IR 05000346/2018002
| ML18227A105 | |
| Person / Time | |
|---|---|
| Site: | Davis Besse (NPF-003) |
| Issue date: | 08/15/2018 |
| From: | Jamnes Cameron Reactor Projects Region 3 Branch 4 |
| To: | Bezilla M FirstEnergy Nuclear Operating Co |
| Shared Package | |
| ML18227A103 | List: |
| References | |
| IR 2018002 | |
| Download: ML18227A105 (25) | |
Text
August 15, 2018
SUBJECT:
ERRATADAVIS-BESSE NUCLEAR POWER STATIONNRC INTEGRATED INSPECTION REPORT 05000346/2018002
Dear Mr. Bezilla:
The U.S. Nuclear Regulatory Commission (NRC) identified administrative errors in NRC Inspection Report 05000346/2018002 dated August 10, 2018 (ADAMS Accession Number ML18222A345). Specifically, the Sections entitled 71114.02 - Alert and Notification System Testing, 71114.03 - Emergency Response Organization Staffing and Augmentation System, and 71114.05 - Maintenance of Emergency Preparedness were erroneously omitted from the report. These inspection samples were performed during the time period documented in the report. As a result, the NRC has reissued the report in its entirety with these Sections added to correct the errors.
This letter, its enclosure, and your response (if any) will be made available for public inspection and copying at http://www.nrc.gov/reading-rm/adams.html and at the NRC Public Document Room in accordance with 10 CFR 2.390, Public Inspections, Exemptions, Requests for Withholding.
Sincerely,
/RA/
Jamnes L. Cameron, Chief Branch 4 Division of Reactor Projects
Docket Nos. 50-346;72-014 License Nos. NPF-3
Enclosure:
Inspection Report 05000346/2018002
REGION III==
Docket Numbers:
50-346;72-014 License Numbers:
NPF-3 Report Numbers:
05000346/2018002 Enterprise Identifier: I-2018-002-0015 Licensee:
FirstEnergy Nuclear Operating Company (FENOC)
Facility:
Davis-Besse Nuclear Power Station Location:
Oak Harbor, OH Dates:
April 1 through June 30, 2018 Inspectors:
D. Mills, Senior Resident Inspector
M. Garza, Acting Senior Resident Inspector J. Harvey, Resident Inspector J. Rutkowski, Project Engineer J. Beavers, Resident Inspector, Duane Arnold Energy Center
Approved by:
J. Cameron, Chief Branch 4 Division of Reactor Projects
SUMMARY
The U.S. Nuclear Regulatory Commission (NRC) continued monitoring licensees performance by conducting an integrated quarterly inspection at Davis-Besse Power Plant in accordance with the Reactor Oversight Process. The Reactor Oversight Process is the NRCs program for overseeing the safe operation of commercial nuclear power reactors. Refer to https://www.nrc.gov/reactors/operating/oversight.html for more information. Findings and violations being considered in the NRCs assessment are summarized in the table below.
List of Findings and Violations
Failure to Follow the Makeup and Purification Procedure Cornerstone Significance Cross-cutting Aspect Report Section Initiating Events Green NCV 05000346/2018002-01 Closed
H.12 71152 -
Annual Follow-Up of Selected Issues A self-revealed Green finding and associated Non-Cited Violation of Technical Specification 5.4.1.a, Procedures, was identified when the licensee failed to follow station procedure DB-OP-06006, Makeup and Purification System. Specifically, the licensee failed to open MU177, the Make-Up Filter 1 Outlet Isolation valve, which resulted in the isolation of letdown while swapping make-up filters.
Failure to Apply Technical Specification for Safety Features Actuation System Instrumentation Cornerstone Significance Cross-cutting Aspect Report Section Mitigating Systems Green NCV 05000346/2018002-02 Closed H.14 71153 -
Follow-Up of Events and Notices of Enforcement Direction The NRC identified a finding of Green significance and an associated Non-Cited Violation of Technical Specification 3.3.5.b, Safety Features Actuation System (SFAS) Instrumentation, for the licensees failure to place the reactor in Mode 3 within six hours of identifying that two channels of Safety Features Actuation System Borated Water Storage Tank level instrumentation were inoperable. Specifically, the licensee inappropriately exited Technical Specification 3.3.5.b, and failed to place the reactor in Mode 3 while two Borated Water Storage Tank level instruments were inoperable for more than six hours.
Failure to Perform a Procedure Affecting Quality Cornerstone Significance Cross-Cutting Aspect Report Section Mitigating Systems Green NCV 05000346/2018002-03 Closed H.8 71153 -
Follow-Up of Events and Notices of Enforcement Direction The NRC identified a finding of Green significance and an associated non-cited violation of 10 Code of Federal Regulation (CFR) Part 50, Appendix B, Criterion V, Instructions,
Procedures, and Drawings, due to the licensees failure to implement DB-OP-03006,
Miscellaneous Instrument Shift Checks, Specifically, the licensee declared SFAS Channel 1 operable without performing the required channel check.
Misapplication of the Operability Determination Process
Cornerstone Significance Cross-Cutting Aspect Report Section Mitigating Systems Green FIN 05000346/2018002-04 Closed H.13 71153 -
Follow-Up of Events and Notices of Enforcement Direction The NRC identified a finding of Green significance due to the licensees misapplication of NOP-OP-1009, Operability Determinations and Functionality Assessments. Specifically, the licensee failed to apply the Operability Determination process in accordance with procedures.
Additional Tracking Items
Type Issue Number Title Report Section Status LER 05000346/2016008-01 Application of Technical Specification for the Safety Features Actuation System Instrumentation 71153 Closed
TABLE OF CONTENTS
PLANT STATUS
INSPECTION SCOPES
................................................................................................................
REACTOR SAFETY
.................................................................................................................
OTHER ACTIVITIES - BASELINE
...........................................................................................
INSPECTION RESULTS
............................................................................................................
EXIT MEETINGS AND DEBRIEFS
............................................................................................ 14
DOCUMENTS REVIEWED
......................................................................................................... 18
PLANT STATUS
The unit remained at or near rated thermal power for the entirety of the inspection period.
On March 28, 2018, FirstEnergy Solutions (FES) / FirstEnergy Nuclear Operating
Company (FENOC) verbally notified the Nuclear Regulatory Commission that they intended to
shut down all four of their operating nuclear power plants. Based on that notification, the first to
shut down will be Davis-Besse, by May 31, 2020. On March 31, 2018, FES, FirstEnergy
Nuclear Generation (FENGEN), and FENOC filed for bankruptcy. The Nuclear Regulatory
Commission continues to maintain focus on public health and safety and the protection of the
environment. This will include a continuous evaluation by inspectors to determine whether the
licensees financial condition is impacting safe operation of the plant.
