ML020780312

From kanterella
Jump to navigation Jump to search

Technical Specification Pages (Paper)
ML020780312
Person / Time
Site: Summer South Carolina Electric & Gas Company icon.png
Issue date: 03/12/2002
From: Edison G
NRC/NRR/DLPM/LPD2
To: Byrne S
South Carolina Electric & Gas Co
References
TAC MB2236
Download: ML020780312 (3)


Text

INSTRUMENTATION BASES REACTOR TRIP AND ENGINEERED SAFETY FEATURE ACTUATION SYSTEM INSTRUMENTATION (continued) will happen, an infrequent excessive drift is expected. Rack or sensor drift, in excess of the allowance that is more than occasional, may be indicative of more serious problems and should warrant further investigation.

The measurement of response time at the specified frequencies provides assurance that the reactor trip and the engineered safety feature actuation associated with each channel is completed within the time limit assumed in the accident analyses. No credit was taken in the analyses for those channels with response times indicated as not applicable.

Response time may be demonstrated by any series of sequential, overlapping or total channel test measurements provided that such tests demonstrate the total channel response time as defined. Response time may be verified by actual response time tests in any series of sequential, overlapping, or total channel measurements, or by the summation of allocated sensor, signal processing, and actuation logic response times with actual response time tests on the remainder of the channel. Allocations for sensor response times may be obtained from: (1) historical records based on acceptable response time tests (hydraulic, noise or power interrupt tests), (2) in place, onsite, or offsite (e.g., vendor) test measurements, or (3) utilizing vendor engineering specifications. WCAP-13632-P-A, Revision 2, "Elimination of Pressure Sensor Response Time Testing Requirements," provides the basis and methodology for using allocated sensor response times in the overall verification of the channel response time for specific sensors identified in the WCAP. Response time verification for other sensor types must be demonstrated by test.

WCAP-14036-P-A, Revision 1, "Elimination of Periodic Response Time Tests,"

provides the basis and methodology for using allocated signal processing and actuation logic response times in the overall verification of the protection system channel response time.

The allocations for sensor, signal conditioning, and actuation logic response times must be verified prior to placing the component into operational service and re-verified following maintenance or modification that may adversely affect response time. In general, electrical repair work does not impact response time provided the parts used for the repair are of the same type and value. Specific components identified in the WCAP may be replaced without verification testing. One example where response time could be affected is replacing the sensing element of a transmitter.

Westinghouse letter CGE-00-018, dated March 28, 2000, provided an evaluation of the Group 05 (11 NLP and 6NSA) 7300 process cards. These cards were revised after the submittal of WCAP-14036, Revision 1. This letter concluded that the failure modes and effects analysis (FMEA) performed for the older versions of these cards and documented in WCAP-14036-P-A, Revision 1, is applicable for these Group 05 cards. The bounding time response values determined by test and evaluation and reported in the WCAP are valid for these redesigned cards.

SUMMER - UNIT 1 B 3/4 3-1a Amendment No. 35, n1-1, 12o, 146, 158

INSTRUMENTATION BASES REACTOR TRIP AND ENGINEERED SAFETY FEATURE ACTUATION SYSTEM INSTRUMENTATION (continued)

The Engineered Safety Features response times specified in Table 3.3-5 which include sequential operation of the RWST and VCT valves (Notes 2 and 3) are based on values assumed in the non-LOCA safety analyses. These analyses are for injection of borated water from the RWST. Injection of borated water is assumed not to occur until the VCT charging pump suction isolation valves are closed following opening of the RWST charging pumps suction valves. When the sequential operation of the RWST and VCT valves is not included in the response times (Note 1) the values specified are based on the LOCA analyses. The LOCA analyses take credit for injection flow regardless of the source.

Verification of the response times specified in Table 3.3-5 will assure that the assumptions used for the LOCA and non-LOCA analyses with respect to the operation of the VCT and RWST valves are valid.

