency Plan classification actions?

a. Declare RU1 Unusual Event at this time.
b. Declare RU1 Unusual Event after the release has exceeded sixty minutes.
c. Declare RA1 Alert with a classification time of fifteen minutes ago.
d. Declare RA1 Alert at this time; upgrade the classification to the next level if leak is not isolated within the next forty five minutes.

ANSWER

a.

SENIOR REACTOR OPERATOR Page 84 of 100 QUESTION# 084 Both Units are in normal full power operation when a fire develops in the control boards. The fire causes the following conditions:

Spurious cycling of plant equipment The crew will be forced to evacuate the Control Room As a Control Room Supervisor, which of the following describes your response?

a. Trip the reactor and enter EOP-0, 'Reactor Trip or Safety Injection'. Perform AOP-10A,

'Safe Shutdown - Local Control' in parallel until the Control Room is accessible.

b. Enter AOP-10A, 'Safe Shutdown - Local Control'; Entering EOP-0, 'Reactor Trip or Safety Injection' is not required.
c. Trip the reactor and perform the immediate actions of EOP-0, 'Reactor Trip or Safety Injection' then transition to AOP-10A, 'Safe Shutdown - Local Control.'
d. Enter AOP-10A, 'Safe Shutdown - Local Control'; Entering EOP-0, 'Reactor Trip or Safety Injection' is required after the Control Room is accessible.

ANSWER

b.

SENIOR REACTOR OPERATOR Page 85 of 100 QUESTION# 085 An event has occurred on Unit 2 with the following results:

Automatic reactor trip and safety injection.

Immediate actions of EOP-0 have been performed and validated.

While providing Attachment A Automatic Action Verification to the 3d license, the OS notes that there are two faulted S/Gs and one ruptured S/G.

The OS considers entering EOP-0.0, 'Rediagnosis' to aid in determining the next course of action.

If the OS were to exit EOP-0 at step 5 and transition to EOP-0.0, the next procedure transition would be ___________.

a. Back to EOP-0, 'Reactor Trip or Safety Injection' to continue diagnostic steps.
b. EOP-2, 'Faulted Steam Generator Isolation' to address a faulted steam generator.
c. EOP-3, 'Steam Generator Tube Rupture' to address the ruptured steam generator.
d. ECA-2.1, 'Uncontrolled Depressurization of Both Steam Generators' to address the faulted steam generators.

ANSWER

a.

SENIOR REACTOR OPERATOR Page 86 of 100 QUESTION# 086 Which statement describes the Technical Specification Safety Limit for Reactor Coolant System Pressure and its bases?

The Reactor Coolant System pressure shall not exceed 2735 psig...

a. at COLD SHUTDOWN during hydrostatic testing to prevent exceeding 115% of design pressure, the maximum transient pressure allowable under ASME Code.
b. in all MODES with settings providing protection to prevent exceeding this value for all analyzed transients.
c. during at power operation to ensure DNBR during steady-state operation, normal operational transients, is maintained greater than or equal to the 95/95 DNBR criterion.
d. while the RCS is greater than or equal to 200ºF in order to prevent exceeding design containment pressure resulting from the postulated Design Basis Accident.

ANSWER

b.

SENIOR REACTOR OPERATOR Page 87 of 100 QUESTION# 087 You are the Unit Supervisor for Unit 2, responding to the following conditions:

A Large Break LOCA has occurred inside Containment.

Containment pressure is 32 PSIG and lowering slowly.

Both Containment Spray trains are running and delivering flow to Containment.

Unit 2 RO is performing the Immediate Action steps of EOP-0, 'Reactor Trip or Safety Injection'.

The RO informs you that 2SI-836A and 2SI-836B, Spray Additive Eductor Suction valves, did NOT open.

What are the potential consequences of this failure AND what direction should be given to the RO?

a. Increased hydrogen generation within Containment; manually open the valves during the performance of EOP-0 Attachment A, Automatic Action Verification.
b. Decreased retention of radioactive iodine in the Containment sump; allow completion of EOP-0 Immediate Action steps, then direct the RO to open 2SI-836A and 2SI-836B.
c. Increased corrosion of components within Containment; ensure the RO manually initiates Containment Spray during the performance of Step 4 of EOP-0 Immediate Actions.
d. Increased radiation levels within Containment; direct the RO to immediately open 2SI-836A and 2SI-836B.

