IR 05000280/2006006

From kanterella
(Redirected from IR 05000281/2006006)
Jump to navigation Jump to search
IR 05000280-06-006, 05000281-06-006, on 01/13, 01/23 - 27, 02/06 -02/10/2006, Surry, Units 1 and 2, Component Design Bases Inspection
ML060670515
Person / Time
Site: Surry  
Issue date: 03/08/2006
From: Ogle C
NRC/RGN-II/DRS/EB1
To: Christian D
Virginia Electric & Power Co (VEPCO)
References
IR-06-006
Download: ML060670515 (30)


Text

March 8, 2006

SUBJECT:

SURRY POWER STATION - NRC COMPONENT DESIGN BASES INSPECTION REPORT 05000280/2006006 AND 05000281/2006006

Dear Mr. Christian:

On February 10, 2006, the U.S. Nuclear Regulatory Commission (NRC) completed an inspection at your Surry Power Station, Units 1 and 2. The enclosed inspection report documents the inspection findings which were discussed on February 9, 2006, with Mr. Jernigan and other members of your staff.

The inspection examined activities conducted under your license as they relate to safety and compliance with the Commissions rules and regulations and with the conditions of your license.

The inspectors reviewed selected procedures and records, observed activities, and interviewed personnel.

The report documents one NRC-identified finding of very low safety significance (Green). This finding was determined to involve a violation of NRC requirements. However, because of its very low safety significance and because it had been entered into your corrective action program, the NRC is treating this issue as a non-cited violation in accordance with Section VI.A.1 of the NRCs Enforcement Policy. If you deny this non-cited violation you should provide a response within 30 days of the date of this inspection report, with the basis for your denial, to the U.S. Nuclear Regulatory Commission, ATTN: Document Control Desk, Washington, D.C.

20555-0001, with copies to the Regional Administrator, Region II; the Director, Office of Enforcement, U.S. Nuclear Regulatory Commission, Washington, D.C. 20555-0001; and the NRC Resident Inspector at the Surry Power Station.

VEPCO

In accordance with 10 CFR 2.390 of the NRCs Rules of Practice, a copy of this letter, its enclosure, and your response (if any) will be available electronically for public inspection in the NRC Public Document Room or from the Publicly Available Records (PARS) component of NRCs document system (ADAMS). ADAMS is accessible from the NRC Web site at http://www.nrc.gov/reading-rm/adams.html (the Public Electronic Reading Room).

Sincerely,

\\\\RA\\\\

Charles R. Ogle, Chief Engineering Branch 1 Division of Reactor Safety Docket Nos.: 50-280, 50-281 License Nos.: DPR-32, DPR-37

Enclosure:

NRC Inspection Report 05000280/2006006 and 05000281/2006006 w/Attachment: Supplemental Information

VEPCO

REGION II==

Docket Nos.: 50-280, 50-281 License Nos.: DPR-32, DPR-37 Report Nos.:

05000280/2006006, 05000281/2006006 Licensee:

Virginia Electric and Power Company (VEPCO)

Facility:

Surry Power Station, Units 1 & 2 Location:

5850 Hog Island Road Surry, VA 23883 Dates:

January 9 - February 10, 2006 Inspectors:

R. Moore, Lead Inspector J. Leivo, Contractor C. Peabody, Reactor Inspector/ NSPDP B. Holland, Reactor Inspector D. Mas-Penaranda, Reactor Inspector H. Anderson, Contractor Approved by: Charles R. Ogle, Chief Engineering Branch 1 Division of Reactor Safety

Enclosure

SUMMARY OF FINDINGS

IR 05000280/2006006, 05000281/2006006; 01/09/2006 - 01/13/2006, 01/23/2006 - 01/27/2006, 02/06/2006 - 02/10/2006; Surry Power Station, Units 1 & 2; Component Design Bases Inspection.