The Engineered Safety Features Actuation System senses selected plant parameters and determines whether or not predetermined limits are being exceeded. Ifthey are, the signals are combined into logic matrices sensitive to combinations indicative of various accidents, events, and transients. Once the required logic combination is completed, the system sends actuation signals to those engineered safety features components whose aggregate function best serves the requirements of the condition. As an example, the following actions may be initiated by the Engineered Safety Features Actuation System to mitigate the consequences of a steam line break or loss of coolant accident 1) safety injection pumps start and automatic valves position, 2) reactor trip, 3) feedwater isolation,

4) startup of the emergency diesel generators, 5) containment spray pumps start and automatic valves position, 6) containment isolation, 7) steam line isolation, 8) turbine trip,
9) auxiliary feedwater pumps start and automatic valves position, 10) containment cooling fans start and automatic valves position, 11) essential service water pumps start and automatic valves position, and 12) control room isolation and ventilation systems start.

Several automatic logic functions included in this specification are not necessary for Engineered Safety Feature System actuation but their functional capability at the specified setpoints enhances the overall reliability of the Engineered Safety Features functions. These automatic actuation Systems are purge and exhaust isolation from high containment radioactivity, turbine trip and feedwater isolation from steam generator high-high water level, initiation of emergency feedwater on a trip of the main feedwater pumps, automatic transfer of the suctions of the emergency feedwater pumps to service water on low suction pressure, and automatic opening of the containment recirculation sump suction valves for the RHR and spray pumps on low-low refueling water storage tank level.

SUMMER - UNIT 1 B 3/4 3-1b Amendment No. 67,!-44,6, 158

INSTRUMENTATION BASES REACTOR TRIP AND ENGINEERED SAFETY FEATURE ACTUATION SYSTEM INSTRUMENTATION (continued)

The service water response time includes: 1) the start of the service water pumps and, 2) the service water pumps discharge valves (3116A,B,C-SW) stroking to the fully opened position. This condition of the valves assures that flow will become established through the component cooling water heat exchanger, diesel generator coolers, HVAC chiller, and to the suction of the service water booster pumps when these components are placed in-service. Prior to this time, the flow is rapidly approaching required flow and sufficient pressure is developed as valves finish their stroke. Each of the above-listed components will be starting to perform their accident mitigation function, either directly or indirectly depending upon the use of the component, and will be operational within the service water response time of 71.5/81.5 seconds". Only the service water booster pumps have a direct impact on the accident analysis via the RBCUs' heat removal capability as discussed below.

The RBCU response time includes: 1) the start of the RBCU fan and the service water booster pumps and, 2) all the service water valves which must be driven to the fully opened or fully closed position. This condition of the valves allows the flow to become fully established through the RBCU. Prior to this time, the flow is rapidly approaching required flow as the valves finish their stroke. Although the RBCU would be removing heat through out the Engineered Safety Features response time, the accident analysis does not assume heat removal capability from 0 to 71.5 seconds 2/ because the industrial cooling water system is not completely isolated until 71.5 seconds. A linear ramp increase from 95% full heat removal capability to 100% full heat removal capability is assumed by the accident analysis to start at 71.5 seconds and end at 86.5 seconds-. Full heat removal capability is assumed at 86.5 seconds based on the position of the valve 3107-SW.

-* Total time is 1.5 second instrument response after setpoint is reached, plus 10 seconds diesel generator start, plus 10 seconds to reach service water pump start and begin 3116-SW opening via Engineered Safety Features Loading Sequencer, plus 60 seconds stroke time for 3116-SW. During this total time, the service water pumps start and the service water pump discharge valve begins to open at 11.5 seconds and the pump discharge valve is fully open at 71.5 seconds without a diesel generator start required and 21.5 seconds and 81.5 seconds including a diesel generator start.

2/ Total time is 1.5 second instrument response after setpoint Is reached, plus 10 second diesel start plus 60 seconds* for valves to isolate industrial cooling water system.

21 Total time is 1.5 second instrument response after setpoint is reached, plus 10 second diesel generator start plus 75 seconds to stroke valves 3107A, B-SW.

  • During this time period, the Engineered Safety Features Loading Sequencer starts the RBCU fans at 25 seconds and service water booster pumps at 30 seconds after the valves begin to stroke.

SUMMER- UNIT 1 B 3/4 3-1c Amendment No. 67, 14,158

  • .