INSPECTION SCOPES
Inspections were conducted using the appropriate portions of the inspection procedures (IPs) in
effect at the beginning of the inspection unless otherwise noted. Currently approved IPs with
their attached revision histories are located on the public website at http://www.nrc.gov/reading-
rm/doc-collections/insp-manual/inspection-procedure/index.html. Samples were declared
complete when the IP requirements most appropriate to the inspection activity were met
consistent with Inspection Manual Chapter (IMC) 2515, Light-Water Reactor Inspection
Program - Operations Phase. The inspectors performed plant status activities described in
IMC 2515 Appendix D, Plant Status and conducted routine reviews using IP 71152, Problem
Identification and Resolution. The inspectors reviewed selected procedures and records,
observed activities, and interviewed personnel to assess licensee performance and compliance
with Commission rules and regulations, license conditions, site procedures, and standards.
REACTOR SAFETY
71111.01Adverse Weather Protection
Summer Readiness (1 Sample)
The inspectors evaluated summer readiness of offsite and alternate alternating current
power systems.
71111.04Equipment Alignment
Partial Walkdown (4 Samples)
The inspectors evaluated system configurations during partial walkdowns of the following
systems/trains:
(1) Auxiliary feedwater train 1 during planned maintenance and testing on auxiliary
feedwater train 2 during the week ending April 14, 2018;
(2) Motor driven feedwater pump during auxiliary feedwater train 2 maintenance during the
week ending April 21, 2018;
(3) Containment spray system during the week ending April 28, 2018; and
(4) Decay heat/low pressure injection train 2 when train 1 was out of service during the
week ending June 2, 2018.
Complete Walkdown (1 Sample)
The inspectors evaluated system configurations during a complete walkdown of the High
Pressure Injection system during the week ending April 28, 2018.
71111.05QFire Protection Quarterly
Quarterly Inspection (4 Samples)
The inspectors evaluated fire protection program implementation in the following selected
areas:
(1) Emergency core cooling system pump room 1-2, (fire area A), during the week ending
April 28, 2018;
(2) Auxiliary building rooms 104, 106, 106A, and 109, (fire area A), during the week ending
April 28, 2018;
(3) Auxiliary feedwater train 2, (fire area F) during the week ending May 19; and
(4) Component cooling water room, (fire area T), during the week ending May 26, 2018.
71111.06Flood Protection Measures
Underground Cables (1 Sample)
The inspectors evaluated cable submergence protection in:
(1) Manholes mh3101, mh3108, mh3109, mh3010 during the week ending April 14, 2018.
71111.07Heat Sink Performance
Heat Sink (1 Sample)
The inspectors evaluated closed cooling water 3 performance following a pinhole leak repair
during the week ending May 19, 2018.
71111.11Licensed Operator Requalification Program and Licensed Operator Performance
Operator Requalification (1 Sample)
The inspectors observed and evaluated licensed operator requalification training during the
week ending May 26, 2018.
Operator Performance (1 Sample)
The inspectors observed and evaluated operators perform a reactor downpower and place
feedwater components in manual control to support planned maintenance on a feedwater
flow component during the week ending May 26, 2018.
71111.12Maintenance Effectiveness
Routine Maintenance Effectiveness (2 Samples)
The inspectors evaluated the effectiveness of routine maintenance activities associated
with the following equipment and/or safety significant functions:
(1) Decay heat/low pressure injection train 1; and
(2) Component cooling water availability.
71111.13Maintenance Risk Assessments and Emergent Work Control (4 Samples)
The inspectors evaluated the risk assessments for the following planned and emergent
work activities:
(1) Auxiliary feedwater train 2 out of service for planned maintenance during the week
ending May 12;
(2) E-31A outage to relieve cable stress due to turbine building floor movement during the
week ending May 12;
(3) Control room emergency ventilation system train 1 out of service for planned
maintenance during the week ending May 26; and
(4) Decay heat/low pressure injection train 1 out of service for planned maintenance during
the week ending June 2.
71111.15Operability Determinations and Functionality Assessments (4 Samples)
The inspectors evaluated the following operability determinations and functionality
assessments:
(1) Forward flow / closure valve SW277CR 2018-03174 during the week ending April 6;
(2) Containment Isolation Valve Train 2 position indication lights not litCR 2018-04305
during the week ending May 12, 2018;
(3) Leading Edge Flow Monitor FailureCR 2018-04296 during the week ending
May 12, 2018; and
(4) Emergency Diesel Generator 2 silencer through-wall leakCR 2018-04599 during the
week ending May 26, 2018.
71111.18Plant Modifications (1 Sample)
The inspectors evaluated the following temporary or permanent modifications:
(1) Borated Water Storage Tank Loop Seal, ECP 16-0478, during the week ending
June 23, 2018.
71111.19Post Maintenance Testing (3 Samples)
The inspectors evaluated the following post maintenance tests:
(1) Auxiliary feedwater train 2 following planned maintenance, during the week ending
May 12, 2018;
(2) Service water train 1 following planned maintenance, during the week ending
May 26, 2018; and
(3) Decay heat/low pressure injection train 1 following planned maintenance, during the
week ending June 9, 2018.
71111.22Surveillance Testing
The inspectors evaluated the following surveillance tests:
Routine (1 Sample)
(1) Emergency diesel generator 1 monthly surveillance during the week ending
April 7, 2018.
71114.02Alert and Notification System Testing (1 Sample)
The inspectors evaluated the maintenance and testing of the alert and notification system on
April 9-13, 2018.
71114.03Emergency Response Organization Staffing and Augmentation System (1 Sample)
The inspectors evaluated the readiness of the Emergency Response Organization on
April 9-13, 2018.
71114.05Maintenance of Emergency Preparedness (1 Sample)
The inspectors evaluated the maintenance of the emergency preparedness program on
April 9-13, 2018.
71114.06Drill Evaluation
Emergency Planning Drill (1 Sample)
The inspectors evaluated a tabletop drill at the Emergency Operations Facility on
June 4, 2018.
OTHER ACTIVITIES - BASELINE
71151Performance Indicator Verification (6 Samples)
The inspectors verified licensee performance indicators submittals listed below:
(1) MS05: Safety System Functional Failures (SSFFs) for the period from the second
quarter 2017 through the first quarter 2018;
(2) MS06: Emergency AC Power Systems for the period from the second quarter 2017
through the first quarter 2018; and
(3) MS07: High Pressure Injection Systems for the period from the second quarter 2017
through the first quarter 2018.
