IR 05000424/2002005

From kanterella
Jump to navigation Jump to search
IR 05000424-02-005 & IR 05000425-02-005, on 11/12/2002 - 11/15/2002 & 12/02/2002 - 12/06/2002, Vogtle Electric Generating Plant Units 1 & 2
ML030060145
Person / Time
Site: Vogtle  
(NPF-068, NPF-081)
Issue date: 01/03/2003
From: Brian Bonser
NRC/RGN-II/DRP/RPB2
To: Gasser J
Southern Nuclear Operating Co
References
IR-02-005
Download: ML030060145 (17)


Text

January 3, 2003

SUBJECT:

VOGTLE ELECTRIC GENERATING PLANT - NRC PROBLEM IDENTIFICATION AND RESOLUTION INSPECTION REPORT NOS. 50-424/02-05 AND 50-425/02-05

Dear Mr. Gasser:

On December 6, 2002, the NRC completed a team inspection at the Vogtle Electric Generating Plant, the enclosed report documents the inspection findings, which were discussed with Mr. George Frederick and other members of your staff during an exit meeting December 5, 2002.

The inspection was an examination of activities conducted under your license as they relate to the identification and resolution of problems, and compliance with the Commissions rules and regulations and with the conditions of your operating license. Within these areas, the inspection involved examination of selected procedures and representative records, observations of activities, and interviews with personnel.

On the basis of the sample selected for review, there were no findings of significance identified.

The team concluded that problems were properly identified, evaluated, and resolved within the problem identification and resolution programs. A very low threshold for entering problems into your corrective action program was observed. However, during the inspection, examples of minor problems were identified, including conditions adverse to quality that were not being entered into the corrective action program and narrowly focused corrective actions. Also, human performance errors contributed to two recent manual reactor trips and a dual unit shutdown.

In accordance with 10 CFR 2.790 of the NRC's "Rules of Practice," a copy of this letter and its enclosure will be available electronically for public inspection in the NRC Public Document Room or from the Publicly Available Records (PARS) component of NRCs document system (ADAMS).

SNC

ADAMS is accessible from the NRC Web site at http://www.nrc.gov/reading-rm/adams.html (the Public Electronic Reading Room).

Sincerely,

/RA/

Brian R. Bonser, Chief Reactor Projects Branch 2 Division of Reactor Projects Docket Nos. 50-424 and 50-425 License Nos. NPF-68 and NPF-81

Enclosure:

NRC Inspection Report 50-424/02-05 and 50-425/02-05

REGION II==

Docket Nos.

50-424 and 50-425 License Nos.

NPF-68 and NPF-81 Report Nos:

50-424/02-05 and 50-425/02-05 Licensee:

Southern Nuclear Operating Company, Inc. (SNC)

Facility:

Vogtle Electric Generating Plant Units 1 and 2 Location:

7821 River Road Waynesboro, GA 30830 Dates:

November 12-15, December 2-6, 2002 Inspectors:

T. Johnson (Lead Inspector), Farley Senior Resident Inspector R. Moore, Reactor Inspector, Region II T. Morrissey, Vogtle Resident Inspector Approved by:

Brian R. Bonser, Chief Reactor Projects Branch 2 Division of Reactor Projects Enclosure

SUMMARY OF FINDINGS

IR 05000424-02-05, IR 05000425-02-05, on November 12-15, and December 2-6, 2002,

Southern Nuclear Operating Company; Vogtle Electric Generating Plant, Units 1 and 2, biennial baseline inspection of the identification and resolution of problems.

The inspection was conducted by a senior resident inspector, a resident inspector, and a regional reactor inspector. The inspection focused on corrective action program performance in the period since the previous inspection in January 2001. No findings of significance were identified.

Identification and Resolution of Problems Overall, the licensees Corrective Action Program (CAP) was effective at identifying, evaluating, and correcting problems. The threshold for entering problems into the CAP was low, resulting in a large number of Condition Reports (CRs). Problems entered into the CAP were adequately evaluated and appropriate actions were taken to resolve the problem. Recent events, including two reactor trips during low power feed water operations, and a dual unit shutdown due to secondary chemistry problems, were caused in part by human performance errors combined with weak supervisory oversight. The licensee is currently addressing these common root causes and developing corrective actions.

Some instances of missed problem identification were noted. System engineers were found to use the CAP effectively to address equipment issues. Quality Assurance organization audits were effective in identifying issues. Self-assessments were appropriate and findings were entered into the CAP. A safety conscious work environment was found where employees felt free to raise safety issues in CRs or the employee concerns program.

