IR 05000263/2024402

From kanterella
Jump to navigation Jump to search
– Security Baseline Inspection Report 05000263/2024402; Independent Spent Fuel Storage Installation Security Inspection Report 07200058/2024401
ML24340A142
Person / Time
Site: Monticello 
Issue date: 12/06/2024
From: Michael Ziolkowski
NRC/RGN-III
To: Hafen S
Northern States Power Co
References
IR 2024401
Download: ML24340A142 (1)


Text

SUBJECT:

MONTICELLO NUCLEAR GENERATING PLANT - SECURITY BASELINE INSPECTION REPORT 05000263/2024402; INDEPENDENT SPENT FUEL STORAGE INSTALLATION SECURITY INSPECTION REPORT 07200058/2024401

Dear Shawn Hafen:

On October 24, 2024, the U.S. Nuclear Regulatory Commission (NRC) completed an inspection at Monticello Nuclear Generating Plant. On October 24, 2024, the NRC inspectors discussed the results of this inspection with you and other members of your staff. The results of this inspection are documented in the enclosed report.

No findings or violations of more than minor significance were identified during this inspection.

This letter, its enclosure, and your response (if any) will be made available for public inspection and copying at http://www.nrc.gov/reading-rm/adams.html and at the NRC Public Document Room in accordance with Title 10 of the Code of Federal Regulations 2.390, Public Inspections, Exemptions, Requests for Withholding.

Sincerely, Michael E. Ziolkowski, Chief Security, Emergency Preparedness, and Incident Response Branch Division of Radiological Safety and Security Docket No. 05000263, 07200058 License No. DPR-22, DPR-74 General License (ISFSI)

Enclosure:

As stated

Inspection Report

Docket Number:

05000263, 07200058

License Number:

DPR-22, DPR-74; General License (ISFSI)

Report Number:

05000263/2024402; 07200058/2024401

Enterprise Identifier:

I-2024-402-0044; I-2024-401-0082

Licensee:

Northern States Power Company

Facility:

Monticello Nuclear Generating Plant

Location:

Monticello, MN

Inspection Dates:

September 23, 2024 to October 24, 2024

Inspectors:

D. Garner, Security Specialist

K. Maloney, Sr Physical Security Inspector

Approved By:

Michael E. Ziolkowski, Chief

Security, Emergency Preparedness, and Incident Response Branch

Division of Radiological Safety and Security

SUMMARY

The U.S. Nuclear Regulatory Commission (NRC) continued monitoring the licensees performance by conducting a security baseline inspection at Monticello Nuclear Generating Plant, in accordance with the Reactor Oversight Process. The Reactor Oversight Process is the NRCs program for overseeing the safe operation of commercial nuclear power reactors.

Refer to https://www.nrc.gov/reactors/operating/oversight.html for more information.

The NRC also conducted an independent spent fuel storage installation security inspection, in accordance with the Spent Fuel Storage Oversight Process. The Spent Fuel Storage Oversight Process is the NRCs program for overseeing the safe storage of spent nuclear fuel.

Refer to https://www.nrc.gov/waste/spent-fuel-storage/oversight.html for more information.

List of Findings and Violations

No findings or violations of more than minor significance were identified.

Additional Tracking Items

None.

INSPECTION SCOPES

Inspections were conducted using the appropriate portions of the inspection procedures (IPs) in effect at the beginning of the inspection unless otherwise noted. Currently approved IPs with their attached revision histories are located on the public website at http://www.nrc.gov/reading-rm/doc-collections/insp-manual/inspection-procedure/index.html.

Samples were declared complete when the IP requirements most appropriate to the inspection activity were met consistent with Inspection Manual Chapter (IMC) 2201, Security Inspection Program for Commercial Nuclear Power Reactors. The inspectors reviewed selected procedures and records, observed activities, and interviewed personnel to assess licensee performance and compliance with Commission rules and regulations, license conditions, site procedures, and standards.

SAFEGUARDS

71130.01 - Access Authorization

The inspectors evaluated the access authorization program. The following elements were evaluated:

Access Authorization

(1)

  • Tier I: All
  • Tier II: 02.05 a-b; 02.06 a-c; 02.08 a;
  • Tier III: 02.10 a-c; 02.11 a.