(4) EP01: Drill/Exercise Performance (1st quarter 2017 through 4th quarter 2017)
(5) EP02: Emergency Response Organization Drill Participation (1st quarter 2017 through
4th quarter 2017)
(6) EP03: Alert and Notification System Reliability (1st quarter 2017 through 4th
quarter 2017)
71152Problem Identification and Resolution
Annual Follow-Up of Selected Issues (1 Sample)
The inspectors reviewed the licensees implementation of its corrective action program
related to the following issues:
(1) CR 2018-03036; Misposition of Make Up Filter 1 Outlet Isolation (MU177)
One violation for this issue is documented in this report.
71153Follow-Up of Events and Notices of Enforcement Discretion
Licensee Event Reports (1 Sample)
The inspectors evaluated the following licensee event reports which can be accessed at
https://lersearch.inl.gov/LERSearchCriteria.aspx:
(1) Licensee Event Report (LER) 05000346/2016-008-01, Application of Technical
Specifications for the Safety Features Actuation System Instrumentation. Two violations
and a finding for this issue are documented in this report. This LER is closed.
Evaluation of Davis-Besse Safety Condition in Light of Financial Conditions
The licensees parent company, FirstEnergy Solutions, was under bankruptcy
protection/reorganization during the inspection period. As such, NRC Region III conducted
special reviews of processes at Davis-Besse. Using the flexibilities in the baseline inspection
program, the inspectors evaluated several aspects of the licensees operations to assess
whether any identified plant performance issues could be related to the stations financial
condition. The factors reviewed included: (1) impact on regulatory-required plant staffing,
(2) corrective maintenance backlog, (3) changes to the planned maintenance schedule,
(4) corrective action program implementation, and (5) reduction in outage scope, including
risk-significant modifications. In particular, the inspectors verified that licensee personnel
continued to identify problems at an appropriate threshold and enter these problems into the
corrective action program for resolution. The inspectors also verified that the licensee continued
to develop and implement corrective actions commensurate with the safety significance of the
problems identified.
The review of processes at Davis-Besse included continuous reviews by the Resident
Inspectors, as well as the specialist-led baseline inspections completed during the inspection
period which are documented previously in this report.
INSPECTION RESULTS
71152Problem Identification and Resolution
Observation - Selected Issue Follow-Up for
CR-2018-03036: Misposition of Make Up Filter 1
Outlet Isolation (MU 177)
71152 - Annual Sample Review
On March 31, 2018, while placing makeup system filter 1 in service using DB-OP-06006,
Makeup and Purification System, Revision 42, the licensee received two unexpected alarms:
Letdown or MU [make-up] Filter dP [differential pressure] Hi followed by Letdown Pressure
Hi. The licensee immediately opened MU12B, the Makeup Filter 2 Inlet Isolation, to establish
letdown flow. During this time the letdown relief valve lifted and reseated, diverting
approximately six gallons of water to the reactor coolant drain tank.
Through the investigation of the issue, the licensee found MU177, the Make-Up Filter 1 Outlet
Isolation valve, had not been opened on March 30, 2018, as required by Step 4.9.16.j of
DB-OP-06006. The licensees corrective actions included operator remediation, a
requirement to have shiftly engagement calls with Operations Management, and
reinforcement of the value of reverse briefs by operators as a human performance tool. This
issue was documented in CR-2018-03036, Disposition of Make-Up Filter 1 Outlet
Isolation (MU177).
As appropriate, the inspectors verified the following attributes during their review of the
licensee's corrective actions for the above condition reports and other related condition
reports:
complete and accurate identification of the problem in a timely manner commensurate
with its safety significance and ease of discovery;
consideration of the extent of condition, generic implications, common cause, and
previous occurrences;
evaluation and disposition of operability/functionality/reportability issues;
classification and prioritization of the resolution of the problem commensurate with
safety significance;
identification of corrective actions, which were appropriately focused to correct the
problem; and
completion of corrective actions in a timely manner commensurate with the safety
significance of the issue.
The inspectors verified the licensee assessed and corrected the issue in a timely manner. A
violation associated with this issue is documented in this report.
Failure to Follow the Makeup and Purification Procedure
Cornerstone
Significance
Cross-cutting
Aspect
Report
Section
Green
Closed
H.12
71152 -
Annual
Follow-Up of
Selected
Issues
A self-revealed Green finding and associated Non-Cited Violation (NCV) of Technical Specification 5.4.1.a, Procedures, was identified when the licensee failed to follow station
procedure DB-OP-06006, Makeup and Purification System. Specifically, the licensee failed
to open MU177, the Make-Up Filter 1 Outlet Isolation valve, which resulted in the isolation of
letdown while swapping make-up filters.
Description:
On March 31, 2018, while placing make-up system filter 1 in service using DB-OP-06006,
Makeup and Purification System, Revision 42, the licensee received two unexpected
alarms: Letdown or MU [make-up] Filter dP [differential pressure] Hi followed by Letdown
Pressure Hi. The licensee immediately opened MU12B, the Makeup Filter 2 Inlet Isolation,
to establish letdown flow.
During investigation of the issue the licensee found MU177, the Make-up Filter 1 Outlet
Isolation Valve, unexpectedly closed. This was because on March 30, 2018, when preparing
to swap filters, the licensee failed to follow Step 4.9.16.j of DB-OP-06006, which required
opening of MU177. Additionally, the licensee determined that while letdown flow was
isolated, the letdown relief valve lifted and reseated. Approximately six gallons of water were
diverted to the reactor coolant drain tank.
Corrective Actions: The licensees corrective actions included operator remediation, a
requirement to have shiftly engagement calls with operations management, and
reinforcement of the value of reverse briefs by operators as a human performance tool.
Corrective Action Reference: This issue was documented in CR-2018-03036, Misposition
of Make-Up Filter 1 Outlet Isolation (MU177).
Performance Assessment:
Performance Deficiency: The inspectors determined the licensees failure to follow
DB-OP-06006, Makeup and Purification System, Revision 42, was a performance deficiency.
Specifically, the licensee failed to open MU177, Make-Up Filter 1 Outlet Isolation, as required
by Step 4.9.16.j.
Screening: The performance deficiency was more than minor because it was associated with
Initiating Events cornerstone attribute of equipment performance, and adversely affected the
cornerstone objective of limiting the likelihood of events that upset plant stability and
challenge critical safety functions during shutdown as well as power operations. Specifically,
the licensees failure to open MU177 resulted in the letdown relief valve lifting, diverting
reactor coolant to the reactor coolant drain tank.
Significance: Using Inspection Manual Chapter (IMC) 0609, Attachment 4, Initial
Characterization of Findings, and IMC 0609 Appendix A, The Significance Determination
Process for Findings at Power, issued June 19, 2012, the finding was screened against the
Initiating Events cornerstone. The inspectors determined this issue was of very low safety
significance (Green) because the inspectors answered No to all the screening questions.
