_ _..

.

.

.

.

U.S. NUCLEAR REGULATORY COMMISSION

REGION III

Report No. 50-461/90015(DRSS)

Docket No. 50-461 License No. NPF-62 Licensee:

Illinois Power Company 500 South 27th Street Decatur, IL 62525 Facility Name:

Clinton Power Station Inspection At:

Clinton Site, Clinton, Ohio Inspectiun Conducted: July 23-27, 1990 MN h SM ~

Inspectors:

Thomas Ploski 8/5/)0 Team Leader Date hsYost it?

iirap Accompanying Personnel:

Thomas Lonergan Phil Brockman uSLSJ Approved By:

William Snell, Chief M/fo ~~

Radiologica' Controls and Date Emergency Preparedness Section Inspection Summary Inspection on July 23-27 1990 (Report No. 50-461/90015(DRSSj)

Areas Inspec Qd:

%utine, announced inspection of the Cl nton Power Station i

annual emergency preparedness exercise involving follow up on licensee actions on previously identified items (IP 92701), review of Lhe exercise scenario (IP 02302). and observations by four NRC represent.tives of key functions, activities, ad locations during the exercise (IP 82301).

Results:

No vio'ations, deficiencies or deviations were identified. The licensee demonstrated a good overall response to a hypothetical scenario involving multiple equipment failures.

One Exercise Weakness (related to delayed State notification of the Site Area Emergency declaration) which will require corrective action is identified in this report and the Appendix to the report's transmittal letter.

l 9008000t70 c,00 Eu? ?

l r-DF ADOC1 0 500[>c.@ l v

rDt

_ _. _ _. _

__

-

_ _ _ _..

-

.

.

DETAILS 1.

NRC Observers and Areas Observed T. Ploski, Technical Support Center (TSC)

J. Foster, Simulator Control Room, Emergency Operations Facility P. Brockman, Operational Support Center (OSC), in-plant teams T. Lonergan, OSC, medical drill, in-plant teams 2.

Persons Contacted Illinois Power Company *

J. Perry, Vice President J. Cook, Manager - Clinton Power Station F. Spangenberg, Manager - Licensing and Safety D. Antonelli, Acting Manager - Nuclear Training R. Wyatt, Manager - Quality Assurance P. Hall, Director - Nuclear Program Assessment P. Yocum, Director - Plant Operations D. Miller, Director - Radiation Protection D. Waddel, Director - Emergency Response R. Gardner, Supervisor - Emergency Planning W. Yaroz, Supervisor - Emergency Exercises United Kingdom Observers T. Driscoll, Nuclear Installations Inspectorate M. Segal, Ministry of Agriculture P. Edwards, Department of Energy A. Jones, Somerset County Emergency Planning J. Parker - Jones, Avon and Somerset Constabulary N. Oakes, British Nuclear Fuels

  • These and approximately 25 other licensee representatives attended the exit interview held on July 26, 1990.

The inspector (s) also contacted other licensee personnel during the course of the inspection.

3.

Licensee Action on Previously Identified items (IP 92701)

a.

(Closed) Open Item No.461/89020-01: During the 1989 exercise, the Shift Supervisor in the Control Room Simulator and the Technical Support Center's Emergency Coerations Supervisor had differing opinions regarding whether toe postulated failure of the reactor protection system to initiate and complete a SCRAM warranted an Alert or a Site Area Emergency declaration per the Emergency Action Levels (EALs) of Condition No. 9.2, " Failure to SCRAM."

The Alert and Site Area Emergency EALs for Condition No. 9.2 have been revised to clearly differentiate between those situations

,.

warranting an Alert versus a Site Area Emergency declaration.

The

,

l

____-

_ _......... _.

.

revised EAL classification guidance includes specific criteria to determine if the reactor is shutdown, based on control rod position (s), reactor coolant boron indication, or reactor power level.

The two revised EALs were approved in June 1990 as part of Revision 8 to the licensee's Emergency Plan, and have been proceduralized. This item is closed, b.

[ Closed) Open item No.461/89020-02:

During the 1989 exercise, the licensee did not follow procedures for notifying State and simulated NRC officials of a simulated contaminated, injured victim who required hospital treatment.

The scenario used for the 1990 practice exercise was essentially the 1989 scenario, which included a response to a contaminated injured victim.

Records review of initial and followup messages from the 1990 practice exercise indicated that State and simulated NRC officials were adequately informed of the contaminated, injured victim.

The 1990 evaluated exercise's scenario also included a similar contaminated, injured victim response.

As indicated in Sections 6.b and 6.d of this Inspection Report, State and simulated NRC officials were informed of the contaminated, injured victim's transport to a local hospital.

This item is closed.

b.

(Closed) Severity Level IV Violation No.461/89035-01:

Review of a sample of 1989 training records for members of the Emergency Response Organization (ERO) indicated that several persons had not completed all training requirements within the prescribed time limit.

It was also noted that administrative procedures lacked provisions for deleting an individual from the ERO roster in the event that refresher training was not successfully completed within the required time period.

The licensee responded to this Violation by letter dated January 5, 1990, indicating that corrective actions were in progress.

Corrective actions have now been completed, including a review of previous training records.

The licensee determined that 12 persons'

previous refresher training had exceeded the 15 month time limit.

Three of these persons were removed from the EP~ roster, while the others were given refresher training during January 1990.

Procedure AP-10, "ER0 Assignments," has been revised to upgrade provisions for informing ERO members and their Department Managers when -efresher training deadlines are being approached and when they have been exceeded.

Per the current procedure, the Vice President would be notified if an individual's refresher training deadline had been exceeded.

Procedure AP-05, " Emergency Preparedness Training Requirements," has been revised to more clearly specify refresher training f requency and the various means of completing ref resher training.

The licensee was also developing a computerized means of tracking an ERO member's emergency prepar Sess training to facilitate the identification of persons whose rt Nesher training deadline is

_ _ - _ _ _ - _ _ _ _ _ _ _ - _ _ _ _

-

-

-

.,

..... - -

.

..

.

-

--

-

- -

-

-

- -- - - -

--

'.

,z

..

.

.

,

apprcaching or has been exceeded.

Persons who have not completed-refresher training within the required time limit would be arpropriately identified on the ERO roster pending corrective t.ction to resolve such training problems. This item is closed.,

4.

General

'

An announced, daytime exercise of the Clinton Power Station Emergency Plan was conducted at the'Clinton Power Station site on July 25, 1990.