ANSWER

b.

SENIOR REACTOR OPERATOR Page 88 of 100 QUESTION# 088 Given the following full power conditions:

A Tave channel failed HIGH causing rod motion Taking rod control to MANUAL did not stop rod motion The reactor trip was not successful The turbine trip was successful Which of the following states the status of the Condenser Steam Dumps and the procedure selected by the Operating Supervisor to mitigate the event?

a. The Condenser Steam Dumps are OPEN and CSP-S.1, 'Response to Nuclear Power Generation/ATWS' will shut the MSIVs minimizing the cooldown to address reactivity effects.
b. The Condenser Steam Dumps are SHUT and EOP-0, 'Reactor Trip or Safety Injection' will direct use of the Condenser Steam Dumps to control RCS temperature in the desired band after transition out of CSP-S.1, 'Response to Nuclear Power Generation/ATWS.'
c. The Condenser Steam Dumps are OPEN and EOP-2, 'Faulted Steam Generator Isolation' will shut the MSIVs to address the faulted S/G concern.
d. The Condenser Steam Dumps are SHUT and EOP-0.1, 'Reactor Trip Response' will control S/G pressure utilizing the Condenser Steam Dumps in pressure control mode.

ANSWER

a.

SENIOR REACTOR OPERATOR Page 89 of 100 QUESTION# 089 Unit 1 is responding to a Steam Generator Tube Rupture on the 'A' Steam Generator.

The crew is currently implementing EOP-3.1 'Post Steam Generator Tube Rupture Cooldown Using Backfill' in order to cooldown and depressurize the RCS Equipment malfunctions have caused the level in the 'A' Steam Generator to begin rising 1C03 1E2 1-2, 'Steam Generator 'A' Level Setpoint Deviation' is LIT and level is currently 95% and slowly rising The Shift Technical Adviser has informed the Operating Supervisor that a Yellow Path condition exists on the Heat Sink Critical Safety Function and that entry conditions for CSP-H.3 'Response to Steam Generator High Level' are met If not corrected, (1) which of the following describes the most imminent damaging effects of this situation and (2) how the SRO will prioritize the use of CSP-H.3?

a. (1) Damage to 1P-29 Turbine Driven Auxiliary Feedwater Pump is likely.

(2) The SRO must enter CSP-H.3 to address the challenge to the Heat Sink safety function because CSP-H.3 is a higher priority procedure than EOP-3.1.

b. (1) Potential damage to the Main Turbine is likely.

(2) The SRO may enter CSP-H.3 at his discretion. If entered, the requirements of CSP-H.3 will supersede any continuous actions that were in effect in EOP-3.1.

c. (1) Potential damage to the 'A' Steam Generator Atmospheric Dump Valve is likely.

(2) The SRO may enter CSP-H.3 at his discretion. If entered, any continuous actions that were in effect in EOP-3.1 will have priority over actions directed in CSP-H.3.

d. (1) Potential damage to 'A' Steam Generator Safety Valves is likely.

(2) CSP-H.3 may NOT be used in this situation because the crew is now in the event-specific recovery procedure.

ANSWER

c.

SENIOR REACTOR OPERATOR Page 90 of 100 QUESTION# 090 Unit 1 is in MODE 1.

Unit 2 is in MODE 6 for a refueling outage.

All Auxiliary Feedwater pumps are OPERABLE All six Service Water pumps are OPERABLE All required offsite power sources to Units 1 & 2 are OPERABLE G02, Emergency Diesel Generator is OUT OF SERVICE with G01, Emergency Diesel Generator aligned to both 4160v Safeguards Buses.

Given these conditions, which of the following statements correctly describes the requirements associated with cross-tying 2B-03 to 2B-04, Unit 2 480v AC Safeguards buses?

The buses may be cross tied for ___(1)___ provided ___(2)___.

a. (1) up to 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> (2) 1 RHR loop is OPERABLE OR the Unit 2 Reactor Cavity water level is maintained

> 23 feet above the Reactor Vessel flange

b. (1) up to 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> (2) 1 RHR loop is OPERABLE AND the Unit 2 Reactor Cavity water level is maintained

> 23 feet above the Reactor Vessel flange

c. (1) up to 7 days (2) loads on the Unit 2 480v Safeguards Buses are limited to avoid overloading the standby Emergency Diesel Generator
d. (1) up to 7 days (2) G02, Emergency Diesel Generator is restored to an OPERABLE status and re-aligned to its associated 4160v Safeguards Bus ANSWER
b.

