Information Notice 2005-23, Vibration-Induced Degradation of Butterfly Valves

From kanterella
(Redirected from Information Notice 2005-23)
Jump to navigation Jump to search
Vibration-Induced Degradation of Butterfly Valves
ML051740299
Person / Time
Site: San Onofre Southern California Edison icon.png
Issue date: 08/01/2005
From: Hiland P
NRC/NRR/DIPM/IROB
To:
Schmitt R, DIPM/IROB, 301-415-2297
References
IN-05-023
Download: ML051740299 (5)


UNITED STATES

NUCLEAR REGULATORY COMMISSION

OFFICE OF NUCLEAR REACTOR REGULATION

WASHINGTON, D.C. 20555-0001

August 1, 2005

INFORMATION NOTICE 2005-23:

VIBRATION-INDUCED DEGRADATION OF

BUTTERFLY VALVES

ADDRESSEES

All holders for operating licenses for nuclear power reactors except those who have

permanently ceased operation and have certified that fuel has been permanently removed from

the vessel.

PURPOSE

The U.S. Nuclear Regulatory Commission (NRC) is issuing this information notice to alert

addressees to the degradation of butterfly valves supplied by Fisher Controls and other

manufacturers. It is expected that recipients will review the information for applicability to their

facilities and consider actions, as appropriate, to avoid similar problems. However, suggestions

contained in this information notice are not NRC requirements; therefore, no specific action or

written response is required.

DESCRIPTION OF CIRCUMSTANCES

On February 10, 2005, Southern California Edison declared component cooling water (CCW)

outlet isolation valve 2HV6500 for the Train B shutdown cooling (SDC) heat exchanger in Unit 2 at the San Onofre Nuclear Generating Station (SONGS) inoperable in response to an abnormal

reduction in flow through the valve. Valve 2HV6500 is an 18-inch butterfly valve manufactured

by Fisher Controls. The operability of the containment spray (CS) system at SONGS Unit 2 depends on the availability of the SDC heat exchanger. Therefore, the licensee started a

manual shutdown of SONGS Unit 2 on February 14, 2005, to repair the valve.

The licensee disassembled the valve and found that it could not fully open as a result of losing

two taper pins that connect the valve disc to the valve stem. During the original installation, the

taper pins are impact-driven into holes in the valve disc and stem and are intended to be held in

place by the interference fit. The licensee could not determine the exact cause of the loss of

the taper pins during plant operation. As corrective action, the licensee installed new taper pins

and staked the pins to the valve disc to make them more secure.

Since 1993, five Fisher Controls 28-inch butterfly valves in the CCW systems of SONGS

Units 2 and 3 have lost one of the taper pins used to connect the valve disc to the valve stem.

The licensee has also found additional Fisher Controls butterfly valves with improperly seated

taper pins during internal inspections.

The design of the Fisher Controls butterfly valves can allow leakage through the valve if a taper

pin is lost. For example, SONGS experienced leakage rates of approximately 50 gallons per

minute (gpm) through 28-inch Fisher Controls butterfly valves in the CCW system in 1998 and

2004. After disassembling the butterfly valves, the licensee identified the cause of the leakage

as the loss of a single taper pin in each of the valves.

Taper pins that come loose from butterfly valves can be carried with the system fluid and

interfere with the operation of other plant equipment. For example, one of the missing taper

pins from 2HV6500 at SONGS Unit 2 became lodged in train B CCW pump manual discharge

isolation valve 2HCV6509, which is normally locked open and closed only for maintenance

purposes. After maintenance on the train B CCW pump, the licensee had difficulty opening

2HCV6509 because of the taper pin lodged in the valve.

The licensee plans to review all butterfly valves in safety-related applications where loss of

valve function or leakage because of a missing taper pin cannot be tolerated. On the basis of

the review, the licensee will determine which butterfly valves to inspect during the upcoming

refueling outages at SONGS Units 2 and 3. As part of the valve inspections, the licensee will

stake the taper pins in the butterfly valves to ensure the pins remain in place during plant

operation.

DISCUSSION

Over the years, nuclear power plants have experienced vibration-induced degradation of plant

equipment during operation at the original licensed power and under power uprate conditions.

The NRC has issued several information notices on vibration-induced degradation of plant

equipment. For example, the NRC issued Information Notice (IN) No. 83-70, Vibration-Induced

Valve Failures, on October 25, 1983, to alert nuclear power plant licensees to valve failures

and system inoperability as a result of normal operational vibration.