This inspection was conducted by a team of four NRC inspectors from the Region II office and two NRC contract inspectors. One Green finding, which was a non-cited violation, was identified during this inspection. The significance of most findings is indicated by their color (Green, White, Yellow, Red) using IMC 0609, Significance Determination Process (SDP).

Findings for which the SDP does not apply may be Green or be assigned a severity level after NRC management review. The NRCs program for overseeing the safe operation of commercial nuclear power reactors is described in NUREG-1649, Reactor Oversight Process,

Revision 3, dated July 2000.

NRC-Identified and Self-Revealing Findings

Cornerstone: Mitigating Systems

Green.

The team identified a Green, non-cited violation (NCV) of Technical Specification 6.4.A.3, Unit Operating Procedures and Programs, for a non-conservative emergency contingency action (ECA) procedure setpoint regarding low RWST level.

Specifically, the licensee failed to adequately address the potential for vortexing at low RWST levels into the determination of the RWST level for operator action to secure LHSI and HHSI pumps drawing suction from the RWST, in Procedures 1,2-ECA-1.1,

Loss of Emergency Coolant Recirculation, Rev. 23. When the NRC notified the licensee of this condition, the licensee entered it into the corrective action program, and proceeded to revise the ECA setpoint in the affected procedures.

This finding is greater than minor because it is associated with the procedure quality attribute of the Mitigating Systems cornerstone and affected the cornerstone objective of ensuring reliable, available, and capable systems that respond to initiating events to prevent undesirable consequences. This finding is of very low safety significance because no loss of safety function occurred and operators have been trained to identify loss of pump suction. This finding has been entered into the licensees corrective action program as PI S-2006-0334. (Section 1R21.3 )

Licensee-Identified Violations

None

REPORT DETAILS

REACTOR SAFETY

Cornerstones: Mitigating Systems and Barrier Integrity

1R21 Component Design Bases Inspection

.1 Inspection Sample Selection Process

The team selected risk significant components and operator actions for review using information contained in the licensees Probabilistic Risk Assessment (PRA). In general this included components and operator actions that had a risk achievement worth factor greater than two or Birnbaum value greater than 1E-6. The components selected were located within the safety injection, safety-related ventilation, and vital electrical distribution systems, as well as components required for reduced reactor coolant system inventory operations during shutdown, and switchyard components needed for recovery from a loss of offsite power condition. The sample selection included 18 components, five operator actions, and six operating experience items. Additionally, the team reviewed two modifications by performing activities identified in IP 71111.17, Permanent Plant Modifications, Section 02.02.a. and IP 71111.02, Evaluations of Changes, Tests, or Experiments.

The team performed a margin assessment and detailed review of the selected risk-significant components to verify that the design bases have been correctly implemented and maintained. This design margin assessment considered original design issues, margin reductions due to modification, or margin reductions identified as a result of material condition issues. In addition, the licensees Design Margin Issues List was used to provide additional insights into identifying low margin equipment. Equipment reliability issues were also considered in the selection of components for detailed review. These included items such as failed performance test results, significant corrective action, repeated maintenance, Maintenance Rule (a)1 status, GL 91-18 conditions, NRC resident inspector input of problem equipment, system health reports, industry operating experience and licensee problem equipment lists. Consideration was also given to the uniqueness and complexity of the design, operating experience, and the available defense in depth margins. An overall summary of the reviews performed and the specific inspection findings identified are included in the following sections of the report. A specific list of documents reviewed is included in the attachment to this report.

.2 Results of Detailed Reviews

.2.1 Detailed Component and System Reviews

.2.1.1 Residual Heat Removal (RHR) Pumps - Shutdown Operations

a. Inspection Scope

The team reviewed the Updated Final Safety Analysis Report (UFSAR), Technical Specifications (TS), Design Basis Document (DBD) and supporting calculations, pump procurement specifications, manufacturer pump test curves and piping drawings to identify the RHR pumps design bases for shutdown operations. This included review of measures to assure adequate net positive suction head (NPSH) and to prevent potential vortex formation for the RHR pumps in a reduced reactor coolant system (RCS)inventory condition, and associated operating procedures. Testing, maintenance, and corrective action documentation were reviewed to assess the performance capability of the RHR pumps operation for reactor coolant system (RCS) reduced inventory conditions.

b. Findings

No findings of significance were identified.