SENIOR REACTOR OPERATOR Page 91 of 100 QUESTION# 091 Unit 2 is operating at 100% power with the following conditions:

Pressurizer Level 40% and stable Volume Control Tank Level 40% and lowering Charging Pump control is in MANUAL RO reports a primary leak rate of 20 gpm 2RE-211 Containment Air Particulate Monitor is in alarm 2RE-212 Containment Noble Gas Monitor is in alarm How will the RCS leak rate be addressed?

a. Entry into AOP-1A, 'Reactor Coolant Leak' with no plant shutdown required due to the leak size being within the capability of one charging pump.
b. Entry into AOP-1A, 'Reactor Coolant Leak' and conduct a plant shutdown along with declaration of an UNUSUAL EVENT by the Shift Manager.
c. Direct a manual reactor trip, safety injection and containment isolation with entry into EOP-0, 'Reactor Trip or Safety Injection' along with declaration of an ALERT by the Shift Manager.
d. Entry into AOP-3, 'Steam Generator Tube Leak' and conduct a plant shutdown to Mode 3 using AOP-17A, 'Rapid Power Reduction'.

ANSWER

b.

SENIOR REACTOR OPERATOR Page 92 of 100 QUESTION# 092 Unit 2 experienced an accident, in which several vital ECCS systems have failed.

The crew is implementing CSP-H.1 Response to Loss of Heat Sink.

The STA notes that two (2) Core Exit Thermocouple (CET) temperatures on the ASIP recorders are failed high, while two (2) are failed low.

CET recorder average temperature (TCavg) is 600°F and slowly rising.

Reactor Vessel Narrow Range Level is at 20 ft and stable.

Both RCPs are secured.

The OS is reviewing the status of the Core Cooling Critical Safety Function.

As CET temperature continues to raise, the first condition that will require a transition from CSP-H.1 to address a higher priority challenge to the Core Cooling Status Tree is:

The highest 5 CETs on the ASIP recorder exceed:

a. 650°F
b. 700°F
c. 950°F
d. 1200°F ANSWER
b.

SENIOR REACTOR OPERATOR Page 93 of 100 QUESTION# 093 Unit 1 is in MODE 6 with RP-1C, 'Refueling' in effect during a core reload.

'B' RHR Pump and HX are operating providing cooling

'A' RHR Pump and HX are isolated and drained for maintenance The refueling crew has a spent fuel assembly in the manipulator mast transiting to the core The unit now experiences a loss of 480 VAC Safeguards Bus 1B04.

Which of the following would be required by the Core Load Supervisor?

a. Direct the fuel assembly be sent back to the Spent Fuel Pool and suspend loading fuel in the reactor until cooling is restored.
b. Direct the fuel assembly be placed into the core and suspend loading fuel in the reactor until cooling is restored.
c. Continue loading fuel in the core, only 1 train of RHR is required to be operable with the high cavity water level.
d. Continue loading fuel in the core for up to an hour before fuel motion has to be suspended.

ANSWER

a.

SENIOR REACTOR OPERATOR Page 94 of 100 QUESTION# 094 You are OS2 with a full crew complement of licensed individuals in the Control Room.

The Fourth License is assigned as Dedicated Operator while conducting TS-82, 'Emergency Diesel Generator G-02 Monthly'.

The Unit 2 Control Operator has requested to step outside the Control Room and make a personal 5 minute phone call.

What would be required, if anything, to allow the Unit 2 Control Operator to leave?

a. Nothing is required because there are still 5 licensed individuals in the Control Room and it will be less than 10 minutes.
b. Have the Fourth License conduct a short term relief turnover with the Unit 2 Control Operator.
c. Have the Third License conduct a short term relief turnover with the Unit 2 Control Operator.
d. Have the Shift Technical Advisor report to the Control Room while the Unit 2 Control Operator steps out.

ANSWER

c.

SENIOR REACTOR OPERATOR Page 95 of 100 QUESTION# 095 Which event provides the bases for the minimum boron concentration required to maintain shutdown margin while moving irradiated fuel assemblies during a core offload?

a. Shutdown LOCA
b. Boron dilution
c. Dropped fuel assembly
d. Loss of RHR ANSWER
b.