The exercise tested the licensee's and offsite agencies emergency support organizations'. capabilities to respond to a simulated accident scenario involving multiple equipment failures with the potential to result in a major release of radioactive ef fluent. This was a " partial" exercise.

DeWitt county participated fully, and the State of Illinois participated to a limited extent.

Attachment I describes the Scope and Objectives of the exercise and Attachment 2-describes the 1990 exercise scenario.

5.

General Observations a.

Procedures This exercise was conducted in accordance with 10 CFR Part 50, Appendix E requirements, using the Clinton Power Station Emergency Plan and related Emergency Plan Implementing Procedures.

b.

Coordination The licensee's response was generally coordinated, orderly and timely.

If the. scenario events had been real, the actions taken by the licensee's Emergency Response Organization (ERO) would have been sufficient to mitigate the accident and permit State and local authorities to take appropriate actions-to protect the public's health and safety, c.

Observers The licensee's controllers / observers monitored and critiqued this exercise along with four NRC observers. Activities by State and local authorities were observed by a team of sixteen Federal Emergency Management Agency (FEMA) evaluators.

FEMA will be issuing a separate report, evaluating the performance of State and county responders.

liine citizens of the United Kingdom (UK) also observed portions of the onsite and offsite exercise, as well as pre-and post-exercise meetings conducted by the NRC, FEMA, and the licensee. The UK representatives representad several national, local, and nuclear utility organizations.

. - _ _ _ _ _

_

..

..

s w

.-

,

i i

- d.

. Exercise Critiques.

The' licensee's controllers /evtluators held critiques in each facility (with participants) 'mmediately following the exercise.

The licensee held a summary c itique on July 26, 1990, the day following the exercise, to discuss observed strengths and weaknesses for each facility and the ovt.rall exercise. This presentation was

"

followed by the NRC Exit Interview. The NRC discussed observed strengths and weaknesses, developed independently by the NRC evaluation team, during the Exit Interview with the licensee.

The NRC's preliminary findings were also summarized at the public critique, hosted by FEMA Region V on July 27, 1990 at the DeWitt County Emergency Operations Center.

6.

Specific Observations (IP 82301)

- a.

Control Room (CR)

l~

As in previous years, the licensee utilized the Control Room l-simulator to " drive" the annual exercise.

Activities in this area

were directly observed during the initial stages of the exercise

'

only.

Utilization of a simulator greatly enhances the realism of an exercise scenario. An excellent shift turnover-briefing provided the simulator Control Room (CR) staff with the initial conditions of the exercise.

In general, CR staff immediately recognized the conditions displayed

- i on the simulator and responded properly.

Emergency procedures were appropriately utilized, Control Room decorum was good, and noise levels were acceptable.

Radio noise was distracting at times, due to poor hand-held transciever reception in the simulator, which is' a L

short distance from the plant.

The CR Shift Supervisor was responsible for declaring the " Unusual Event",'and " Alert" emergency classifications in a timely fashion-

,

af ter verifying all requirements and indications in the associated Emergency Action Levels (EALs).

Later, CR staff also provided

,

l knowledgable input on subsequent classifications.

Notifications were made within time goals, per procedure. The Alert classification, based on the Shift Supervisor's judgement,' appeared y

L to be well justified and prudent.

-A public address message following each classification alerted plant personnel and prov'ded the reason for the classification.

Providing i

plant personnel such information reduces potential confusion, i

e and is consider.

good practice.

a During the initial reactor scram, it was-immediately noted that three control rods had not automatically inserted, and they also did not insert on initiation of a manual scram. The proper procedure

,

(4404.01) was followed, but the operator stopped short of attempting

[.

Alternate Rod Insertion (ARI). ARI was the next procedural step, i

but the operator was momentarily distracted by other activities, and L

reactor power was then verified to be less than 3%, negating (per L

procedure) the need for ARI.

,

pr-n k

,,1

.

l

<

)._,

,

The Emergency Operating Procedures (EOPs), developed from the recommendations of the BWR Owners Group (Revision 3) were utilized extensively. The present' series of procedures are not easy to use when multiple plant problems exist, as in this exercise. At some points during the exercise, leiel, pressure control, and containment pressure E0Ps were in simultaneous use, making determination of the next procedural step difficult.

Discussion with licensee personnel indicated that Revision 4 of the BWR Owners Group E0P recommendations have been transformed into a series of flowcharts, and training on, and implementation of, these E0Ps will be initiated in the near future. Completed flowcharts were examined.

The flowcharts should greatly simplify making determinations of the most effective E0P action sequence.

At intervals, the shift supervisor would provide a concise briefing to CR shift personnel as to his overview of the situation.

At approximately 0827 hours0.00957 days <br />0.23 hours <br />0.00137 weeks <br />3.146735e-4 months <br />, the simulator was balted, " backed up" several minutes, and restarted. This was due to simulated conditions severely diverging from the exercise scenario.

This was primarily due to activation of the Automatic Depressurization System (ADS), caused by failure to reset the automatic timer on the ADS system.

Revision 4 of the E0Ps provides for inhibiting, rather than continual resetting, of the ADS timer, and this should obviate the problem.

Depressurization of the reactor alicwed low pressure, high volume injection systems to inject, filling the vessel. This diverged from the scenario, which assumed low reactor vessel water-levels.

Controllers-and simulator' personnel performed very well, restarting the simulator at approximately 0833 hours0.00964 days <br />0.231 hours <br />0.00138 weeks <br />3.169565e-4 months <br />'and returning the-exercise scenario to the pre-scripted timeline.

The time consumed in halting / resetting of the simulator also caused a later alteration in the rate of reactor vessel level decrease (to catch up with the reactor vessel water level in the scenario), which caused some concern over reactor coolant system leaks which did not exist.

Simulator software has received an uprade to better model system performance, especially in some degraded modes.

However, the newer model was'not run on the simulator due te scenario development under-the older model. While this was prudent fum an overall exercise standpoint, the latter part of the simulator e e rcise suffered somewhat.

Prudent actions were taken regarding not using safety relief valves while the search / rescue team was in containment.

Throughout the exercise, CR staff were cognizant of overall plant conditions.

At approximately 0844 hours0.00977 days <br />0.234 hours <br />0.0014 weeks <br />3.21142e-4 months <br />, a Public Information Officer (PIO)

called the simulator Control Room.

This was an extremely poor time to call the CR, but apparently the PIO was unaware of the escalation to an Alert and the then ongoing system malfunctions. There is also an " exercise artifact" in that there is only one outside line

T

-

g(

,,

1

.

=c i5i i

.

,

-

3 ;;

y

'^

"

available in the simulator (for' exercises). 'In a real event, calls

!

