From:

john.hufnagel@exeloncorp.com Sent:

Wednesday, February 23, 2011 11:19 AM To:

Brady, Bennett Cc:

Dylan.Cimock@exeloncorp.com; donald.warfel@exeloncorp.com; Ali.Fakhar@pseg.com

Subject:

RE: Question on Hope Creek October Outage

Bennett, In response to your question on HC outage OE, please see the following summary from our Project Buried Piping guy:

Both SW inspections, located at the service water intake structure and RX building, were performed last fall (2010). Both pipes were found coated w/ coating in good to excellent condition. The coatings were removed on each to expose the bare metal. The exposed metal surfaces of the pipes were also in excellent condition.

I hope this satisfactorily answers your question.

- John.

From: Brady, Bennett [1]

Sent: Friday, February 18, 2011 4:32 PM To: Hufnagel Jr, John G:(GenCo-Nuc)

Subject:

RE: Question on Hope Creek October Outage Thats fine. Thanks.

Bennett From: john.hufnagel@exeloncorp.com [2]

Sent: Friday, February 18, 2011 4:31 PM To: Brady, Bennett

Subject:

RE: Question on Hope Creek October Outage I think so but will have to check, Bennett.

From: Brady, Bennett [3]

Sent: Friday, February 18, 2011 3:31 PM To: Hufnagel Jr, John G:(GenCo-Nuc)

Cc: Cunanan, Arthur

Subject:

Question on Hope Creek October Outage

John, In your October 29 letter, LR-N10-0371, it said The configuration of the approximately 12 linear feet of 36 inch diameter carbon steel Service Water System piping is externally coated but not provided with cathodic protection. As described in the PSEG response to RAI B.2.1.24, Hope Creek plans to

inspect two of the four buried pipe segments which make up the 12 linear feet during the next refueling outage in the fall of 2010.

Did this happen?

Bennett Bennett M. Brady Senior Project Manager U.S. Nuclear Regulatory Commission NRR/DLR/RPB1 301-415-2981

                                                                                                    • This e-mail and any of its attachments may contain Exelon Corporation proprietary information, which is privileged, confidential, or subject to copyright belonging to the Exelon Corporation family of Companies.

This e-mail is intended solely for the use of the individual or entity to which it is addressed. If you are not the intended recipient of this e-mail, you are hereby notified that any dissemination, distribution, copying, or action taken in relation to the contents of and attachments to this e-mail is strictly prohibited and may be unlawful. If you have received this e-mail in error, please notify the sender immediately and permanently delete the original and any copy of this e-mail and any printout. Thank You. **************************************************

                                                                                                    • This e-mail and any of its attachments may contain Exelon Corporation proprietary information, which is privileged, confidential, or subject to copyright belonging to the Exelon Corporation family of Companies.

This e-mail is intended solely for the use of the individual or entity to which it is addressed. If you are not the intended recipient of this e-mail, you are hereby notified that any dissemination, distribution, copying, or action taken in relation to the contents of and attachments to this e-mail is strictly prohibited and may be unlawful. If you have received this e-mail in error, please notify the sender immediately and permanently delete the original and any copy of this e-mail and any printout. Thank You. **************************************************