SENIOR REACTOR OPERATOR Page 96 of 100 QUESTION# 096 Unit 1 is at 100% power. At 0800 on 1/10/11, all indications show that Control Bank D Rod K-7 Rod Position Indication has FAILED LOW.

Which of the following statements correctly describes the requirements of Technical Specifications Action Condition 3.1.7, Required Action A.1.2?

a. RA A.1.2 first performance must be done prior to 1600 on 1/10/11. Subsequent performances should be done every eight hours but a 25% extension is allowed.
b. RA A.1.2 first performance must be done prior to 1600 on 1/10/11. Subsequent performances must be done every eight hours with no extension allowed.
c. RA A.1.2 first performance should be done prior to 1600 on 1/10/11, but can be extended to 1800. Subsequent performances must be done every eight hours with no extension allowed.
d. RA A.1.2 first performance should be done prior to 1600 on 1/10/11, but can be extended to 1800. Subsequent performances should be done every eight hours but a 25%

extension is allowed.

ANSWER

a.

SENIOR REACTOR OPERATOR Page 97 of 100 QUESTION# 097 Surveillance testing has determined the following:

G01 output breaker closure failed to generate an auto-start signal for P-32A Service Water Pump.

The pump was able to be manually started from the Control Room.

Which of the following describes the operability implications of this auto-start failure?

a. P-32A and G01 EDG are INOPERABLE.
b. P-32A is OPERABLE and G01 EDG is INOPERABLE.
c. P-32A is INOPERABLE and G01 EDG is OPERABLE.
d. P-32A and G01 EDG are OPERABLE.

ANSWER

b.

SENIOR REACTOR OPERATOR Page 98 of 100 QUESTION# 098 Given the following on Unit 2:

Refueling operations are in progress It has been 7 days since shutdown The Containment Equipment hatch is removed Irradiated fuel is being moved in the manipulator from the core to the containment upender for transfer to the Spent Fuel Pool A leak is reported from the refueling cavity drain line cleanout flange Refueling Cavity water level is slowly lowering Identify the direction the Core Load Supervisor should provide during this event.

a. Store the irradiated fuel assembly in the containment upender Frame Down, THEN shut the Transfer Tube Gate Valve AND the Spent Fuel Pool Transfer Canal Doors.
b. Store the irradiated fuel assembly in the Spent Fuel Pool upender Frame Down, THEN shut the Spent Fuel Pool Transfer Canal Doors.
c. Store the irradiated fuel assembly in any available core location, THEN have the Control Room secure Unit 2 Purge Supply and Exhaust Fans.
d. Store the irradiated fuel assembly in any available core location, THEN shut the Transfer Tube Gate Valve.

ANSWER

d.

SENIOR REACTOR OPERATOR Page 99 of 100 QUESTION# 099 A fire is reported to the Control Room by an Office Assistant and verified by an Auxiliary Operator in the area of the Lube Oil Storage Room.

According to NP 1.9.14, 'Fire Protection Organization,' which of the following describes a responsibility of an Operating Supervisor regarding fire emergency response guidelines?

The responsible Operating Supervisor should...

a. proceed to the scene to act as the fire brigade leader, after assuring the Shift Manager is in the control room.
b. implement the Emergency Plan.
c. contact the Two Creeks Volunteer Fire Department for assistance as soon as fire magnitude is known.
d. relieve the Shift Manager who will proceed to the scene of the fire to direct activities.

ANSWER

a.

SENIOR REACTOR OPERATOR Page 100 of 100 QUESTION# 100 Given the following conditions:

Unit 1 is at 100% power.

Air in leakage to the condenser has resulted in steadily degrading condenser vacuum.

A load reduction is directed in order to maintain vacuum.

With the unit at approximately 85% power, a manual reactor trip is ordered due to the inability to maintain vacuum.

Based solely on the information given, which of the following describes the notification requirements for this event?

a. The NRC must be notified within 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> due to manual actuation of the Reactor Protection System.
b. The State/County must be notified within 15 minutes of the trip due to reaching an Emergency Plan classification for an Unusual Event.
c. WEPSS Balancing Authority must be notified within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> in order to ensure generation planning oversight.
d. No notifications to any outside agencies are required for these conditions.

ANSWER

a.
                                            • END OF EXAMINATION**********************