-

'could be directed to the-Shift Supervisor's office rather than the

Control Room itself.

CR staff prudently declined to talk to the PIO

'

'while attempting to mitigate ongoing system failures and stabilize

,

the plant.

'

.

Based upon the above findings, this portion of the licensee's program was acceptable.

  • b.

Technical Support Center (TSC)

Key and support staff began arriving in the Technical Support Center (TSC) within five minutes of the Public Address (PA) announcement u.

that an Alert had been declared.

Incoming personnel began

'

performing their duties in an organized and efficient manner.

Prior to assuming command and control of onsite response activities,

<

- the Station Emergency Director-(SED) prudently took the lead

responsibility for ensuring that search and rescue activities were begun to locate a technician who had apparently failed to evacuate

'

the containment structure when evacuation had L;:n ordered.

'

The SED and his staff made good efforts to obtain and to share past and current information on changing onsite conditions, with one

!

minor exception.

It was not apparent whether TSC staff eventually

realized that the reactor trip at 0800 hours0.00926 days <br />0.222 hours <br />0.00132 weeks <br />3.044e-4 months <br /> was due to' lightning

'

striking a plant component.

The SED assumed command of emergency response efforts once he had assured himself that all his staff were ready to perform their

'

i:

duties and that he adequately understood plant conditions and l

ongoing response actions.

The timely assumption of lead:respons-

'

'

.ibilities occurred within 35 minutes of the Alert declaration, was promptly announced to TSC staff, and was noted on an Event-Notification Worksheet (ENW) message form intended for transmittal to NRC Duty Officers.

p:

The SED was kept well informed of the successful efforts to locate j

the technician who had become injured and contaminated during a

.l simulated fall within the containment structure.

Onsite and offsite j;

medical assistance was initiated in a timely manner.

State and simulated NRC officials were adequately informed of the need to

transport the contaminated, injured technician to a local hospital.

g By about 0900 hours0.0104 days <br />0.25 hours <br />0.00149 weeks <br />3.4245e-4 months <br />, the SED had decided to have his staff begin preparations for an inplant team to enter containment in order to H

w!-

attempt to perform actions to insert three control rods which had not fully inserted when the reactor had tripped (about one hour

'

+

y earlier).

Engineering staff were also instructed to evaluate J

whether or not the reactor would remain subcritical during its

'

cooldown if these rods could not be fully inserted.

By 0945 hours0.0109 days <br />0.263 hours <br />0.00156 weeks <br />3.595725e-4 months <br />, the engineering staff concluded that the reactor would remain i

subcritical even if the three control rods could not be inserted.

The mission to enter the containment to attempt rod insertion was then cancelled.

Full insertion of the three rods was later

'

.s o

,

a<.

.[,

d

.

.

.

.

'

simulated to~have been successfully accomplished by activation of the-Alternate Rod Insertion system (from the simulator control room).

Once the TSC had become fully operational, TSC staff assumed re'sponsibilities for all simulated notifications to the NRC, beginning with the notification for the Alert declaration, and continuing for the duration of the exercise.- TSC staff only had responsibility for initially notifying the State of the Site Area Emergency declaration'before EOF staff as":aled State notification responsibilities by 1000 hours0.0116 days <br />0.278 hours <br />0.00165 weeks <br />3.805e-4 months <br />. Within

.ie TSC, dedicated communicators were responsible for drn.ing notification messages to. State and NRC officials using appr a iate message forms.. The r

Administrative Supervisor reviewed these messages before forwarding

_

them to the SED for final approval prior to transmittal.

Several-problems in accomplishing initial notifications to the State and to the NRC-are described below.

The Site Area. Emergency was correctly declared at 0915 hours0.0106 days <br />0.254 hours <br />0.00151 weeks <br />3.481575e-4 months <br />, following a simulated tornado strike that damaged some plant structures.

However, due to several unnecessary delays in the message review and approval process, State officials were not initially notified of this emergency reclassification.until approximately 0943 hours0.0109 days <br />0.262 hours <br />0.00156 weeks <br />3.588115e-4 months <br />, roughly 28 minutes after the reclassification decision had been made by the SED. The unacceptable delay in making a timely notification.to the State resulted from the decision to redraft the additional information (item 11) on the NARS form, the fact that both the Administrative Supervisor's and the SED's reviews of the draft and redrafted forms were delayed while these persons responded to several unrelated phone calls, and because the SED conducted a periodic briefing of his key staff while the redrafted form awaited his review and signature.

It was not apparent that the Administrative Supervisor

.or the SED realized that this notification message needed to be transmitted to the State within approximately 15 minutes of the emergency classification decision. The failure of TSC staff to initially notify State officials of an emergency reclassification in a' timely manner is an Exercise Weakness (No. 50-461/90015-01).

Although the'above NARS message form was reviewed and approved by two persons, it contained an error which created needless confusion to State and county officials..Between approximately 0910 hours0.0105 days <br />0.253 hours <br />0.0015 weeks <br />3.46255e-4 months <br /> and 0940 hours0.0109 days <br />0.261 hours <br />0.00155 weeks <br />3.5767e-4 months <br />, the wind direction in the scenario data was from about 180 degrees to about 200 degrees, or roughly blowing from the South to the North. Although the reported wind direction on the NARS message form was from 180 degrees, the affacted downwind sector listed on the form was " Sector J", which is uth of the pla'at.

Thus, State and county officials were given contradictory information on whether potentially affected areas ano special care facilities were North or South from the plant.

Fortunately, TSC staff had made no offsite Protective Action Recommendation (PAR)

along with the Site Area Emergency declaration (none is required for this classification) and no offsite protective actions were necessary at this time in the scenario.

The result is the TSC

_

l

.

~

._

.

.

.

staff failea-to adequately review the HARS form'with respect to correctly providing correct!information to State officials on the current downwind sector.

(0 pen Item (No. 50-461/90015-02) -

'

TSC staff had completed and were ready to transmit initial notification messages t9 the i!RC following the Alert and all subsequent emergency recicssifications well within the regulatory time limit. These messages generolly' contained adequately detailed information, which would have been expanded:upon had scenario events been real, as the NRC wtuld have' required continuous communications over the dedicated Emergency hotification' System (ENS) and the Health Physics Network (HPN). communications lines.

