MONTHYEARL-2006-009, December 2005 Monthly Operating Report for St. Lucie Units 1 & 22006-01-13013 January 2006 December 2005 Monthly Operating Report for St. Lucie Units 1 & 2 L-2005-248, November 2005 Monthly Operating Report for St. Lucie, Units 1 and 22005-12-0808 December 2005 November 2005 Monthly Operating Report for St. Lucie, Units 1 and 2 L-2005-236, October 2005 Monthly Operating Report for St. Lucie, Units 1 & 22005-11-0909 November 2005 October 2005 Monthly Operating Report for St. Lucie, Units 1 & 2 L-2005-221, September 2005 Monthly Operating Report for St Lucie Units 1 and 22005-10-14014 October 2005 September 2005 Monthly Operating Report for St Lucie Units 1 and 2 L-2005-199, August 2005 Monthly Operating Report for St. Lucie 12005-09-13013 September 2005 August 2005 Monthly Operating Report for St. Lucie 1 L-2005-185, July 2005 Monthly Operating Report for St. Lucie Units 1 and 22005-08-11011 August 2005 July 2005 Monthly Operating Report for St. Lucie Units 1 and 2 L-2005-151, June 2005 Monthly Operating Report for St Lucie Units 1 & 22005-07-11011 July 2005 June 2005 Monthly Operating Report for St Lucie Units 1 & 2 L-2005-138, May 2005 Monthly Operating Report for St Lucie Units 1 & 22005-06-15015 June 2005 May 2005 Monthly Operating Report for St Lucie Units 1 & 2 L-2005-114, April 2005 Monthly Operating Report for St Lucie Units 1 & 22005-05-16016 May 2005 April 2005 Monthly Operating Report for St Lucie Units 1 & 2 L-2005-091, March 2005 Monthly Operating Report for St Lucie Units 1 and 22005-04-15015 April 2005 March 2005 Monthly Operating Report for St Lucie Units 1 and 2 L-2005-063, February 2005 Monthly Operating Report for St Lucie Units 1 and 22005-03-15015 March 2005 February 2005 Monthly Operating Report for St Lucie Units 1 and 2 L-2005-036, January 2005 Monthly Operating Report for St. Lucie Units 1 and 22005-02-0808 February 2005 January 2005 Monthly Operating Report for St. Lucie Units 1 and 2 L-2005-010, December 2004 Monthly Operating Report for St Lucie Units 1 and 22005-01-17017 January 2005 December 2004 Monthly Operating Report for St Lucie Units 1 and 2 L-2004-264, October 2004 Monthly Operating Report for St Lucie Units 1 and 22004-11-12012 November 2004 October 2004 Monthly Operating Report for St Lucie Units 1 and 2 L-2004-225, September 2004 Monthly Operating Report for St Lucie Units 1 and 22004-10-11011 October 2004 September 2004 Monthly Operating Report for St Lucie Units 1 and 2 L-2004-207, August 2004 Monthly Operating Report for St Lucie Units 1 and 22004-09-13013 September 2004 August 2004 Monthly Operating Report for St Lucie Units 1 and 2 L-2004-182, July 2004 Monthly Operating Report for St. Lucie Units 1 and 22004-08-10010 August 2004 July 2004 Monthly Operating Report for St. Lucie Units 1 and 2 L-2004-159, June 2004 Monthly Operating Report for St. Lucie Units 1 and 22004-07-14014 July 2004 June 2004 Monthly Operating Report for St. Lucie Units 1 and 2 ML0417406582004-06-14014 June 2004 May 2004 Monthly Operating Report for St. Lucie Units 1 and 2 L-2004-113, April 2004 Monthly Operating Report for St. Lucie Units 1 & 22004-05-14014 May 2004 April 2004 Monthly Operating Report for St. Lucie Units 1 & 2 L-2004-087, March 2004 Monthly Operating Report for St. Lucie Units 1 and 22004-04-13013 April 2004 March 2004 Monthly Operating Report for St. Lucie Units 1 and 2 L-2004-060, February 2004 Monthly Operating Report for St. Lucie, Units 1 and 22004-03-12012 March 2004 February 2004 Monthly Operating Report for St. Lucie, Units 1 and 2 L-2004-042, January 2004 Monthly Operating Report for St. Lucie, Units 1 and 22004-02-10010 February 2004 January 2004 Monthly Operating Report for St. Lucie, Units 1 and 2 L-2004-005, December 2003 Monthly Operating Report for St. Lucie, Units 1 and 22004-01-15015 January 2004 December 2003 Monthly Operating Report for St. Lucie, Units 1 and 2 L-2003-303, November 2003 Monthly Operating Report for St. Lucie, Units 1 and 22003-12-11011 December 2003 November 2003 Monthly Operating Report for St. Lucie, Units 1 and 2 L-2003-282, October 2003 Monthly Operating Report for St. Lucie, Units 