REPORT DETAILS

OTHER ACTIVITIES (OA)

4OA2 Problem Identification and Resolution (PI&R)

a.

Effectiveness of Problem Identification

(1) Inspection Scope:

The inspectors reviewed issues and items selected across the seven cornerstones of safety that were either documented in NRC inspection reports or entered into the licensees corrective action program (CAP) since the last performance of an NRC PI&R inspection in January 2001 (Inspection Report (IR) No. 50-424 and 425/2001-02). The inspectors assessed whether these items were being properly identified, characterized, and entered into the CAP for evaluation and resolution. The inspectors discussed PI&R observations from the baseline NRC inspection program with the resident inspectors.

The inspectors reviewed condition reports (CRs) for risk significant systems and discussed them with the responsible system engineer to determine whether problems were effectively identified and evaluated. The risk significant systems the inspectors reviewed included the following: Emergency Diesel Generator (EDG), electrical power, Residual Heat Removal (RHR), Safety Injection (SI), Component Cooling Water (CCW),

Nuclear Service Cooling Water (NSCW), and Auxiliary Feedwater (AFW). A walkdown of each system was conducted to assess the material condition and determine if any unidentified degraded equipment conditions existed. The walkdowns were conducted with the system engineer or discussed with the system engineer after the walkdown.

The condition of the system, past performance issues, and any planned modifications were discussed. System health reports were also reviewed.

The inspectors verified that problems in CRs were properly evaluated using the Maintenance Rule when appropriate. Selected maintenance work orders were reviewed to verify proper classification of deficiencies as either work orders or CRs.

The inspectors reviewed 15 licensee operating experience (OE) items to determine if they were appropriately evaluated for applicability and if identified problems were entered into the CAP.

During the inspection ongoing plant activities were reviewed including a review of the following: shift turnover meetings, plant status and plan of the day meetings, surveillance testing and maintenance, operational activities including unit trip recovery, startup, and power operation, a Safety Review Board (SRB) meeting, a Human Performance Review Board (HPRB) meeting, and a Plant Review Board (PRB) meeting; operating logs and the Major Problem Status Report (June 2002); and, discussion of issues with plant employees. The inspectors spot-checked completed technical specification surveillances for accuracy and timeliness. In addition, maintenance scheduling was reviewed to verify appropriate risk management was utilized. A sampling of maintenance work orders (MWOs) from calendar years 2001 and 2002 were reviewed to verify proper classification of deficiencies as either work orders or CRs. The inspectors attended the daily work control meeting to evaluate the interfaces between the work control process and the CAP. Several equipment problems discussed during the plan of the day meetings were selected by the inspectors to verify the issues had been entered into the CAP, if necessary.

The inspectors reviewed self-assessment reports, audit reports, internal assessment reports, HPRB data, and minutes of the PRB and SRB meetings to determine if oversight activities were effective and if self-identified issues were appropriately entered into the CAP. Documents reviewed are listed in the attachment.

(2) Issues:

The licensees program for identification of problems was effective and provided a suitable mechanism for the identification and documentation of plant problems. The threshold for entering issues was low and employees were encouraged to enter items.

Initiators of CRs were from all plant groups which demonstrated the plant staff was familiar and involved with the corrective action program. However, the inspectors found several instances where minor housekeeping problems, fire protection deficiencies, and equipment material issues were not documented in the CAP. Examples included AFW system oil/water leaks, low oil bubbler level, valve position labeling, RHR Limitorque plastic cover, area housekeeping, and fire protection issues. When these issues were identified to the licensee, appropriate actions were taken.

Quality Assurance (QA) group audits were effective in identifying issues. The scope of PRB and SRB meetings was consistent with the documented charter for those activities and addressed CRs, procedure changes, license document changes and modifications in a thorough and questioning manner. The HPRB process provided valuable feedback for the selected human performance related CRs.

As documented in IR 50-424 and 425/2001-02, some issues from the assessments were not entered into the CAP. During this inspection, the inspectors found that self-assessments of the CAP were appropriately scoped and issues identified during the self-assessments were properly entered into the CAP. Self-assessments were performed by most departments.

The licensee was effective in identifying and placing OE issues into the CAP. The inspectors found several examples of actions necessary to address OE issues not entered and tracked in the CAP. In these cases, necessary actions were the responsibility of a cognizant individual, such as a system engineer.

b.

Prioritization and Evaluation of Issues

(1) Inspection Scope The inspectors reviewed the licensees quarterly trend reports to determine whether identified trends were placed in the CAP. The inspectors also reviewed the Major Problem Status Report (June 2002) and selected completed CRs to determine whether the conditions identified had been resolved. The licensee classified CRs on safety significance ranging from Severity Level (SL) 1 (high significance) through SL 5 (little or no significance). All SL 3 and above CRs required a formal root cause determination.