TSC staff, provided unclear information-to the NRC regarding the initiL1 and upgraded offsite PARS based on comparisons of PARS documented on NARS message forms, transmitted to State officials and PAR information listed on message forms prepared for transmittal ~to the NRC. -The wording of the PARS on the message forms drafted for transmittal to the NRC were enclear regarding whether certain geographic areas being recommended for evacuation were radial distances from the plant or only four specified sectors downwind of the plant. Messages to State officials clearly indicated that-radial. distances were intended in the evacuation portions of the recommendations.

Under more realistic conditions, the unclear information would havr been resolved through further discussion with NRC staff over the dedicated communications lines.

'Promptly'after the Site Area Emergency declaration at 0915 hours0.0106 days <br />0.254 hours <br />0.00151 weeks <br />3.481575e-4 months <br /> due to the tornado strike, radiation protection staff chose an evacuation route for nonessential-onsite. personnel, based on current wind direction data. The SED prudently ordered security to assess:

damage along this route and;to ensure that the severe weather.

. activity had passed the plant site before simulating the-evrcuation of nonessential onsite personnel.

A limited accountability demonstration was successfully conducted'

.

during'the exercise-About-50 individuals, who were not otherwise-

.

exercise participants, had been predesignated to assemble and be-accounted for at the " craft worker exit portal" from the Protected Area. The site evacuation siren was sounded after security had verified that these evacuees would not be encountering weather or damaged equipment hazards during their departure. All but five of the predesignated nonessential personnel had completed the accountability demonstration within 30 minutes of the sounding of the site evacuation siren. These five were verified as being within the Protected Area, and were located within about another 20 minutes.

The above demonstration was not considered as overly challanging to the licensee's system for conducting assembly / accountability. At the NRC Exit Interview, the licensee stated that there will be a 1990 " full scale" accountability drill to demonstrate the capability to account for all personnel within the Protected Area on a typical workday in a timely manner. This demonstration is partly in response to NRC concerns expressed in the 1989 exercise inspection

l e

.

_ -.

_

<

.

-

A

.

,

'

g.

l t

report and during-the current exercise. inspection, that recent years' accountability drills involved only those ERO members i

t who participated in each exercise plus a limited number of

predesignated, nonessential personnel..The licensee's' plan to i

conduct the " full scale" drill is a good response to such concerns.

Tie SED. conducted a number of-good briefings with his key staff to. discuss priorities, concerns, and any new information not yet circulated. The information flow between TSC staff and the SED was generally good inbetween these briefings.

Several status boards

<

were effectively utilized to trend critical plant parameters, to I

display information on the status of inplant team activities,.and to list significant events and decisions.

Logkeeping by individual TSC staff members-was adequate to permit ~1ater reconstruction'of their activities and awareness of many key events and decisions. A dedicated logkeeper was effectively used to maintain the SED's log.

l TSC staff gradually compiled a number of onsite recovery action items following the General Emergency declaration.

In a number of cases, these items related to current or planned inplant team missions. TSC staff maintained good awareness of what tasks could j'

not be ' accomplished and what plant systems remained inoperable, L

pending further power restorations and damage assessments. TSC staff's efforts to compile onsite recovery action items was adequate and was in response, to some extent, to the EOF's SEM's request to L

identify concerns to be resolved prior to downgrading from the

'

General. Emergency classification.

However, before the TSC. staff's list'of items could be discussed in detail with EOF staff, the SED

was informed that the-E0F staff had' ceased their exercise participation.

These-initial onsite-recovery planning discussions in the TSC were

~

marginally acceptable to satisfy exercise objective No. -21 regarding-demonstration of recovery. Among other items, the discussions did not address the needs to establish long term staffing.of emergency response facilities or the need to interface with internal accident investigation teams or with an NRC Site Team and Incident Investigation Team.

Based upon the above findings, this portion of the-licensee's-program was acceptable; however, the following item should be considered for improvement:

Initial recovery planning demonstrations should include a discussion of concerns and action items developed by the persons in charge of all Emergency Response Facilities.

c.

Operational Support Center (OSC) and Inplant. Teams A revised OSC team tracking board has been devised and implemented, utilizing magnetic identifiers for OSC personnel.

This has simplified and added to the efficiency of overall OSC operations.

- -

-

- -

-

-

- - -

- -

-

- - -

-

- -

-

- -

-

-

_.. _ _ _ _...

--

.

.

.

The OSC was promptly activated after the Alert declaration. The facility was well staffed and fully operational within about 30 minutes.

Status boards were effectively used to track which technicians having specific areas of expertise were available within the OSC and which had been dispatched from the facility.

Another status board was utilized to list significant problems relevant to OSC activities.

This board was not always updated in a timely manner as inplant problems were resolved.

A sequence of events status board was adequately utilized to list major scenario events and decisions to supplement verbal briefings to all OSC staff.

Lines of authority and communication were clear to OSC personnel; however, such might not be the case to relief personnel or NRC Site Team representatives.

Providing OSC supervisory and support staff with some type of position identification would resolve that

..

potential problem.

Several communicators manned OSC telephones without apparent relief for the duration of the OSC activation.

Rotation of personnel as communicators should be considered for prolonged facility operations.

Teams entered and left the OSC through the same doorway.

Manual processing of incoming and outgoing personnel was relatively slow and cumbersome.

However, the process was effective from contamination control and accountability standpoints.

Surveys were also periodically performed within the OSC to better ensure contamination control.

Eighteen inplant teams were dispatched from the OSC during the exercise.

Inspectors accompanied roughly one third of these teams and observed a number of teams during briefings and debriefings.

Briefings were well done and addressed radiological concerns and communication requirements in addition to the repair or assessment task being assigned.

Team members were expected to sign a briefing form which documented the items covered in the briefing upon completion of the briefings.

Several persons were observed to have signed the briefing form prior to the forms being ot'2rwise

.

completed. The forms were, however, later completed with no noted differences in information when compared to the verbal briefing.

Debriefings varied in quality from good to sketchy.

However, teams'

simulated radiological exposures were adequately tracked.

Several debriefings did not occur promptly after the teams had returned.

It was unclear from the debriefing of one team, which had been sent to assess damage to the Division I DC power supply, whether OSC supervisory personnel clearly understood the scope of the damage to this equipment that the team had found.

A search and rescue team was dispatched to locate a technician who had apparently not evacuated the containment when its evacuation had been ordered.

The team soon located the technician, who had supposedly f allen down some stairs while carrying a simulated sample of reactor coolant.

A first aid team was promptly dispatched to the l

_ _ _ _ _ _ _ _ _.

<

_

t n

.

p

!

-

,

accident scene.

Upon evaluation of the victim's simulated injuries,

_the team promptly requested that an~ ambulance be dispatched <to the '

i plantisite.

