IR 05000387/2023010

From kanterella
Jump to navigation Jump to search
Fire Protection Team Inspection Report 05000387/2023010 and 05000388/2023010
ML23345A017
Person / Time
Site: Susquehanna  
Issue date: 12/11/2023
From: Glenn Dentel
Division of Operating Reactors
To: Berryman B
Susquehanna
References
IR 2023010
Download: ML23345A017 (1)


Text

December 11, 2023

SUBJECT:

SUSQUEHANNA STEAM ELECTRIC STATION, UNITS 1 AND 2 - FIRE PROTECTION TEAM INSPECTION REPORT 05000387/2023010 AND 05000388/2023010

Dear Brad Berryman:

On November 16, 2023, the U.S. Nuclear Regulatory Commission (NRC) completed an inspection at Susquehanna Steam Electric Station, Units 1 and 2 and discussed the results of this inspection with Mark Jones, Acting Site Vice President, and other members of your staff.

The results of this inspection are documented in the enclosed report.

No findings or violations of more than minor significance were identified during this inspection.

This letter, its enclosure, and your response (if any) will be made available for public inspection and copying at http://www.nrc.gov/reading-rm/adams.html and at the NRC Public Document Room in accordance with Title 10 of the Code of Federal Regulations (10 CFR) 2.390, Public Inspections, Exemptions, Requests for Withholding.

Sincerely, Glenn T. Dentel, Chief Engineering Branch 2 Division of Operating Reactor Safety

Docket Nos. 05000387 and 05000388 License Nos. NPF-14 and NPF-22

Enclosure:

As stated

Inspection Report

Docket Numbers:

05000387 and 05000388

License Numbers:

NPF-14 and NPF-22

Report Numbers:

05000387/2023010 and 05000388/2023010

Enterprise Identifier: I-2023-010-0036

Licensee:

Susquehanna Nuclear, LLC

Facility:

Susquehanna Steam Electric Station, Units 1 and 2

Location:

Berwick, PA

Inspection Dates:

October 30, 2023 to November 16, 2023

Inspectors:

L. Cline, Senior Reactor Inspector

D. Kern, Senior Reactor Inspector

J. Tifft, Reactor Inspector

Approved By:

Glenn T. Dentel, Chief

Engineering Branch 2

Division of Operating Reactor Safety

SUMMARY

The U.S. Nuclear Regulatory Commission (NRC) continued monitoring the licensees performance by conducting a fire protection team inspection at Susquehanna Steam Electric Station, Units 1 and 2, in accordance with the Reactor Oversight Process. The Reactor Oversight Process is the NRCs program for overseeing the safe operation of commercial nuclear power reactors. Refer to https://www.nrc.gov/reactors/operating/oversight.html for more information.

List of Findings and Violations

No findings or violations of more than minor significance were identified.

Additional Tracking Items

None.

INSPECTION SCOPES

Inspections were conducted using the appropriate portions of the inspection procedures (IPs) in effect at the beginning of the inspection unless otherwise noted. Currently approved IPs with their attached revision histories are located on the public website at http://www.nrc.gov/reading-rm/doc-collections/insp-manual/inspection-procedure/index.html. Samples were declared complete when the IP requirements most appropriate to the inspection activity were met consistent with Inspection Manual Chapter (IMC) 2515, Light-Water Reactor Inspection Program - Operations Phase. The inspectors reviewed selected procedures and records, observed activities, and interviewed personnel to assess licensee performance and compliance with Commission rules and regulations, license conditions, site procedures, and standards.

REACTOR SAFETY

===71111.21N.05 - Fire Protection Team Inspection (FPTI)

Structures, Systems, and Components Credited for Fire Prevention, Detection, Suppression, or Post-Fire Safe Shutdown Review (IP Section 03.01)===

The inspectors verified that components and/or systems will function as required to support the credited functions stated for each sample. Additional inspection considerations are located in the fire hazards analysis (FHA) or safe shutdown analysis (SSA).

(1) Fire Barrier System (NDAP-QA-0446)
(2) Fire Detection/Alarm System
(3) Emergency Service Water and Residual Heat Removal Service Water System
(4) Core Spray System

Fire Protection Program Administrative Controls (IP Section 03.02) (2 Samples)

The inspectors verified that the selected control or process is implemented in accordance with the licensees current licensing basis. If applicable, ensure that the licensees FPP contains adequate procedures to implement the selected administrative control. Verify that the selected administrative control meets the requirements of all committed industry standards.

(1) Control of Ignition Sources, and Hot Work permits (NDAP-QA-0442)
(2) Aging Management Program (10CFR54) as it Relates to Fire Protection Components

Fire Protection Program Changes/Modifications (IP Section 03.03) (2 Samples)

The inspectors verified the following:

a. Changes to the approved fire protection program (FPP) do not constitute an adverse effect on the ability to safely shutdown.

b. The adequacy of the design modification, if applicable.

c. Assumptions and performance capability stated in the SSA have not been degraded through changes or modifications.

d. The FPP documents, such as the Updated Final Safety Analysis Report, fire protection report, FHA, and SSA were updated consistent with the FPP or design change.

e. Post-fire safe shutdown operating procedures, such as abnormal operating procedures, affected by the modification were updated.