During the period reviewed, several SL 2 CRs for plant trips were issued. The inspectors reviewed these SL 2 CRs and selected SL 3, SL 4, and SL 5 CRs. A sample of voided CRs was also reviewed to verify they were voided for appropriate reasons.

(2) Issues:

The licensee was generally effective in the use of trending, problem status reports, and SL classification of CRs to prioritize and evaluate issues. Quarterly trend report issues were entered into the CR program as SL 3 CRs and were appropriately evaluated.

Classification levels were appropriate for the sample of CRs reviewed.

A concern with the licensees resolution of configuration control problems was identified in IR 50-424 and 425/01-02. The effectiveness of corrective actions was limited and the condition of excessive mis-positions was not captured in an overall trend CR.

Therefore, a scope analysis and comprehensive corrective action plan had not been developed. In response to this concern, the licensee initiated CR 2001000135 which resulted in the licensee performing a scope analysis and developing a comprehensive corrective action plan. The inspectors found that the corrective actions in this plan were extensive and included increased management oversight, training, individual evaluations of mis-position occurrences, benchmarking mis-positions at another nuclear station, a place-keeping policy for procedures which manipulate components, and post job briefings to specifically address configuration restoration. Additionally, valve, breaker, switch mis-positions were tracked as an area of interest in the Station Quarterly Trend Report.

The inspectors identified that CRs 2002002570 and 2002002796 did not address all the root causes. CR 2002002570, a SL 3 CR regarding a maintenance preventable functional failure, did not properly address the human performance root cause. The licensee documented this issue in the CAP as CR 2002003540. CR 2002002796 concerned a personnel error (wrong train event) during surveillance testing. During the HPRB, the licensee also identified that the root cause and corrective actions were narrowly focused. The licensee took actions for additional review of the CR.

c.

Effectiveness of Corrective Actions

(1) Inspection Scope:

The inspectors reviewed root cause evaluations, corrective actions, the backlog of open items and actions items, and selected CRs to determine if appropriate corrective actions were documented, assigned, and implemented. This included verification of Action and Open Item Tracking activities and maintenance work orders or modification packages which implemented corrective actions. Where possible field verification of corrective actions was performed. The inspectors attended an HPRB meeting.

The inspectors reviewed licensee actions relative to two reactor trips, Unit 1 on April 20, 2002, and Unit 2 on November 13, 2002, caused partly by human error. The inspectors were also briefed by the licensee of an on-going event investigation of a forced dual unit shutdown on November 24, 2002, due to secondary chemistry problems. The inspectors reviewed the related CRs, event investigations, trends, and selected corrective actions to evaluate effectiveness. The inspectors also attended several event investigation meetings associated with the Unit 2 reactor trip.

(2) Issues:

In general, corrective actions were effective. System engineers were knowledgeable of equipment issues and effectively used the CAP to deal with equipment issues. The inspectors monitored the effectiveness of corrective actions and concluded the backlog of open items and action items were manageable.

The Open and Action Item Tracking processes were effective in verifying the completion of specified corrective actions in CRs and LERs. The inspectors were able to verify that the specified corrective actions were performed. With respect to configuration control issues discussed in the previous P&IR report, although mis-positioning continued to occur, the trending information showed improvement which indicated the corrective actions were having a positive effect on station activities.

The root causes for two unit trips and the dual unit shutdown were similar. This included procedural non compliances (not following the procedure or unaware of procedure existence) and weak supervisory oversight. The oversight weaknesses included missed or weak pre-job briefings, conducting risk significant activities in parallel, weak command and control, and poor communications. While some initiatives had been implemented, the licensee had not yet achieved positive results from their corrective actions.

The inspectors found the multi-discipline event team assembled for the most recent Unit 2 reactor trip was effective in developing corrective actions. The event team appropriately reviewed the effectiveness of the corrective actions associated with a similarly caused trip of Unit 1. The inspectors found the corrective actions associated with the Unit 1 trip were adequate. However, the corrective actions focused primarily on the specifics of the trip. Operator performance, including procedure use during startup and lower power feed water operations was not addressed. Also, there were no corrective actions relative to supervisory performance or command and control expectations. The inspectors characterized this as a missed opportunity.

d.