The first aid team demonstrated good teamwork-and proper concern for

~

<

the-victim's comfort while administering treatment at the scene and while carefully transporting the victim to the ambulance.. OSCiand TSC staff were kept adequately informed by.the team _of-the situation beginning at the accident scene through the departure of the ambulance. Good contamination control practices were demonstrated while caring for.the victim.

The victim's injuries and vital signs were accurately reported

'

in a timely manner so that ambulance and hospital staff were well informed.

Due to simulated background radiation levels at the accident-scene, the relatively low contamination levels on the victim could not be fully assessed and reported until the victim-was removed from the area. Offsite medical responders were informed of the victim's contamination levels once that assessment-could be r.de.

The victim was carefully and--promptly transported to the ambJiance, which left the plant site with licensee Health

_

Physics staff support, in a timely manner.

The overall demonstrations of the-capabilities of the inplant medical emergency responders to perform decontamination-of themselves, their equipment, and the accident scene and route to the-r ambulance was good, with one minor flaw. The team should have placed'several articles of potentially contaminated waste in a bag

before disposal.

Inplant maintenance teams demonstrated good understandings of.

their assigned tasks and were provided with adequate radiological protection support when appropriate.

Several equipment mockups were pre-deployed in the plant to provide greater realism to the teams and to avoid sending the teams into inplant' areas where they may have received some radiation exposure.

One team was dispatched to repair a mockup of a degraded High Pressure Core Spray (HPCS) system injection valve. Once at the-job site,-the. teams were informed by radio to wait for further instructions before beginning their task. The team appropriately reported their readiness to their OSC supervisor on several occasions over about a 45 minute waiting period.

The' team was not informad that decisionmakers had changed their priorities to proceed on repairs of what seemed to be a more likely way to restore injection capability-to the reactor vessel. When this alternate method proved more difficult than was contemplated, the HPCS team was told to begin their work.

Several inplant teams and their OSC supervisor demonstrated good initiative and inventiveness.

For' example, the fire brigade was ordered to report to the Division II diesel generator room in case an oil fire would somehow start due to the overheated diesel

,

,

. u.

'

>.,

,

..

generator. -Several creative means were devised to utilize water

- from the fire protection system to restore _ water to the damagtd -

shutdown service water system.-

On several occasions, inplant teams successfully demonstrated their capabilities to-repair degraded equipment earlier than scenario developers had anticipated or had devised unanticipated methods to resolve a problem.: Controllers accompanying such teams seemed to be at a loss on how to prevent a plausible reason to delay-the repair efforts in order to preserve the scenario timeline so that-future

,

onsite:and offsite exercise objectives' demonstrations could take place.- Future scenarios.

uld provide better guidance to controllers in such situations so that inplant teams' creative and/or very timely efforts to simulate repairs to degraded equipment or to develop alternative corrective actions are not frustrated by essentially informing them that their work was somehow unsuccessful for no other reason than to preserve the scenario timeline.

Very minor items were also noted.

Several teams could have been provided with extra flashlights due to the simulated station blackout conditions. A lack of. signs designating routes to the assembly areas was also noted.

Based upon the above findings, this portion of the licensee's program was acceptable; however, the following items should be considered for improvement:

An inplant teams briefing form should only be signed as " read and understood" after a briefing has been adequately documented on the form.

. Status boards used to list'significant problems that require-inplant team response-should-be kept promptly> updated, d.

Emergency Operations facility (EOF)

The E0F was rapidly staffed and organized, activating at 0935 hours0.0108 days <br />0.26 hours <br />0.00155 weeks <br />3.557675e-4 months <br />.

Noise levels.were low, status boards were generally kept current, logs and other documentation were very good. The log kept for the Emergency Manager was particularly detailed.

Habitability of the facility was well monitored.

Excellent command and control of the overall li',ensee respcn=a to the accident was demonstrated by the Emergency Manager (EM).

He actively " looked ahead" to possible problem areas.

Periodic

" table head" (principal emergency staff) meetings were held at his direction.

" Table head" meetings served to update the EH and his staff on overall status and ongoing activities.

Meetings were kept short so that lead personnel were w out of the main EOF room for long periods.

The EM effectively ti-ted his staf f to focus on various issues during these meetings.

i<riodic briefings of the general EOF staff assisted in keeping -

responders up to date.

_

_ _ _ _ - _ _ _

-

-

d m

,

u9:

.

-

-

-

v

,

The Vice President Nuclear assumed a general oversight role-free

,

of the need to att ed to details. This worked well, enabling him-

'

to step in-only when-needed to enhance ongoing efforts.

I The status of the injured / contaminated person was not ignored or

-

forgotten, even during the most active periods. Good coordination.

was evident.

State personnel as well as hospital staff were advised i

,

of the status of the contaminated / injured person.

Emergency Action Levels (EAls) were frequently reviewed to determine-which further system failures could itad to the declaratior, of a General Emergency.

Status boards were well used to track vessel 1avel, and projections'were made of tne approximate time of fuel uncovery based on level decrease trends.

'The engineering group actively pursued ways of restoring electrical l

power and coolant injection pathways, in concert with similar staff in the-Technical Support Center.

Several creative approaches were

'

explored to utilize the onsite fire engine or fire suppression system to supply water for diesel generator cooling.

The administrative group was stressed by the scenario.

They responded well, contacting vendors and attempting to arrange for

the transport (by truck or-National Guard airlift) of an auxiliary

diesel generator.

At approximately 1024 hours0.0119 days <br />0.284 hours <br />0.00169 weeks <br />3.89632e-4 months <br />, the State questioned the wind direction-(180 degrees) listed on the most recent Nuclear. Accident Ceporting System (NARS) form.

It was confirmed that-the wind had shifted to approximately 310 degrees, and a new NARS form was-generated.

Per-the scenario, wind: direction had changed from 190 degrees to 285

'

degrees between 0910 hours0.0105 days <br />0.253 hours <br />0.0015 weeks <br />3.46255e-4 months <br /> and 1020 hours0.0118 days <br />0.283 hours <br />0.00169 weeks <br />3.8811e-4 months <br />, so this update should

'

have been more timely.

.

>

The General Emergency was declared at 1028 hours0.0119 days <br />0.286 hours <br />0.0017 weeks <br />3.91154e-4 months <br />, based on EAL 10.2 and overall plant degradation.

Protective Action Recommendations (PARS) were made per the proceduralized flowchart, based on plant

,

i conditims rather than an ongoing radioactive release. As the scenario electrical power failures would have disabled the Standby j

Gas Treatment System (SGTS), an eventual unfiltered release was-assumed.