(1) EC-2352782, Replace Heat Detectors (2)86-10 Fire Hazards Analysis for Diesel Driven Fire Pump Room Fire Barrier Gap (CR 2020-13254).

INSPECTION RESULTS

No findings were identified.

EXIT MEETINGS AND DEBRIEFS

The inspectors verified no proprietary information was retained or documented in this report.

  • On November 16, 2023, the inspectors presented the fire protection team inspection results to Mark Jones, Acting Site Vice President, and other members of the licensee staff.

DOCUMENTS REVIEWED

Inspection

Procedure

Type

Designation

Description or Title

Revision or

Date

71111.21N.05 Calculations

EC-013-0162

Scope Review of Fire Protection Features TRM

Requirements

Revision 4

EC-013-0852

Evaluation for Identification and Disposition of Appendix R

Section III.G Non-compliant Cables

Revision 1

EC-013-0920

Assessment of Fire Detectors and Suppression Systems

Revision 12

EC-013-1076

SSES Raceway Fire Barrier Upgrade Qualification

Records for NRC Generic Letter 92-08

Revision 1

EC-SIMU-1004

Time Critical Operator Action (TCOA) and Time Sensitive

Operator Action (TSOA) Margin Evaluation

Revision 1

Corrective Action

Documents

2018-09760

21-13801

22-00350

Corrective Action

Documents

Resulting from

Inspection

23-17118

23-17130

23-17132

23-17143

23-17274

23-17283

23-17329

23-17331

23-17347

23-17348

23-17366

23-17375

23-17376

23-17393

23-17440

23-17774

23-17809

23-17825

23-17840

Inspection

Procedure

Type

Designation

Description or Title

Revision or

Date

23-17854

23-17864

23-17867

23-17896

23-17928

23-17943

23-17944

23-17960

Drawings

C-1723, Sht 10

SSES U1 RB Fire zone Plan of Protected Tray Raceway

Elevation 719-1

Revision 4

M-111, Sht 1

SSES Common Emergency Service Water System

Revision 52

M-112, Sht 1

SSES U1 RHR Service Water System

Revision 56

M-112, Sht 2

SSES U1 RHR Service Water System

Revision 24

Engineering

Changes

DCP 214698

Unit 2 - Reactor Building Fire Detection System Upgrade

03/15/2000

EC 2352782

Replace Heat Detectors

Revision 0

Engineering

Evaluations

86-10 Fire Hazards Analysis Evaluation for Diesel Driven

Fire Pump Fire Barrier Gap

Revision 0

Miscellaneous

SSES Fire Protection Review Report

Revision 13

SNE-DTG-007

License Renewal Commitments for Fire Protection

Engineering

Revision 1

Procedures

NDAP-QA-0343

SSES Time Critical and Time Sensitive Operator Actions

Revision 6

NDAP-QA-0409

Door, Floor Plug, and Hatch Control

Revision 23

NDAP-QA-0442

Control of Ignition Sources, Cutting, Welding, and Hot

Work Permits

Revision 20

NSEP-QA-0002

License Renewal System Walkdown Program

Revision 1

NSEP-QA-0433

Buried Piping Surveillance Program (AMP-16) License

Renewal Program Basis Document

Revision 0

NSEP-QA-0440

Fire Protection Program (AMP-15) License Renewal

Program Basis Document

Revision 0

NSEP-QA-0449

System Walkdown Program (AMP-28) License Renewal

Program Basis Document

Revision 2

ON-CREVAC-

101

Control Room Evacuation

Revision 7

Inspection

Procedure

Type

Designation

Description or Title

Revision or

Date

OP-054-001

Emergency Service Water System

Revision 45

OP-100-001

Remote Shutdown Panel

Revision 14

OP-116-001

RHR Service Water

Revision 60

SE-013-007

Month Inspection of Unit Common Fire Barriers

Revision 13

SE-013-009

Month Inspection of Fire Windows/Fire Dampers and

Associated Hardware

Revision 8

SE-113-006

Month Inspection of Unit 1 Fire Rated Penetration

Seals

Revision 12

SI-013-225

Annual Functional Test of Fire Protection Smoke

Detectors For Fire Zones 0-25A and 0-25E

Revision 9

SI-213-241

Annual Functional Test of Fire Protection Ionization and

Photoelectric Detectors for Fire Zones 2-5A-N, 2-5A-S, 2-

5A-W, 2-5B, 2-5C and 2-5H (Preaction System PA-251)

Revision 13

SI-213-254

Annual Functional Test of Preaction System Fire

Protection Heat Detectors for Fire Zone 0-25A

Revision 7