.2.1.2 Low Head Safety Injection (LHSI) Containment Sump Suction

a. Inspection Scope

This component group included the motor operated valves (MOVs), 1/2-SI-MOV-1860A/B; check valves, 1/2-SI-47 and 1/2-SI-56; and piping between the containment sump and the LHSI pumps. The team reviewed MOV calculations and test documentation to verify that design basis accident conditions and allowable degraded voltage conditions were incorporated into motor actuator setpoint determinations. Motor sizing and valve performance was verified for anticipated operating conditions. Thermal overload (TOL) calculations and installation work orders were reviewed to verify installed TOLs were correctly sized. Maintenance history, Plant Issue Reports (PIs), foreign material exclusion (FME) controls and design changes were reviewed to assess the potential for flowpath obstruction and material degradation. Maintenance history was reviewed to verify that check valves were periodically tested and inspected.

b. Findings

No findings of significance were identified.

.2.1.3 LHSI Pumps/Motors

a. Inspection Scope

The team reviewed the design basis and testing documentation to identify and verify implementation of design requirements related to flow, developed head, NPSH, vortex formation, minimum flow and runout protection, and motor sizing requirements for all LHSI operating conditions. Design calculations and periodic test documentation and results were reviewed to verify that LHSI pump 1-SI-P-1A design and licensing performance requirements were met for the various operating configurations, including the high pressure recirculation (piggyback) configuration in which the LHSI pumps provide flow to the suction of the HHSI pumps. Maintenance, in-service testing (IST),corrective action, and design change history were reviewed to assess potential component degradation and impact on design margins or performance.

Pump motor assessment included review of the adequacy of the available power supply under worst case conditions, pump motor brake horse power (BHP) for anticipated loading, as well as the testing, setting, and coordination of overcurrent protective relays.

The team verified the pump installation and periodic maintenance were consistent with vendor recommendations and that the pump start logic was consistent with design assumptions and appropriately tested.

b. Findings

No findings of significance were identified.

.2.1.4 High Head Safety Injection (HHSI) Pumps/Motors

a. Inspection Scope

The team reviewed the design basis documentation to identify design requirements related to flow, developed head, NPSH, vortex formation, minimum flow and runout protection and motor sizing for all HHSI pump operating conditions and configurations.

Design calculations and in-service and periodic test documentation and results for HHSI pump 1-CH-P-1B were reviewed to verify that all design performance requirements were met. Maintenance, in-service testing (IST), corrective action, and design change history were reviewed to assess the potential for component degradation and impact on design margins or performance. The team reviewed the installed charging pump flow instrumentation design, installation configuration, and calibration documentation to verify the adequacy of flow measurement used for American Society of Mechanical Engineering (ASME)Section XI testing and design flow verification.

Pump motor assessment included review of the adequacy of the available power supply under worst case conditions, pump motor brake horse power (BHP) for anticipated loading, as well as the testing, setting, and coordination of overcurrent protective relays.

The team also reviewed the HHSI pump control circuit configurations for potential vulnerability to common cause failures that might be introduced by interfaces with non safety-related control circuits, including a visual inspection of the internal wiring of the auxiliary relay racks.

b. Findings

No findings of significance were identified.