71130.09 - Security Plan Changes

The inspectors evaluated the security plan changes through completion of the following procedure elements:

Security Plan Changes (1 Partial)

(1)

(Partial)

The opportunity to apply this procedure was not available in accordance with IMC 0306. This sample was not available because the licensee did not conduct the activity covered by this IP. Specifically, the licensee has not initiated a physical security plan change in accordance with 10 CFR 50.54(p(2) since the last performance of this IP.

OTHER ACTIVITIES

- INDEPENDENT SPENT FUEL STORAGE INSTALLATION (ISFSI)

81311 - Physical Security Requirements for Independent Spent Fuel Storage Installations

(1)02.01 a-c; 02.02 a-h; 02.03 a-m; 02.04; 02.05 a-t; 02.06; 02.07 a-b; 02.08 a-c

INSPECTION RESULTS

No findings were identified.

EXIT MEETINGS AND DEBRIEFS

The inspectors verified no proprietary information was retained or documented in this report.

  • On October 24, 2024, the inspectors presented the security baseline inspection results to Shawn Hafen and other members of the licensee staff.

DOCUMENTS REVIEWED

Inspection

Procedure

Type

Designation

Description or Title

Revision or

Date

Miscellaneous

Each - Initial,

Updated,

Reinvestigation 30,

Reinvestigation

31-365,

Reinvestigation

365-3yr

Employee Records - Initial, Updated, Reinvestigation 30,

Reinvestigation 31-365, Reinvestigation 365-3yr

FP-S-AA-01

Access Authorization Program

71130.01

Procedures

QF1720

Fitness for Duty Handbook

71130.09

Self-Assessments QF0406

Snapshot Self-Assessment for 71130.09 Security Plan

Changes and 81311 ISFSI Security

Corrective Action

Documents

CR#610000003875

Change Request Close Out Report - Security Radio

Programing.

2/24/2022

Recordable Physical Security Safeguards Events Log

(02/15/24 - 04/03/24).

(ML080510249)

Monticello Nuclear Generating Plant Response to

EA-07-195

2/15/2008

(ML082050270)

NRC Confirmation Letter: Response to Order for

Implementation of Additional Security Measures and

Fingerprinting for Unescorted Access for Certain Spent Fuel

Storage Licensees - Monticello Nuclear Generating Plant

Independent Spent Fuel Storage Installation.

07/22/2008

(NS12615)

Monticello Nuclear Generating Plant Physical Security

NRC Order

EA-07-19

Issuance of Order for Implementation of Additional Security

Measures and Fingerprinting for Unescorted Access for

Certain Spent Fuel Storage Licensees - Monticello Nuclear

Generating Plant Independent Spent Fuel Storage

Installation (Ml091110627).

01/28/2008

81311

Miscellaneous

QF1755

Local Law Enforcement Agreement (LLEA) Memorandum of

Understanding (MOU) Law Enforcement Support, Wright

County Sheriffs Office, QF1755, Rev. 3 (FP-S-FSIP-13).

03/20/2024

1397-01

Vehicle Barrier System Inspection Procedure for

W/O # 700118020.

CWP-05.01

Security Computer System Startup/Shutdown/Failover

FP-S-FSIP-01

Security Compensatory Measure - Compensatory Measure

Matrix

FP-S-FSIP-08

Contingency Plan Implementing Procedures (CPIP)

(FP-S-FSIP-08), 1.19 Independent Spent Fuel Storage

Installation Contingency Response.

09/23/2024

FP-S-FSIP-09

Monticello Specific Alarm Response Matrix

QF1506

Software Test Plan, Computer Room Security Computer

System (SCS), Rev. 9 (FP-IT-SQA-10),

Document ID: STP - 611000005342

08/08/2024

QF1734

(FP-S-FSIP-04)

Weapons and Ammunition Disposition Log

Procedures

QF1763

(FP-S-FSIP-02): Post Orders, Zone 52 Offline - Dedicated

Observer, opened 06/16/24, closed 06/18/24.

QF1500

Computer Work Order: Bi-Weekly Cyber

Maintenance - (FP-IT-SQA-05),

Document ID: 61100005342.

WM-WO-1565

Quarterly Vehicle Barrier System Inspection

Work Order 1397-02

Annual Vehicle Barrier System Inspection

Work Orders

Work Order 4087-01

Preventative Maintenance SEC MO Gates and Barriers

(5-year Preventative Maintenance)

0