The degradation of Fisher Controls butterfly valves as a result of the loss of their taper pins at

SONGS Units 2 and 3 is another example of vibration-induced degradation during plant

operations. There have also been problems with the taper pins that connect the valve disc to

the stem in butterfly valves supplied by other manufacturers. In 1989 Turkey Point Nuclear

Plant, Unit 4, lost taper pins in a 36-inch intake cooling water head isolation butterfly valve

manufactured by the Henry Pratt Company. In 2003 Davis-Besse Nuclear Power Station, Unit 1, lost taper pins in a 10-inch decay heat cooler butterfly valve with the brand name Valtek

marketed by the Flowserve Corporation. Depending on the valve design, the loss of a taper pin from a butterfly valve may result in

significant leakage through the valve before interfering with valve operation. The size of the

taper pin and fluid conditions can cause the leakage limits for the applicable plant system to be

exceeded. In addition, leakage through a valve can be masked by another closed valve in the

system until the second valve is opened.

Taper pins that come loose from butterfly valves can be carried with the system fluid and

interfere with the operation of other plant equipment. The example of 2HCV6509 at SONGS

Unit 2 had low safety significance because this valve is only used for maintenance at the plant.

Some nuclear power plants have experienced more severe vibration-induced degradation of

equipment under power uprate conditions. For example, the NRC staff described vibration- induced degradation of plant equipment during power uprate operation in IN 2002-26, Supplement 2, Additional Flow-Induced Vibration Failures After a Recent Power Uprate

(January 9, 2004). Increased steam and feedwater flow during power uprate operation can

increase vibration of plant equipment, including valves and valve actuators. The higher

vibration levels can impact the appropriate inspection intervals for some plant components.

In summary, degradation of butterfly valves supplied by Fisher Controls and other

manufacturers has occurred during plant operation as a result of the loss of taper pins used to

connect the valve disc to stem. The degradation can involve leakage and affect valve

operation. Taper pins lost from butterfly valves can also interfere with the operation of other

plant components in fluid systems. The cause of the loss of valve taper pins is not known for

certain, but operating experience suggests that the most likely cause is vibration-induced

degradation. Staking the taper pins after their installation in the butterfly valves is one method

of providing a more secure interference fit of the pins. The increased steam and feedwater flow

during power uprate operation can accelerate vibration-induced degradation of plant equipment, including valves and valve actuators.

RELATED GENERIC COMMUNICATIONS

NRC Information Notice 83-70, Vibration-Induced Valve Failures, October 25, 1983.

NRC Information Notice 2002-26, Supplement 2, Additional Flow-Induced Vibration Failures

After a Recent Power Uprate, January 9, 2004.

This information notice requires no specific action or written response. However, recipients are

reminded that they are required by 10 CFR 50.65 to consider industry-wide operating

experience (including information presented in NRC information notices) where practical, when

setting goals and performing periodic evaluations.

CONTACT

Please direct any questions about this matter to the technical contact(s) listed below or the

appropriate Office of Nuclear Reactor Regulation (NRR) project manager.

/D.C. Trimble for/

Patrick L. Hiland, Chief

Reactor Operations Branch

Division of Inspection Program Management

Office of Nuclear Reactor Regulation

Technical contacts:

Thomas G. Scarbrough, NRR

Mark A. Sitek, Region IV

(301) 415-2794

(949) 492-2641 E-mail: tgs@nrc.gov

E-mail: mas3@nrc.gov

Ronald V. Schmitt, NRR

(301) 415-4082 E-mail: rvs@nrc.gov

Note: NRC generic communications may be found on the NRC public Website, http://www.nrc.gov, under Electronic Reading Room/Document Collections.

ML051740299 OFFICE EMEB:DE

Tech Editor

Region IV

A:SC:EMEB:DE

NAME

TGScarbrough

PKleene

MASitek (by e-mail)

RLKaras

DATE

07/13/2005

06/24/2005

07/142005

07/13/2005 OFFICE OES:IROB:DIPM

TL:C:IROB:DIPM

SC:OES:IROB:DIPM

C:IROB:DIPM

NAME

RVSchmitt

EJBenner

MJRoss-Lee

PLHiland (DTrimble

for)

DATE

/ /2005

/ /2005

08/01/2005

08/01/2005