.2.1.5 High Pressure Recirculation Function MOVs (Piggyback mode)

a. Inspection Scope

The team reviewed the MOV calculations for LHSI discharge to HHSI suction valves 1/2-SI-MOV-1863A/B to verify that appropriate design basis event conditions and degraded voltage conditions were used as inputs into the determination of motor actuator setpoints and sizing. Testing results were reviewed to verify valve performance was monitored and performance degradation would be identified. Calculations for TOL sizing and installation work orders were reviewed to verify appropriate TOLs were installed. The team reviewed the MOV control logic drawings and logic testing to verify that the interlock and permissive circuits satisfied requirements for redundancy and independence; the circuits included no undetectable failure vulnerability having significant consequences; and appropriate testing overlap was incorporated.

b. Findings

No findings of significance were identified.

.2.1.6 Control Room and Switchgear Ventilation Chillers

a. Inspection Scope

The team reviewed chiller specifications, vendor technical manuals, documentation of chiller condenser service water pump 1-VS-P-1A and chilled water pump 1-VS-P-2A in-service testing, system performance analyses, and maintenance of chiller equipment to verify this equipment was capable of removing design heat loads for the control room and emergency switchgear equipment spaces. This included service water flow to the chiller condensers, chilled water flow to the air handling units (AHUs), unit fan capacity, and chiller performance testing. Additionally, chiller design changes, maintenance, and corrective action histories were reviewed to assess potential degradation of design margin or performance capability. This included the potential impact on electrical loading and system protective features due to the installation of additional chiller units.

The team reviewed the potential for common cause failure mechanisms associated with loss of chilled water or service water flow including rotating strainer, Y-strainer, and other potential flow path blockage or degradation.

b. Findings

No findings of significance were identified.

.2.1.7 HHSI Pump Cooling Components

a. Inspection Scope

This component group included the HHSI (charging) pump service water duplex strainers, 1/2-SW-S-2A/B; charging pump service water pumps, 1/2-SW-P-10A/B; and piping to provide cooling for the charging pumps lube oil coolers and intermediate seal coolers. The charging pump service water duplex strainer clearance sizing and minimum downstream flow restrictions were reviewed to assess the potential for common cause failure of HHSI pumps due to flow path obstruction. Charging pump service water pump 1-SW-P-10A capacity, required and available NPSH, and flow/developed head requirements were reviewed to verify flow capability was consistent with design requirements for the charging pump lube oil and intermediate seal coolers heat removal. In-service and periodic testing results for 1-SW-P-10A, maintenance history, and corrective actions were reviewed to assess potential degradation of performance or design margin of cooling components. The design, installed configuration, and calibration of flow instrumentation were reviewed to verify the accuracy of cooling flow measurement. The team reviewed the sizing, start logic, environmental qualification, and installation of the 1-SW-P-10A/10B pump motors to verify the adequacy of the pump motors to support the charging pump cooling requirements.

b. Findings

No findings of significance were identified.

.2.1.8 Refueling Water Storage Tank (RWST)

a. Inspection Scope

The team reviewed the design basis information and supporting calculations and drawings to identify and verify the design assumptions regarding levels and contained volumes of water within the RWST. These design assumptions were related to the LHSI and HHSI pumps taking suction from the RWST and included available NPSH, vortexing potential, and minimum and maximum flow rates. Additionally, the volume of the RWST tank contents transferred to the containment sump was reviewed to verify adequate NPSH was available prior to a switchover from injection to recirculation mode. The team reviewed documentation of the seismic qualification of RWST attached return piping from the low head safety injection pump recirculation line to the RWST through lines 2"-

CH-212-152 and 6"-CS-14-152. The team reviewed RWST vent design to verify that adequate measures were implemented to assure the tank vent remains open and functional. The potential for air voids and the adequacy of measures to prevent air voids in the normally isolated RWST unit cross-connect piping to the suction of the HHSI pumps were reviewed.

The team reviewed RWST level instrument scaling and uncertainty calculations to verify the margins in the automatic and operator action setpoints associated with RWST level included allowance for instrument uncertainty. This included review of the loop diagrams, elementary diagrams, schematic diagrams, and logic test procedures to verify the independence and adequacy of testing of the redundant logic circuits. Calibration and test results were reviewed to verify that instrument performance degradation would be identified. The team visually inspected the level transmitter configurations and outdoor enclosures, to assess observable material condition, vulnerability to hazards, and the potential for environmental impact on instrument reliability and performance.

b. Findings

No findings of significance were identified.