Cross Cutting Aspect: This finding has a cross-cutting aspect of Avoid Complacency in the
area of the Human Performance because the licensee failed to recognize and plan for the
possibility of mistakes, latent issues, and inherent risk, even while expecting successful
outcomes. Individuals implement appropriate error reduction tools. Specifically, the licensee
did not appropriately implement error reduction tools. [H.12]
Enforcement:
Violation: Technical Specification 5.4.1.a, Procedures, states, in part, written procedures
shall be established, implemented, and maintained covering the following activities: the
applicable procedures recommended in Regulatory Guide 1.33, Revision 2, Appendix A,
February 1978. Section 3.n of Regulatory Guide 1.33, Revision 2, Appendix A,
February 1978, states, in part, instructions for energizing, filling, venting, draining, startup,
shutdown, and changing modes of operation should be prepared, as appropriate, for the
following systems: chemical and volume control system (including letdown/purification
system). Step 4.9.16.j of DB-OP-06006, Makeup and Purification System, Revision 42,
stated, open MU177, Make-up Filter 1 Outlet Isolation.
Contrary to the above, on March 30, 2018, the licensee failed to implement a written
procedure required by Technical Specification 5.4.1.a. Specifically, the licensee failed to
implement procedure DB-OP-06006, Makeup and Purification System, Revision 42, which
resulted in the isolation of letdown while swapping make-up filters.
Disposition: Because it was of very low safety significance and was entered into the
licensees corrective action program as CR-2018-03036, this violation is being treated as an
NCV consistent with Section 2.3.2 of the Enforcement Policy. (NCV 05000346/2018002-01:
Failure to follow Makeup and Purification Procedure)
71153Follow-Up of Events and Notices of Enforcement Discretion
Failure to Apply Technical Specification for Safety Features Actuation System Instrumentation
Cornerstone
Significance
Cross-cutting
Aspect
Report
Section
Mitigating
Systems
Green
Closed
H.14
71153 -
Follow-Up of
Events and
Notices of
Enforcement
Direction
The NRC identified a finding of Green significance and an associated NCV of Technical Specification 3.3.5, Safety Features Actuation System (SFAS) Instrumentation for the
licensees failure to place the reactor in Mode 3 within six hours of identifying that two
channels of SFAS Borated Water Storage Tank level instrumentation were inoperable.
Specifically, the licensee exited Technical Specification (TS) 3.3.5.b, the six hour shutdown
technical specification, while two BWST level instruments were still inoperable.
Description:
Licensee Event Report (LER) 05000346/2016-008-01, Application of Technical
Specifications for the Safety Features Actuation System Instrumentation.
On June 30, 2016 at 0829 EDT, Channel 1 of the Borated Water Storage Tank (BWST) level
instrumentation for the Safety Features Actuation System (SFAS) was declared inoperable
and removed from service for scheduled maintenance. The Limiting Condition for
Operation (LCO) for Technical Specification 3.3.5 stated in part, four channels of SFAS
instrumentation for each Parameter [BWST level] shall be operable. At this time, Reactor
Operators entered TS 3.3.5.a, which required the inoperable channel be tripped. Later that
day at 2344, Channel 2 became inoperable due to a loss of power from a failed power supply.
At this time, operators should have entered TS 3.3.5.b, which required restoring at least one
channel immediately or placing the reactor into Mode 3 (hot shutdown), within six hours. At
0140 on July 1, 2016, operators realized that they should apply TS 3.3.5.b, but did not enter
the Technical Specification until 0245. At 0330, operators exited TS 3.3.5.b with Channel 1
declared operable with compensatory measures, including proceduralized operator actions to
be performed for a manual suction swap. At that time, the Channel 1 instrument was
electrically and physically disconnected and incapable of performing its function or passing
the Technical Specification required surveillance, which is required to be met in all modes of
applicability of the LCO.
The inspectors questioned the licensees basis for operability. From discussions with the
licensee on July 1, 2016, the inspectors determined the defined compensatory measures
were not sufficient for the licensee to declare Channel 1 operable. At 1325 on July 1, 2016,
the licensee declared Channel 1 inoperable and reentered TS 3.3.5.b. At 1351, the licensee
exited TS 3.3.5.b after maintenance was completed and Channel 1 was restored to service.
The inspectors determined the reactor had been in a Mode other than Mode 3 (or lower) for a
total of 14 hours1.62037e-4 days <br />0.00389 hours <br />2.314815e-5 weeks <br />5.327e-6 months <br /> and 7 minutes.
Corrective Actions: The corrective actions included reentering TS 3.3.5.b and performing
corrective maintenance on the Channel 1 instrumentation to restore it to operable. The
Licensee performed a root cause analysis and developed a case study from lessons learned.
Additionally, the licensee issued an operations standing order; revised multiple procedures;
and performed additional training regarding lessons learned from this event, Technical
Specification compliance, and correct application of the operability determination process.
Corrective Action Reference: The licensee documented this issue in CR 2016-08419
Performance review of LCO 3.3.5 application during LT1525A maintenance.
Performance Assessment:
Performance Deficiency: The inspectors determined the licensees failure to place the reactor
in Mode 3 within six hours, as required by TS 3.3.5.b, was a performance deficiency.
Specifically, with two channels of the BWST level instrumentation inoperable, the licensee
failed to enter Mode 3 within six hours.
Screening: The finding was determined to be more than minor because it was associated
with the Mitigating Systems function of Long Term Heat Removal, and affected the
cornerstones objective of ensuring the availability, reliability, and capability of systems to
respond to initiating events to prevent undesirable consequences. Specifically, the finding
resulted in the loss of the emergency core cooling system (ECCS) suction swap permissive
function, which could have resulted in the loss of system safety function (i.e., ECCS due to a
premature suction source transfer).
Significance: The inspectors determined the finding could be evaluated using the SDP in
accordance with IMC 0609, Significance Determination Process, Attachment 0609.04,
Phase 1-Initial Screening and Characterization of Findings, for the Mitigating Systems
cornerstone. The inspectors evaluated the finding using Appendix A, The Significance
Determination Process for Findings At-Power. The inspectors answered Yes to Question
A.2 in Exhibit 2 because the finding represented the inoperability of the ECCS suction swap
permissive for fourteen hours, which was greater than the TS 3.3.5 allowed outage time of
hours for this function. Therefore, a detailed risk evaluation was performed using
IMC 0609, Appendix A. The risk evaluation was performed by Region III SRAs and the
bounding core damage frequency (CDF) was determined to be 7.0E-7/yr. Since the total
estimated change in core damage frequency was less than 1.0E-6/year, the finding/violation
was initially determined to be Green. Additionally since the CDF was greater than
1.0E-7/year, the finding was reviewed for potential Large Early Release Frequency (LERF)
contribution. Davis Besse is a 2-loop Babcock and Wilcox Pressurized Water Reactor with a
large dry containment. The core damage sequences important to LERF were steam
generator tube rupture events and inter-system LOCA events. These events were not the
dominant core damage sequences for this finding. Therefore, based on the detailed risk
evaluation, the SRAs confirmed that the finding was of very-low safety significance (Green).