Assessment of Safety-Conscious Work Environment

(1) Inspection Scope:

The inspectors assessed if any conditions existed causing employees reluctance to raise safety issues. This included identifying deficient conditions through the CAP and the understanding and use of the employee concerns program (ECP). The inspectors also reviewed the ECP procedure and a summary of employee concerns and interviewed the ECP supervisor to assess visibility of the program.

(2) Issues:

The inspectors determined the licensee had established and maintained a safety-conscious work environment as evidenced by the number of CRs written, a visible ECP, and the results of the NRC discussions during the course of the inspection.

All employees were aware of the process and the location and accessibility of the ECP coordinator. The inspectors concluded that employees felt free to raise issues.

4OA6 Management Meetings

Exit Meeting Summary

Inspectors presented the inspection results to members of licensee management at the conclusion of the inspection on December 5, 2002. The licensee acknowledged the findings presented. No proprietary information was identified.

SUPPLEMENTAL INFORMATION

PARTIAL LIST OF PERSONS CONTACTED

Licensee

W. Bargeron, Plant Support Assistant General Manager
W. Burmeister, Manager Engineering Support
G. Frederick, Plant General Manager
T. Petrak, Maintenance Supervisor
P. Rushton, Plant Operations Assistant General Manager
M. Sheibani, NSAC Supervisor
T. Tynan, Operations Manager

LIST OF DOCUMENTS REVIEWED

Licensee Procedures:

00150-C, Condition Reporting and Tracking System

80014-C, Handling of Condition Reports for Deficient Conditions

80016-C, Trend Identification and Reporting

00040-C, Self Assessment Program

00414-C, Operating Experience Program

VSAER-WP-03, Safety Audit and Engineering Review Field Audits

VSAER-WP-05, Annual SAER Department Assessment

00058-C, Root Cause Determination

00409-C, Action Item, Open Item, and Commitment Tracking

VNS-AP-16, Condition Reporting and Tracking System

SNOC Concerns Program Procedure

00057-C, Event Investigation

50028-C, Engineering Maintenance Rule Implementation

50023-C, System Health and Monitoring Program

00354-C, Maintenance Scheduling

29540-C, Risk Assessment Monitoring

29542-C, Shutdown Risk Assessment

10000-C, Conduct of Operations

00002-C, Plant Review Board - Duties and Responsibilities

VSRB-05, Southern Nuclear Vogtle Project Support, Safety Review Board

00056-C, 10 CFR 50.59 Screening and Evaluations

28707-C, 480 Volt Air Circuit Breaker Maintenance and 60 Month Check

00404-C, Surveillance Test Program

00409-C, Action Item, Open Item, and Commitment Tracking

10024-C, Equipment Troubleshooting

81060-C, Open Item/Commitment Tracking Program Coordination

VSAER-WP-03, Safety Audit and Engineering Review Field Audits

Operating Experience:

IN 2001-09, Main Feedwater System Degradation in Safety-Related ASME Code Class 2

Piping inside the Containment of a Pressurized Water Reactor

IN 2002-09, Potential for Top Nozzle Separation and Dropping of a Certain Type of

Westinghouse Fuel Assembly

IN 2002-24, Potential Problems with Heat Collectors on Fire Protection Sprinklers

IN 2002-25, Challenges to Licencees Ability to Provide Prompt Public Notification and

Information During an Emergency Preparedness Event

IN 2002-02, Supplement 1, Recent Experience with Plugged Steam Generator Tubes

IN 2002-18, Effect of Adding Gas into Water Storage Tanks on the Net Positive Suction Head

for Pumps

SER 2-01,

EDG Failure Resulting from Inadequate Performance Monitoring and Inadequate

Response to Symptoms of Impending Failure

SER 3-02, Workers Exit Plant Site with Detectable External Radioactive Contamination

SER 5-01, 4-kV Breaker Failure, Switchgear Fire and Turbine Generator Damage

SEN 220, Pressure Boundary Leakage at Palisades

SEN 226, Stress Corrosion Cracking on a Portion of Safety Injection System Piping

SEN 230, Pressurizer Spray Valve Failure Resulting in Reactor Scram and Safety Injection

RIS 01-015, Performance of DC-Powered Motor-Operated Valve Actuators

RIS 01-009, Control of Hazard Barriers

OE 14513, Concern with Boron Concentration in Mode 3 below P-11 with SI Blocked

Condition Reports:

2001000203

2001002960

2001000162

2001001064

2001000434

2001001069

2001000468

2001001106

2001000598

2001001837

2001001460

2001001853

2001000727

2001002194

2001000529

2001002198

2001000533

2001002246

2001000970

2002000103

2001000971

2002001700

2001001443

2002002212

2001001444

2002002645

2001001514

2001003040

2001001516

2002000744

2001001582

2002000745

2001002097

2002000856

2001002951

2001000006

2001001580

2001001704

2001000165

2001000464

2001000581

2001002138

2001001907

2001002139

2001000960

2001002142

2002000319

2001002141

2001000681

2002000090

2001000178

2002000264

2002000301

2001000043

2001000132

2001000299

2001000307

2002002295

2001000310

2001000423

2001000519

2001003034

2001000723

2001002083

2002000723

2002001319

2000001563

2001000031

2001000113

2001000501

2001001022

2001002604

2002000107

2002000518

2002002281

2002001328

2001000361

2002002581

2002003295

2002002023

2002001647

2002001371

2002000589

2002002430

2002002685

2002001992

2002002302

2002002429

2002001841

2002002122

2002002224

2001000988

2001001061

2001001686

2001002177

2001002250

2001002570

2001002711

2001002771

2002000088

2002000431

2002000756

2002000859

2002001062

2002001088

2002001129

2002001299

2002001540

2002001655

2002001837

2002002385

Maintenance Work Orders:

Maintenance Work Orders for SI, RHR, AFW, EDG, CCW, NSCW, AC power

10101119

200276

20100832

20101733

20101413

20102735

10101119

200276

20102735

20101413

20101733

10100044

10100539

10101390

10101430

10101639

10102299

10102307

10103500

200764

10101084

20102150

Licensee Audits and Self-Assessments:

SAER Audit of Corrective Actions, OP21-02/15, VSAER-2002-079

SAER Audit of Corrective Actions, OP21-01/01, VSAER-2001-013

SAER Audit of Corrective Actions, OP21-00/14, VSAER-2000-077

SAER Audit of Corrective Actions, OP21-02/01, VSAER-2002-019

SAER Audit of Corrective Actions, OP21-01/16, VSAER-2001-071

SAER Audit of Outage Activities, OP06/16/17/25/26-01/08,VSAER-2001-039

SAER Audit of Fire Protection Program, OP20-02/11, VSAER-2002-062

Count Room and Chemistry Self-Assessment, NOH-02449, July 2002

Maintenance Fire Protection Self-Assessment, NOM-02252, May 2002

Training Department Self-Assessment, February 2002

Health Physics Self-Assessment, NOH-02452, July 2002

Engineering Support Department Self-Assessment, NOE-03480, November 2001

Equipment Reliability Self-Assessment, NOE-03493, July 2002

2002 Operations Self Assessment, NOP 01357, June 2002

Safety Review Board (corporate) Meeting Minutes

Major Meetings: 02-02, 02-03, 02-05, 01-02, 01-04, 01-05, 01-08

Plant Safety Review Board (station) Minutes

9/11/02, 9/10/02, 8/30/02, 8/27/02, 8/20/02, 8/13/02

NRC Violations

NCV 50-424,425/00-05-02 (CR 2000001563)

NCV 50-424,425/00-06-01 (CR 2001000521)

NCV 50-424,425/01-03-01 (CR 2001000477)

NCV 50-424,425/01-03-02 (CR 2001000694)

NCV 50-424,425/01-08-01 (CR 2001002851)

NCV 50-424,425/02-02-01 (CR 2002001165, 2002001172, 2002001322)

NCV 50-424,425/02-02-02 (CR 2002001346, 2002001392, 2002001697)

NCV 50-424,425/02-02-03 (CR 2002001251)

NCV 50-424,425/02-02-04 (CR 20020000723, 2002001223)

Vogtle Quarterly Trend Reports

May - July, 2002

February - April, 2002

November, 2001 - January 2002

August - October, 2001

May - July, 2001

LERs, Event Investigation Reports (EIR)

LER 1-2001-001, Unit 1 Reactor Trip Due to Loss of Generator Excitation

EIR 1-2003-03, Reactor Trip due to Generator Excitation Loss

LER 1-2002-001, Improperly Wired Interlock Affects ECCS Re-circulation Valve

LER 2-2001-001, Reactor Trip While Testing Main Feedwater Pump Trip Signals

EIR 2-2001-01, Reactor Trip Due to Loss of Feedwater Flow

LER 1-2002-003, Loss of Main Feedwater ESF Actuation and Manual Reactor Trip

EIR 1-2002-001, Loss of Main Feedwater and Manual Reactor Trip

LER 1-2002-002, Containment Isolation Valve Rendered Inoperable

EIR 2-2002-002, Both Units Shutdown Due to Wrong Chemicals Added to Feed Systems

EIR 2-2002-001, Manual Reactor Trip Due to SG#3 HI-HI Level