.2.1.9 LHSI Suction MOV from RWST

a. Inspection Scope

The team reviewed MOV calculations for the LHSI pump RWST suction valves 1/2-SI-MOV-1862(2862) A/B to verify that accident pressure and degraded voltage were used as design input for motor actuator setpoint determinations, motor sizing, and MOV testing acceptance criteria. Test results, maintenance, and corrective action histories were reviewed to verify that performance or margin degradation was identified and addressed. Sizing of thermal overloads was reviewed to verify that adequate motor thermal overload protection was provided.

.

b. Findings

No findings of significance were identified.

.2.1.1 0 Pressurizer Power Operated Relief Valves (PORV) Air Supply

a. Inspection Scope

The team reviewed the adequacy and availability of the backup air supply for the pressurizer PORVs. This included sizing of the backup air accumulators and pressure regulating setpoints to verify the availability of backup air at adequate volumes and pressures to provide the capability to cycle each PORV consistent with the accident analysis assumptions. This review included design basis sizing calculations, accumulator drawings, and accident analysis assumptions for PORV cycling.

b. Findings

No findings of significance were identified.

.2.1.1 1 LHSI Discharge Check Valves

a. Inspection Scope

The team reviewed the design, installed orientation, and the licensees actions to monitor potential degradation of LHSI pump discharge check valves, 1/2-SI-50 and 1/2-SI-58. This included periodic internal inspections and in-service flow testing to demonstrate full open and closure. Maintenance and corrective action history, test results, FME controls, and design changes were reviewed to assess the potential for material degradation and the licensees capability to identify degradation.

b. Findings

No findings of significance were identified.

.2.1.1 2 Reactor Vessel Level Indication - Reduced Inventory Operations

a. Inspection Scope

The team reviewed the two independent methods, which included a standpipe and an ultrasonic level measuring device, used to monitor reactor vessel level when the RCS is in a reduced inventory condition. The review was to verify the adequacy of margins associated with the reactor vessel low level setpoint alarms and input to RHR pumps NPSH and vortex analyses and included instrumentation design, uncertainty calculations, and operating procedures. The team also reviewed testing, calibration, maintenance, and corrective action history, to verify that equipment accuracy and reliability were being maintained.

b. Findings

No findings of significance were identified.

.2.1.1 3 Upper Canal Level Instrumentation

a. Inspection Scope

The team reviewed the level instrumentation for its capability to provide sufficiently accurate indication of the upper canal water level and reviewed the capability of the control circuits to provide a close signal to the circulating water isolation MOVs when required. This included verifying that the initiation setpoint was consistent with the design basis assumptions for isolating circulating water and that the control and indication circuit design incorporated appropriate single failure and independence criteria. Additionally, the team reviewed the installed instrumentation configuration to verify the adequacy of environmental protections, to verify that installation was consistent with the manufacturers recommendations, and to observe the material conditions. The calibration documentation and corrective action history were reviewed to verify the instrumentation accuracy was monitored and maintained.

b. Findings

No findings of significance were identified.

.2.1.1 4 Emergency Diesel Generators (EDG) Start Logic and Circuits

a. Inspection Scope

The team reviewed the design of the EDG start circuit, to verify its capability to actuate the air start motors and start the diesels within the ten-second time period required by TS. Additionally, the team reviewed the identification and resolution of recent EDG start circuit problems and the potential impact on design assumptions regarding EDG start time. Industry experience on air start components was reviewed to determine applicability to Surry equipment. The team reviewed the testing, detectability of device failures, potential for test preconditioning, validity of test acceptance criteria, and results of past testing to verify the capability to monitor start system performance and identify degradation.

b. Findings

No findings of significance were identified.