Such.a release:could have a relatively high radioiodine and particulate content due to lack of SGTS filtering.

PARS j

generated appeared correct based on plant conditions and probable

'

release path.

,

Electrical power failures had disabled the Safety Parameter Display

'

System and mainframe dose projection computers in the EOF. This

. equipment was available in the Technical Support Center and TSC

'

staff shared data with their EGF counterparts, i

A minor improvement has been made in the EOF by adding a small window from the dose projection room into the E0F proper. While

,

this is a relatively.small change, it made the exchange of dose projection information more efficient and helped minimize the number of personnel present in the dose projection room.

j

-

-

-

-

-

_ _ _ _ - _ -

.

.

t

Dose projection in the EOF was performed via a manual calculation method and a personal computer (Pi) based program.

The PC-based program, Interactive Radioactive D"a A;sessment Method (IRDAM) was on a computer down the hall from th$ 3:se projection room, and this could have been made more efficient by use of a personal desktop or laptop computer in the dose projection room itself.

With redundant copies of PC-based dose projection software, especially on battery powered laptops, elimination of hand dose calculation

,

methods is acceptable, and eliminates the considerable propensity for error inherent in hand calculations.

,

The PAR generated at 1121 hours0.013 days <br />0.311 hours <br />0.00185 weeks <br />4.265405e-4 months <br /> was " shelter anyone 0-5 that cannot

be evacuated". This is not exactly the wording from the applicable procedure RA-02 " evacuate 0-5 miles and shelter those who.cannot be evacuated", and may have led to minor confusion. The State elected to evacuate all personnel in a 0-5 miles radius, i

It should be understood that sheltering is not a preferred option when the duration of a radioactive release cannot be estimated to

some degree.

Sheltering prior to long releases has the potential of requiring later evacuation of sheltered individuals under plume conditions, with their cumulative radiation dose consisting of that

,

accumulated during sheltering and evacuation.

At the termination of the exercise, plant conditions were such that

,

declaraticn of a Recovery phase of operations would not have

.

occurred for some time.

As such, only brief reviews and discussions pertained to the Recovery procedure and organization.

While overall knowledge of actions during the accident was evident, it was apparent from discussions that EOF staff were not aware of the minor fire that had occurred in the radwaste building early in the scenario. The fire had been rapidly extinguished, and was of minor overall consequence, but this info mation should have been

.

passed on to the EOF.

'

Based upon the above findings, this portion of the licensee's program was acceptable, e.

Field Monitoring Teams Field monitoring teams were not directly observed during this exercise.

f.

Joint Public Information Center (JPIC)

-

The JPIC was not directly observed during this exercise.

7.

Exercise Objectives and Scenario Review (IP 82302)

The licensee submitted the exercise and scope and objectives and a draft scenario package for review by the NRC within the established timeframes.

Scenario review did not indicate any significant problems, ana the licensee adequately responded to the questions raised during scenario

h,,,y,.,,-.

,,,,,,,,,,,,.,,, -.

-

-

-

~

-

- '

'

' -

'

'

.

.

,

.

.

review. The scenario package was adequate in scope and content to ensure ease cf use and contained enough information so that licensee controllers could control the exercise. Backup information was available in the event that the plant simulator, utilized to " drive" the exercise, f ailed.

The licensee's scenario was considered generally challenging, including:

multiple equipment failures and a contaminated / injured individual.

Virtually all portions of the licensee's emergency plan were exercised.

Simulation of player actios.s was minimized.

The degree of challenge in an exercise scenario is considered when assessino observed exercise weaknesses.

Based upon the above findings, this portion of the licensee's program was acceptable.

8.

Exercise Control Overall, exercise control was considered adequate.

There were adequate controllers to control the exercise, and they were knowledgeable regarding their tasks. No instances of controller prompting were observed.

Based upon the above findings, this portion of the licensee's program was acceptable.

9.

Licensee Critimies The licensee held a controller exercise critique, and a critique where the conclusions of the Controller / Evaluator.s presented their findings to the players.

NRC personnel attended these critiques, and determined that significant NRC identif bd exercise deficiencies had also been identified by licensee personnel.

1, addition, licensee controller / evaluators also identified a rxmber of min r prob b ms experienced during the exercise.

The licensee demonstrated he capability of self-identifying exercise problems.

Ba:.ed upon the above findings, this portion of the licensee's program was acceptablo.

10. TMI S4fety Issues j4an33qment System (GiS) Items On October 31, 1980, the NRC issued NUREG-0737, which incorporated inte one document all TMI-related i'.eas approved for implementation by tbo Comm9ssion at that t4me. On December 17,1982, the NRC issued Supplement i to NUREG-0737 to provide additienti clarification regarding Regulatory Guide 1.97 (Revision 2) - Application to Emergency Resporise Facilities, Emergency Respone Facilities, ard Mateorolociic21 Dat'#, as well as other areas, The status of the completion of thesu TMI S3MS itemt are internally tracked by the NRC.

.The below listing prevides the basis for the closure of all of the SIMS items related to emergency preparedness.

W

_ __-________-_

-

.

,

!

'

.

.

.

.

!

III.A

~l

.

This item refers to implementation of Chapter 8 of Supplement 1 to NUREG-0737. and was closed based upon completion of the April 25-28,

,

1988 ERF Appraisal: Report No. 50-461/88008 dated June 21, 1988.

!

III.A.1.1 I

.

i This item involved short term improvements to the emergency preparedness program and was closed at-the conclusion of the Emergency Preparedness

,

Implementation Appraisal:

Report No. 50-461/85039 dated December 20, 1985.

,

III.A.1.2.1 l

This item involved interim upgrades to the ERF's and was closed at the conclusion of the Emergency Preparedness Implementation Appraisal:

,

Report No. 50-461/85039 dated December 20, 1985.

III.A.1.2.2

,

This. item involved design criteria for upgraded ERF's, but was subsequently determined to be not applicable (N/A).

,

III.A.I.2.3 L

.

.,

Becau e this item involved ERF modifications that were incorporated j

~

into '0A-F-63, 64 and 65,'this item was closed based on the Emergency

!

Preparedness' Implementation Apiraisal:

Report No. 50-461/85039 dated

December 20, 1985.

III.A.2.1

!

v This item involved the submittal of upgraded emergency plans.

This item was closed with the issuance of the SER:

NUREG-0853 dated February 1982, Suppivment I to NUREG-0853 dated July 1982, and

.

Supplement 2 to NUREG-0853 dated May 1983.