1 and 22003-11-13013 November 2003 October 2003 Monthly Operating Report for St. Lucie, Units 1 and 2 L-2003-268, September 2003 Monthly Operating Report for St. Lucie, Units 1 & 22003-10-15015 October 2003 September 2003 Monthly Operating Report for St. Lucie, Units 1 & 2 L-2003-228, August 2003 Monthly Operating Report for St. Lucie Units 1 & 22003-09-10010 September 2003 August 2003 Monthly Operating Report for St. Lucie Units 1 & 2 L-2003-210, July 2003 Monthly Operating Report for St. Lucie Units 1 & 22003-08-13013 August 2003 July 2003 Monthly Operating Report for St. Lucie Units 1 & 2 L-2003-177, June 2003 Monthly Operating Report for St. Lucie Units 1 and 22003-07-15015 July 2003 June 2003 Monthly Operating Report for St. Lucie Units 1 and 2 L-2003-150, May 2003 Monthly Operating Report for St. Lucie Units 1 and 22003-06-13013 June 2003 May 2003 Monthly Operating Report for St. Lucie Units 1 and 2 L-2003-119, April 2003 Monthly Operating Report for St. Lucie, Units 1 & 22003-05-14014 May 2003 April 2003 Monthly Operating Report for St. Lucie, Units 1 & 2 L-2003-090, March 2003 Monthly Operating Report for St. Lucie Units 1 & 22003-04-14014 April 2003 March 2003 Monthly Operating Report for St. Lucie Units 1 & 2 L-2003-060, February 2003 Monthly Operating Report for St. Lucie Units 1 & 22003-03-11011 March 2003 February 2003 Monthly Operating Report for St. Lucie Units 1 & 2 L-2003-025, January 2003 Monthly Operating Report for St. Lucie Units 1 & 22003-02-11011 February 2003 January 2003 Monthly Operating Report for St. Lucie Units 1 & 2 L-2003-004, December 2002 Monthly Operating Report for St. Lucie Units 1 & 22003-01-13013 January 2003 December 2002 Monthly Operating Report for St. Lucie Units 1 & 2 L-2002-244, November 2002 Monthly Operating Report for St. Lucie, Units 1 & 22002-12-10010 December 2002 November 2002 Monthly Operating Report for St. Lucie, Units 1 & 2 L-2002-227, October 2002 Monthly Operating Report for St. Lucie Units 1 & 22002-11-15015 November 2002 October 2002 Monthly Operating Report for St. Lucie Units 1 & 2 L-2002-206, September 2002 Monthly Operating Report for St. Lucie Units 1 & 22002-10-14014 October 2002 September 2002 Monthly Operating Report for St. Lucie Units 1 & 2 L-2002-184, August 2002 Monthly Operating Report for St Lucie Units 1 and 22002-09-11011 September 2002 August 2002 Monthly Operating Report for St Lucie Units 1 and 2 L-2002-164, July 2002 Monthly Operating Report for St. Lucie Units 1 & 22002-08-13013 August 2002 July 2002 Monthly Operating Report for St. Lucie Units 1 & 2 L-2002-133, June 2002 Monthly Operating Report for St. Lucie, Units 1 & 22002-07-11011 July 2002 June 2002 Monthly Operating Report for St. Lucie, Units 1 & 2 L-2002-098, April 2002 Monthly Operating Report for St. Lucie Units 1 & 22002-05-14014 May 2002 April 2002 Monthly Operating Report for St. Lucie Units 1 & 2 L-2002-066, March 2002 Monthly Operating Report for St. Lucie Units 1 and 22002-04-12012 April 2002 March 2002 Monthly Operating Report for St. Lucie Units 1 and 2 L-2002-050, February 2002 Monthly Operating Report for St. Lucie, Units 1 & 22002-03-13013 March 2002 February 2002 Monthly Operating Report for St. Lucie, Units 1 & 2 L-2002-034, January 2002 Monthly Operating Report for St. Lucie, Units 1 & 22002-02-13013 February 2002 January 2002 Monthly Operating Report for St. Lucie, Units 1 & 2 L-2002-010, December 2001 Monthly Operating Report for St. Lucie Units 1 and 22002-01-14014 January 2002 December 2001 Monthly Operating Report for St. Lucie Units 1 and 2 2006-01-13
[Table view] |
Text
Florida Power & Light Company, 6501 S. Ocean Drive, Jensen Beach, FL 34957 0
FPL October 15, 2003 L-2003-268 10 CFR 50.36 U. S. Nuclear Regulatory Commission Attn: Document Control Desk Washington, DC 20555 Re: St. Lucie Units 1 and 2 Docket Nos. 50-335 and 50-389 Monthly OPerating Report Pursuant to Technical Specification 6.9.1.6, and the guidance of Generic Letter 97-02, attached are the September 2003 Operating Data Report, Summary of Operating Experience Report, and Unit Shutdowns and Power Reductions for St. Lucie Units 1 and 2.