.2.1.1 5 Volume Control Tanks (VCT) Level Indication

a. Inspection Scope

The team reviewed the instrumentation design and the design basis for establishing the setpoint for an automatic switchover from the VCT to the RWST for the charging pump suction, to assure that the design adequately addressed charging pump NPSH and vortex considerations. The team reviewed detailed drawings to verify calibration and setpoint calculation assumptions. The team reviewed the logic functional testing for the switchover, and reviewed test results to verify appropriate overlap testing of the instrument loop. A field inspection of the installed instrumentation was performed to assess observable material condition, instrument impulse line slopes, and vulnerability to hazards such as flooding and missiles. The calibration results were reviewed to verify setpoint accuracy was maintained.

b. Findings

No findings of significance were identified.

.2.1.1 6 Degraded Voltage Relays (27 relays)

a. Inspection Scope

The team reviewed the uncertainty calculation for the relays as well as the calibration procedures and results to verify that the licensee had appropriately accounted for uncertainties in the degraded voltage protection circuits. The team reviewed the licensees analyses to verify the TS allowed 88 percent of 4160 volts alternating current (VAC) bus relay setting resulted in no adverse impact on equipment operation. This review was to verify that under degraded voltage conditions at the 4160 VAC bus, motor terminal voltages were greater than or equal to 90 percent of motor rated voltages; MOV pickup voltage conditions were adequate; MOVs could develop the required torque; and the emergency bus minimum voltage was greater than the degraded relay reset value.

The last three calibrations of the vital 4160 VAC H bus degraded voltage relays were reviewed to assess performance history and to verify that the calibration and measuring and test equipment (M&TE) tolerances were consistent with the uncertainty calculation assumptions. Also, the team performed and independent voltage drop calculation from the 1H1-2 Motor Control Center to MOV 1-SI-MOV-1863A, to assess the adequacy of the licensees voltage drop calculation.

b. Findings

No findings of significance were identified.

.2.1.1 7 Switchyard Control Power - Restoration of Off Site Power

a. Inspection Scope

The team reviewed the design and installation of the battery which provided control power for operation of the switchyard breakers and disconnects needed to restore offsite power following a loss of off site power. The stations four-hour coping period licensing commitment was the basis for assessing the switch yard battery load profile.

The team performed a field review to assess observable material conditions and verify field conditions were consistent with equipment manufacturers recommendations for the switchyard batteries. Testing and periodic maintenance were reviewed to assess the licensee actions to monitor equipment degradation

b. Findings

No findings of significance were identified.

.2.1.1 8 Safety-Related Instrument Bus - Inverters and Chargers

a. Inspection Scope

The team reviewed the design basis and equipment capability for the 120 VAC safety related instrument bus inverters and chargers, which provide the licensees uninterruptible power supply (UPS) associated with each instrument bus. The team verified the isolation of safety-related circuits from non safety-related circuits, reviewed the adequacy of equipment performance testing and maintenance, and assessed potential common cause failure mechanisms. System related PIs were reviewed to assess the recent performance history of the equipment. The team also reviewed the voltage drop to the RWST unit cross-connect valve pilot solenoids, which are served from the 120 VAC instrument bus, to verify that adequate voltage would be available at the terminals of the solenoids under design basis conditions.

b. Findings

No findings of significance were identified.

.3 Review of Low Margin Operator Actions

a. Inspection Scope

The team performed a margin assessment and detailed review of a sample of risk significant, time critical operator actions. Where possible, margins were determined by the review of the assumed design basis and UFSAR response times and performance times documented by job performance measures (JPM) results. For the selected components and operator actions, the team performed a walk through of associated Emergency Procedures (EPs), Abnormal Procedures (APs), Annunciator Response Procedures (ARPs), and other operations procedures with an appropriate plant operator to assess operator knowledge level, adequacy of procedures, and availability of special equipment when required. The following operator actions were reviewed:

  • Operator actions in response to a loss of all AC power
  • Operator actions in response to a small break loss of coolant accident (SBLOCA) - Transfer to recirculation and post-LOCA cooldown
  • Operator actions required for Unit(s) 1 / 2 cross-connects for:

Unit 1 and Unit 2 RWSTs Unit 1 and Unit 2 cross-plant charging capability Unit 1 and Unit 2 cross-plant auxiliary feedwater supply

  • Operator actions in response to inadequate core cooling
  • Operator actions in response to recovery from a loss of emergency coolant recirculation

b. Findings

Introduction:

The team identified a Green, non-cited violation (NCV) of TS 6.4.A.3, Unit Operating Procedures and Programs, for a non-conservative emergency contingency action (ECA) procedure setpoint regarding low RWST level. Specifically, the licensee failed to adequately address the potential for vortexing at low RWST levels into the determination of the RWST level for operator action to secure LHSI and HHSI pumps drawing suction from the RWST, in Procedures 1,2-ECA-1.1, Loss of Emergency Coolant Recirculation, Rev. 23.

Description:

Appropriate instructions were not provided in Procedures 1,2-ECA 1.1 Rev.

23, for operator actions to secure the LHSI and HHSI pumps suction from the RWST on low level. In particular, the stated setpoint for operator actions at 3 percent level would not preclude damage or degradation to these pumps due to vortex formation in the RWST in all cases.

The procedures instruct control room operators to secure the pumps when RWST level falls to 3 percent. However, subsequent steps in the procedures specify using the pumps again after an adequate suction source is recovered. The inspectors were concerned that if the pumps were damaged or degraded due to vortexing at low-levels in the RWST, that the pumps may not be able to subsequently perform their safety function.

Licensee Calculation CME 98-011, Rev. 1, RWST Incipient Vapor Entrainment and Vortex Concerns during SI RMT Switchover and CS Pump Operation, Surry Power Station - Units 1 & 2, dated March 2, 1998, determined that the onset of vortexing would occur at 3.4 per cent RWST level. In addition, licensee calculation EE-0112, Rev. 1, RWST Level Uncertainty, dated June 8, 1995, determined that the uncertainty associated with the level instrumentation was 2.6 per cent. Thus, to ensure appropriate protection from vortexing, the inspectors concluded that the procedural guidance should have specified securing the pumps at an RWST level greater than the specified 3 percent.

The licensee verified that the 3 percent RWST level setpoint in Procedures 1,2-ECA-1.1 was not conservative. The licensee issued Plant Issue S-2006-0334 to document the deficiency and prepared procedure changes to secure any operating LHSI and HHSI pumps at a more conservative ECA setpoint of 6 percent. Additionally, a standing order to notify operators of this condition was established as an interim compensatory measure until the procedures were revised.

Analysis:

Failing to provide adequate procedure guidance to preclude damage or degradation to the LHSI and HHSI pumps on loss of RWST level in Procedures 1,2-ECA-1.1 Rev. 23, is a performance deficiency. This finding is greater than minor because it is related to the procedure quality attribute of the Mitigating Systems cornerstone and affects the objective of ensuring the availability, reliability, and capability of systems that respond to initiating events to prevent undesirable consequences. This finding is of very low safety significance because although the HHSI and LHSI pumps could be degraded or damaged, the actual safety system function is not lost due to the availability of a standby HHSI pump and the tolerance of LHSI pumps to short term cavitation. Additionally, the procedures caution the operators to monitor pump parameters for indication of suction loss and the operators receive training on this phenomenon.