Cross Cutting Aspect: This finding had a cross-cutting aspect of Conservative Bias in the
area of Human Performance, which states individuals use decision making practices that
emphasize prudent choices over those that are simply allowable. A proposed action is
determined to be safe in order to proceed, rather than unsafe in order to stop. Specifically,
the licensee failed to use decision making practices that emphasized prudent choices, over
those that they believed were simply allowable. [H.14]
Enforcement:
Violation: Technical Specification 3.3.5.b, SFAS Instrumentation, states in part, with one of
more Parameters with two or more channels inoperable, be in Mode 3 within six hours.
Enforcement Actions: Contrary to the above, on July 1, 2016, the licensee failed to place the
reactor into Mode 3 within six hours of identifying one Parameter of SFAS instrumentation
with two channels inoperable. Specifically, licensee operators entered TS 3.3.5.b. at 0245
hours on July 1, 2016, following the determination that Channels 1 and 2 of SFAS
Instrumentation were inoperable. At 0330, licensee operators used inappropriate actions to
declare Channel 1 of SFAS Instrumentation operable, and subsequently failed to place the
reactor in Mode 3 before 0845 hours0.00978 days <br />0.235 hours <br />0.0014 weeks <br />3.215225e-4 months <br /> on July 1, 2016. Licensee operators appropriately
exited TS 3.3.5.b. at 1351 hours0.0156 days <br />0.375 hours <br />0.00223 weeks <br />5.140555e-4 months <br /> on July 1, 2016.
Disposition: Because it was of very low safety significance and was entered into the
licensees corrective action program as CR-2016-08419, this violation is being treated as an
NCV consistent with Section 2.3.2 of the Enforcement Policy. (NCV 05000346/2018002-02:
Failure to Apply Technical Specification for SFAS Instrumentation)
Failure to Perform a Procedure Affecting Quality
Cornerstone
Significance
Cross-cutting
Aspect
Report
Section
Mitigating
Systems
Green
Closed
H.8
71153 -
Follow-Up of
Events and
Notices of
Enforcement
Direction
The NRC identified a finding of Green significance and an associated non-cited violation of
CFR Part 50, Appendix B, Criterion V, Instructions, Procedures, and Drawings, due to
the licensees failure to implement DB-OP-03006, Miscellaneous Instrument Shift Checks,
Specifically, the licensee declared SFAS Channel 1 operable without performing the required
channel check.
Description:
Licensee Event Report (LER) 05000346/2016-008-01, Application of Technical
Specifications for the Safety Features Actuation System Instrumentation.
On June 30, 2016, at 0829 EDT, Channel 1 of the Borated Water Storage Tank (BWST) level
instrumentation for the Safety Features Actuation System (SFAS) was declared inoperable
and removed from service for scheduled maintenance. On July 1, 2016, at 0330, the channel
was declared operable with reference to compensatory measures. At that time, the
Channel 1 instrument was electrically and physically disconnected, and incapable of
performing its function.
On July 1, 2016, at 0700, the licensee performed DB-OP-03006, Miscellaneous Instrument
Shift Checks. Step 2.1.1 states, in part, a channel check shall be the qualitative assessment,
by observation, of channel behavior during operation. Section 4.2 requires a channel check
comparison for all four channels of the BWST level instrumentation. At that time, the level
instrumentation string for Channel 1 was de-energized, with the level instrument
disassembled. The licensee declared the channel check results satisfactory for Channel 1 by
referring to compensatory measures, including proceduralized operator actions that were not
applicable to the DB-OP-03006 acceptance criteria.
The inspectors questioned the licensees basis for operability and noted that the Channel 1
level instrument was not energized and was not physically attached to the system. The
inspectors subsequently determined the licensee failed to complete section 4.2 of
DB-OP-03006 for Channel 1 in accordance with Step 2.1.1 because the instrument string
was not in operation at the time the surveillance was completed. Additionally, the inspectors
determined the compensatory measures were not sufficient for the licensee to credit them
toward satisfactory test results.
Corrective Actions: The corrective actions included declaring Channel 1 inoperable and
performing corrective maintenance on the Channel 1 instrumentation to restore it to operable.
The Licensee performed a root cause analysis and developed a case study from lessons
learned. Additionally, the licensee issued an operations standing order; revised multiple
procedures; and performed additional training regarding lessons learned from this event,
Technical Specification compliance, and correct application of the operability determination
process.
Corrective Action Reference: The licensee documented this issue in CR 2016-08419,
Performance review of LCO 3.3.5 application during LT1525A maintenance.
Performance Assessment:
Performance Deficiency: The inspectors determined the licensees failure to implement
DB-OP-03006 was a performance deficiency. Specifically, step 2.1.1 requires a channel
check be performed by observation during operation. However, the licensee could not
perform the BWST level channel check comparison for Channel 1, as required by Step 4.2,
because the Channel 1 instrument string was de-energized and disconnected from its
associated system.
Screening: The performance deficiency was determined to be more than minor because it
was associated with the Mitigating Systems cornerstone attribute of Equipment Performance
and affected the cornerstone objective of ensuring the availability, reliability, and capability of
systems that respond to initiating events to prevent undesirable consequences. Specifically,
the failure to follow procedures to establish the operability of SFAS Channel 1 negatively
affected the ability of the system to perform its accident mitigating function. Additionally, this
failure led to a violation of Technical Specifications as detailed elsewhere in this report.
Significance: The inspectors assessed the significance of the finding using IMC 0609.04,
Initial Characterization of Findings, and IMC 0609, Appendix A, Exhibit 2, Mitigating
Systems Screening Questions. The inspectors determined that this performance deficiency
did not result in a loss of a single train of a safety system for greater than its Technical
Specification allowed outage time. Therefore, the inspectors determined the finding to be of
very low safety significance (Green).
Cross Cutting Aspect: This finding had a cross-cutting aspect of Procedure Adherence in the
area of Human Performance, which states individuals follow processes, procedures, and work
instructions. Specifically, the licensee declared the SFAS Channel 1 operable without
meeting the acceptance criteria of the required procedures. [H.8]
Enforcement:
Violation: Title 10 CFR Appendix B, Criterion V, Instructions, Procedures, and Drawings,
requires, in part, that activities affecting quality be prescribed by documented instructions,
procedures, or drawings, of a type appropriate to the circumstances and shall be
accomplished in accordance with these instructions, procedures, or drawings. Instructions,
procedures, or drawings shall include appropriate quantitative or qualitative acceptance
criteria for determining that important activities have been satisfactorily accomplished.