Please contact us should there be any questions regarding this information.
Vice President St. Lucie Plant WJ/tit Attachments
-::Ceo an FPL Group company
DOCKET NO.: 50-335 UNIT NAME: St. Lucie Unit I DATE: October 7, 2003 COMPLETED BY: W. D. Mead, Jr.
TELEPHONE: (772) 467-7293 REPORTING PERIOD: September 2003
- 1. Design Electrical Rating (Mwe-Net).. - 830
- 2. Maximum Dependable Capacity (Mwe-Net)_ 839 MONTH -YTD- CUMULATIVE
- 3. Number of Hours Reactor Critical_ ,__ 720 6551 191335
- 4. Number of Hours Generator On Line_ 720 6551 189501.3
- 5. Unit Reserve Shutdown Hours _ 0.0 0.0 0.0
- 6. Net Electrical Energy (MWH) - 612047 5615869 155212003
SUMMARY
OF OPERATING EXPERIENCE DOCKET NO.: 50-335 UNIT: St. Lucie Unit 1 DATE: October 7, 2003 COMPLETED BY: W. D. Mead, Jr.
TELEPHONE: (772) 467-7293 REPORT MONTH: September 2003 Unit 1 operated at essentially full power through the entire month of September.
In accordance with the requirements of Technical Specification 6.9.1.6, there were no challenges to the power operated relief valves (PORV) or the safety valves during the report period.
UNIT SHUTDOWNS AND POWER REDUCTIONS DOCKET NO.: 50-33!
UNIT: St. Lucie Unit I DATE: October 7, 2003 COMPLETED BY: W. D. Mead, Jr.
TELEPHONE: (772) 467-7293 REPORT MONTH: September 2003 Number Date Typel Duration Reason2 Method of Cause & Corrective (Hours) Shutting Down Action to Reactor3 Prevent Recurrence Unit I operated at essentially full power for the entire month of
. - - - _______________ Septem ber.
I 2 3 F Forced Reason Method S Scheduled A - Equipment Failure (Explain) I -Manual B - Maintenance or Test 2 - Manual Scram C - Refueling 3 -Automatic Scram D- Regulatory Restriction 4 - Continued E - Operator Training & License Examination 5 -Load Reduction F - Administrative 9 -Other (Explain)
G -Operational Error (Explain)
H -Other (Explain)
DOCKET NO.: 50-389 UNIT NAME: St. Lucie Unit 2 DATE: October 8, 2003 COMPLETED BY: W. D. Mead, Jr.
TELEPHONE: (772) 467-7293 REPORTING PERIOD: September 2003
- 1. Design Electrical Rating (Mwe-Net)_ 830
- 2. Maximum Dependable Capacity (Mwe-Net).. 839 MONTH -YTD- CUMULATIVE
- 3. Number of Hours Reactor Critical __ 720 5209.2 153967.8
- 4. Number of Hours Generator On Line_ 720 5104.45 152104.75
- 5. Unit Reserve Shutdown Hours_ 0.0 0.0 0.0
- 6. Net Electrical Energy (MWH )..._- 601916 4211148 125369861
SUMMARY
OF OPERATING EXPERIENCE DOCKET NO.: 50-389 UNIT: St. Lucie Unit 2 DATE: October 8,, 2003 COMPLETED BY: W. D. Mead, Jr.
TELEPHONE: (772) 467-7293 REPORT MONTH: September 2003 Unit 2 operated at essentially full power through the entire month of September.
In accordance with the requirements of Technical Specification 6.9.1.6, there were no challenges to the power operated relief valves (PORV) or the safety valves during the report period.
9 UNIT SHUTDOWNS AND POWER REDUCTIONS DOCKET NO.: 50-389 UNIT: St. Lucle Unit 2 DATE: October 8, 2003 COMPLETED BGY: W. D. Mead, Jr.
TELEPHONE: (772) 467-7293 REPORT MONTH: September 2003 Number Date Typel Duration Reason 2 Method of Cause &Corrective (Hours) Shutting Down Actlon to Reactor3 Prevent Recurrence Unit 2 operated at essentially full power for the entire month of
. ~~~~~~~~~~~~~~Septembr 1 2 3 F Forced Reason Method S Scheduled A - Equipment Failure (Explain) 1- Manual B - Maintenance or Test 2 - Manual Scram C - Refueling 3 -Automatic Scram D -Regulatory Restrirlcion 4 -Continued E- Operator Trainig & License Examination 5- Load Reduction F - Administrative 9 -Other (Explain)
G- Operational Error (Explain)
H - Other (Explain)