Enforcement:

TS 6.4.A.3. states that detailed written procedures with appropriate checkoff lists and instructions shall be provided for actions to be taken for specific and foreseen malfunctions of systems or components. Procedures 1,2-ECA-1.1 were written, in part, to fulfill this requirement. Contrary to TS 6.4.A.3, appropriate instructions were not provided in procedures 1,2-ECA 1.1, Loss of Emergency Coolant Recirculation, Rev. 23, for operator actions to secure LHSI and HHSI pumps at a level in the RWST that would preclude pump damage or degradation due to vortex formation in the RWST. This incorrect procedure setpoint was established in 1,2-ECA 1.1, Rev 1A, dated December 29, 1989, and was in effect until identified by the NRC inspectors in January 2006. Because of the licensee actions to revise this procedure setpoint and enter this item into the station corrective action program (PI S-2006-0334), this violation is identified as a non-cited violation (NCV) consistent with Section VI.A of the NRC Enforcement Policy, and is identified as NCV 05000280/2006006-01, Non-Conservative ECA Procedure Setpoint for Operator Action to Secure LHSI and HHSI Pumps on Low RWST Level.

.4 Review of Industry Operating Experience

a. Inspection Scope

The team reviewed selected operating experience issues that had occurred at domestic and foreign nuclear facilities for applicability at Surry. The team performed an independent applicability review, and issues that appeared to be applicable to Surry were selected for a detailed review. The issues that received a detailed review by the team included:

  • AOV Motive Power Potential Problems including PORV Accumulator Capacity Calculations at Diablo Canyon, dated 12/20/05, and NRC Information Notice 02-29, Recent Design Problems in Safety Function of Pneumatic Air Systems
  • Potential for Gas Binding for HHSI Pumps including the Diablo Canyon ECCS Cross Over Pipe Voiding When Swapping Charging Pumps, dated 10/21/04, and NRC Information Notice 88-23, Supplements 1 - 5, Potential for Gas Binding of High Pressure Safety Injection Pumps During a Loss-of-Coolant Accident.
  • Westinghouse Motor Reverse Starter Failures at Cooper, dated 9/23/05.

b. Findings

No findings of significance were identified.

.5 Review of Permanent Plant Modifications

a. Inspection Scope

The team reviewed two modifications related to the selected risk significant components in detail to verify that the design bases, licensing bases, and performance capability of the components have not been degraded through modifications. The adequacy of design and post-modification testing of these modifications was reviewed by performing activities identified in IP 71111.17, Permanent Plant Modifications, Section 02.02.a.

Additionally, the team reviewed the modifications in accordance IP 71111.02, Evaluations of Changes, Tests, or Experiments, to verify the licensee had appropriately evaluated the 10 CFR 50.59 applicability. The following modifications were reviewed:

DCP 02-060, Installation of Replacement Charging Pump 1-CH-P1B DCP 04-055, Charging System Header Isolation MOV Replacement

b. Findings

No findings of significance were identified.

OTHER ACTIVITIES

4AO6 Meetings, Including Exit

Exit Meeting Summary

On February 9, 2006, the team presented the inspection results to Mr. D. Jernigan, Site Vice President, and other members of the licensee staff. The team returned all proprietary information examined to the licensee. No proprietary information is documented in the report.

SUPPLEMENTAL INFORMATION

KEY POINTS OF CONTACT

Licensee:

M. Crist, Nuclear Operations Manager
B. Garber, Licensing Supervisor
J. Hartka, Operations Unit Supervisor
T. Huber, Nuclear Engineering Manager
D. Ingell, Mechanical Design Engineer
D. Jernigan, Site Vice President
L. Kolonay, I&C Engineer
W. Oppenhimer, Assistant Engineering Manager
R. Simmons, Outage & Planning Manager
B. Sloan, Auxiliary Systems Engineering Supervisor
J. Wronewicz, Site Engineering director

NRC

D. Arnett, Resident Inspector
N. Garrett, Senior Resident Inspector
C. Ogle, Chief, RII, Engineering Branch 1

ITEMS OPENED, CLOSED, AND DISCUSSED

Open/Closed NCV

05000280,281/2006006-01 NCV Non-Conservative ECA Procedure Setpoint for Operator Action to Secure LHSI and HHSI Pumps on Low RWST Level (Section 1R21.3)

DOCUMENTS REVIEWED