Step 2.1.1 of DB-OP-03006, Revision 55, an Appendix B procedure affecting Technical
Specification-required equipment, states, in part, a channel check shall be the qualitative
assessment, by observation, of channel behavior during operation.
Contrary to the above, on July 1, 2016, the licensee failed to accomplish activities affecting
quality in accordance with procedures of a type appropriate to the circumstances.
Specifically, the licensee attempted to perform the Channel 1 BWST level instrument channel
check while the instrument was de-energized and physically disconnected from its associated
system, and thus not operating.
Disposition: Because it was of very low safety significance and was entered into the
licensees corrective action program as CR-2016-08419, this violation is being treated as an
NCV consistent with Section 2.3.2 of the Enforcement Policy. (NCV 05000346/2018002-03:
Failure to Perform a Procedure Affecting Quality)
Misapplication of the Operability Determination Process
Cornerstone
Significance
Cross-cutting
Aspect
Report
Section
Mitigating
Systems
Green
Closed
H.13
71153 -
Follow-Up of
Events and
Notices of
Enforcement
Direction
The NRC identified a finding of Green significance due to the licensees misapplication of
NOP-OP-1009, Operability Determinations and Functionality Assessments. Specifically,
the licensee failed to apply the Operability Determination process in accordance with
procedures.
Description:
Licensee Event Report (LER) 05000346/2016-008-01, Application of Technical
Specifications for the Safety Features Actuation System Instrumentation.
On June 30, 2016, at 0829 EDT, Channel 1 of the Borated Water Storage Tank (BWST) level
instrumentation for the Safety Features Actuation System (SFAS) was declared inoperable
and removed from service for scheduled maintenance. At this time, Reactor Operators
entered TS 3.3.5.a, which required the inoperable channel be tripped. On July 1, 2016,
at 0330, the channel was declared operable with reference to compensatory measures. At
this time, the Channel 1 instrument was electrically and physically disconnected, and
incapable of performing its function. A Prompt Operability Determination (POD) was initiated
in an attempt to evaluate operability based on the compensatory measures. NOP-OP-1009,
Operability Determinations and Functionality Assessments step 4.3.11 required that in the
case of PODs which have compensatory measures, the engineering director or designee
must grant concurrence. However, the duty engineering manager (directors designee)
indicated that operability could not be supported because the instrument could not meet its
surveillance requirements, and therefore, he did not provide his concurrence.
The inspectors questioned the licensees basis for operability. From discussions with the
licensee on July 1, 2016, the inspectors determined the defined compensatory measures
were not sufficient for the licensee to declare Channel 1 operable. At 1325 on July 1, 2016,
the licensee agreed with the inspectors assessment and declared Channel 1 inoperable.
At 1351 maintenance was completed on Channel 1 and the channel was restored to service.
Corrective Actions: The corrective actions included declaring channel 1 inoperable and
performing corrective maintenance on the Channel 1 instrumentation to restore it to operable.
The Licensee performed a root cause analysis and developed a case study from lessons
learned. Additionally, the licensee issued an operations standing order, performed additional
training regarding lessons learned from this event, Technical Specification compliance, and
correct application of the operability determination process.
Corrective Action Reference: The licensee documented this issue in CR 2016-08416,
Performance review of LCO 3.3.5 application during LT1525A maintenance.
Performance Assessment:
Performance Deficiency: The inspectors determined the licensees failure to implement
NOP-OP-1009 was a performance deficiency. Specifically, step 4.3.11 required that in the
case of a POD relying on compensatory measures, the engineering director or designee must
grant concurrence. However, the engineering duty manager (directors designee) stated that
operability could not be supported and that a POD could not be performed because the
instrument could not meet its surveillance requirements, and therefore did not provide his
concurrence.
Screening: The performance deficiency was determined to be more than minor because it
was associated with the Mitigating Systems cornerstone attribute of Equipment Performance
and affected the cornerstone objective of ensuring the availability, reliability, and capability of
systems that respond to initiating events to prevent undesirable consequences. Specifically,
the failure to follow procedures to establish the operability of SFAS Channel 1 negatively
affected the ability of the system to perform its accident mitigating function. Additionally, this
failure led to a violation of Technical Specifications as detailed elsewhere in this report.
Significance: The inspectors assessed the significance of the finding using IMC 0609.04,
Initial Characterization of Findings, and IMC 0609, Appendix A, Exhibit 1, Initiating Events
Screening Questions. The inspectors determined that this performance deficiency did not
cause a reactor trip and the loss of mitigation equipment relied upon to transition the plant
from the onset of the trip to a stable shutdown condition. Therefore, the inspectors
determined the finding to be of very low safety significance (Green).
Cross Cutting Aspect: This finding had a cross-cutting aspect of Consistent Process in the
area of Human Performance, which states individuals use a consistent, systematic approach
to make decision. Risk insights are incorporated as appropriate. Specifically, the licensee
continued to push forward in the POD process despite the fact that they could not meet the
requirements of the process. [H.13]
Enforcement: No violation was identified. (FIN 05000346/2018002-04: Misapplication of
the Operability Determination Process)
EXIT MEETINGS AND DEBRIEFS
The inspectors confirmed that proprietary information was controlled to protect from public
disclosure. No proprietary information was documented in this report.
On July 31, 2018, the inspectors presented the quarterly integrated inspection results to
Mr. M. Bezilla and other members of the licensee staff.
On April 13, 2018, the inspector presented the emergency preparedness program inspection
results to Mr.
- M. Bezilla, Site Vice President, and other members of the licensee staff.