!

!

i III.A.2.2 This. item involved the submittal of emergency procedures. This item was closed at the conclusion of the Emergency Preparedness Implementation r

Appraisal:

Report No. 50-461/85039 dated December 20, 1985.

III.A.2.3

'

L

-

This item involved an acceptable interim meteorological program.

This

'

item was closed at the conclusion of the Emergency Preparedness Implementation Appraisal:

Report No. 50-461/85039 dated December 20, 1985.

.

-

,

- - - - - - - - - - - - - - - - - -. - - - - - - -. - - - - - - -

,

- - - - - -

_

..

..

- _ _ _ - _ _ - _ _ _ _

,-

-

.

'

.

III.A.2.4 This item involved an acceptable final meteorological program and was closed based upon conclusion of the ERF Appraisal: Reert No.

50-461/88008 dated June 21, 1988.

III.A.2.5 This item involved an acceptable Class A meteorolegical model and was closed based upon completion of the ERF Appraisal: Report No.

50-461/88008 dated June 21, 1988.

III.A.2.6 This item involved a licensee's review of their Class A meteorological model and was closed based upon completion of the ERF Appraisal:

Report No. 50-451/88008 dated June 21, 1988.

III.A.2.7 This item required the licensee to provide a description of the Class B meteorological model to the NRC.

Based on the final structure of the ERF Appraisal program, the NRC did not review submittals of the Class B model. Therefore this item is not applicable (N/A).

III.A.2.8 This item involved an acceptable Class B meteorological model and was closed based upon ccmpletion of the ERF Appraisal:

Report No.

50-461/88008 dated June 21, 1988.

MPA-F-63 This item involved a review of the TSC during the ERF Appraisal and was closed upon :omp;etion of the ERF Appraisal:

Report No. 50-461/88008 dated June 21, 1988.

MPA-F-64 This item involved a review of the OSC, which was completed during the June 28, 1989 exercise:

Report No. 50-461/89020(DRSS) dated July 12, 1989.

MPA-F-65 This item involved a review of the E0F during the ERF Appraisal and was closed based upon completion of the ERF Appraisal:

Report No.

50-461/88008 dated June 21, 1988.

MPA-F-66 This item involved the Nuclear Data Link, which has been superseded by the Emergency Response Data System (ERDS). Therefore thir item is not applicable (N/A).

l

l

...

.

..

-

..

.

--

.

.

,

.

.

11. Open Item _s Open Items are matters which have been discussed with the licensee which will be reviewed further by the inspector and which involves some actions on the part of the NRC or licensee or both. An Open Item disclosed during this inspection is discussed in Section 6.b of this report.

11.

Exit Interview (IP 30703)

The inspectors held an exit interview the day a.'ter the exercise on July 26, 1990, with the representatives denotsd in Section 2.

The NRC Team Leader discussed the scope er,s findings of the inspection.

Overall exercise performance was considered to be good, with the exception of the Exercise Weakness related to timely notifications resulting from the Site Area Emergency Declaration.

The licensee was also asked if any of ths information discussed during the exit interview was proprietary. The licensee responded that none of the information was proprietary.

Attachments:

1.

Clinton Power Station 1990 Exercise Scope and Objectives 2.

Clinton Power Station 1990 Exercise Scenario Outline

.

Attachment 1

..

..

.

,

.

'

.

.

INTRODUCTION Ef0PE OF PARTICIPATION The Clinton Power Station Emergency Exercise will be conducted during normal working hours to demonstrate the integrated capability of Illinois Power Company to respond to a simulated emergency at Clinton Power Station (CPS).

The Exercise is designed ',o test as much of the Clinton Power Station Emergency Plan as is

. reasonably achievable. This is a partial participation exercise. There will be participation from local governments. Participation by state government will be limited to telephone notifications.

I

. Illinois Power ( P) will participate in the CPS Exercise by activating the Emergency Response Organization and Emergency Response Facilities as appropriate, subject to limitations that may become necessary to provide for safe operations of the Plant.

In lieu of using tha Main Control Room, the CPS Simulator Control Room will be used during the Exercise, llereinafter, any reference to the Main Control Room implies.the Simulator. An off. duty Main Control Room shif t crew will be pre.

positioned in the Simulator to receive Exercise Messages.

Illinois Power. Company has established specific objectives and ground rules for the Exercise. These objectives and ground rules may be found later in this section, iP has also limited its participation in the area of accountability and evacuation of non-essential personnel. This activity will be simulated.

.

.

.

.

-

-

.

.

.

_._.

.,,

Attachment 1

..

CLINTON POWER STATION

-

~'

1990 EXERCISE ORJECTIVES

-

~

-f

[ Primary Oblective:

,

Demonstrate the capability to implement the Clinton Power Station (CPS) Emergency plan to protect the health and safety of the general public as well as plant personnel.

Supportine Obiectives:

'

l.

Demonstrate the capability of the Main Control Room Staff to reco6nize the emergency conditions, to classify the event, and to perform mitigating actions, i

2.

Demonstrate the capability to quickly and accurately identify and classify the accident as conditions change.

3.

Once the emergency is classified or reclassified, to demonstrate the capability to timely notify the Illinois Emergency Services and Disaster Agency (IESDA), the Illinois Department of Nuclear Safety (IDNS) and the Nuclear' Regulatory Commission (NRC) within the time required by implementing procedures.

!

Demonstrate the capability to properly notify Illinois Power Company (IP)

Emergency Response Organization personnel in accordance with implementing-procedures.

, s(

l J5..

Demonstrate the ability to notify site personnel of the emergency condition.

'

,

i s,_/

,

6.

' Demonstrate the capability to activate the Technical Support Center (TSC),

'

,

Emergency Operations Facility. (EOF), Operations Support Center (OSC),

Headquarters Support Center (HSC) and Joint Public Information Center (JPIC)

,

in accordance with implementing procedures.

'

7.

Demonstrate the clear transfer of Command Authority from the Shift Supervisor, to the Station Emergency Director, to the Emergency Manager in accordance with implementing procedures.

8.

Demonstrate the capability to assess accident conditions by performing reactor I

coro damage estimations and by performing offsite dose assessments.

9.

Demonstrat.. the capability to dispatch and control Field Monitoring Teams for plume tracking and environmental monitoring.

10.

Demonstrate the capability of Field Monitoring Teams to conduct field radiological surveys, ine'uding the collection and analysis of air samples, radiciodine, and to collect, as needed, additional liquid, vegetation and soil

'

samples.

.rs

- !

(

,

-

~,

-

Attachment 1

,.

,,

.

-

11.

Demonstrato tha o:psbility to roceivs, en21yze, cnd stero field sempiss in tho 20F Environmental Laboratory while following approved procedures and

.

acceptable radiological controls.

92.

Demonstrate the capability of the operations Support Center to control emergency teams including emergency maintenance activities.

.

13.

Demonstrate implementation of effective health physics controls by the Emergency Teams.

14.

Demonstrate realism in responding to scenario events by incorporating casualty control sub scenarios that will require real time response for personnel in the OSC and TSC.

15.

Demonstrate the capability to provide dosimetry and monitor radiation exposure to onsite emergency workers and Field Monitoring Teams.

16.-

Demonstrate the capability to effectively communicate reports, information and assessments of the situation among participating principal command and control centers, personnel and emergency teams.

17.

Demonstrate the capability to perform onsite accountability within approved time frames.

18.

Demonstrate the capability to make appropriate, timely public protective-action recommendations to offsite authorities in accordance with implementing procedures.

19.

Demonstrate timely, effective information flow from the Emergency operations Facility (EOF) to the Joint Public Information Center (JPIC).

20.

Demonstrate the capability to provide accurate, timely information to the news media from the JPIC.

21.

Demonstrate the ability to implement appropriate measures associated with recovery activities in order to restore the plant to a pre emergency condition.

22.

Demonstrate the capability of the First Aid Team and Radiation Protection personnel to properly respond to an accident involving contaminated and/or injured personnel and to provide proper first aid.

23.

Demonstrate the capability to transport an-injured / contaminated person (s) to an offsite medical facility and to provide support as necessary.

24.

Demonstrate the capability-to critique objectively the emergency response and to identify deficiencies.

This will require an evaluation of items such as (1) the operation of the Emergency Response Facilities, (2) suitability of individuals in fulfilling emergency assignments and (3) the adequacy of emergency procedures and equipment availabl.

.. *

Attachment 2

,

,.

.-

,

.

I

i

.

NARRATIVE SUMMARY

.

,

}

v Initial Conditions:

The Reserve Auxiliary Transformer (RAT) is out of service for oil change due to foreign substance found during routine inspections. A severe thunderstorm warning is in effect for northern Macon, DeWitt and McLean counties until 0845. A line of severe thunderstorms was detected by radar at 0745 from i

1111opolis to north of Heyworth moving NE at 35 miles per hour.

Summary:

At 0800, as a severe thunderstorm is moving through the area, a lightning strike causes a phase differential current on the C phase of the main transfotmer. This results in a turbine trip and reactor scram.

Several control rods do not fully insert, but the reactor shutdown criteria is rnet.

This should result in a NOTIFICATION OF UNUSUAL EVENT being declared in accordance with Section 9.1 of EC 02. EMERGENCY CLASSIFICATION. Another lightning strike occurs shortly which results in the loss of the Division I 125 volt battery charger and damages the Divisien I battery cables to the 125 volt Distribution Panel 1A, This results in a loss of all DC Power to Division I.

This in turn results in the loss of the Reactor Core Isolation

Cooling (RCIC) System since DC power from Division I is required for opening J

the RCIC injection valve, pump suction valves, steam supply valve, minimum flow valve and the RCIC turbine cooling water supply valve.

In addition the High Pressure Core Spray System (llPCS) fails to operate when the llPCS p)

injection valve F004 fails to open. The severe thunderstorm produces g

sustained high winds of 76 mph around 0820.

This should trigger an ALERT being declared in accordance with EC 02, EMERGENCY CLASSIFICATION Section 14.2.

Shortly after this time a fire breaks out in the radwaste building.

At approximately 0900 a chemistry technician who has obtained a routine reactor water sample trips on the stairway in containment.

He breaks a leg and becomes contaminated froin the reactor water that is spilled.

A tornado warning is issued for DeWitt County at 0900. A tornado was reported on the ground north of Maroa. At 0915 a tornado moves through the area hitting the Screenhouse and the 138 KV line.

This results in the loss of all offsite power. This should result in a SITE AREA EMERGENCY being declared in

-

accordance with EC 02, Section 14.2 for tornadoes.

Upon loss of offsite power, the Division II Diesel vill start.

Division II Diesel vill overheat and fail due to Shutdown Service Water (SX) being damaged from the tornado.

Escalation to a CENERAL EMERCENCY should be declared in accordance with EC 02 when it is determined that a prolonged loss of offsite power exists that will result in an inability to remove decay heat.

The main success paths to be followed will be the repair of the HPCS Injection Valve and restoration of DC Power to Division I.

Other success paths that may be pursued would be restoring offsite power, cross connecting power sources and using Fire Protection Water Injection into the vessel in accordance with section 8.2.9 of CPS No. 3213.01 FIRE DETECTION AND PROTECTION.

Failure to succeed in on= of

_

these paths will lead to eventual core melt.

b

_

_

-

_ - - - _ - _.. _ _,,

-

,

.

,

a

.

,

' Attachment 2'

'. 'l6 3;'

,

,

,

.

?

"

a;

,

,

-

r EXERCISE TIME LINE

-

'

-

'

APPROXIHATE EVENTS TIME ~LINE Lightning strikes' transformer.

0800 I

' Reactor' scrams. Some control rods fall to

"

fully insert. Reactor suberitical.

NOTIFICATION OF UNUSUAL EVENT-0830

~'

declared in accordance with EC 02, Symptom 9.1~.

!

Lightning strike.affects Div. 1 0815

,

battery l charger and cables.-

loss of Div I DC.

'

i

Sustained high winds in excess of 75 mph.

0820

-

'

'

Fire-in Radwasta Building.

.0845

,

ALERT declared in accordance with 0850 l

EC 02,sSymptom 14.2..

Injury and contamination of 0900'

i

- chemistry. technician.

.

.

Tornado hits the. Screenhouse and 0915 t

t

,

[

138. Kv' line resulting in loss of

'

all offsite power and damage to

'

- Shutdown Service' Water.-

,

SITE AREA EMERCENCY' declared in accordance 0945 with;EC 02,. Symptom 14.2.

~

Injured victim sent ito hospital.

0945'

Loss of.Div. II Diesel.

1025

,

CENERAL EMERGENCY should 'be -declared 1100 in accordance with EC 02, Symptom 10.2,

-

. Repair of Div. I DC and/or llPCS 1230 p

. Injection Valve.

.

.

lloid Critique.

1400

,

h I

l l

l

% i-a

!

?ii:

'

' '

.

.-

.

.

-

.

.

.