DOCUMENTS REVIEWED
71111.01Adverse Weather Protection
- Davis-Besse Off-site Power Voltage Assessment; Summer 2018
- DB-OP-01300; Switchyard Management; Revision 14
- DB-OP-02546; Degraded Grid; Revision 07
- DB-OP-06311; 345 KB Switchyard No. 1 (Main) Transformer, No. 11 (Auxiliary) Transformer,
and Startup Transformer (01 and 02); Revision 48
- DB-OP-06913; Seasonal Plant Preparation Checklist; Revision 30
- DB-SC-03023; Off-site AC Sources Lined Up and Available; Revision 34
- NOBP-CC-2008; Transformer, Switchyard, and Grid Reliability Design Interface and Control;
Revision 01
- NOP-CC-3002-01; AC Power Systems Analysis; Revision 05
- NOP-OP-1003; Grid Reliability Protocol; Revision 09
71111.04Equipment Alignment
- CR-2015-00459; 2015 CDBI SA: Auxiliary Feed Pump (AFP) 1 and 2 Response Time Testing
- Davis-Besse Nuclear Power Station Lubrication Date Sheet; Decay Heat Pumps and Motors,
Auxiliary Building, 545 Level
- DB-OP-06011; High Pressure Injection System; Revision 31
- DB-OP-06012; Decay Heat Pump; Revision 71
- DB-OP-06013; Containment Spray System; Revision 26
- DB-OP-0623; Auxiliary Feedwater System; Revision 42
- DB-OP-06262; Valve Line Up Checklist for CCW Pump 2; Revision 38
- DB-SS-03090; Motor Driven Feed Pump Monthly Valve Verification; Revision 11
- M-0060; Auxiliary Feedwater System; Revision 59
- OS-003; High Pressure Injection System; Revision 36
- OS-005; Containment Spray System; Revision 14
71111.05AQFire Protection Annual/Quarterly
- PFP-AB-238; Auxiliary Feed Pump 2 Room; Revision 4
- PFP-AB-328; Protected Area Pre-Fire Plan-Component Cooling Water Heat Exchanger and
Pump Room; Revision 4
- Pre-Fire Plan; PFP-AB-115, Revision 5, ECCS Pump Room 1-2
- Pre-Fire Plan; PFP-AB-109, Revision 7, Rooms 104, 106, 106A and 109
71111.06Flood Protection Measures
- DWG E-328; Raceway & Grounding Start-Up, Main & Aux Transformers; Revision 15
- WO 200676046; Electric Hand/Manholes
71111.07Heat Sink Performance
- CR 2018-00844; CCW Hx 1-3 Pin-Hole Leak
- WO200741172 DB-SUB16-03; Component Cooling Water Heat Exchanger
71111.11Licensed Operator Requalification Program and Licensed Operator Performance
- DB-OP-06401; Integrated Control System Operating Procedure; Revision 27
- DB-OP-06902; Revision 62
- NOBP-TR-1151; 4.0 Crew Critique; 09/28/17
- NOP-OP-1002; Conduct of Operations; Revision 12
71111.12Maintenance Effectiveness
- 2017-2; Davis Besse System Health Report; Decay Heat Low Pressure Injection; 02/01/2018
- Cycle 20 Periodic Maintenance Effectiveness Assessment Report
- CR 201709888; CCW 2 Cable Testing Exceeded the Acceptance Criteria; 09/27/2017
- CR 201700704; CRD Booster Pump 1 Trip; 01/21/2017
- CR 201805257; CRD Booster Pump 2 Trip on Overload; 06/06/2018
- CR 201702171; CCW Train 3 Exceeded Maintenance Rule Unavailability Limit
- CCW System Health Report; 2017-02
71111.13Maintenance Risk Assessments and Emergent Work Control
- CA 03-05256-01; Control Room Habitability Systems Licensing Basis Validation; Attachment 2
- CR 2018-05995; UFSAR Description of CREVS and CREATCS does not Match Technical
Specifications; 06/29/2018
- Davis-Besse Unit 1 UFSAR; Revision 30
- DBBP-OPS-0011; Protected Equipment Posting; Revision 10
- DB-SS-03301; Control Room Unfiltered Air Inleakage Test for Control Room Emergency
Ventilation, Train 1; Revision 00
- Drawing 05-020 SH 1; Operational Schematic Service Water System; Revision 100
- Drawing 05-032B; Operational Schematic Control Room Emergency Ventilation System;
Revision 22
- NOP-LP-4008; Licensing Document Change Process; Revision 5
- NOP-LP-4008; Licensing Documents Change Process; Revision 1
- NOP-OP-1007; Risk Management; Revision 25
- Procedure NOP-OP-1007; Risk Management; Revision 25
71111.15Operability Determinations and Functionality Assessments
- CR 2018-04305; Y212 Fuse Blown During TD14950; 05-08/2018
- CR 2018-03174; SW277 Excessive Leakage
- CR 2018-04296; LEFM Parameter Revision Results in Changes to Indicated Loop Flows;
05/08/2018
- CR 2018-04599
- DB-PF-03020; Service Water Train 1 Valve Test; Revision 42
- DB-SC-03121; SFAS Train 2 Integrated Response Time Test; Revision 07
- WO 200676009; PF3020-033 05.000 SW276, SW277
71111.18Plant Modifications
- CR 201800027; BWST Loop Seal Pipe Elevation Discrepancy; 01/02/2018
- CR 201803211; BWST Leak Near BW33 Outside; 04/06/2018
- Engineering change package 16-0478-001, Loop Seal in BWST to SFP Purification Supply
Pipe Civil Structural
- Engineering Change Package 16-0478-002, Loop Seal in BWST to SFP Purification Supply
Pipe Piping and Mechanical
- Engineering Change Package 16-0478-003, Loop seal in BWST to SFP Purification Supply
Pipe (freeze protection)
71111.19Post Maintenance Testing
- CA 2011-02670; WO 200481565 was Initiated to Troubleshoot DH2733; 04/29/2016
- CR 2015-08968; Evaluation of Service Water Pump P3-1 Baseline Data; 07/02/2015
- CR 2018-04974; Critical Preventive Order Removed from Schedule at T-0; 05/29/2018
- DB-PF-03017; Service Water Pump 1 Testing; Revision 23
- Procedure DB-SP-03161, AFW Train 2 Level Control, Interlock, and Flow Transmitter Test,
Revision 34
- WO 200683205; Perform SW Pump 1 Quarterly Test; 05/22/2018
- WO 200683879; DH/LPI 1-1 Quarterly; 05/30/2018
- WO 200747497, AFP 2 Quarterly Test; 05/07/2018
- WO 200704976 DB-SUB049-02; Decay Heat and Low Pressure Injection; 05/31/2018
71111.22Surveillance Testing
- DB-SC-03070; Emergency Diesel Generator 1 Monthly Test; Revision 38
71114.02Alert and Notification System Testing
- Prompt Notification System Design Report; Revision 0
- NOP-LP-5005; FENOC Siren Testing and Maintenance; Revision 0
- Alert and Notification System Testing Results; 3rd Quarter 2016 through 1st Quarter 2018
- Alert and Notification Equipment Maintenance Records; 3rd Quarter 2016 through 1st
Quarter 2018
- NOP-LP-5005-05; DB Siren Maintenance Schedule (Results for 2016 and 2017)
- CR-2016-13929; Trending of Alert and Notification System (Sirens); 12/02/2016
- CR-2017-03323; Tending of Alert and Notification System (Sirens)
- CR-2017-05073; 2017 NRC Evaluated Exercise Inspection - Siren Test Documentation Issue;
05/04/2017
- CR-2017-11280; MS-C-17-11-24: Annual Siren Maintenance Issues; 11/10/2017
- CR-2017-11865; MS-C-17-11-24: Incomplete Siren Test Report Records; 12/01/2017
- CR-2017-12185; Two Siren Issues After the 12/13/2017 - 10 Second Silent Test; 12/13/2017
- CR-2018-00632; DB Sirens 504, 509, and 510 Indicated a Communication Failure; 01/24/2018
71114.03Emergency Response Organization Staffing and Augmentation System
- RA-EP-00100; Emergency Plan Training Program; Revision 21
- RA-EP-00550; computerized Automated Notification System; Revision 7
- Unannounced Augmentation Call-In Drill Results for the 3rd Quarter 2016 through the 1st
Quarter 2018
- CR-2017-06973; Several Individuals Experienced Issues Calling Into CANS during June 27th
Call-In Drill; 06/28/2017
- CR-2017-07038; Employee did not Respond for Unannounced Call-In Drill; 06/29/2017
- CR-2017-08961; Several Individuals Experienced Issues Calling Into CANS during August 30th
Call-In Drill; 8/30/2017
- CR-2017-09148; Employee Failed to Call In during ERO Call-In Drill; 09/05/2017
71114.05 Maintenance of Emergency Preparedness
- Davis-Besse Nuclear Power Station Emergency Plan; Revision 32
- Assessment of Davis-Besse Nuclear Power Station Interface with State and Local
Governments for 2016 and 2017
- Fleet Oversight Audit Report - Emergency Preparedness for 2016 and 2017
- RA-EP-01500; Davis-Besse Nuclear Power Station Emergency Plan Implementing Procedure;
Revision 16
- CR-2016-12834; EP Drill - Premature SAE Classification during October 25, 2016 Integrated
Drill; 10/27/2016
- CR-2016-12839; Initial Notification to State and County Delayed for the Site Area Emergency;
10/27/2016
- CR-2016-12823; EP Drill - RA-EP-02320 Emergency Technical Assessment, Figure 3-1 does
not Agree with DBRM-EMER-1500B Hot EAL Wallboard, Graphs F-1 and F-2, 10/27/2016
- CR-2016-12856; EP Drill - Missed Drill Objective for Health Physics Drill; 10/27/2016
- CR-2016-12885; EP Drill - Operations Support Center Controller Provided Cue Card Early for
Makeup Pump #1 Failure; 10/28/2016
- CR-2017-00484; Worsening Condition on RE1003B; 01/15/2017
- CR-2017-02014; EP Drill 2/21/17 CT9 and CT10 Potential Ambiguity; 02/23/2017
- CR-2017-02139; EP Drill 2/21/2017: Reactor Operation Considerations for Site Area and
General Emergency Classification; 02/27/2017
- CR-2017-02309; EP Drill - Incorrect Characterization of Release in Progress; 03/03/2017
- CR-2017-03299; EP Drill 3/21/17 ED Declaration Time Requirements; 03/23/2017
- CR-2017-05025; EP Exercise - RA-EP-01500, Emergency Classification, Procedure
Enhancement; 05/03/2017
- CR-2017-05029; EP Exercise - SAE Notification Timeliness, 2017 Evaluated Exercise;
05/03/2017
- CR-2017-05040; EP Exercise - Objective F.7 PAR Development Met with Comment;
05/03/2017
- CR-2017-05057; EP Drill - Mischaracterization of Release in Progress; 05/04/2017
71114.06Drill Evaluation
- CR 2018-05418; ERO Tabletop Drill Improvement Opportunities; 06/11/2018
71151Performance Indicator Verification
- Station Unit Logs
71152Problem Identification and Resolution
- CR 2018-03036; Misposition of Make Up Filer 1 Outlet Isolation (MU17); 03/31/2018
- NOBP-OP-0004; Plant Status Control and Worker Protection Events; Revision 17
- Drawing M-031C; Piping and Instrument Diagram Make Up and Purification System;
Revision 43
- Drawing M031A; Piping and Instrument Diagram Make Up and Purification System;
Revision 52
- DB-OP-06006; Makeup Filter 1 Replacement; Revision 42
71153Follow-Up of Events and Notices of Enforcement Discretion
- Station Unit Logs
- LER 2016-008-01; Application of Technical Specification for the Safety Features Actuation
System Instrumentation
- Root Cause Analysis Report; CR-2016-08419; 10/07/2016
- DB-OP-06405; Safety Features Actuation System Procedure; Revisions 13 & 14
- DB-OP-03006; Miscellaneous Instrument Shift Checks; Revisions 55 & 61
- DB-MI-03145; Functional Test/Calibration of LT-1525A BWST Level Transmitter to SFAS
Channel 1; Revisions 9 & 12
- DB-MI-03146; Functional Test/Calibration of LT-1525B BWST Level Transmitter to SFAS
Channel 2; Revisions 9 & 12
- DB-SC-03110; SFAS Channel 1 Functional Test; Revisions 20 & 22
- DB-SC-03111; SFAS Channel 2 Functional Test; Revisions 16 & 18
- NOP-OP-1002; Conduct of Operations; Revisions 11 & 12
- NOP-OP-1009; Operability Determinations and Functionality Assessments; Revisions 6 & 8
- NOBP-OP-0014; FENOC Duty Teams; Revision 2 & 5
- NOBP-OP-1002; Operations Administrative Guidelines and Common Processes; Revision 2&4
- NOBP-OP-0002; Operations Briefing and Challenge Calls; Revisions 3 & 4
- NOBP-OP-0002-05; Control Room Shift Brief Checklist
- NOBP-OP-0002-05A; Control Room Shift Brief Checklist
- NORM-OP-1002; Conduct of Operations; Revision 6
- NOP-OP-1015; Event Notifications; Revisions 3 & 6
- CR 2016-08419; Performance Review of LCO 3.3.5 application during LT1525A maintenance
- CR 2016-08699; Crew Briefing Performance Shortfall
- CR 2016-13611; Did Not Receive VP Approval Within 30 Days After CARB Approval
- CR 2016-11711; Red Key Performance Indicator D-SPO-05L - Open CRs With Extensions
- CR 2017-07598; Technical Specification Upgrade Criteria Not Accurately Communicated On
1530 Duty Team Phone Call
- CR 2016-11681; Common Cause Evaluation For DB Performance Issues
- CR 2016-10440; Red Key Performance Indicator D-SPO-05L - Open CRs With Extensions
- CR 2016-13335; Fleet Operations Elevation Letter - Regulatory Document Implementation -
Supplemental Review
- CR 2016-08700; Delayed Request For Prompt Operability Determination
- CR 2016-08402; SFAS Channel 2 +15V Power Supply Failure
- CR 2016-08765; Restoration of SFAS CH1 (LT-1525A) - Assessment Of Organizational
Response To Extended Work Window
- CR 2016-08539; A Schedule Work Not Completed By Instrument and Control Shop
- CR 2016-08922; Assessment of Schedule Adherence for Maintenance Activities
- CR 2016-08415; Parameter 5 BWST Level-Low Low Operability